I 1 11 1 1 1 1 1 1 1 1 111 1 1 I I I III 11 1 ' 1 II 1 1 II 1 1 1 1 1 1 11 1 1 1 I'leml 11 of I <br />EXIST. G.O. <br />INV.72.0' <br />(VERIFY) — <br />TIE INTO EXIST. — <br />GO. INV. IN EX15T. <br />5.5. LINE <br />10 ��uM151NG PLAN <br />SCALE: 3/32 " = V -011 <br />PLUMBING GENERAL NOTES <br />1. THE REQUIREMENTS OF THE GENERAL CONDITIONS AND SUPPLEMENTARY <br />GENERAL CONDITIONS SHALL APPLY TO ALL PLUMBING WORK. <br />INSTALLATION SHALL BE IN ACCORDANCE WITH THE 2007 FLORIDA <br />BUILDING CODE WITH 2O09 AMENDMENTS, STATE AND LOCAL CODES AND <br />THE LATEST AMENDMENTS THERETO. <br />2. THE WORK COVERED BY THIS SECTION OF THESE SPECIFICATIONS <br />CONSISTS OF FURNISHING ALL LABOR, EQUIPMENT, MATERIALS AND <br />SERVICE NECESSARY FOR AND REASONABLY INCIDENTAL TO THE <br />PROPER COMPLETION OF ALL PLUMBING WORK SHOWN ON THE DRAWINGS <br />AND SPECIFIED. MATERIALS OR PRODUCTS SPECIFIED BY TRADE <br />NAME, MANUFACTURER'S NAME OR CATALOG NUMBER SHALL BE <br />INTERPRETED AS ESTABLISHING A STANDARD OF QUALITY AND <br />DESIGN. SUBSTITUTIONS SHALL NOT BE ALLOWED UNLESS THEY ARE <br />SUBMITTED FOR REVIEW TO USE AND APPROVED BY THE ARCHITECT. <br />FIXTURES BY ELJER, KOHLER OR AMERICAN —STANDARD ARE APPROVED <br />EQUAL. <br />4. PLUMBING CONTRACTOR SHALL COORDINATE WITH ARCHITECTURAL, <br />CIVIL, STRUCTURAL, ELECTRICAL, FIRE PROTECTION, MECHANICAL AND <br />ALL OTHER TRADES FOR PIPE ROUTING AND EQUIPMENT PLACEMENT. AVOID <br />INTERFERENCE WITH ARCHITECTURAL FEATURES, BEAMS, FOOTINGS, <br />WINDOWS, ETC. NOTIFY ARCHITECT IMMEDIATELY OF ANY CONFLICTS. <br />SLEEVES SHALL BE INSTALLED WHERE PIPING PASSES THROUGH STRUCTURE. <br />5. CONTRACTOR SHALL KEEP A RECORD OF THE LOCATIONS OF ALL <br />CONCEALED WORK AND UPON COMPLETION OF THE JOB, SHALL SUPPLY AS — <br />BUILT DRAWINGS SHOWING IN COLORED PENCIL ON BLACK LINE PRINTS ANY <br />DEVIATION FROM THE ORIGINAL DRAWINGS. THESE DRAWINGS SHALL <br />INDICATE DIMENSIONS OF BURIED UTILITY LINES FROM BUILDING WALLS. <br />6. ALL WORK SHALL BE GUARANTEED, BOTH MATERIAL AND <br />INSTALLATION, FOR A PERIOD OF ONE YEAR FROM ACCEPTANCE BY OWNER. <br />SANITARY, WASTE AND VENT PIPING <br />1. SANITARY, WASTE AND VENT PIPING SHALL BE SCHEDULE 40 PVC <br />(ASTM-2665) WITH APPROVED PVC SOLVENT WELDED FITTINGS. COMPLY <br />WITH FLORIDA BUILDING CODE. PVC PIPING SHALL NOT BE RUN IN <br />RETURN AIR PLENUM OR FIRE RATED ASSEMBLIES. <br />2. ALL SOIL AND WASTE PIPING, 2-1/2" AND SMALLER, SHALL BE <br />SLOPED AT 1/4" PER FOOT. LARGER WASTE PIPING SHALL BE SLOPED AT <br />1 /8" PER FOOT. <br />3. TEST SANITARY, WASTE AND VENT PIPING BY A 10' WATER COLUMN <br />FOR TWENTY—FOUR (24) HOURS OR AS REQUIRED BY THE BUILDING <br />DEPARTMENT. <br />WATER PIPING <br />1. WATER PIPING SHALL BE (CPVC) CHLORINATED POLYVINYL <br />CHLORIDE PLASTIC PIPE AND TUBING (ASTM-2846) WITH APPROVED CPVC <br />SOLVENT WELDED FITTINGS. COMPLY WITH FLORIDA BUILDING CODE. <br />2. THE SITE SUBCONTRACTOR SHALL PROVIDE THE BACKFLOW PREVENTOR <br />AND THE WATER METER. <br />3. A SERVICE VALVE SHALL BE PROVIDED ON THE DOMESTIC WATER <br />WHERE WATER ENTERS THE BUILDING. <br />4. TEST ALL WATER PIPING AT 100 PSIG FOR TWENTY—FOUR (24) HOURS <br />OR AS REQUIRED BY CODE. <br />5. STERILIZE ALL WATER PIPING IN ACCORDANCE WITH HEALTH <br />DEPARTMENT REGULATIONS AND AMERICAN WATER WORKS SPECIFICATIONS. <br />6. WATER SERVICE PIPING SHALL BE SLEEVED AT LEAST 60" HORIZ. FROM THE <br />SEWER PIPE CENTERLINE ON BOTH SIDES OF WHERE THE WATER SERVICE <br />PIPE CROSSES A SEWER PIPE. SEE FLORIDA PLUMBING CODE 603.2. <br />`' <br />.o <br />MET <br />am <br />a <br />= <br />V <br />MDJ <br />m4-28-2011 <br />m <br />c <br />c <br />m <br />O <br />V <br />� <br />V <br />Jw <br />C <br />O <br />77 <br />'o <br />U <br />ori <br />� <br />u- <br />C <br />ed <br />�d <br />Q <br />3 <br />0 <br />C <br />V <br />O <br />Q <br />In <br />� <br />M <br />1 <br />06-06-2011 <br />Z <br />3 <br />4 <br />SHEET <br />P-1 <br />OF <br />