I I ELECTRICAL GENERAL NOTES
<br />GENERAL:
<br />l . PROVIDE SHALL MEAN FURNISH AND INSTALL.
<br />2. THE COMPLETE ELECTRICAL SYSTEM SHALL BE PROVIDED BY THE CONTRACTOR
<br />SHALL INCLUDE ALL WORK, MATERIALS AND APPARATUSES SPECIFIED HEREINAFTER
<br />AND INDICATED ON THE DRAWINGS. ALL WORKMANSHOP SHALL BE OF THE
<br />HGIHEST QUALITY AND NO SUBSTANDARD WORK WILL BE ACCEPTED,
<br />3. PROVIDE ALL WORK AND ELECTRICAL SYSTEMS COMPONENTS REQUIRED TO SERVE
<br />LOADS AS SPECIFIED HEREINAFTER AND INDICATED IN THE DRAWINGS. THE WORK
<br />SHALL INCLUDE COMPLETE TESTING OF ALL ELECTRICAL SYSTEMS AT THE
<br />COMPLETION OF THE WORK AND MAKE ANY CHANGES AND ADJUSTMENTS
<br />NECESSARY FOR THE PROPER FUNCTIONING OF THE SYSTEMS.
<br />4. MAKE A THOROUGH EXAMINATION OF THE SITE AND THE CONTRACT DOCUMENTS
<br />PRIOR TO EXECUTING THE CONTRACT. NO CLAIM FOR ADDITIONAL
<br />COMPENSATION WILL BE RECOGNIZED FOR DIFFICULTIES ENCOUNTERED WHICH
<br />AN EXAMINATION OF SITE CONDITIONS AND CONTRACT DOCUMENTS WOULD
<br />HAVE REVEALED.
<br />5. ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED ABOVE THE FLOODPLAIN
<br />ELEVATION. CONTRACTOR SHALL COORDINATE FLOODPLAIN ELEVATION AND
<br />EQUIPMENT REQUIREMENTS WITH OWNER PRIOR TO ROUGH -IN.
<br />6. THE PLANS ARE GENERALLY DIAGRAMMATIC. COORDINATE ALL WORK WITH
<br />OTHER TRADES AS REQUIRED TO AVOID INTERFERENCES BETWEEN TRADES (I.E.
<br />BEAMS, CONDUITS, EQUIPMENT, DUCTWORK, ECT.)
<br />WORK PERFORMANCE:
<br />1. JOB SITE SAFETY AND WORKER SAFETY IS THE RESPONSIBILITY OF THE CONTRACTOR
<br />2. ARRANGE, PHASE AND PERFORM ALL WORK DURING TIME PERIODS SCHEDULED
<br />WITH AND ACCEPTABLE TO THE OWNER BEFORE PROCEEDING, NO ADDITIONAL
<br />COMPENSATION WILL BE AUTHORIZED FOR WORK NECESSITATED BY ILL-TIMED,
<br />DEFECTIVE, OR NON -CONFORMING WORK.
<br />3. THE CONTRACTOR SHALL ENSURE THAT ALL SYSTEMS OPERATE AS DESIGNED
<br />AND/OR REQUIRED AND SHALL REVIEW THEIR OPERATION WITH THE OWNER UPON
<br />COMPLETION OF CONSTRUCTION AND TESTING. COMPILE COMPLETE AND
<br />UPDATED AS -BUILT DRAWINGS/DOCUMENTS AND ISSUE ONE (1) SET TO THE
<br />OWNER.
<br />4. ELECTRICAL WORK SHALL BE ACCOMPLISHED WITH ALL AFFECTED CIRCUITS OR
<br />EQUIPMENT DE -ENERGIZED, WHEN AN ELECTRICAL OUTAGE CANNOT BE
<br />ACCOMPLISHED IN THIS MANNER FOR THE REQUIRED WORK, THE FOLLOWING
<br />REQUIRED WORK, THE FOLLOWING REQUIREMENTS ARE MANDATORY:
<br />4.1. ELECTRICIANS MUST USE AND WEAR FULL PROTECTIVE EQUIPMENT (PPE).
<br />WHILE WORKING ON ENERGIZED SYSTEMS IN ACCORDANCE W/ NFPA 70E.
<br />THE LEVEL OF PPE SHALL BE DETERMINED BY A COMPUTER GENERATED ARC
<br />FLASH CALCULATION PROVIDED AND PAID FOR BY THE CONTRACTOR. THE
<br />ARC FLASH DATA SHALL BE PRESENTED WITH THE SUBMITTAL BELOW.
<br />4.2. WORK ON ENERGIZED CIRCUITS OR EQUIPMENT CANNOT BEGIN UNTIL PRIOR
<br />WRITTEN APPROVAL IS OBTAINED FROM THE OWNER.
<br />5. ENSURE THAT ELECTRICAL SERVICE REMAINS UNINTERRUPTED FOR OTHER BUILDINGS
<br />AND FACTILITIES AT ALL TIMES. PERFORM ALL TEMPORARY WORK NECESSARY TO
<br />MAINTAIN CONTINUITY OF ELECTRICAL SERVICE WHEN CONNECTION IS MADE TO
<br />EXISTING SYSTEMS.
<br />6. ELECTRICAL EQUIPMENT SHALL NOT BE STORED OUTDOORS. EQUIPMENT SHALL BE
<br />STORED IN AN OWNER/E3NGINEER APPROVED MEDIUM AND LOCATION.
<br />CODES & STANDARDS:
<br />l . PERFORM WORK IN COMPLIANCE WITH THE LATEST EDITION OF ALL
<br />APPLICABLE,FEDERAL, STATE AND LOCAL CODES, REGULATIONS AND STANDARDS,
<br />TO INCLUDE THOSE LISTED BELOW, ADOPTED BY THE AUTHORITY HAVING
<br />JURISDICTION. WHERE DIFFERENCES MAY OCCUR THE MORE STRINGENT
<br />REQUIREMENTS SHALL GOVERN. IN CASE OF CONFLICT PROVIDE WRITTEN
<br />NOTIFCATION AND OBTAIN A DECISION FROM THE ARCHITECT.
<br />1.1. NFPA 70: NATIONAL ELECTRICAL CODE (2020)
<br />1.2. NFPA 70E: STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE (2018)
<br />1.3. NFPA 72: NATIONAL FIRE ALARM CODE (2019)
<br />1.4. NFPA 241: STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION
<br />AND DEMOLITION OPERATIONS (2019)
<br />1.5. FBC: FLORIDA BUILDING CODE 8TH ED. (2023)
<br />1.6. OASHA PART 1910: OCCUPATIONAL SAFETY AND HEALTH STANDARDS
<br />1.7. OASHA PART 1926: SAFETY AND HEALTH REGULATIONS FOR CONSTRUCTION
<br />MATERIALS AND METHODS:
<br />1. MATERIALS AND APPARATUSES SHALL COMPLY WITH ALL APPLICABLE TESTS,
<br />RATINGS, SPECIFICATIONS AND REQUIREMENTS OF THE IEEE,NEMA, NFPA, AND UL,
<br />SHALL BEAR THE UL LABEL OF APPROVAL AND BE LISTED FOR THE PROPOSED
<br />APPLICATION.
<br />2. FINISHED PRODUCTS SHALL BE FACTORY PRIMED AND FINISH COATED WITH THE
<br />MANUFACTURER'S PRIME COAT AND STANDARD FINISH UNLESS SPECIFIED
<br />OTHERWISE BY THE ARCHITECT.
<br />3. UNLESS OTHERWISE SPECIFIED, UNFINISHED PRODUCTS SHALL BE GALVANIZED,
<br />COATED OR PLATED TO RESIST CORROSION.
<br />4. INSTALLATIONS SHALL BE IN ACCORDANCE WITH ALL APPLICABLE CODES, AS
<br />RECOMMENDED BY THE MANUFACTURER AND AS CLOSE AS PRACTICABLE TO
<br />LOCATIONS INDICATED ON DRAWINGS.
<br />5. INSTALLATIONS SHALL FACILITATE MAINTENANCE AND REPAIR OR REPLACEMENT
<br />OF EQUIPMENT COMPONENTS. ACCESS, WORKING SPACES AND CLEARANCES
<br />SHALL NOT BE LESS THAN SPECIFIED BY THE NEC FOR ALL VOLTAGES SPECIFIED.
<br />6. PROVIDE APPROVED FIRE STOPPING MATERIALS AT ALL CHASES TO PREVENT
<br />DRAFTS.
<br />2 1 ELECTRICAL GENERAL NOTES
<br />7. FIRE RATING: RESTORE FIRE RATING WHERE PIERCING OCCURS THROUGH FIRE
<br />RATED CEILINGS OR BETWEEN FIRE RATED WALLS. FIRE STOP MATERIALS SHALL BE
<br />AS MANUFACTURED BY 3M COMPANY AND UL LISTED FOR USE IN THE
<br />CONSTRUCTION ASSEMBLY IN WHICH IT IS TO BE USED. REFER TO ARCHITECTURAL
<br />PLANS FOR LOCATIONS OF FIRE RATED WALLS AND CEILINGS.
<br />IDENTIFICATION:
<br />1. INSTALL LABEL TAGS ON ALL WIRE AND CABLE IN JUNCTION BOXES, WIREWAYS
<br />AND WIRING GUTTER OF PANELS. TAGS SHALL IDENTIFY WIRE AND CABLE CIRCUIT
<br />NUMBER AND/OR EQUIPMENT SERVED AS INDICATED ON DRAWINGS.
<br />2. JUNCTION BOXES SHALL BE LABELED IN A PERMANENT MANNER REFLECTING
<br />PANELBOARD/CIRCUIT NUMBER OF BRANCH CIRCUIT WIRING CONTAINED WITHIN.
<br />3. PANEL BOARD DIRECTORIES SHALL BE TYPEWRITTEN, REFLECTING RECORD
<br />CONDITION TO INCLUDE CIRCUIT NUMBER, TYPE AND LOCATION OF LOAD.
<br />RACEWAYS:
<br />1. RACEWAYS:
<br />1.1. INTERIOR EXPOSED, CONCEALED IN WALLS OR ABOVE CEILINGS: ELECTRICAL
<br />METALLIC TUBING (EMT) OR MC CABLE
<br />2. ALL CONDUIT SHALL BE PROPERLY ALIGNED, GROUPED AND SUPPORTED. EXPOSED
<br />CONDUIT SHALL BE INSTALLED AT RIGHT ANGLES TO OR PARALLEL TO THE
<br />PRINCIPAL STRUCTURAL MEMBERS. PROVIDE SUPPORT A MINIMUM OF 18" FROM
<br />BENDS AND OUTLET BOXES AND ON INTERVALS NOT TO EXCEED 8'-0". CONDUIT IS
<br />NOT TO SPAN ANY SPACE UNSUPPORTED. ALL CONDUIT SHALL BE SUPPORTED
<br />FROM STRUCTURE AND NOT FROM CEILING SUPPORT SYSTEM.
<br />3. PROVIDE NYLON PULL CORD AND LEAVE IN PLACE IN EACH EMPTY CONDUIT.
<br />BOXES:
<br />1. ALL BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH SUITABLE
<br />SCREW FASTENED COVERS, OPEN KNOCK -OUTS OR HOLES IN BOXES SHALL BE
<br />PLUGGED WITH A SUITABLE BLANKING DEVICE.
<br />CONDUCTORS:
<br />1. UNLESS OTHERWISE INDICATED, ALL BRANCH CIRCUIT CONDUCTORS SHALL BE NO.
<br />12 AWG. BRANCH CIRCUITS RUN OVER 75-FEET IN LENGTH, MEASURING ONE WAY
<br />FROM THE FIRE OUTLET OF THE CIRCUIT TO THE PANEL, SHALL BE NO. 10 AWG FOR
<br />THE ENTIRE CIRCUIT.
<br />2. CONDUCTORS SHALL BE COPPER WITH THHN/THWN-2 90 C INSULATION, THE
<br />FOLLOWING SYSTEMS OF COLOR CORDING SHALL BE STRICTLY ADHERED TO AND
<br />SHALL BE CONSISTENTLY FOLLOWED THROUGHOUT:
<br />2.1. GROUND WIRES: GREEN
<br />2.2. GROUNDED NEUTRAL WIRES: WHITE
<br />2.3. 208/120 VOLT, UNGROUNDED PHASE WIRES: BLACK, RED AND BLUE
<br />2.4. 480/270 VOLT, UNGROUNDED PHASE WIRES: BROWN, ORANGE AND YELLOW
<br />2.4.1. WHERE EXISTING BASE BUILDING COLOR CODING DIFFERS FROM COLOR
<br />CODING ASSIGNED HERE -IN, USE EXISTING COLOR CODING AS REQUIRED
<br />TO MAINTAIN CONSISTENCY.
<br />3. WIRING IN AIR PLENUMS OR PLENUM SPACES NOT IN CONDUIT SHALL BE UL LISTED
<br />AS SUITABLE FOR PLENUM USE.
<br />4. CONDUITS AND WIRING PENETRATING RATED FLOORS AND WALLS SHALL BE
<br />SEALED TO MAINTAIN FIRE RATING AND INTEGRITY OF SEPARATION.
<br />5. FOR NEW CIRCUITS, MULTIPLE CIRCUITS IN SAME CONDUIT SHALL NOT SHARE
<br />NEUTRAL CONDUCTORS. FOR EXISTING CIRCUITS, WHERE REQUIRED BY NEC,
<br />PROVIDE AND INSTALL HANDLE TIES ON EXISTING CIRCUIT BREAKERS.
<br />6. INSTALL INSULATED SPRING WIRE CONNECTORS WITH PLASTIC CAPS FOR COPPER
<br />CONDUCTOR SPLICES AND TAPS, 10 AWG AND SMALLER.
<br />7. "PUSH -IN" OR "STAB" TYPE CONNECTORS ARE NOT ACCEPTABLE.
<br />GROUNDING:
<br />1. THE ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED AS
<br />REQUIRED BY THE NEC AND AS SPECIFIED HEREINAFTER.
<br />2. ALL METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY SECURE
<br />AT ALL JOINTS AND AT ALL BOXES, CABINETS, FITTINGS, AND EQUIPMENT. METALLIC
<br />RACEWAYS SHALL BE CONNECTED TO A DIRECT GROUND AT THE POINT OF
<br />ELECTRICAL SERVICE ENTRANCE AND SHALL BE ELECTRICALLY CONTINUOUS
<br />THROUGHOUT THE ENTIRE SYSTEM.
<br />3. ALL GROUND CONDUCTORS SHALL BE INSULATED COPPER UON.
<br />4. ALL RACEWAYS WITH NO. 10 OR 12 AWG PHASE CONDUCTORS FOR
<br />RECEPTACLES, LIGHTING FIXTURES AND SIMILAR CIRCUITS (NEW BRANCH CIRCUITS)
<br />SHALL BE PROVIDED WITH A PARITY SIZED GREEN EQUIPMENT GROUND
<br />CONDUCTOR. GROUND CONDUCTOR SHALL BE INSTALLED IN ENTIRE RACEWAY
<br />SYSTEM INCLUDING WALL SWITCHES AND FLEXIBLE CONDUIT TO LIGHT FIXTURES.
<br />EQUIPMENT GROUND CONDUCTOR SIZES FOR CIRCUITS WITH PHASE
<br />CONDUCTORS LARGER THAN NO. 12 AWG ARE INDICTED ON DRAWINGS.
<br />GROUND CONDUCTORS SHALL BE CONNECTED TO GROUND BUS IN PANEL
<br />BOARDS.
<br />5. TERMINATE FEEDER AND BRANCH CIRCUIT INSULATED EQUIPMENT GROUNDING
<br />CONDUCTORS WITH GROUNDING LUG, BUS OR BUSHING. CONDUCTORS LOOPED
<br />UNDER SCREW OR BOLT HEADS WILL NOT BE PERMITTED.
<br />6. INSTALL CLAMP -ON CONNECTORS ON CLEAN METAL CONTACT SURFACES TO
<br />ENSURE ELECTRICAL CONDUCTIVITY AND CIRCUIT INTEGRITY.
<br />7. TEST THE GROUNDING SYSTEM TO ASSURE CONTINUITY AND THAT RESISTANCE TO
<br />GROUND DOES NOT EXCEED 25 OHMS UNLESS OTHERWISE NOTED. TEST EACH
<br />GROUND ROD FOR RESISTANCE TO GROUND BEFORE MAKING CONNECTIONS TO
<br />THE ROD; THEN TIE ENTIRE GROUNDING SYSTEM TOGETHER AND TEST FOR
<br />RESISTANCE TO GROUND. MAKE RESISTANCE MEASUREMENTS IN NORMALLY DRY
<br />WEATHER, NOT LESS THAN 48 HOURS AFTER RAINFALL. MAKE GROUND RESISTANCE
<br />MEASUREMENTS WITH A GROUND RESISTANCE TEST METER CALIBRATED WITHIN THE
<br />LAST TWELVE MONTHS.
<br />3 I ELECTRICAL GENERAL NOTES
<br />SWITCHES & RECEPTACLES:
<br />l . RECEPTACLES SHALL BE THE GROUNDING TYPE WITH GROUND CONNECTION
<br />MADE THROUGH AN EXTRA POLE WHICH SHALL BE PERMANENTLY CONNECTED TO
<br />GROUND CONDUCTOR.
<br />2. CONNECT WIRING DEVICES BY WRAPPING SOLID CONDUCTOR AROUND SCREW
<br />TERMINAL. WHEN STRANDED CONDUCTORS ARE USED IN LIEU OF SOLID, USE
<br />CRIMP ON FORK TERMINALS FOR DEVICE TERMINATIONS. DO NOT PLACE BARE
<br />STRANDED CONDUCTORS DIRECTLY UNDER DEVICE SCREWS.
<br />3. GFCI RECEPTACLES SHALL MEET CURRENT UL 943 REQUIREMENTS WITH
<br />AUTO -MONITORING OR SELF -TEST FUNCTIONALITY; IF THE SELF -TEST FUNCTION
<br />DETECTS A PROBLEMS, THE UNIT MUST DENY POWER OR PROVIDE VISUAL AND/OR
<br />AUDIBLE INDICATION.
<br />4. GFCI RECEPTACLES LOCATED IN DAMP, WET OR EXTERIOR LOCATIONS SHALL BE
<br />WEATHER -RESISTANT TYPE TO COMPLY WITH NEC 406.9.
<br />5. RECEPTACLES FOR 20 AMPERE, 120 VOLT APPLICATION SHALL BE SPECIFICATION
<br />GRADE, THREE -WIRE, TWO POLE, RATED 20 AMPERES AT 125 VOLTS, PASS AND
<br />SEYMOUR OR APPROVED EQUAL.
<br />6. LIGHT SWITCHES SHALL BE SPECIFICATION GRADE, 120/277 VOLT, PASS AND
<br />SEYMOUR OR APPROVED EQUAL.
<br />7. PROVIDE WALL PLATES FOR SINGLE AND COMBINATION DEVICES OR TYPES, SIZES
<br />AND WITH GANGING AND CUTOUTS AS INDICATED, SELECT PLATES WHICH MATE
<br />AND MATCH WIRING DEVICES TO WHICH ATTACHED. CONSTRUCT WITH METAL
<br />SCREWS FOR SECURING PLATES TO DEVICES; SCREW HEADS COLOR TO MATCH
<br />FINISH OF PLATES, WALL PLATES COLOR TO MATCH DEVICES, COLOR BY
<br />ARCHITECT.
<br />EQUIPMENT:
<br />CIRCUIT BREAKERS SHALL PLUG STYLE BREAKERS
<br />LIGHTING FIXTURES:
<br />1. THE CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE IN ALL RESPECTS ALL
<br />LIGHTING FIXTURES INDICATED ON THE PLANS.
<br />2. FIXTURES SHALL BE SUPPORTED INDEPENDENTLY FROM CEILING AND SHALL BE
<br />PROPERLY AND CAREFULLY ALIGNED. FIXTURE BOTTOMS, EDGES, AND ENDS SHALL
<br />BE EVEN AND TRIM SHALL BE SNUG TO SURFACE. THE CONTRACTOR SHALL FURNISH
<br />AND INSTALL ALL NECESSARY HARDWARE, ECT, FOR SUPPORT OF FIXTURES AS
<br />REQUIRED.
<br />3. RECESSED FIXTURES SHALL BE CONNECTED WITH A MAXIMUM 6 FOOT FLEXIBLE
<br />WHIP.
<br />4. FIXTURES SHALL BE CLEAN AND LENSES SHALL BE CLEAR OF FINGERPRINTS.
<br />MANUALS:
<br />CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING MANUAL AND
<br />MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING OWNER. THE MANUALS SHALL
<br />INCLUDE, AT A MINIMUM, THE FOLLOWING:
<br />1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTION FOR EACH
<br />PIECE OF EQUIPMENT REQUIRING MAINTENANCE.
<br />2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF
<br />EQUIPMENT REQUIRING MAINTENANCE. REQUIRED ROUTINE MAINTENANCE
<br />ACTIONS SHALL BE CLEARLY IDENTIFIED.
<br />3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY.
<br />DOCUMENTATION REQUIREMENTS:
<br />THE CONSTRUCTION DOCUMENTS SHALL SPECIFY THAT DOCUMENTS CERTIFYING THAT
<br />THE INSTALLED LIGHTING CONTROLS MEET DOCUMENTED PERFORMANCE CRITERIA OF
<br />SECTION C405 ARE TO BE PROVIDED TO THE BUILDING OWNER WITHIN 90 DAYS FROM
<br />THE DATE OF RECEIPT OF THE CERTIFICATE OF OCCUPANCY.
<br />4 1 LIGHTING FIXTURE &CONTROL SCHEDULE
<br />LIGHTING FIXTURE SCHEDULE
<br />TYPE PER
<br />MANUFACTURER
<br />CATALOG NO.
<br />MOUNTING
<br />QTY
<br />WATTS
<br />TYPE
<br />A
<br />EXISTING
<br />2X2 LAY -IN LED
<br />EX.
<br />21
<br />EX.
<br />EX.
<br />B
<br />EXISTING
<br />6" LED CAN LIGHT
<br />EX.
<br />4
<br />EX.
<br />EX.
<br />X
<br />EXISTING
<br />APCH7R APELH2
<br />EX.
<br />3
<br />EX.
<br />-
<br />ELECTRICAL LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />DUPLEX RECEPTACLE: 20A, 125VAC
<br />*C
<br />CEILING DUPLEX RECEPTACLE: 20A, 125VAC
<br />{GFCI PROTECTED W/ GFCI BREAKER}
<br />DUPLEX RECEPTACLE: 20A, 125VAC
<br />{GFCI PROTECTED W/ GFCI BREAKER}
<br />®
<br />208V RECEPTACLE: PER EQUIPMENT
<br />{GFCI PROTECTED W/ GFCI BREAKER}
<br />Qo Qo ®
<br />LED LIGHT FIXTURE (SEE LIGHTING SCHEDULE)
<br />EXIT
<br />EMERGENCY EXIT SIGN W/ LIGHT
<br />EMERGENCY EXIT LIGHT
<br />G
<br />OCCUPANCY SENSOR (SEE CONTROL SCHEDULE)
<br />PP
<br />POWER PACK (SEE CONTROL SCHEDULE)
<br />VS
<br />WALL OCC SENSOR (SEE CONTROL SCHEDULE)
<br />34
<br />MANUAL SWITCH / THREE-WAY TOGGLE SWITCH / FOUR-WAY TOGGLE
<br />SWITCH
<br />fD
<br />DIMMER SWITCH (150D WATTS, U.N.O.)
<br />O
<br />JUNCTION BOX
<br />ZtE
<br />QUADRAPLEX RECEPTACLE OUTLET C/L 18" A.F.F. U.O.N
<br />0�
<br />DISCONNECT SWITCH - 30A/3/NF LION
<br />WALL TELE/DATA OUTLET. PROVIDE MIN. 1" CONDUIT WITH PULL WIRES
<br />TO ABOVE CEILING. MTD. 18" A.F.F. U.O.N.
<br />ENGINEERING & CONSTRUCTION
<br />AUSTIN CONSTRUCTION GROUP
<br />2706 STALLONE DRIVE
<br />TAMPA, FLORIDA 33605
<br />(813) 293-8883
<br />FLORIDA PE 48917 192169 -
<br />CGC1521407 - CUC1224196 -
<br />CFC1430334 - FPC15-4000052
<br />PROJECT INFORMATION:
<br />CLIENT:
<br />RICHARD KAZBOUR
<br />PROJECT NAME:
<br />HUNGRY HOWIES RESTAURANT
<br />ADDITION
<br />PROJECT LOCATION:
<br />5440 GALL BLVD
<br />ZEPHYRHILLS, FL 33542
<br />SEAL:
<br />GOATS -'*1
<br />��� ���•••• S E•••`
<br />• v� 9 % dam:
<br />= • y�o Lo =
<br />s���111t11t1111��`
<br />FL COA NO. 30178
<br />ENGINEER OF RECORD
<br />FL LICENSE NO.
<br />TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE
<br />PLANS AND SPECIFICATIONS COMPLY WITH THE
<br />APPLICABLE MINIMUM BUILDING CODES
<br />REVISIONS:
<br />NO.
<br />DATE
<br />COMMENTS