METER CAN BY O <br />ELECTRIC UTILITY CO - <br />TO UNDERGROUND <br />SERVICE BY ELECTRIC <br />UTILITY CO. <br />200 AMP MAIN BREAKER <br />40 CIRCUIT SURFACE MOUNT <br />PANEL—� <br />200 <br />AMP <br />2" C WITH 3-4/0 THW AL <br />#4 CU. GROUND <br />(2) 5/8" X 8' GROUND LINE <br />(BACK TO BACK SERVICE/OFFSET SIMILAR) <br />UNDERGROUND SERVICE <br />TO OVERHEAD <br />SERVICE BY ELECTRIC <br />UTILITY CO. <br />200 AMP MAIN BREAKER <br />40 CIRCUIT SURFACE MOUNT <br />PANEL <br />METER CAN BY O <br />ELECTRIC UTILITY CO. M <br />(2) 5/8" X 8' GROUND LINE <br />200 <br />AMP <br />2" C WITH 3-4/0 THW AL <br />#4 CU. GROUND <br />(BACK TO BACK SERVICE/OFFSET SIMILAR) <br />OVERHEAD SERVICE <br />ELECTRICAL SCHEDULE <br />SYMBOL <br />DESCRIPTION <br />-- — <br />INDICATES SWITCH LEG CAbUITING <br />DUPLEX RECEPTACLE <br />DUPLEX RECEPT. MOUNTED ABV. C6u1k1TElt 6 42" A.F.F. <br />SWITCHED DUPLEX RECEPTACLE <br />220V RECEPTACLE <br />220V RECEPOUNTED ABV T. M. COUNTkR A.F.F. <br />GFI <br />PPOM <br />GROUND FAULT INTERRUPT RECEPTACLE <br />WP <br />WEATHER PROOF DUPLEX RECEPTACLE <br />rSPECIAL PURPOSE OUTLET <br />FLOOR OUTLET W/JUNCTION BOX <br />WALL TELEPHONE (CAT 5 (4) TWISTED PAIR) <br />0 <br />FLOOR OUTLET FOR TELEPHON€ <br />TV <br />TELEVISION JACK <br />DISCONNECT <br />$ <br />SINGLE POLE SWITCH <br />$3 <br />3-WAY SWITCH <br />$4 <br />4-WAY SWITCH <br />$DM <br />DIMMER SWITCH <br />CEILING MOUNTED INCANDESCENT LIGHT <br />® <br />RECESSED MOUNTED INCANDESCENT LIGHT <br />SURFACE MOUNTED INCANDESCENT LIGHT <br />CEILING HUNG INCANDESCENT LIGHT (PENDANT) <br />®-� <br />RECESSED DIRECTIONAL INCANDESCENT LIGHT <br />STRIP FLORESCENT (440, 240, 220) <br />UNDER CABINET LIGHTING <br />SECURITY FLOOD LIGHT <br />EXHAUSTFAN <br />EXHAUST FAN w/ LIGHT <br />,1B <br />JUNCTION BOX <br />IC <br />INTERCOM <br />TP <br />SECURITY TOUCHPAD <br />ELECTRICAL & A/V PANEL BOARD <br />SD <br />SMOKE DETECTOR <br />KIDDE MODEL #4618 <br />SD,C <br />CARBON MONOXIDE/SMOKE DETECTOR COMBO <br />KIDDE MODEL #KN-COSM-IBA <br />T <br />THERMOSTAT <br />—OPB <br />PUSH BUTTON FOR DOOROELL <br />-� <br />PUSH BUTTON FOR GARAGE b6oiR Q>i*_.NtR <br />CHIME <br />DOOR CHIME <br />• <br />(5) BLADE, (3) SPEED REVERSIBLE FAN <br />(5) BLADE, (3) SPEED REVERSIBLE FAN W/ LIGHT <br />ELECTRICAL NOTES <br />1. All work shall be in strict accordance with National Electrical Code all applicable local ordinances <br />and in cooperation with the utility companies. <br />2. Coordinate all work with all trades. <br />3. Provide and install ground fault circuit-interupters (gfi) as indicated on plans. <br />4. Mount all outlets and receptacles plumb and flush with walls. <br />5. Unless otherwise indicated, install switches & receptacles at the following heights above finish <br />floor: <br />Switches 42" <br />Outlets 14" <br />Telephones 14" <br />CAN 14" <br />6. Install electrical cable, wire and connectors as Indicated in accordance with the manufacturer's <br />written instruction, the applicable requirements of nec and the national electrical contractors <br />association "standard of installation' and in accordance with recognized industry practices to ensure <br />that production serve the intended functions. <br />7. All wire shall be std. #10 and #12 and shall be romex or nm cable Type "B" or approved equal. <br />8. Coordinate electrical requirements for A/C with A/C contractor. <br />9. All receptacles in sleeping rooms shall be on a A.F.C.I. protected circuit. <br />10. Receptacles will be "Tamper Resistant" per Section 406.11 of the National Electrical Code 2008. <br />11. Arc -Fault Circuit Interrupters will be installed per Section 210.12 of the National Electrical Code <br />2008. <br />SECTION R314 SMOKE ALARMS <br />R314.1 Smoke detection and notification. All smoke alarms shall be listed and labeled in <br />accordance with UL 217 and installed In accordance with the provisions of this code and the <br />household fire warning equipment provisions of NFPA 72. <br />R314.2 Smoke detection systems. Household fire alarm systems installed In accordance with NFPA <br />72 that include smoke alarms, or a combination of smoke detector and audible notification device <br />installed as required by this section for smoke alarms, shall be permitted. The household fire alarm <br />system shall provide the same level of smoke detection and alarm as required by this section for <br />smoke alarms. Where a household fire warning system is installed using a combination of smoke <br />detector and audible notification device(s), it shall become a permanent fixture of the occupancy <br />and owned by the homeowner. The system shall be monitored by an approved supervising station <br />and be maintained in accordance with NFPA 72. <br />Exception: Where smoke alarms are provided meeting the requirements of Section R314.4. <br />R314.3 Location. Smoke alarms shall be installed in the following locations: <br />1. In each sleeping room. <br />2. Outside each separate sleeping area in the immediate vicinity of the bedrooms. <br />3. On each additional story of the dwelling, including basements and habitable attics but not <br />Including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split levels and <br />without an intervening door between the adjacent levels, a smoke alarm installed on the upper level <br />shall suffice for the adjacent lower level provided that the lower level is less than one full story below <br />the upper level. <br />SECTION R315 CARBON MO!NOX[DE ALARMS <br />R315.1 Carbon monoxide protection. Every separate building or an addition to an existing building <br />for which a permit for new construction is issued and having a fossil -fuel -burning heater or <br />appliance, a fireplace, an attached garage, or other feature, fixture, or element that emits carbon <br />monoxide as byproduct of combustion shall have an operational carbon monoxide alarm installed <br />within 10 feet (3048 mm) of each room used for sleeping purposes. <br />Exception: This section shall not apply to existing buildings that are undergoing alterations or repair <br />unless the alteration is an addition as defined in Section R315.1.3. <br />R315.1.1 Carbon monoxide alarm. The requirements of Section R315.1 shall be satisfied by <br />providing for one of the following alarm installations: <br />(1) A hard -wired carbon monoxide alarm. <br />(2) A battery -powered carbon monoxide alarm. <br />(3) A hard -wired combination carbon monoxide and smoke alarm. <br />(4) A battery -powered combination carbon monox- ide and smoke alarm. <br />R315.1.2 Combination alarms. Combination smoke/car- bon monoxide alarms shall be listed and <br />labeled by a nationally recognized testing laboratory. <br />DATE: <br />09/14/2015 <br />JOB NO: <br />HA9139 <br />DESIGN BY: <br />-- <br />DRAWN BY: <br />JRH <br />CHECKED BY: <br />GC <br />PROJECT: <br />3615-HA9139 <br />CHECKED BY: <br />JRH,JGZ <br />EST: <br />-- <br />CONST. MNGR: -- <br />SUPER: <br />CV CM <br />U <br />LO <br />IMM <br />♦'/ <br />N <br />J <br />LL <br />cn <br />Q <br />CO^ T <br />LLI <br />LL <br />LU <br />> <br />T <br />r <br />N <br />Z <br />CY) <br />--�- <br />LU <br />UCO <br />cY) <br />CO <br />Z <br />o <br />Li <br />O <br />MODEL: <br />9-15 <br />SPECS <br />CUSTOMER: <br />LUCKEY <br />39119 PARK DR. <br />ZEPHRYHILLS, FL 33542 <br />o E E <br />rn u u <br />v <br />00 <br />ar un <br />M tGN <br />-a N <br />Ln tp <br />O M <br />E CM <br />O LL en <br />0 00 <br />El .1 <br />