I I ELECTRICAL GENERAL NOTES <br />GENERAL: <br />l . PROVIDE SHALL MEAN FURNISH AND INSTALL. <br />2. THE COMPLETE ELECTRICAL SYSTEM SHALL BE PROVIDED BY THE CONTRACTOR <br />SHALL INCLUDE ALL WORK, MATERIALS AND APPARATUSES SPECIFIED HEREINAFTER <br />AND INDICATED ON THE DRAWINGS. ALL WORKMANSHOP SHALL BE OF THE <br />HGIHEST QUALITY AND NO SUBSTANDARD WORK WILL BE ACCEPTED, <br />3. PROVIDE ALL WORK AND ELECTRICAL SYSTEMS COMPONENTS REQUIRED TO SERVE <br />LOADS AS SPECIFIED HEREINAFTER AND INDICATED IN THE DRAWINGS. THE WORK <br />SHALL INCLUDE COMPLETE TESTING OF ALL ELECTRICAL SYSTEMS AT THE <br />COMPLETION OF THE WORK AND MAKE ANY CHANGES AND ADJUSTMENTS <br />NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEMS. <br />4. MAKE A THOROUGH EXAMINATION OF THE SITE AND THE CONTRACT DOCUMENTS <br />PRIOR TO EXECUTING THE CONTRACT. NO CLAIM FOR ADDITIONAL <br />COMPENSATION WILL BE RECOGNIZED FOR DIFFICULTIES ENCOUNTERED WHICH <br />AN EXAMINATION OF SITE CONDITIONS AND CONTRACT DOCUMENTS WOULD <br />HAVE REVEALED. <br />5. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED ABOVE THE FLOODPLAIN <br />ELEVATION. CONTRACTOR SHALL COORDINATE FLOODPLAIN ELEVATION AND <br />EQUIPMENT REQUIREMENTS WITH OWNER PRIOR TO ROUGH -IN. <br />6. THE PLANS ARE GENERALLY DIAGRAMMATIC. COORDINATE ALL WORK WITH <br />OTHER TRADES AS REQUIRED TO AVOID INTERFERENCES BETWEEN TRADES (I.E. <br />BEAMS, CONDUITS, EQUIPMENT, DUCTWORK, ECT.) <br />WORK PERFORMANCE: <br />1. JOB SITE SAFETY AND WORKER SAFETY IS THE RESPONSIBILITY OF THE CONTRACTOR <br />2. ARRANGE, PHASE AND PERFORM ALL WORK DURING TIME PERIODS SCHEDULED <br />WITH AND ACCEPTABLE TO THE OWNER BEFORE PROCEEDING, NO ADDITIONAL <br />COMPENSATION WILL BE AUTHORIZED FOR WORK NECESSITATED BY ILL-TIMED, <br />DEFECTIVE, OR NON -CONFORMING WORK. <br />3. THE CONTRACTOR SHALL ENSURE THAT ALL SYSTEMS OPERATE AS DESIGNED <br />AND/OR REQUIRED AND SHALL REVIEW THEIR OPERATION WITH THE OWNER UPON <br />COMPLETION OF CONSTRUCTION AND TESTING. COMPILE COMPLETE AND <br />UPDATED AS -BUILT DRAWINGS/DOCUMENTS AND ISSUE ONE (1) SET TO THE <br />OWNER. <br />4. ELECTRICAL WORK SHALL BE ACCOMPLISHED WITH ALL AFFECTED CIRCUITS OR <br />EQUIPMENT DE -ENERGIZED, WHEN AN ELECTRICAL OUTAGE CANNOT BE <br />ACCOMPLISHED IN THIS MANNER FOR THE REQUIRED WORK, THE FOLLOWING <br />REQUIRED WORK, THE FOLLOWING REQUIREMENTS ARE MANDATORY: <br />4.1. ELECTRICIANS MUST USE AND WEAR FULL PROTECTIVE EQUIPMENT (PPE). <br />WHILE WORKING ON ENERGIZED SYSTEMS IN ACCORDANCE W/ NFPA 70E. <br />THE LEVEL OF PPE SHALL BE DETERMINED BY A COMPUTER GENERATED ARC <br />FLASH CALCULATION PROVIDED AND PAID FOR BY THE CONTRACTOR. THE <br />ARC FLASH DATA SHALL BE PRESENTED WITH THE SUBMITTAL BELOW. <br />4.2. WORK ON ENERGIZED CIRCUITS OR EQUIPMENT CANNOT BEGIN UNTIL PRIOR <br />WRITTEN APPROVAL IS OBTAINED FROM THE OWNER. <br />5. ENSURE THAT ELECTRICAL SERVICE REMAINS UNINTERRUPTED FOR OTHER BUILDINGS <br />AND FACTILITIES AT ALL TIMES. PERFORM ALL TEMPORARY WORK NECESSARY TO <br />MAINTAIN CONTINUITY OF ELECTRICAL SERVICE WHEN CONNECTION IS MADE TO <br />EXISTING SYSTEMS. <br />6. ELECTRICAL EQUIPMENT SHALL NOT BE STORED OUTDOORS. EQUIPMENT SHALL BE <br />STORED IN AN OWNER/E3NGINEER APPROVED MEDIUM AND LOCATION. <br />CODES & STANDARDS: <br />l . PERFORM WORK IN COMPLIANCE WITH THE LATEST EDITION OF ALL <br />APPLICABLE,FEDERAL, STATE AND LOCAL CODES, REGULATIONS AND STANDARDS, <br />TO INCLUDE THOSE LISTED BELOW, ADOPTED BY THE AUTHORITY HAVING <br />JURISDICTION. WHERE DIFFERENCES MAY OCCUR THE MORE STRINGENT <br />REQUIREMENTS SHALL GOVERN. IN CASE OF CONFLICT PROVIDE WRITTEN <br />NOTIFCATION AND OBTAIN A DECISION FROM THE ARCHITECT. <br />1.1. NFPA 70: NATIONAL ELECTRICAL CODE (2020) <br />1.2. NFPA 70E: STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE (2018) <br />1.3. NFPA 72: NATIONAL FIRE ALARM CODE (2019) <br />1.4. NFPA 241: STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION <br />AND DEMOLITION OPERATIONS (2019) <br />1.5. FBC: FLORIDA BUILDING CODE 8TH ED. (2023) <br />1.6. OASHA PART 1910: OCCUPATIONAL SAFETY AND HEALTH STANDARDS <br />1.7. OASHA PART 1926: SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION <br />MATERIALS AND METHODS: <br />1. MATERIALS AND APPARATUSES SHALL COMPLY WITH ALL APPLICABLE TESTS, <br />RATINGS, SPECIFICATIONS AND REQUIREMENTS OF THE IEEE,NEMA, NFPA, AND UL, <br />SHALL BEAR THE UL LABEL OF APPROVAL AND BE LISTED FOR THE PROPOSED <br />APPLICATION. <br />2. FINISHED PRODUCTS SHALL BE FACTORY PRIMED AND FINISH COATED WITH THE <br />MANUFACTURER'S PRIME COAT AND STANDARD FINISH UNLESS SPECIFIED <br />OTHERWISE BY THE ARCHITECT. <br />3. UNLESS OTHERWISE SPECIFIED, UNFINISHED PRODUCTS SHALL BE GALVANIZED, <br />COATED OR PLATED TO RESIST CORROSION. <br />4. INSTALLATIONS SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES, AS <br />RECOMMENDED BY THE MANUFACTURER AND AS CLOSE AS PRACTICABLE TO <br />LOCATIONS INDICATED ON DRAWINGS. <br />5. INSTALLATIONS SHALL FACILITATE MAINTENANCE AND REPAIR OR REPLACEMENT <br />OF EQUIPMENT COMPONENTS. ACCESS, WORKING SPACES AND CLEARANCES <br />SHALL NOT BE LESS THAN SPECIFIED BY THE NEC FOR ALL VOLTAGES SPECIFIED. <br />6. PROVIDE APPROVED FIRE STOPPING MATERIALS AT ALL CHASES TO PREVENT <br />DRAFTS. <br />2 1 ELECTRICAL GENERAL NOTES <br />7. FIRE RATING: RESTORE FIRE RATING WHERE PIERCING OCCURS THROUGH FIRE <br />RATED CEILINGS OR BETWEEN FIRE RATED WALLS. FIRE STOP MATERIALS SHALL BE <br />AS MANUFACTURED BY 3M COMPANY AND UL LISTED FOR USE IN THE <br />CONSTRUCTION ASSEMBLY IN WHICH IT IS TO BE USED. REFER TO ARCHITECTURAL <br />PLANS FOR LOCATIONS OF FIRE RATED WALLS AND CEILINGS. <br />IDENTIFICATION: <br />1. INSTALL LABEL TAGS ON ALL WIRE AND CABLE IN JUNCTION BOXES, WIREWAYS <br />AND WIRING GUTTER OF PANELS. TAGS SHALL IDENTIFY WIRE AND CABLE CIRCUIT <br />NUMBER AND/OR EQUIPMENT SERVED AS INDICATED ON DRAWINGS. <br />2. JUNCTION BOXES SHALL BE LABELED IN A PERMANENT MANNER REFLECTING <br />PANELBOARD/CIRCUIT NUMBER OF BRANCH CIRCUIT WIRING CONTAINED WITHIN. <br />3. PANEL BOARD DIRECTORIES SHALL BE TYPEWRITTEN, REFLECTING RECORD <br />CONDITION TO INCLUDE CIRCUIT NUMBER, TYPE AND LOCATION OF LOAD. <br />RACEWAYS: <br />1. RACEWAYS: <br />1.1. INTERIOR EXPOSED, CONCEALED IN WALLS OR ABOVE CEILINGS: ELECTRICAL <br />METALLIC TUBING (EMT) OR MC CABLE <br />2. ALL CONDUIT SHALL BE PROPERLY ALIGNED, GROUPED AND SUPPORTED. EXPOSED <br />CONDUIT SHALL BE INSTALLED AT RIGHT ANGLES TO OR PARALLEL TO THE <br />PRINCIPAL STRUCTURAL MEMBERS. PROVIDE SUPPORT A MINIMUM OF 18" FROM <br />BENDS AND OUTLET BOXES AND ON INTERVALS NOT TO EXCEED 8'-0". CONDUIT IS <br />NOT TO SPAN ANY SPACE UNSUPPORTED. ALL CONDUIT SHALL BE SUPPORTED <br />FROM STRUCTURE AND NOT FROM CEILING SUPPORT SYSTEM. <br />3. PROVIDE NYLON PULL CORD AND LEAVE IN PLACE IN EACH EMPTY CONDUIT. <br />BOXES: <br />1. ALL BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH SUITABLE <br />SCREW FASTENED COVERS, OPEN KNOCK -OUTS OR HOLES IN BOXES SHALL BE <br />PLUGGED WITH A SUITABLE BLANKING DEVICE. <br />CONDUCTORS: <br />1. UNLESS OTHERWISE INDICATED, ALL BRANCH CIRCUIT CONDUCTORS SHALL BE NO. <br />12 AWG. BRANCH CIRCUITS RUN OVER 75-FEET IN LENGTH, MEASURING ONE WAY <br />FROM THE FIRE OUTLET OF THE CIRCUIT TO THE PANEL, SHALL BE NO. 10 AWG FOR <br />THE ENTIRE CIRCUIT. <br />2. CONDUCTORS SHALL BE COPPER WITH THHN/THWN-2 90 C INSULATION, THE <br />FOLLOWING SYSTEMS OF COLOR CORDING SHALL BE STRICTLY ADHERED TO AND <br />SHALL BE CONSISTENTLY FOLLOWED THROUGHOUT: <br />2.1. GROUND WIRES: GREEN <br />2.2. GROUNDED NEUTRAL WIRES: WHITE <br />2.3. 208/120 VOLT, UNGROUNDED PHASE WIRES: BLACK, RED AND BLUE <br />2.4. 480/270 VOLT, UNGROUNDED PHASE WIRES: BROWN, ORANGE AND YELLOW <br />2.4.1. WHERE EXISTING BASE BUILDING COLOR CODING DIFFERS FROM COLOR <br />CODING ASSIGNED HERE -IN, USE EXISTING COLOR CODING AS REQUIRED <br />TO MAINTAIN CONSISTENCY. <br />3. WIRING IN AIR PLENUMS OR PLENUM SPACES NOT IN CONDUIT SHALL BE UL LISTED <br />AS SUITABLE FOR PLENUM USE. <br />4. CONDUITS AND WIRING PENETRATING RATED FLOORS AND WALLS SHALL BE <br />SEALED TO MAINTAIN FIRE RATING AND INTEGRITY OF SEPARATION. <br />5. FOR NEW CIRCUITS, MULTIPLE CIRCUITS IN SAME CONDUIT SHALL NOT SHARE <br />NEUTRAL CONDUCTORS. FOR EXISTING CIRCUITS, WHERE REQUIRED BY NEC, <br />PROVIDE AND INSTALL HANDLE TIES ON EXISTING CIRCUIT BREAKERS. <br />6. INSTALL INSULATED SPRING WIRE CONNECTORS WITH PLASTIC CAPS FOR COPPER <br />CONDUCTOR SPLICES AND TAPS, 10 AWG AND SMALLER. <br />7. "PUSH -IN" OR "STAB" TYPE CONNECTORS ARE NOT ACCEPTABLE. <br />GROUNDING: <br />1. THE ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS <br />REQUIRED BY THE NEC AND AS SPECIFIED HEREINAFTER. <br />2. ALL METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE <br />AT ALL JOINTS AND AT ALL BOXES, CABINETS, FITTINGS, AND EQUIPMENT. METALLIC <br />RACEWAYS SHALL BE CONNECTED TO A DIRECT GROUND AT THE POINT OF <br />ELECTRICAL SERVICE ENTRANCE AND SHALL BE ELECTRICALLY CONTINUOUS <br />THROUGHOUT THE ENTIRE SYSTEM. <br />3. ALL GROUND CONDUCTORS SHALL BE INSULATED COPPER UON. <br />4. ALL RACEWAYS WITH NO. 10 OR 12 AWG PHASE CONDUCTORS FOR <br />RECEPTACLES, LIGHTING FIXTURES AND SIMILAR CIRCUITS (NEW BRANCH CIRCUITS) <br />SHALL BE PROVIDED WITH A PARITY SIZED GREEN EQUIPMENT GROUND <br />CONDUCTOR. GROUND CONDUCTOR SHALL BE INSTALLED IN ENTIRE RACEWAY <br />SYSTEM INCLUDING WALL SWITCHES AND FLEXIBLE CONDUIT TO LIGHT FIXTURES. <br />EQUIPMENT GROUND CONDUCTOR SIZES FOR CIRCUITS WITH PHASE <br />CONDUCTORS LARGER THAN NO. 12 AWG ARE INDICTED ON DRAWINGS. <br />GROUND CONDUCTORS SHALL BE CONNECTED TO GROUND BUS IN PANEL <br />BOARDS. <br />5. TERMINATE FEEDER AND BRANCH CIRCUIT INSULATED EQUIPMENT GROUNDING <br />CONDUCTORS WITH GROUNDING LUG, BUS OR BUSHING. CONDUCTORS LOOPED <br />UNDER SCREW OR BOLT HEADS WILL NOT BE PERMITTED. <br />6. INSTALL CLAMP -ON CONNECTORS ON CLEAN METAL CONTACT SURFACES TO <br />ENSURE ELECTRICAL CONDUCTIVITY AND CIRCUIT INTEGRITY. <br />7. TEST THE GROUNDING SYSTEM TO ASSURE CONTINUITY AND THAT RESISTANCE TO <br />GROUND DOES NOT EXCEED 25 OHMS UNLESS OTHERWISE NOTED. TEST EACH <br />GROUND ROD FOR RESISTANCE TO GROUND BEFORE MAKING CONNECTIONS TO <br />THE ROD; THEN TIE ENTIRE GROUNDING SYSTEM TOGETHER AND TEST FOR <br />RESISTANCE TO GROUND. MAKE RESISTANCE MEASUREMENTS IN NORMALLY DRY <br />WEATHER, NOT LESS THAN 48 HOURS AFTER RAINFALL. MAKE GROUND RESISTANCE <br />MEASUREMENTS WITH A GROUND RESISTANCE TEST METER CALIBRATED WITHIN THE <br />LAST TWELVE MONTHS. <br />3 I ELECTRICAL GENERAL NOTES <br />SWITCHES & RECEPTACLES: <br />l . RECEPTACLES SHALL BE THE GROUNDING TYPE WITH GROUND CONNECTION <br />MADE THROUGH AN EXTRA POLE WHICH SHALL BE PERMANENTLY CONNECTED TO <br />GROUND CONDUCTOR. <br />2. CONNECT WIRING DEVICES BY WRAPPING SOLID CONDUCTOR AROUND SCREW <br />TERMINAL. WHEN STRANDED CONDUCTORS ARE USED IN LIEU OF SOLID, USE <br />CRIMP ON FORK TERMINALS FOR DEVICE TERMINATIONS. DO NOT PLACE BARE <br />STRANDED CONDUCTORS DIRECTLY UNDER DEVICE SCREWS. <br />3. GFCI RECEPTACLES SHALL MEET CURRENT UL 943 REQUIREMENTS WITH <br />AUTO -MONITORING OR SELF -TEST FUNCTIONALITY; IF THE SELF -TEST FUNCTION <br />DETECTS A PROBLEMS, THE UNIT MUST DENY POWER OR PROVIDE VISUAL AND/OR <br />AUDIBLE INDICATION. <br />4. GFCI RECEPTACLES LOCATED IN DAMP, WET OR EXTERIOR LOCATIONS SHALL BE <br />WEATHER -RESISTANT TYPE TO COMPLY WITH NEC 406.9. <br />5. RECEPTACLES FOR 20 AMPERE, 120 VOLT APPLICATION SHALL BE SPECIFICATION <br />GRADE, THREE -WIRE, TWO POLE, RATED 20 AMPERES AT 125 VOLTS, PASS AND <br />SEYMOUR OR APPROVED EQUAL. <br />6. LIGHT SWITCHES SHALL BE SPECIFICATION GRADE, 120/277 VOLT, PASS AND <br />SEYMOUR OR APPROVED EQUAL. <br />7. PROVIDE WALL PLATES FOR SINGLE AND COMBINATION DEVICES OR TYPES, SIZES <br />AND WITH GANGING AND CUTOUTS AS INDICATED, SELECT PLATES WHICH MATE <br />AND MATCH WIRING DEVICES TO WHICH ATTACHED. CONSTRUCT WITH METAL <br />SCREWS FOR SECURING PLATES TO DEVICES; SCREW HEADS COLOR TO MATCH <br />FINISH OF PLATES, WALL PLATES COLOR TO MATCH DEVICES, COLOR BY <br />ARCHITECT. <br />EQUIPMENT: <br />CIRCUIT BREAKERS SHALL PLUG STYLE BREAKERS <br />LIGHTING FIXTURES: <br />1. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE IN ALL RESPECTS ALL <br />LIGHTING FIXTURES INDICATED ON THE PLANS. <br />2. FIXTURES SHALL BE SUPPORTED INDEPENDENTLY FROM CEILING AND SHALL BE <br />PROPERLY AND CAREFULLY ALIGNED. FIXTURE BOTTOMS, EDGES, AND ENDS SHALL <br />BE EVEN AND TRIM SHALL BE SNUG TO SURFACE. THE CONTRACTOR SHALL FURNISH <br />AND INSTALL ALL NECESSARY HARDWARE, ECT, FOR SUPPORT OF FIXTURES AS <br />REQUIRED. <br />3. RECESSED FIXTURES SHALL BE CONNECTED WITH A MAXIMUM 6 FOOT FLEXIBLE <br />WHIP. <br />4. FIXTURES SHALL BE CLEAN AND LENSES SHALL BE CLEAR OF FINGERPRINTS. <br />MANUALS: <br />CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING MANUAL AND <br />MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING OWNER. THE MANUALS SHALL <br />INCLUDE, AT A MINIMUM, THE FOLLOWING: <br />1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTION FOR EACH <br />PIECE OF EQUIPMENT REQUIRING MAINTENANCE. <br />2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF <br />EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE <br />ACTIONS SHALL BE CLEARLY IDENTIFIED. <br />3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY. <br />DOCUMENTATION REQUIREMENTS: <br />THE CONSTRUCTION DOCUMENTS SHALL SPECIFY THAT DOCUMENTS CERTIFYING THAT <br />THE INSTALLED LIGHTING CONTROLS MEET DOCUMENTED PERFORMANCE CRITERIA OF <br />SECTION C405 ARE TO BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS FROM <br />THE DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY. <br />4 1 LIGHTING FIXTURE &CONTROL SCHEDULE <br />LIGHTING FIXTURE SCHEDULE <br />TYPE PER <br />MANUFACTURER <br />CATALOG NO. <br />MOUNTING <br />QTY <br />WATTS <br />TYPE <br />A <br />EXISTING <br />2X2 LAY -IN LED <br />EX. <br />21 <br />EX. <br />EX. <br />B <br />EXISTING <br />6" LED CAN LIGHT <br />EX. <br />4 <br />EX. <br />EX. <br />X <br />EXISTING <br />APCH7R APELH2 <br />EX. <br />3 <br />EX. <br />- <br />ELECTRICAL LEGEND <br />SYMBOL <br />DESCRIPTION <br />DUPLEX RECEPTACLE: 20A, 125VAC <br />*C <br />CEILING DUPLEX RECEPTACLE: 20A, 125VAC <br />{GFCI PROTECTED W/ GFCI BREAKER} <br />DUPLEX RECEPTACLE: 20A, 125VAC <br />{GFCI PROTECTED W/ GFCI BREAKER} <br />® <br />208V RECEPTACLE: PER EQUIPMENT <br />{GFCI PROTECTED W/ GFCI BREAKER} <br />Qo Qo ® <br />LED LIGHT FIXTURE (SEE LIGHTING SCHEDULE) <br />EXIT <br />EMERGENCY EXIT SIGN W/ LIGHT <br />EMERGENCY EXIT LIGHT <br />G <br />OCCUPANCY SENSOR (SEE CONTROL SCHEDULE) <br />PP <br />POWER PACK (SEE CONTROL SCHEDULE) <br />VS <br />WALL OCC SENSOR (SEE CONTROL SCHEDULE) <br />34 <br />MANUAL SWITCH / THREE-WAY TOGGLE SWITCH / FOUR-WAY TOGGLE <br />SWITCH <br />fD <br />DIMMER SWITCH (150D WATTS, U.N.O.) <br />O <br />JUNCTION BOX <br />ZtE <br />QUADRAPLEX RECEPTACLE OUTLET C/L 18" A.F.F. U.O.N <br />0� <br />DISCONNECT SWITCH - 30A/3/NF LION <br />WALL TELE/DATA OUTLET. PROVIDE MIN. 1" CONDUIT WITH PULL WIRES <br />TO ABOVE CEILING. MTD. 18" A.F.F. U.O.N. <br />ENGINEERING & CONSTRUCTION <br />AUSTIN CONSTRUCTION GROUP <br />2706 STALLONE DRIVE <br />TAMPA, FLORIDA 33605 <br />(813) 293-8883 <br />FLORIDA PE 48917 192169 - <br />CGC1521407 - CUC1224196 - <br />CFC1430334 - FPC15-4000052 <br />PROJECT INFORMATION: <br />CLIENT: <br />RICHARD KAZBOUR <br />PROJECT NAME: <br />HUNGRY HOWIES RESTAURANT <br />ADDITION <br />PROJECT LOCATION: <br />5440 GALL BLVD <br />ZEPHYRHILLS, FL 33542 <br />SEAL: <br />GOATS -'*1 <br />��� ���•••• S E•••` <br />• v� 9 % dam: <br />= • y�o Lo = <br />s���111t11t1111��` <br />FL COA NO. 30178 <br />ENGINEER OF RECORD <br />FL LICENSE NO. <br />TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE <br />PLANS AND SPECIFICATIONS COMPLY WITH THE <br />APPLICABLE MINIMUM BUILDING CODES <br />REVISIONS: <br />NO. <br />DATE <br />COMMENTS <br />SHEET TITLE: <br />ELECTRICAL <br />NOTES & SCHEDULES <br />SHEET INFORMATION: <br />DRAWN: A.C. <br />SHEET NO. <br />DATE: 7/22/2024 <br />• <br />CHECKED: K.C. <br />7/22/2024 <br />IjDATE: <br />EOO <br />PROJECT NUMBER: <br />SCALE: <br />INDEX: <br />AS SHOWN <br />