Laserfiche WebLink
1 1 1 GENERAL NOTES 1 3 1 CONCRETE NOTES (CONTINUED) 1 4 1 DESIGN LOADS 1 5 1 ROOF BRACING AND COLUMN DETAIL <br />SCALE: N.T.S <br />1. THE STRUCTURAL DESIGN IS BASED ONLY ON THE STRUCTURE IN IT'S <br />COMPLETED STATE. CONTRACTORS AND THEIR SUBS SHALL TAKE WHATEVER <br />PRECAUTIONS THAT ARE NECESSARY IN THEIR OPINIONS TO WITHSTAND ALL <br />HORIZONTAL AND VERTICAL LOADS THAT MAY BE ENCOUNTERED DURING <br />THE CONSTRUCTION, PRIOR TO COMPLETION. <br />2. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, ELEVATIONS, AND <br />CONDITIONS AT THE JOB SITE AND BRING TO THE ENGINEERS ATTENTION OF <br />ANY DISCREPANCIES. <br />3. THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ALL EXCAVATION <br />PROCEDURES, INCLUDING SHORING AND PROTECTION OF ANY ADJACENT <br />PROPERTY, STRUCTURES, STREETS, AND UTILITIES IN ACCORDANCE WITH <br />LOCAL BUILDING CODES. <br />4. CONSTRUCTION DEAD AND LIVE LOADS SHALL NOT EXCEEDS ACTUAL DESIGN <br />LOADS FOR ANY STRUCTURAL COMPONENT. <br />5. TEMPORARY BRACING SHALL BE PROVIDED AS REQUIRED TO HOLD ALL <br />COMPONENTS OF THE STRUCTURE IN PLACE UNTIL FINAL SUPPORT IS <br />SECURELY ANCHORED. <br />6. ALL INSPECTIONS, SPECIAL OR OTHERWISE, THAT ARE REQUIRED BY THE <br />BUILDING CODES, LOCAL BUILDING DEPARTMENT, OR THESE PLANS, SHALL BE <br />DONE BY AN INDEPENDENT QUALIFIED TESTING COMPANY. <br />7. SHOP DRAWINGS SUBMITTED FOR STRUCTURAL REVIEW SHALL BEAR THE <br />CONTRACTORS APPROVAL STAMP ACCEPTING RESPONSIBILITY FOR <br />DIMENSIONS, QUANTITY AND COORDINATION WITH ALL DISCIPLINES. NO <br />CHANGES OR DEVIATIONS FROM THE CONTRACT DOCUMENTS ARE <br />ACCEPTED UNLESS EACH IS CLEARLY IDENTIFIED AS SUCH, AND EACH IS <br />SPECIFICALLY ACCEPTED OR REJECTED. ANY ACCEPTED CHANGE OR <br />DEVIATION FOR REVISION OF THE PERMITTED CONSTRUCTION DOCUMENTS <br />OR VALUE ENGINEERING COST SAVINGS IS SUBJECT TO A REDUCTION OF THE <br />CONTRACT LUMP SUM. ONLY ONE MARKED UP SET WITH THE STRUCTURAL <br />ENGINEERS COMMENTS WILL BE RETURNED TO THE CONTRACTOR. ALLOW <br />TWO WEEKS TIME FOR SHOP DRAWING REVIEW BY ACG. <br />8. THE CONTRACTOR SHALL COORDINATE THE STRUCTURAL DRAWINGS WITH <br />THE ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING, AND CIVIL / SITE <br />WORK PLANS FOR DIMENSIONS AND DETAILS OF THE ITEMS WHICH PENETRATE <br />OR ATTACH TO THE BUILDING STRUCTURE. <br />9. NO STRUCTURAL MEMBER SHALL BE CUT, NOTCHED OR REDUCED IN <br />STRENGTH. <br />1 2 1 EARTH WORK NOTES <br />A- QUALITY ASSURANCE: <br />A.1. CODES AND STANDARDS: ACI-301, ACI-315, ACI-318, CRSI, COMPLY WITH <br />APPLICABLE PROVISIONS EXCEPT AS OTHERWISE INDICATED. <br />A.2. OWNER SHALL EMPLOY TESTING LABORATORY TO TEST AND EVALUATE <br />CONCRETE DELIVERED TO AND PLACED AT SITE. THIS TESTING DOES NOT RELIEVE <br />SUBCONTRACTOR OF RESPONSIBILITY OF PROVIDING CONCRETE IN <br />COMPLIANCE WITH CONTRACT DOCUMENTS. <br />A.3. SAMPLING FRESH CONCRETE: COMPLY WITH ASTM C 172, EXCEPT <br />MODIFIED FOR SLUMP TO COMPLY WITH ASTM C 94. <br />a) SLUMP - ASTM C143, ONE TEST FOR EACH LOAD AT POINT OF DISCHARGE. <br />b) AIR CONTENT - ASTM C173, ONE FOR EACH SET OF COMPRESSIVE <br />STRENGTH SPECIMENS. <br />c) COMPRESSIVE TEST SPECIMEN - ASTM C 31, FOUR STANDARD CYLINDERS <br />FOR EACH COMPRESSIVE STRENGTH TEST. MOLD AND STORE CYLINDERS FOR <br />LABORATORY -CURED TEST SPECIMENS EXCEPT WHEN FIELD -CURED TEST <br />SPECIMENS ARE REQUIRED. <br />d) COMPRESSIVE STRENGTH TESTS - ASTM C 39, ONE SET FOR EACH DAY'S <br />POUR EXCEEDING 5 CU. YD. PLUS ADDITIONAL SETS FOR EACH 50 CU. YD. MORE. <br />ONE CYLINDER TO BE TESTED AT 7 DAYS, TWO CYLINDERS TESTED AT 28 DAYS, <br />AND ONE CYLINDER RETAINED IN RESERVE FOR LATER TESTING IF REQUIRED. <br />A.l. REPORT TEST RESULTS TO G.C., ARCHITECT AND OWNER IN WRITING ON <br />SAME DAY TESTS ARE MADE. <br />B) SUBMITTALS: <br />A.l. CONCRETE MIX DESIGN -PER ACI 301. EACH MIX DESIGN SHALL BE <br />LABELED TO INDICATE THE AREA IN WHICH THE CONCRETE IS TO BE PLACED (I.E. <br />FOUNDATIONS, SLAB -ON -GRADE, COLUMNS, ETC. FAILURE TO DO SO WILL <br />CAUSE DELAYS AND/OR REJECTION OF SUBMITTAL. <br />A.2. REINFORCING STEEL FABRICATIONS AND PLACEMENT DRAWINGS - PER <br />ACI 315 <br />C) PRODUCTS: <br />C.1 CONCRETE MATERIALS: <br />a) PORTLAND CEMENT - ASTM C 150, TYPE 1 <br />b) AGGREGATES - ASTM C33 (NORMAL WEIGHT) ASTM C330 (LIGHT WEIGHT). <br />c) WATER - CLEAN, DRINKABLE <br />C.2 REINFORCING MATERIALS: REINFORCING MATERIALS: <br />a) DEFORMED REINFORCING BARS - ASTM A 615, GRADE 60. REINFORCING <br />STEEL TO BE WELDED: ASTM A706 (FOR EMBED., ANCHORS, ETC.) <br />b) WELDED WIRE FABRIC - ASTM A 185 MINIMUM YIELD STRENGTH OF 20,000 <br />PSI. <br />c) FIBER REINFORCEMENTS - ENGINEERED POLYPROPYLENE FIBERS DESIGNED <br />FOR SECONDARY REINFORCEMENTS OF CONCRETE SLABS. <br />C.3 CHAIRS, BOLSTERS, SPACERS, RUNNERS, OTHER SUPPORT DEVICES: CRSI <br />CHAIRS, BOLSTERS, SPACERS, RUNNERS, OTHER SUPPORT DEVICES: CRSI CRSI <br />STANDARDS. <br />C.4 ADMIXTURES: PROVIDE ADMIXTURES THAT CONTAIN NOT MORE THAN 0.1% <br />CHLORIDE IONS. ADMIXTURES: PROVIDE ADMIXTURES THAT CONTAIN NOT MORE <br />THAN 0.1 % CHLORIDE IONS. PROVIDE ADMIXTURES THAT CONTAIN NOT MORE <br />THAN 0.1 % CHLORIDE IONS. <br />1) AIR -ENTRAINING ADMIXTURES: ASTM C260 <br />2) WATER -REDUCING, RETARDING, AND ACCELERATING CHEMICAL <br />ADMIXTURES: ASTM C 494 <br />C.5 RELATED MATERIALS: <br />a) VAPOR RETARDER - CLEAN 10 MIL THICK POLYETHYLENE ASTM E 154 <br />b) ABSORPTIVE COVER - BURLAP CLOTH MADE FROM JUTE OR KENAF, <br />WEIGHING APPROXIMATELY 9 oz PER SQ. YD., COMPLY WITH AASHTO M 182, <br />CLASS 2. <br />c) MOISTURE - RETAINING COVER - WATERPROOF PAPER, POLYETHYLENE FILM, <br />OR POLYETHYLENE -COATED BURLAP, COMPLYING WITH ASTM C 171. <br />d) MEMBRANE - FORMING CURING COMPOUND - ASTM C 309, TYPE 1. <br />e) EVAPORATION CONTROL - MONOMOLECULAR FILM -FORMING COMPOUND <br />APPLIED TO EXPOSED CONCRETE SLAB SURFACES FOR TEMPORARY PROTECTION <br />FROM RAPID MOISTURE LOSS. <br />f) WATER STOPS: FLAT DUMBBELL OR CENTER BULB TYP, SIZE TO SUIT JOINTS, OF <br />EITHER RUBBER OR PVC. <br />g) NON SHRINK GROUT - 7,000 PSI CRD C 621 <br />D. MIX DESIGN: <br />D.1 PROPORTION MIXES COMPLYING WITH MIX DESIGN PROCEDURES SPECIFIED I <br />ACI 301. <br />D.2 PROVED READY -MIX CONCRETE COMPLYING WITH ASTM C 94. <br />D.3 ALL CONCRETE SHALL BE NORMAL WEIGHT (139 PCF - 150 PCF), WITH MIXES <br />DESIGNED TO MEET THE FOLLOWING CRITERIA FOR USE IN VARIOUS ELEMENTS OF <br />THE STRUCTURE AS FOLLOWS: <br />STRUCTURAL ELEMENT <br />COMP (PSI) <br />MAX. AGGREGATE SIZE <br />SLUMP <br />FOOTING, FOUNDATION <br />WALLS <br />3000 <br />1 2 <br />4 +/- 1" <br />SLAB ON GRADE <br />3500 <br />1 2" <br />4 +/- 1" <br />COLUMNS, BEAMS <br />4000 <br />1 <br />4 +/- 1" <br />ELEVATED SLAB <br />3500 <br />1 <br />4 +/- 1" <br />FILLED CELL GROUT <br />2500 <br />3/8" <br />8" TO 11" <br />NOTE: <br />1. WATER/ CEMENT RATIO = .58 MAX. (NON -AIR -ENTRAINED) <br />WATER/ CEMENT RATIO= .46 MAX. (AIR ENTRAINED) <br />2. PEA ROCK PUMP MIXES NOT PERMITTED <br />3. ELEVATED SLABS ON METAL DECK TO USE LIGHT WEIGHT AGGREGATE (115 <br />PCF MAX) <br />E. EXECUTION: <br />El. HOT WEATHER COMPLY WITH ACI 305 <br />E2. REINFORCING STEEL PLACEMENT TO COMPLY WITH ACI 315, AND CRSI. <br />a) WHERE SPLICE LENGTHS ARE NOT SPECIFIED, USE 48 BAR DIAMETER IN <br />MASONRY AND 40 BAR DIAMETERS IN CAST CONCRETE. <br />b) REINFORCING STEEL SHALL NOT BE TACK WELDED FOR ANY REASON. WELDED <br />REINFORCING STEEL SPLICES ARE NOT PERMITTED. <br />c) LAP ALL WELDED WIRE FABRIC A MINIMUM DISTANCE OF ONE CROSS WIRE <br />SPACING PLUS 2 INCHES. <br />d) ALL REINFORCING STEEL SHALL BE SUPPORTED ON STANDARD ACCESSORIES, <br />HELD RIGIDLY AND ACCURATELY IN PLACE, AND PROTECTED AGAINST <br />DISPLACEMENT BEFORE AND DURING PLACEMENT OF CONCRETE, SUPPORTING <br />ACCESSORY LEGS THAT REST ON CONCRETE SURFACES THAT WILL BE EXPOSED IN <br />THE FINISHED STRUCTURE SHALL BE FABRICATED ON STAINLESS STEEL. <br />E3. CONCRETE COVER: CONCRETE COVER:: <br />a) FOOTINGS AND FOUNDATION PADS PLACED AGAINST THE GROUND = 3". <br />b) CONCRETE SURFACE AFTER REMOVAL OF FORMS EXPOSED TO WEATHER OR <br />GROUND: <br />No. 5 BAR or SMALLER =1 1\2" <br />No. 6 BAR or LARGER = 2" <br />c) CONCRETE NOT EXPOSED TO WEATHER OR GROUND: <br />SLABS AND WALLS = 3/4" <br />BEAMS AND GIRDER TIES = 1 1 \2" <br />COLUMN TIES = 1 1 \2" <br />E4. FOUNDATION REINFORCEMENTS SHALL BE CONTINUOUS WITH CORNER BARS <br />(48 x BAR DIA. EACH LEG) AT INTERSECTIONS AND CORNERS, ONE FOR EACH <br />EACH HORIZONTAL BAR. <br />E5. PROVIDE KEYED CONSTRUCTION JOINTS (KCJ) IN EARTH OR FILL SUPPORTED <br />SLABS AT LOCATIONS NOTED ON PLAN. PROVIDE CONTROL JOINTS (CJ) <br />AT ALL LOCATIONS NOTED ON PLAN. IF 'CJ' IS SAW CUT, THE CUT MUST BE MADE <br />AS SOON AS POSSIBLE, BUT NOT LATER THAN 18 HOURS AFTER THE POUR UNLESS <br />OTHERWISE NOTED ON PLAN - PROVIDE CJ AT SPACINGS NOT TO EXCEED <br />DIMENSIONS IN TABLE BELOW - PATTERNS SHALL BE APPROXIMATELY SQUARE <br />WITH A RATIO OF LONG SIDE TO SHORT SIDE NOT GREATER THAN 1.5 TO 1 <br />SLAB THICKNESS (IN) <br />CJ SPACING (FT) <br />4 <br />12 <br />5 <br />13 <br />6 <br />14 <br />7 <br />15 <br />E6. SLAB FINISHES AS FOLLOWS: <br />a) EXPOSED TO VIEW AND SLAB SURFACES TO BE COVERED WITH RESILIENT <br />FLOORING, CARPET, PAINT, OR OTHER FILM, TO BE FINISH COATING SYSTEM, <br />FLOAT AND TROWEL FINISH. <br />b) SURFACES TO BE COVERED WITH CERAMIC TILES, TROWEL FINISH FOLLOWED <br />IMMEDIATELY WITH FINE BROOMING TO SLIGHTLY SCARIFY SURFACE. <br />1. WIND DESIGN DATA: <br />ULTIMATE WIND SPEED, VULT= 140 MPH <br />NOMINAL DESIGN WIND SPEED, VASE= 108 MPH <br />RISK CATEGORY = II <br />WIND EXPOSURE = C <br />Kzt = 1.00 <br />Kd = 0.85 <br />Ke = 1.00 <br />COMPONENTS AND CLADDING <br />PRESSURES = SEE TABLE BELOW <br />3. FLOOD DESIGN DATA: <br />FLOOD HAZARD ZONE DESIGNATION = X <br />ZONE <br />POSITIVE WIND PRESSURE P+ (psf) <br />NEGATIVE WIND PRESSURE P- (psf) <br />4 <br />38.0 <br />- 42.0 <br />5 <br />38.0 <br />- 51.0 <br />APPROVED PRODUCTS LIST <br />CATEGORY <br />SUB -CATEGORY <br />MANUFACTURER <br />APPROVAL # <br />WINDOWS <br />PASS -THROUGH <br />READY ACCESS <br />FL5102.3 <br />r- - - - - - - - - - - - - - - - - - - - - - - <br />i I <br />I I <br />I <br />THE BOTTOM <br />PROPOSED ROOFTOP <br />UNIT MUA-1 <br />EXISTING ROOF SYSTEM <br />ENGINEERING & CONSTRUCTION <br />AUSTIN CONSTRUCTION GROUP <br />2706 STALLONE DRIVE <br />TAMPA, FLORIDA 33605 <br />(813) 293-8883 <br />FLORIDA PE 48917 192169 - <br />CGC1521407 - CUC1224196 - <br />CFC 1430334 - FPC 15-4000052 <br />PROJECT INFORMATION: <br />CLIENT: <br />RICHARD KAZBOUR <br />PROJECT NAME: <br />HUNGRY HOWIES RESTAURANT <br />ADDITION <br />PROJECT LOCATION: <br />5440 GALL BLVD <br />ZEPHYRHILLS, FL 33542 <br />SEAL: <br />GOATS,�����i�� <br />o ••.•�,� S E •'•• <br />• <br />Q �G SzN d <br />• t.\O' : W <br />0 <br />i FL0 0�(,`� <br />• <br />••..•• <br />FL COA NO. 30178 <br />ENGINEER OF RECORD <br />FL LICENSE NO. <br />TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE <br />PLANS AND SPECIFICATIONS COMPLY WITH THE <br />APPLICABLE MINIMUM BUILDING CODES <br />REVISIONS: <br />NO. <br />DATE <br />COMMENTS <br />SHEET TITLE: <br />STRUCTURAL <br />NOTES & DETAILS <br />SHEET INFORMATION: <br />DRAWN: A.C. <br />SHEET NO. <br />DATE: 7/22/2024 <br />CHECKED: K.C. <br />DATE: 7/22/2024 <br />soel <br />PROJECT NUMBER: <br />SCALE: <br />INDEX: <br />AS SHOWN <br />