GENERAL ELECTRI A N T
<br />I- ALL NEW ELECTRICAL WORK SHALL BE INSTALLED IN COMPLIANCE WITH ALL
<br />PROVISIONS OF THE NATIONAL ELECTRICAL CODE; LATEST EDITION AND THE
<br />FLORIDA BUILDING CODE; NATIONAL ELECTRICAL SAFETY CODE, OSHA, AND THE
<br />NATIONAL FIRE PROTECTION CODES,
<br />2 ALL NEW EQUIPMENT AND MATERIALS FURNISHED SHALL BE FREE OF DEFECTS,
<br />WHERE UNDERWRITER'S LABORATORIES, INC. HAVE. ESTABLISHED STANDARDS FOR
<br />SUCH MATERIALS; PROVIDE THE MATERIALS/EQUIPMENT BEARING THE UL LABEL,
<br />3- CONTRACTOR SHALL PROVIDE SKILLED WORKMEN WHO ARE THOROUGHLY
<br />TRAINED'AND EXPERIENCED IN THE NECESSARY CRAFTS AND WHO ARE COMPLETELY
<br />FAMILIAR WITH THE REQUIREMENTS AND THE METHODS NEEDED FOR PROPER
<br />INSTALLATION OF THE WORK,
<br />4- CONTRACTOR SHALL FURNISH ALL TEMPORARY POWER DURING THE
<br />CONSTRUCTION RENOVATION OF THIS FACILITY AS REQUIRED BY ALL TRADES;
<br />COORDINATE SPECIFIC REQUIREMENTS WITH THE INDIVIDUAL TRADESMEN,
<br />5 ALL WORK AND NEW EQUIPMENT SHALL HAVE A ONE YEAR WARRANTY ON ALL
<br />LABOR AND MATERIALS,
<br />6- PROVIDE ALL WIRING, CONNECTIONS AND CONDUIT REQUIRED. TO ALL HVAC
<br />EQUIPMENT, INCLUDING DISCONNECTING MEANS, UNLESS SPECIFICALLY INDICATED
<br />OTHERWISE ON THE DRAWINGS OR FURNISHED AS. PART OF FACTORY PACKAGED
<br />EQUIPMENT,
<br />7 CONFIRM CONTRACTOR CO IR M ALL MOTORS AND EQUIPMENT HAVE THE PROPER
<br />VOLTAGE TO OPERATE AND THAT EACH MOTOR HAS THERMAL OVERLOAD
<br />PROTECTION, PROPERLY SIZED TO NAMEPLATE DATA.
<br />8- ALL RACEWAYS, WIREMOLD, CONDUITS, SUPPORTS,.HNGERS WHERE EXPOSED
<br />SHALL BE PAINTED TO MATCH THE MOUNTING SURFACE OR SURROUNDING SURFACES,
<br />PANELS AND EQUIPMENT WITH DAMAGED SURFACES SHALL BE RE -FINISHED TO
<br />PRESENT A SMOOTH CONTINUOUS FINISH,
<br />9- ALL CONDUCTORS SHALL BE COPPER, FOR 600 VOLTS WITH INSULATION TYPES
<br />- THWN, THW, THHN., 'OR XHHW, ALL NEW CONDUCTORS SHALL BE COLOR CODED TO
<br />MATCH SERVICE ENTRANCE FEEDERS.
<br />10- A GROUND CONDUCTOR, COLOR CODED GREEN, SHALL BE RUN IN ALL NEW
<br />BRANCH AND FEEDER CIRCUITS, ALL NEW EQUIPMENT SHALL BE GROUNDED,
<br />11- ALL NEW RECEPTACLES SHALL BE DUPLEX TYPE, 20 AMP, 125V, 2P .3W
<br />GROUNDING TYPE, IVORY COLOR, PROVIDE NEW SINGLE RECEPTACLE FOR THE
<br />EXISTING COPIER MACHINE, WHERE SHOWN ON THE DRAWINGS,
<br />12- ALL DEVICE COVER PLATES SHALL PLASTIC TYPE, COLOR TO MATCH FINISH'
<br />SURFACE COLOR, WHERE GROUPED TOGETHER, FURNISH GANG BOXES WITH ONE
<br />COVER PLATE.
<br />13- ALL CONDUITS SHALL BE RIGID HOT DIPPED GALVANIZED STEEL CONDUIT, ALL
<br />CONNECTORS SHALL BE COMPRESSION TYPE FITTINGS, ALL C❑NDUITS SHALL BE
<br />SUPPORTED AT EIGHT FOOT INTERVALS WITH TWO -HOLE CONDUIT STRAPS.
<br />RACEWAYS AND CONDUITS SHALL NOT BE SUPPORTED FROM CEILING. PROVIDE
<br />ADDITIONAL SUPPORT AT EACH OUTLET OR JUNCTION BOX, 6" FROM BOXES,
<br />SURFACE METAL RACEWYS (WIREMOLD) SHALL BE SUPPORT BY MEANS 'AS
<br />RECOMMENDED BY THE MANUFACTURER,
<br />14- ALL OUTLET AND JUNCTION BOXES SHALL BE STEEL SUITABLE FOR THE
<br />DEVICE INTENDED. ALL PULL BOXES AND JUNCTION BOXED SHALL BE STEEL, SIZED
<br />PER NEC REQUIREMENTS,
<br />15- ALL SAFETY SWITCHES SHALL BE NEW HEAVY DUTY, HORSEPOWER RATED,
<br />QUICK -MAKE, QUICK -BREAK, TYPE FUSIBLE OR NON -FUSIBLE AS SHOWNON THE
<br />DRAWINGS: FURNISH NEMA 1 FOR INDOORS AND NEMA 3R FOR OUTDOOR
<br />INSTALLATION OR IF SUSCEPTIBLE TO WATER OR MOISTURE,
<br />16- ALL FLEXIBLE MEATLLIC CONDUITS SHALL BE THE LIQUID -TIGHT TYPE, USE
<br />LIQUID --TIGHT FLEXIBLE CONDUIT WHERE SUBJECT TO MOISTURE, VIBRATION OF IF
<br />THE EQUIPMENT IS OUTDOORS,
<br />FIXTURE SCHEDULE
<br />TYPE
<br />DESCRIPTION
<br />LAMP
<br />MOUNTING
<br />FLUORESCENT 2x4 TROFFER
<br />A
<br />ARYLIC LENS; ELECTRONIC BALLAST
<br />3-32 W
<br />RECESSED
<br />T-8
<br />LITHONIA # 2GT-' 332—Al2-120—ES
<br />LAVATORY WALL LIGHT
<br />B �
<br />ACRYLIC LENS &LENS GASKET.
<br />2-32 W
<br />WALL SURFACE.
<br />T-8
<br />ABOVE MIRROR
<br />LITHONIA # W-232-120--GEB
<br />EXTERIOR .WALL BRACKET
<br />C
<br />POLYCARBONATE LENS & HIGH ABUSE
<br />2-32 W
<br />WALL SURFACE
<br />8'-0" AB: GRADE
<br />T-8
<br />LITHONIA # VR2C-70S-120-IR—WL—CW=
<br />SELF CONTAINED EMERGENCY LIGHT
<br />Y
<br />TWIN HALOGEN LIGHTS/ NiCAD BATTERY
<br />W/ UNIT
<br />WALL SURFACE
<br />18" BELOW CLG.
<br />DUAL --LIGHT # EZ-21
<br />SELF CONTAINED EXIT LIGHT— RED
<br />X
<br />BATTERY OPERATED/120V
<br />W/ UNIT
<br />SURFACE
<br />DUAL -LIGHT #LX—SRWE—I
<br />ELECTRICAL SYMBOL SCHEDULE
<br />SYMBOL "_.. ..... __...__. _ DESCRIPTION .__.......�. MOUNTING N.O.N,) I 4
<br />5 IN BOX WITH IVORYS ANDLE ANDSCOVC'ER PLATE.M5PNT CIRCUIT � +52" A.F.F. �
<br />20 AMP 120 VOLT A.C. 3 WIRE GROUNDING TYPE DUPLEX +18" A.F.F. {
<br />RECEPTACLE FLUSH MOUNTED IN FS BOX WITH IVORY
<br />COVER PLATE.
<br />GFI 20 AMP 120. VOLT A.C. GROUND FAULT INTERUPTER TYPE '
<br />DUPLEX RECEPTACLE FLUSH MOUNTED IN FS BOX WITH
<br />IVORY COVER _PLATE.
<br />GFI 20 AMP 120 VOLT A.C. GROUND FAULT INTERRUPTER TYPE WITH {
<br />11 (2) TWO DUPLEX RECEPTACLE FLUSH MOUNTED IN FS BOX WITH f
<br />IVORY COVER PLATE. (QUADRUPLEX)
<br />NON —FUSED DISCONNECT SWITCH
<br />ENCLOSURE AND SIZE AS NOTED {
<br />i a
<br />TELEPHONE OUTLET BOX —RUN 1/2" DIA. EMT CONDUIT +18" A.F.F. '
<br />INTO SPACE ABOVE CEILING.WP Z N M v us <o ae
<br />20 AMP 120 VOLT A.C. 3 WIRE GROUNDING TYPE Co
<br />DUPLEX RECEPTACLE SURFACE MOUNTED IN FS BOX WITH
<br />qP IVORY COVER PLATE & WEATHER—PROOF COVER PLATE. • I
<br />• PAN,...._. �. .�..._..._......._...._._..__....._......,..... ;..... _... ....._.... _ ._...._.... _� ....._..._. ....... ...,.. __ _ ....._...w.. •._.. ..... ...... � � C,1 �
<br />"AFL PANELBOARD - 120/208 VOLTS, THREE PHASE FOUR WIRES TOP +66" A.F.F.
<br />SEE SCHEDULEQ its
<br />p�
<br />FLUORESCENT FIXTURE — WALL MOUNTED ABOVE MIRROR Ol `
<br />SEE LIGHTING FIXTURE SCHEDULE. AB. MIRROR
<br />'w
<br />� BATTERY OPERATED EXIT LIGHT — SEE SCHEDULE.
<br />L^1 SEE SCHEDULE �
<br />BATTERY OPERATED EMERGENCY LIGHT - SEE LIGHTING U
<br />SEE SCHEDULE
<br />FIXTURE SCHEDULE.
<br />t � Uhpp
<br />FLUORESCENT LIGHT FIXTURE, SURFACE MTD e
<br />G LETTER INDICATES TYPE, NUMBER BRANCH CIRCUIT SEE SCHEDULE ` �3
<br />y SEE LIGHTING FIXTURE SCHEDULE.
<br />V�
<br />V
<br />C
<br />I —add
<br />Q)
<br />• V�
<br />`lz� o
<br />614 ti 0-4�
<br />o —
<br />c, C
<br />4_4
<br />Date: 03/07/00
<br />Scale: AS Holm
<br />Job No. 0487
<br />Drawn By: L RODM U
<br />CAD: EOf.t.dwp —Afar. 7, 200d 10:39 am. Fabb Acod fB.O Checked By: H. mm
<br />Sheet -
<br />LU/S ROOMOUES, TURE of - Sheets
<br />FLORIOA RE0. NO.
<br />ELECTRICAL ENGINEER �: l r,lI' Drawing No. Rev.
<br />PLAN� 410.mcss E01 �
<br />AALSE+3' SEAL - AMXED.
<br />4�J (7rbNy1 Corc~.w'3�n tZchrvrh{tls I' L11Arc�'+^^++►�^" ^1.dwq, •�/1 "�I?_Or " ' 1:11 AM, W {1" ',t1tN-210W1