STRUCTURAL SPECIFICATIONS <br />I. GENERAL <br />I. SUBCONTRACTOR IS RESPONSIBLE FOR MEANS AND METHODS OF CONSTRUCTION <br />TO ENSURE THE SAFETY OF THE BUILDING UNTIL STRUCTURAL SYSTEM 16 COMPLETED. <br />THiS INCLUDES, BUT IS NOT LIMITED TO, T14= ADDITION OF WHATEVER TEMPORARY <br />BRACING, SHORING, GUYS TO TIE -DOWNS THAT MAY BE NECESSARY. <br />2. SUBCONTRACTOR 18 SOLELY RESPONSIBLE FOR THE SAFETY OF HIS WORK DURING CONSTRUCTION. <br />3. APPLICABLE BUILDING CODES: - FLORIDA BUILDING CODE (2010, RESIDENTIAL EDITION) <br />4. DESIGN LOADS - <br />A. ROOF: LIVE LOAD- 20 PWF(MNIMUM). <br />DEAD LOAD_ 10 PGF(SHNGLE) 20 PSF (TILE). <br />B. FLOOR: LIVE LOAD. 60 PSF BALCONIES, 40 FOR ALL OTHER ROOMS <br />DEAD LOAD-10 PSF <br />C. SOIL PRESSURE: 2000 PSF (ASSUMED MIND, <br />5. STRUCTURAL MEMBER ALLOWABLE DEFLECTION <br />Rafters having slopes greater than 3.12 with no flniehed calling attached to rafters <br />LAW <br />Interior walls and partitions <br />H/180 <br />Floors and plastered cellMge <br />L/360 <br />All other structural members <br />L/240 <br />Exterior walls with plaster or stucco finish <br />H/360 <br />Exterior walls-iukid loads with brittle finishes <br />14/140 <br />Exterior walls --wind loads with flexible finishes <br />LA20d <br />Lintels supporting masonry veneer walls <br />L/600 <br />6. ALL CONTRACTORS, SUBCONTRACTORS, SUPPLIERS AND FABRICATORS <br />SHALL BE RESPONSIBLE FOR THE CONTENT OF DRAWINGS, AND FOR THE <br />SUPPLY AND DESIGN OF APPROPRIATE MATERIALS AND WORK <br />PERFORMANCE. <br />1. ALL MANUFACTURED ARTICLES, MATERIALS AND EQUIPMENT SHALL <br />MBE APPLIED, INSTALLED, ERECTED, USED, CLEATED, AND CONDITIONED IN STRICT <br />ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. <br />II. SITE WORK <br />L FOUNDATION DESIGN IS BASED ON A MINIMUM SOIL PRESSURE OF 2000 PGF. IF A SOILS <br />REPORT WAS NOT PREPARED, THE CONTRACTOR IS RESPONSIBLE TO RETAIN A <br />GEOTECFINICAL ENGNNEER TO CONFIRM THE SOIL CONDITIONS. SHOULD FIELD <br />CONDITIONS INDICATE THIS MINIMUM CONDITION DOES NOT EXIST, THE CONTRACTOR <br />SHALL IMMEDIATELY NOTIFY ENGINEER OF RECORD. <br />2. THE SUBGRADE UNDER THE NEW CONCRETE FOUNDATIONS SHALL BE COMPACTED <br />TO 9596 OPTIMUM DENSITY. SOIL COMPACTION TESTS TO BE TAKEN BY A <br />QUALIFIED SOILS LAB PRIOR TO POURING ANY CONCRETE. <br />3. FOOTINGS SHALL BE NEAT EXCAVATED WHERE POSSIBLE WITH SIDES AND TOP EDGES <br />FREE OF LOOSE OR WET MATERIALS. WHERE NEAT EXCAVATION IS NOT POSSIBLE, <br />FOOTINGS EXCAVATION SHALL BE OPEN CUT WITH EDGES FORMED AND BRACED. ALL <br />FOOTINGS WITH FORMED EDGES SHALL BE BAGKFILLED FROM BOTTOM TO TOP OF <br />FOOTING WITH SELECT FILL. THE BOTTOM EXCAVATION SHALL BE CLEAN AND DRY <br />WITH ALL LOOSE MATERIAL REMOVED FOR AN ESSENTIALLY FLAT WARNS SURFACE. <br />4. PROVIDE SOIL TREATMENT FOR TERMITES PER THE 2010 FBC, RESIDENTIAL. <br />III. CAST IN PLACE CONCRETE <br />1. CONC STE TO BE NORMAL UUEOW WITH THE FOLLOWING MINIMUM C-OMPM681VE <br />STRENGTHS AT 28 DAYS: <br />a) FOOTINGS, SLAB -ON -GRADE, SLAB FILL1500 P61 <br />bJ MASONRY WALL TIE BEAMS, TIE COLUMVB_2500 P61 <br />2. CONC*MTE SHALL BE READYMIX PER ASTM C94: <br />a) PORTLAND CEMENT - ASTM CI50 <br />b) AGGREGATES - ASTM C33 (3/4" MAX) <br />cJ NO CALCIUM CHLORIDE <br />dJ AIR ENTRAINING - ASTM C260 <br />e) WATER REDUCING - ASTM C494 <br />f) FLYASH - ABTM C618-18 CLASS F (20 % MAX) <br />gJ WATER - CLEAN AND POTABLE <br />3. REINFORCING STEEL: ASTM A615 GRADE 40, DEFORMED BARS. <br />4. REQUIRED SLUMP RANGE ■ 3" TO 5". <br />5. WELDED WIRE FABRIC: ASTM A185 <br />6. MOISTURE BARRIER: 6 MIL POLYETHYLENE. <br />1. CODES AND STANDARDBt <br />ad ACI 301 "SPEC FOR STRUCTURAL CONCRETE FOR BUILDINGS." <br />b) ACI 305 "RECOMMENDED PRACTICE FOR HOT WEATHER CONCRETING" <br />c) ACI 318 "ELM CODE REQUIREMENTS FOR PEW. CONCRETE" <br />dJ ACT 315 "DETAILS AND DETAILING OF CONCRETE REINFORCEMENT." <br />8. MINIMUM LAP SPLICE ■ 40 BAR DIAMETERS UNLESS NOTED OTHERWISE. <br />9. CONCRETE FINISHES SHALL BE PER CONTRACTOR'S SPEC-8. <br />10. SIbCONTRACTOR 18 RESPONSIBLE FOR THE PROPER DESIGN AND CONSTRUCTION <br />OF ALL FORMWORK SHORING, AND R261­1ORING. <br />IL REINFORCING BAR COVER: <br />aJ FOOTINGS 3"q <br />b) COLUMNS 1 1/2" <br />cJ BEAMS AND WALLS 1 1/2" <br />dJ 6LA 58 3/4" (INTERIOR), 1 1/2" (EXTERIOR) <br />12. CONCRETE SHALL BE PLACED WITHIN ah0 MINUTES OF BATCH TIME. <br />13. PROVIDE CORNER BARS AT ALL WALL FOOTING CORNERS TO MATCH HORIZONTAL BARS. <br />(25" MINIMUM LAP). <br />14. ALL BUILDING SLABS -ON -GRADE SHALL BE NOMINAL 4" THICK, FIBER -MESH CONC. OR <br />REINFORCED WITH 6x6-W1A W A ON 6 MIL VAPOR BARRIER SEE PLANS FOR OTHER CONDITIONS. <br />15. ANCHORR BOLTS FOR WOOD PLATES TO CONCRETE OR MASONRY (ALTERVATIVESA <br />a. J BOLTS - USE 1/2" X 8" "J" BOLTS WITH 6" EMBEDMENT AND 2" PROJECTION WHEN INSTALLED <br />PRIOR TO PLACING CONCRETE, AS SHOWN ON DRAWNGB. <br />b. EXPANSION ANCHORS - USE 1/2" X 4" EMBED, WILT( KWIK BOLT II, OR EQUAL, AT LOCATIONS <br />(OTHER THAN EDGE CONDITIONS) N LIEU OF 112" X 8" "J" BOLTS. <br />a EPDXY ANCHORS IN CONCRETE - USE V2" X 4-1/4" IMBED, WITH WILTI COO), OR ANC 4OR <br />BOND BY CELTITE, INC. AT EDGE OF SLAB CONDITION WERE BOLT 16 LEGG THAN 6" TO <br />A CONCRETE EDGE. <br />d. EPDXY ANC( -TORS IN TOP OF BLOCK WALLS - USE THREADED ROD (3/4" X A6-5/8" IMBED) ON <br />TOP OF 8" MASONRY WALLS WITH WILTI HIT C-100 ADHESIVE OR ANCHIOR BOND, WHEN 1/2" X 8" <br />"J BOLTS ARE OMITTED. <br />16. FOOTING SIZES SHOWN ARE TYPICAL ONLY FOR STATED SOIL BEARING PRESSURE AND <br />CON616TED COMPACTION. CONTRACTOR SHALL BE RESPONSIBLE FOR FOOTINGS <br />COMPLYING WITH THE DESIGN REQUIREMENTS OF SPECIFIC SOIL CONDITIONS. <br />11. PROVIDE 1/2" EXPANSION JOINT MATERIAL BETWEEN ALL CONCRETE SLABS AND <br />AMMNG CONCRETE OR MASONRY WALLS OCCURRING IN EXTERIOR OR UNHEATED AREAS. <br />IV. MASONRY <br />1. HOLLOW LOAD BEARING WITS (CM D SHALL CONFORM TO ASTM C90, NORMAL WEIGHT, TYPE I, GRADE N. <br />MINIMUM NET COMPRESSIVE STRENGTH ■ 1900 "1. <br />2. MORTAR SHALL BE TYPE M OR S AND CONFORM TO ASTM C210. <br />3. CONCRETE GROUT SHALL CON" -OW TO ASTM C416: <br />ad 30M P61 AT 28 DAYS. <br />b) 3/6" MAXIMUM AGGREGATE. <br />cJ 8" - II" SLUMP. <br />4. BARB SHALL HAVE MINIMUM CLEARANCE OF 1/2" FROM MASONRY. THE CLEAR DISTANCE <br />BETWEEN BARS 844ALL NOT BE LESS THAN ONE BAR DIAMETER NOR LESS THAN 1". <br />S. VERTICAL REINFORCING SHALL BE AT ALL CORERS, EACH JAMB OF OPENINGS OVER 4 FT. WIDE, <br />UNDER ALL GIRDER LOADS, AND NOT TO EXCEED &'On O/C FOR STRAICsWT WALLS, OR AS GWOM <br />ON THE DRAWINGS. FILL CELLS WITH CONCRETE GROUT AS SPECIFIED. PROVIDE ACI 9O DEGREE <br />STANDARD HOOKS INTO FOOTING, AND TIE BEAMS. <br />6. RENFORCING BARS SHALL BE STRAIGHT EXCEPT FOR BENDS AROUND CORNERS AND WERE <br />BENDS OR HOOKS ARE DETAILED ON THE PLANS. <br />1. REINFORCING BARS SHALL BE LAPPED 40 BAR DIAMETERS WHERE SPLICED AND SHALL <br />BE WIRED TOGETHER <br />8. WHEN A FOUNDATION DOWEL DOES NOT LINE UP WITH A VERTICAL CORE, IT SHALL NOT DE <br />SLOPED MORE THAN ONE HORIZONTAL N SIX VERTICAL. DOWELS SHALL. BE GROUTED INTO A <br />CORE IN VERTICAL ALIGNMENT, EVEN THOUGH! IT IB IN AN ADJACENT CELL TO THE VERTICAL <br />WALL REm�F01®CEMENT. <br />S CLEANOUTS SHALL BE PROVIDED IN THE BOTTOM COURSE OF MASONRY IN EACH GROUT <br />POUR WHEN THE POUR HEIGHT EXCEEDS 5'. PROVIDE 4" X 4" OBSERVATION HOLE TO <br />VERIFY CONCRETE GROUT PLACEMENT. <br />1V. PLACE ALL MASONRY N RUNNING 1100 0 WITH 3/8" MORTAR JOINTS. PROVIDE COMPLETE <br />COVERAGE FACE SHELL MORTAR BEDDING, HORIZONTAL AND VERTICAL. FULLY <br />MORTAR WEDS IN ALL COURSES OF PIERS, COLUMNS, AND PILASTERS AND <br />AND ADJACENT TO GROUTED CELLS. <br />11. PROVIDE 8" X 8" PRECAST REINFORCED CONCRETE LINTELS OVER ALL MASONRY OPENINGS <br />NOT SHOWN! TO WAVE A STRUCTURAL BEAM. MINIMUM END DEARING - 4" <br />REI ER TO LINTEL SCHEDULE (MINIMUM CAPACITY OF 10" PLF), <br />12. PROVIDE METAL CAVITY CAPS, 6" WIRE MESH, OR DUR-O-STOP BY DUR-A-WALL, INC. WHERE <br />REQUIRED TO RETAIN GROUT IN VERTICAL CELLS. <br />V. CARPENTRY <br />L DIMENSIONED LUMBER SHALL BE DRESSED 646, AND SHALL BEAR THE GRADE STAMP <br />OF THE MANUFACTURER'S ASSOCIATION. <br />2. ALL LUMBER SHALL BE SOUND, SEASONED, AND FREE FROM WARP. <br />3. ALL STRUCTURAL BEAMS AND HEADERS SHALL BE SOUTHERN YELLOW PINE (6YPJ NO. 1 <br />GRADE OR BETTER WITH SINGLE MEMBER (UNFACTOI11100) STMOM6 AS FOLLOWS: <br />Fv ■ 90 P81 <br />Fc ■ 915 PSI <br />E 1,600,000 PSI <br />19% MAXIMUM MOISTURE CONTENT <br />A. FRAMING LUMBER SHALL BE 4 SPRUCE-PNE-FIR OR BETTER <br />S. INTERIOR NON -LOAD BEARING WALLS MAY IRE UTILITY GRADE. <br />4. ALL LUMBER IN CONTACT WITH MA60NRY OR CONCRETE SHALL BE PRESSURE TREATED. <br />S. PRESSURE TREATED LUMBER SHALL BE IMPREGNATED WITH A CCA SALT TREATMENT IN <br />ACCORDANCE WITH Flo. TT-W-511 AND BEAR THE AMERICAN WOOD PRESERVERS <br />INSTITUTE EQU,AL-ITY MARK Lie- 2. <br />6. SMAT14NG FOR ROOFS AND WALLS SHALL BE APA RATED (EXPOSURE 1) SHEATHING <br />WITH EXTERIOR GLUE. ALL ROOF SHEATHING TO BE INSTALLED WITH PLYCLIPS. <br />(MAXIMUM 24' O/C). SEE DETAILS FOR SHEATHING THIICIQESM& <br />1. NAILING FOR PLYWOOD ROOFS AND WALL SHEATHING SHALL BE 8d COMMONS e <br />4" O.G. a PANEL EDGER, AND 6" O.C. INTERMEDIATE, FOR 1/1" SWEAT14NG OR <br />LESS. NAILING FOR STRUCTURALLY APPROVED ARCHITECTURAL WALL PANELS (1/4"0 <br />SHALL BE 6D COMMON a 4" O/C AT PANEL EDGES, AND 6" O/C INTERMEDIATE. <br />e. ALL FLOORING MATERIAL TO BE 3/4" T41G PLYWOOD, NAILED AND GLUED TO FLOOR <br />JOISTS. FLOOR NAIL WITH IOd NAILS AT 3" O/C AT PANEL EDGE8, 6" O/C N THE <br />FIELD. STAGGER NAILS AT 2" O/G AT BUTT ENDS OF PLYWOOD SHEATHING <br />9. INSTALL BRIDGING N ALL (2X) FLOOR OR ROOF JOISTS AT 8'-0" MAXIhIUUM. <br />INSTALL 15LOCKM N ALL BEARING WALLS AND PARTITIONS OVER 9'-0" a <br />MID -HEIGHT. BRACE GABLE END WALLS AT 4'0" O/C WHERE WALL FRAMING 16 <br />NOT CONTINUOUS FROM FOUNDATION TO ROOF, OR AS SHOWN ON DRAAANG8. <br />1V. ALL NAILING AND BOLTNG SHALL COMPLY WITH AJMERICAN INSTITUTE OF TIMBER CONSTRUCTION <br />REQUIREMENTS. ALL NAILS EXPOSED TO THE EXTERIOR SHALL BE GALVANIZED. <br />11. ALL CONNECTION HARDWARE SHALL BE GALVANIZED AND SUPPLIED BY GR IP60N <br />STRONGTIE CO. OR EQUIVALENT. SUBMIT CUT SHEETS FOR ALL CONNECTION <br />HARDWARE TO CONTRACTOR FOR APPROVAL. ALL NAIL HOLES SHALL BE FILLED <br />OR AS PRESCRIBED BY THE MANFACTURER. <br />12. PROVIDE A SINGLE PLATE AT THE BOTTOM AND DOUBLE PLATE AT THE TOP OF ALL <br />LOAD BEARIN33 STUD WALLS. STAGGER END JOINTS N DOUBLE PLATES AT LEAST 4'-0" <br />PER DETAIL. 2 X 4 SILL PLATES FOR WARNS WALLS SHALL BE BOLTED TO <br />FOUNDATION AS PER BEARING WALL DETAIL. <br />13. LOAD BEARING STUDS SHALL BE DOUBLED AT ALL ANGLER AND AROUND ALL OPENINGS, <br />AND AT STRUCTURALLY APPROVED ARCHITECTURAL WALL PANEL JOINTS. STUDS SHALL <br />15E TRIPLED AT ALL CORNERS. <br />14. WOOD LNTELS OVER OPENINGS SHALL BE DOUBLED 2x12 HEADERS LKZ66 <br />NOTED OTHERWISE ON PLANE, WITH CONTINUOUS 1/2" PLYWOOD FILLER CUT TO <br />FULL DEPTH OF BEAM BETiLEEiV 2x MEMBERS. <br />b RAFTER SCHEDULE FOR CONVENTIONAL FRAMED AREAS. <br />MAXIMUM MAXIMUM <br />MEMBER SIZE SPAN (GYP 02) SPAN (610 2) <br />2 X 4 1 FT. 6 FT. <br />2 X 6 9 FT. 8 FT. <br />2 X 8 12 FT. 1V FT. <br />2 X 1V 14 FT. 12 FT. <br />2X12 16 FT. 14 Fr. <br />NOTE I: RAFTERS MUST BE BRACED LATERALLY BY A CONTINUOUS NAILING OF <br />SHEATHING OR BRACED AT 24" O/C, WITH MINIMUM iX4. <br />NOTE 2: RAFTER SPACING NOT TO EXCEED 24" O✓C. <br />NOTE 3: RIDGE BOARDS TO BE ONE SIZE LARGER THAN RAPIER UNLEG6 <br />OTHERWISE NOTED ON PLANS. <br />NOTE 4: CONNECTOR SCHEDULE <br />A 6Ir1PSO114 MT620 (OR EQUAL) BETWEEN CAT 15LOCKM AND ROOF TRUGGES. <br />5. SIMIPBCN H5 (OR EQUAL) WTU 04 RAFTER TAILS TO CAT BLOCKING. <br />a SIMPSON W5 (OR EQUAL) BETWEEN THE RAFTERS AND RIDGE BOARD. <br />D. SIMPSON C620 AT ENDS OF RIDGE BOARD, OR 8IMP80N JOIST <br />HANGER WERE APPLICABLE. <br />VI. PRE-ENGINEERED WOOD TRUSSES <br />1. THIS SECTION DEFINES PRE-ENGINEERED, PREFABRICATED, METAL PLATE CONNECTED <br />WOOD ROOF AND FLOOR TR AW6 AS "WOOD TRUGGEB". <br />2. TRUSS LAYOUTS SHOWN ON PLANS ARE BCI-EMATIC ONLY. TRUSS MANUFACTURER <br />AND/OR ENGINEER SHALL BE RESPONSIBLE FOR THE DES04 AND SPACING OF ALL <br />TRUS6E8 AND SHALL SUBMIT SHOP DRAWWNGS TO THE BUILDER FOR APPROVAL. <br />3. THE WOOD TRUGB MANUFACTURER MUST PARTICIPATE IN A CODE APPROVED THIRD PARTY <br />QUALITY ASSURANCE PROGRAM SUCH AS THE TRUSS PLATE NSTITUTE'6 "GI,LALITY CONTROL <br />INSPECTION PROGRAM" OR EQUIVALENT. <br />4. WOOD TRU66 MEMBERS AND CONNECTIONS GHALL BE DESIGNED FOR ALL LOADS SHOWN ON <br />THE CONTRACT DOCU'ENTS INCLUDING: LIVE, DEAD, AND CONCENTRATED LOADS, PLUS <br />WIND LOADS. <br />5. Ri3ER TO THE FLOOR PLAN AND OTHER STRUCTURAL DETAIL SWEETS FOR IMPORTANT <br />INFORMATION NOT SPECIFICALLY ADDRESSED BY THE TRUSS FRAMING LAYOUT <br />GUCHI AS WARNS WALL HEICsWTB AND CEILING VAULT DETAILS. <br />6. WOOD TRUSS DESIGN SHOP DRAWINGS SHALL INCLUDE, BUT ARE NOT LIMITED TO, <br />THE FOLLOWING INFORMATION: <br />a) SPAN LENGTH, OVERHANG AND EAVE DIMENSIONS, GLOPE AND SPACING OF <br />THE WOOD TRUSSES. <br />bJ ALL DESIGN LOADS AND THEIR POINTS OF APPLICATION, VALLEY AND CONVENTIONAL <br />FRAMING MUST BE CONSIDERED. <br />cJ ADJUSTMENTS TO ALLOWABLE VALUES. <br />dJ REACTIVATE FORCES AND THEIR LOCATIONS. <br />a) BEARING TYPE AND MINIMUM BEARING LENGTH. <br />FJ DETECTIONS. <br />g) METAL CONNECTOR PLATE TYPE, GAUGE, SIZE, AND LOCATIONL <br />Ind LUMBER SIZE, SPECIES, GRADE AND MOISTURE CONTENT. <br />I) LOCATION AND CONNECTION DESIGN OF REQUIRED CONTINUOUS LATERAL BRACING. <br />JJ NET UPLIFT LOADS BASED ON ACTUAL BUILDING DEAD LOAD. <br />w UJE15 REINFORCEMENT DETAILS FOR SABLE END TRUSSES. <br />Id VALLEY GETS FOR OVER -BUILD CONDITIONS. <br />1. LIMIT DEFLECTIONS FOR LIVE LOAD TO GPAN/960 (ROOF), 6PAN/400 (FLOOR), AND <br />LIMIT TOTAL LOAD DEFLECTIONS TO 6PAN/140 (ROOF), 6PAN/960 (FLOOR) UNLESS <br />SPECIFICALLY NOTED OTHERWISE. <br />6. FIRE RETARDANT WOOD IS NOT ALLOWABLE FOR USE AS TRUSS CHORDS OR WEBS. <br />9 WOOD TRUSSES SHALL BE DESIGNED 60 THAT MINIMAL HORIZONTAL REACTIONS <br />ARE IMPOSED ON THE SUPPORTING STRUCTURE UNDER VERTICAL LOADS. NO SLIP <br />CONNECTIONS ARE ALLOWED UNLESS OTHERWGE NOTED. CONTACT CONTRACTOR AS R'.6>UNIOD. <br />10. WOOD TRUSSES MST BE CHECKED FOR WIND. WIND VELOCITY, DESIGN VELOCITY <br />PRESSURES, AND MEAN ROOF HEIGHT MUST BE GWOM ON THE SUBMITTED SHOP DRAWINGS. <br />IL CONTINUOUS BOTTOM CHORD LATERAL. BRACING IS REGtUIRED AT A MINIMUM <br />SPACING OF IW O.C. UNLESS NOTED OTHERWiSE. BOTTOM CHORD BRACING IS <br />CONTINUOUS PROM ONE END OF THE BUILDING TO THE OTHER END. OVERLAP <br />CONTINUOUS BRACING AT LEAST ONE TRUS6 SPACE. USE A MINIMUM OF 2 X 4 <br />(ROOF), 2X6 (MOM GRADE MARKED LUMBER AT LEAST 10' LONG, WTN 2-16d <br />NAILS AT INTERMEDIATE AND 3-16d NAILS AT END CONNECTIONS. <br />12. CRO66 19RACING IS REQUIRED AT MINIMUM 10' OC. UNLESS NOTED OTHERWSE LOCATE <br />CF4066 BRACING AT OR NEAR THE BOTTOM CHORD BRACING& INSTALL CPW66 BRACING AT <br />EACH END AND AT 20' O.C. ALONG THE LENGTH OF THE LATERAL BRACIWL CROW <br />SRACNG IS ACCOI"IPL:IGHED BY ATTACHING DIAGONAL WEB BRACING TO OPPOSITE SIDES <br />OF THE SAME GROUP OF SIMILAR WED ME!'IDERS. SLOPE CRO66 BRACING IN OPPOSITE <br />DIRECTIONS AT APPROXIMATELY 45 DEGREES FORMING A CROSS "X". USE A MINIMUM OF <br />2X4 GRADE MARKED LUMBER WITH AT LEAST 3-16d NAILS AT EACW CONNECTION. <br />13. TRUSS ERECTOR 16 RESPONSIBLE FOR ALL TEMPORARY BRACING OF TRUSS <br />SYSTEM DURING CONSTRUCTION. <br />14. HANDLING, INSTALLATION, AND BRACING OF WOOD TRUSSES SHALL BE N ACCORDANCE <br />WITH "HID-91", PUBLISHED BY THE TRUSS PLATE INSTITUTE. <br />D. ALL WOOD TRUSSES SHALL BE FASTENED TO THEiR SUPPORTS WITH APPROVED HURRICANE <br />ANCHORS, RATED TO CARRY UPLIFT LOADS SPECIFIED BY TRUSS MANUFACTURER <br />16. ALL CONNECTION HARDWARE SHALL BE GALVANIZED AND &)IMPLIED BY SIMIPBON <br />STRONG -TIE, OR APPROVED EQUIVALENT MANFACTURER ALL NAIL HOLES SHOULD <br />BE FILLED, OR AS PRESCRIBED BY THE MANUFACTURER, <br />11. TRUGGIEG ARE TO BE DESIGNED TO ALLOW FOR THE PROPER ROUTING OF A/C <br />DUCT WORK AND PLIUMBNG CHASES SHALL NOT DE BLOCKED BY WOOD TRUSSES. <br />18. PILING OF PLYWOOD ON WOOD TRUSSES IS NOT ALLOWED. <br />M INSTALLATION OF BROKEN, DAMAGED, WARPED, OR IMPROPERLY REPAIRED WOOD <br />TRUGSEB IG NOT ALLOWED. <br />20. IMIPROPER OR UVAUrWoRZED FIELD ALTERATIONS OF WOOD TRUSSES IS NOT ALLOWED. <br />21. GABLE EVDWALL TRUSSES MUST TRANSFER LATERAL LOADS TO THE SWEAR WALLS AND/OR <br />THE ROOF DIAPHIRA Wl. <br />22. WOOD TRUSSES THAT DO NOT MEET INTERIOR LOAD WARNS WALLS MUST BE GHIM1'ED. <br />DO NOT PULL WOOD TRUSSES DOM TO INTERIOR BEARINGS. <br />23. GUi9 MITTALG: ALL SUBMITTALS SHALL BEAR TWE EMBOSSED SEAL OF A LICENSED SMICiURAL <br />ENGINEER IN TIE STATE OF FLORIDA AND SHALL BE SUBMITTED TO CONTRACTOR FOR <br />REVIEW PRIOR TO WOOD TRIM FABRICATION. <br />a) SUBMIT GEA1 WOOD TRUSS DESIGN CALCULATIONS AND PROFILES FOR EACH TYPE OF <br />TRIM WITH PERMANENT BRIOGNIS REQUIREMENTS. <br />b) SUBMIT WOOD TRUSS ERECTION PLAN, NCLUDING CONVECTION DETAILS AND UPLIFT <br />AN04ORS. <br />cJ SUBMIT WOOD TRU88 TEMPORARY ERECTION BRACING FLAN. <br />d) MAINTAIN COPY OF SUBMITTAL ON JOBSITE. <br />PROTECTION AGAINST TERMITES <br />1018.1 Termite Protectlon. Termite protection shell be provided by registered termiticides, including soil applied pesticides, baiting <br />systems and pesticides applied to wood, or other approved methods of termite protection labeled for use as a preventative treatment <br />to new construction. See section 202, Rogtetered I=. .acids. Upon completion of the application of the termite protective treatment, a <br />Certificate of compliance shall be Issued to the building department by the licaread pest control company that contains the rollowine <br />statement: 7rhe building has received a complete treatment for the prevetlon of subterranean termites. Treatment Is In accordance <br />with rules and laws established by the Florida Department of Agriculture and Consumer Services. <br />R318.1.1 If soil treatment is used for subterranean termite prevention, the Initial chemical soil treatment Inside the foundation <br />perimeter shall be done after all excavation, backfilling and compaction is complete. <br />RB18.1.2 If soil treatment 1e used for subterranean termite prevetion, soil area disturbed after initial chemical soil treatment shall <br />be retreated with a chemical soil treatment, Including spaces boxed or formed. <br />R310.13 If soil treatment Is used for subterranean termite prevention, space in concrete floors boxed out or formed for the <br />subsequent installation of plumbing traps, drains or any other purpose shall be created by using plastic or metal permanently <br />placed forms of sufrlaert depth to eliminate any planned soil disturbance after Initial chemical soil treatment. <br />R318.1A If soil treatment Is used for subterranean termite prevention, chemically treated soil shall be protected with a minimum 6 <br />mil vapor retarder to protect against rainfall dilution. If rainfall ocare before vapor retarder placement, retreatmet is required. <br />Any work Including placement of reinforcing steel, done after chemical treatment until the concrete floor Is poured, shall be done <br />In such manner as to avoid penetrating or disturbing treated soil. <br />R318.1b If soil treatment is used for subterranean termite prevetlon, concrete overpow or mortar accumulated along the exterior <br />foundation perimeter shall be removed prior to exterior chemical soil treatment, to enhance vertical penetration of the chemicals. <br />R318.IA If soil treatment Is used for subterranean termite prevention, chemical soil treatments shall also be applied under all <br />exterior concrete or grade within I foot (305 mm) of the primary structure eidewalls. Also, a vertical chemical barrier shall be <br />applied promptly after construction is completed, including Initial landscaping and irrigation/sprinkler installation. Any soil disturbed <br />after the chemical vertical barrier Is applied shall be prompt19 retreated. <br />R318.1.1 If a registered termitieids formulated and registered as a balt system is used for subterranean termite prevention, <br />Sections R318.1.1 through 11310.IA do not apply: however, a signed contract assuring the installation, maintenance and monitoring <br />of the baiting system for a minimum of 5 years from the Issue of the Certificate of Occupancy shall be provided to the building <br />official prior to the pouring of that slab, and the aysteo must be installed prior to final building approval. If the baiting system <br />directions for use require a monitoring phase prior to installation of the pesticide active ingredient, the installation of the <br />monitoring phase components shell be dawned to constitute Installation of the system. <br />R318.1A If a registered termiticide formulated and registered as a wood treatment Is used for subterranean termite prevention, <br />Sections R318.1.1 through R31W.6 do not apply. Application of the wood treatment termiticlde shell be as required by label <br />directions for use, and must be completed prior to final building approval. <br />R3192 Penetration. Protective sleeves around piping penetrating concrete slab -on -grads floors shall not be of cellulose -containing <br />materials and, if atoll treatment is used for subterranean termite protection, the sleeve shall have a maximum wall thickness of civic <br />Inch (025 mm) and be sealed within the slab using non-corroslve clamping device to eliminate the annular space between pips and <br />the sleeve. No termiticides shall be applied inside the sleeve. <br />R3183 Cleaning. Celle and cavities in masonry units and air gaps between brick stone or masorcy veneers and the structure shall ba <br />cleaned of all non -preservative treated or non -naturally durable wood, or other cellulose -containing material prior to concrete <br />placement. <br />Exception. Inorganic material manufactured for closing calls In foundation concrete masonry unit construction or clean earth fill <br />placed in concrete masonry unit volde below slab level before temps treatment Is performed. <br />R318.4 Concrete bearing ledgel5ric. stone or other veneer shall be oupportod by a concrete bearing ledge at least equal to the total <br />thickness of the brick stone or otter veneer which to poured integrally with the concrete foundation. No supplemental concrete <br />foundation pours which will create a hidden cold joint shall be used without supplemental treatment in the foundation unless there Is an <br />approved physical barrier. An approved physical barrier shall also be Installed from below the wall sill plate or first block course <br />horizontally to embed in a mortar joint. If masonry veneer extends below grade, a termite protective treatment must be applied to the <br />cavity created between the veneer and the foundation, In Ileu of a phyelcal barrier. <br />Exception: Veneer supported by a structural member secured to the foundation sidewalk In accordancew with AC1530/ASCE 5/TMS <br />402, provided at least a 6 inch (152 mm) clear Inspection space of the foudation eldeuall exterior exist between the veneer and <br />the top of any soil, sod, mulch or other organic landscaping component, doe*, apron, porch, walk or any other work I medlately <br />adjacent to or adjoining the structure. <br />R318.5 Foam plastic protection. Extruded and expanded polystyrene, polyusocyar urate and other foam plastics shall not be Installed on <br />the exterior face or :ender Interior or exterior foundation walls or slab foundations located below grade. The clearance between roam <br />plastics installed above grade and exposed earth shall be at least 6 Inches (02 mm). <br />Exceptions, <br />I. Suildi ngs where the structural members of walls, floors, cellknge and roofs are entirely of noncombustible materials or <br />pressure -preservative- treated wood. <br />2. When In addition to the requirements of Section R318.1, an approved method of protecting the foam plastic and structure from <br />subterranean termite damage Is used. <br />3. On the Interior side of basement walls. <br />R318A Protection against decay and termitee. condansato lines, irrigation/epri War system risers for spray heads, and roof downspouts <br />shall discharge at least I foot (300 mm) away from the structure sldewall, whether by underground piping, tall exterslons or splash <br />blocks. Gutters with downspouts are required on all buildings with eaves of less than 6 Inches (152 mm) horizontal projection except <br />for gable and rakes or on a roof above another roof. <br />11018.1 Preparation or building site and removal of debris. <br />R318.1.1 All building sass shall be graded to provide drainage under all portions of the building not occupied by basements. <br />R318.1.2 The foundation and the area encompassed within 1 foot (305 mm) therein shall have all vegetation, stumps, dead roots, <br />cardboard, trash and foreign material removed and the fill material shall be free of vegetation and foreign material. The fill shall be <br />compacted to meows adequate support of the foundation. <br />R318.13 After all work is completed, loose wood and debris shall be completely removed from under the building and within I root <br />(3M mm) thereof. All wood forms and supports shall be completely removed. This Includes, but is not limited to: wooden grade <br />stakes, forms, contraction spacers, tub trap boxes, plumbing supports, bracing, shoring, forms or other cellulose -containing <br />material placed in afg location where such materials are not clearly vleible and readlly removable prior to completion of the work <br />Wood shall not be stored In contact with the ground under any building. <br />TYPICAL NAILING SCHEDULE <br />Ledger strip <br />16d common <br />3 at each joist <br />Sole plate to joist or <br />16d common <br />16" oz. <br />b , face nail <br />Top of sob plate to stud, <br />16d common <br />2 <br />and nailed <br />Stud to sole plate, toe nail <br />8d common <br />4 <br />Doubled studs, face nail <br />led common <br />24" OL. <br />Doubled top plates, face <br />led common <br />16" along each <br />nail <br />edge <br />Continuous header to <br />8d common <br />3 <br />stud, toe nail <br />D(8 sheathing or bee to <br />8d common <br />2 <br />each bearing face nail <br />Over Des sheathlrig to <br />Sd common <br />3 <br />each bearing face nail <br />Build-Lp corner etude <br />lbd common <br />24" OL. <br />Build-up gridero and <br />Zed common <br />32" O.C. at top <br />beans up to three members <br />and bottom and <br />staggered 2 ends <br />at each <br />lice <br />In- G pecan Sheathing <br />/n <br />11 ga 1-144 <br />4"OL. at edges <br />1/16" head <br />8" or- at other bear- <br />5/8- G psun Sheathing <br />11 ga 1-3/4" <br />440L. at edges <br />1/16" head <br />8" or- at other bear . <br />Grow lUallboard <br />ON <br />1-3/8" dr9wall nail <br />1"OL. on ceilings <br />8"OL. on walls <br />5/8" <br />1-1/2" dr9wall nail <br />70L. on ceilings <br />8"OL. on walls <br />Hardboard Lap Sift <br />8d corrosion resistant <br />16" O.C. at top <br />Direct to Studs <br />with minimum shank <br />and bottom edges <br />dia. of 009W inch <br />and minimum head <br />dia. of 0240 Inch <br />Hardboard Lap Siding, <br />led corrosion reslstant <br />16" O.C. at top <br />over sheathing <br />with minimum sharper <br />and bottom edges <br />dia. of 00W Inch <br />and minimum head <br />dia. of 0240 inch <br />Hardboard Panel sidlrlg, <br />bd corrosion resistant <br />6" OL. at edges <br />Direct to Etude <br />with minimum eharlk <br />12" OL. at <br />dia. of OAMO inch <br />Intermediate <br />and minimum head <br />supporter <br />dia. of e225 inch <br />Hardboard Panel siding, <br />8d corrosion resistant <br />6" OL. at edges <br />Over to Shewthing <br />with minimum shank <br />12' OL. at <br />dia. of e0920 inch <br />Intermediate <br />and minimum head <br />supports <br />dia. of e225 inch <br />AS PER FLORIDA BUILDING CODE 2010, RESIDENTIAL <br />TABLE R301.2.1.3 AN D <br />ASCE 7-10 METHODS <br />ULTIMATE WIND SPEED (MPH) <br />140 <br />EXPOSURE CATEGORY <br />B <br />BUILDING RISK CATEGORY <br />II <br />ROOF SLOPE <br />Roof > 7 to 27 degrees <br />INTERNAL PRESSURE <br />COEFFICIENT <br />ENCLOSED 0.18 <br />TOPOGRAPHICAL FACTOR <br />FLAT 1.0 <br />MAXIMUM BUILDING HEIGHT <br />35 <br />FT <br />3 <br />2 <br />3 3 <br />2 <br />3 <br />� I <br />I <br />a Zone ¢ 1 5 5 1 2CD <br />a <br />I <br />I I <br />a <br />NI <br />I I <br />r„ lei <br />�, <br />I <br />a <br />13 <br />F-3�2 <br />31 <br />2 13 <br />WCHS <br />Roof <br />WIDTH EDGE <br />STRIPSPS (a) <br />8 <br />FT <br />OPENING PROTECTION REQUIRED <br />COMPONENT & CLADDING DESIGN PRESSURE (PSF) <br />Area <br />ZONE <br />1 <br />ZONE 2 <br />ZONE 3 <br />ZONE 4 <br />ZONE 5 <br />of C&C (SF) <br />Positive <br />Negative <br />Positive <br />Negative <br />Positive <br />Negative <br />Positive <br />Negative <br />Positive <br />Negative <br />10 <br />21.3 <br />-33.9 <br />21.3 <br />-59.0 <br />21.3 <br />-87.3 <br />37.1 <br />-40.1 <br />37.1 <br />-49.6 <br />20 <br />19.4 <br />-33.0 <br />19.4 <br />-54.3 <br />19.4 <br />-81.6 <br />35.4 <br />-38.5 <br />35.4 <br />-46.2 <br />50 <br />16.9 <br />-31.7 <br />16.9 <br />-48.0 <br />16.9 <br />-74.0 <br />33.2 <br />-36.3 <br />33.2 <br />-41.8 <br />100 <br />16.8 <br />-30.8 <br />16.8 <br />-43.3 <br />16.8 <br />-68.4 <br />31.5 <br />-34.7 <br />31.5 <br />-38.5 <br />WINDOWS AND DOORS DESIGN PRESSURE (PSF) BASED ON Vasd <br />Area (SF) or <br />ZONE 1 <br />ZONE 2 <br />ZONE 3 <br />ZONE 4 <br />ZONE 5 <br />Positive <br />Negative <br />Positive <br />Negative <br />Positive <br />Negative <br />Positive <br />Negative <br />Positive <br />Negative <br />description <br />10 <br />16.0 <br />-20.3 <br />16.0 <br />-35.4 <br />16.0 <br />-52.4 <br />22.2 <br />-24.1 <br />22.2 <br />-29.7 <br />20 <br />16.0 <br />-19.8 <br />16.0 <br />-32.6 <br />16.0 <br />-49.0 <br />21.2 <br />-23.1 <br />21.2 <br />-27.7 <br />50 <br />16.0 <br />-19.0 <br />16.0 <br />-28.8 <br />16.0 <br />-44.4 <br />19.9 <br />-21.8 <br />19.9 <br />-25.1 <br />100 <br />16.0 <br />-18.5 <br />16.0 <br />-26.0 <br />16.0 <br />-41.0 <br />18.9 <br />-20.8 <br />18.9 <br />-23.1 <br />Garage Doors <br />19.2 <br />-21.4 <br />19.2 <br />-21.4 <br />CONNECTOR PRIDMT APPROVALS <br />APPL"TiON <br />SIMPSON GON OTOR <br />Fl- APPROVAL No. <br />GAP5 AND BA5E5 <br />GG, EGG, PG, ECG <br />FL 10860 <br />ABU <br />FL 10b4q <br />GONGRE7E / MA501� <br />GONNEGTOR5 <br />HU, HUG <br />FL 10655 <br />HST, MBHA <br />FL l obbb <br />HD, HOQB, HHDQ <br />FL 10441 <br />DETAL, F6TR, HETA, HHETA, HM, <br />HT5M, H&AM, H6UM, 1_611M, LTA, META, <br />M5TAM, MSTGM, MT5M <br />FL 11473 <br />Ht5A10, W, MST, MSTG, V6T <br />FL 11470 <br />HTT, LTT <br />FL 114gb <br />HAN6ER5 <br />L55U, L9U, THA <br />FL 10447 <br />H 46, HSUL, WAR, HU, HUG, IUS,IUT, LU, <br />LUS, MUA L, SUR, U <br />FL 10531 / FL 10b55 <br />H611, H6UQ, H6U5, HH6U, M46, HUGQ, <br />141.15, L.GU, L.115, WU, W5GPT, TWA, TH6B, <br />TH6a TH6W, THJ U <br />FL 114bb <br />B, BA, HB, L.BV <br />FL Illbb <br />E6, 65, 6L5, 61-5T, 6LT, 6LTV, 1­1613, H61-5, <br />%LT, H6LTV, HHB, HHBD, HIT, HK WWI, <br />HWU, ITS,ITT, ME6, MIT, MSG, W, WI, WNW, <br />WNPU, WP, WPM, WPU, <br />FL I0bb1 <br />STRAP5 AND TIES <br />A, FG, &A, HH, L, LS, LPT, Z <br />FL 1044b <br />ETA, H, HST, HTS,LFTA, LTS, MTS, R5P, <br />RST, 50, SPH, 55P <br />FL 10456 <br />GMST, 05, FHA, HST, LSTA, LSTI, MST, <br />M5TA4 M5TG, M5TI, 5T <br />FL lOb52 <br />HOLES AT 12" O.C. SPACING f <br />MAX FOR FASTENERS, <br />RE: FBC - TABLE R30012.1.2 <br />FOR FASTENER TYPE • I <br />I I� <br />/HOLES IN CENTER OF • <br />PLYWOOD FOR PRESSURE <br />EQUALIZATION e <br />\-MIN. vry PLYWOOD s r It I <br />5" <br />W TO 8' MAX <br />PANEL SPAN <br />2 X 4 BRACING AT <br />SEAM ON INTERIOR <br />FACE OF PANEL <br />HOLES AT 9" OR 12" O.G. <br />SPACING MAX. FOR FASTENERS, <br />RE: FBC - TABLE R301.2.1.2 FOR <br />FASTENER TYPE <br />HOLES IN CENTER OF <br />PLYWOOD FOR PRESSURE <br />EQUALIZATION <br />2" TEN GAUGE WOOD SCREUIS <br />TO FASTEN PLYWOOD TO BRACING <br />2 X 4 BRACING ON EXTERIOR <br />FACE OF PANEL <br />WOOD STRUCTURAL PANEL - OPENING PROTECTION OPTION <br />IAA PLYWOOD <br />g <br />�r� <br />0 <br />W <br />N <br />.J <br />Z <br />I- <br />o tl <br />-�o� <br />OU <br />LU <br />J h END <br />Uj <br />Z <br />0Nmm� <br />_ <br />Z <br />0 <br />O <br />�3 <br />tl <br />a; <br />Z <br />') <br />L LL <br />n <br />C <br />W <br />Z <br />� J <br />O Q <br />� o F- <br />Z N Z <br />0ww <br />O o <br />w F_ <br />F- <br />w <br />iZ <br />- Q - LC., <br />F-UJ to Z U <br />n U a <br />J Z <br />=ao <br />LU Up0m <br />M' Z Q <br />Www91 <br />m <br />LLJ rwOQ <br />ri <br />U <br />Z <br />U) <br />W_ <br />Z <br />CD <br />cC <br />G <br />O <br />U <br />Z <br />Q <br />Z <br />W <br />O <br />CU <br />Q <br />W <br />Z <br />Q <br />W <br />0 <br />Z <br />J <br />F- <br />D <br />1) <br />w= <br />F- <br />XLL <br />0 0 <br />OZ <br />O <br />w� <br />¢O <br />LLJ U) a.J <br />QZ <br />0 <br />ojz <br />Z 0 <br />FU)o <br />a <br />U) <br />F- <br />Z <br />00 <br />gZ <br />N Q <br />0 <br />W <br />Z <br />LL 00 <br />au) <br />J (n <br />Q- <br />>F <br />v_� w <br />z0 <br />2w <br />Q= <br />F- <br />oXw <br />U)�¢ <br />F=••Qvi <br />a <br />Q <br />0 <br />LL <br />U) <br />CL <br />U <br />Q <br />O� <br />W <br />J <br />2W <br />W N <br />O <br />FIRST ISSUE <br />12/04/13 <br />SECOND ISSUE <br />THIRD ISSUE <br />FOURTH ISSUE <br />ADDENDUM <br />ADDENDUM <br />2 <br />ADDENDUM <br />3 <br />REVISIONS <br />SEAL DATE <br />SHEET <br />SD1 <br />