GENERAL NOTES: <br />THIS BUILDING HAS BEEN DESIGNED TO CONFORM TO THE 2017 FLORIDA BUILDING CODE <br />6TH EDITION <br />T.L. HANSON A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL ENGINEERING <br />COMPANY; HAS APPLIED "RATIONAL ANALYSIS" FOR THE STRUCTURAL DESIGN OF THIS STRUCTURE. <br />THE BUILDING (INCLUDING ALL COMPONENTS AND CLADDINGS) SHALL BE DESIGNED FOR THE <br />FOLLOWING SUPERIMPOSED LOADS: <br />SLAB: <br />LIVE LOAD - 50 P.S.F. <br />DEAD LOAD - 10 P.S.F. <br />ROOF: <br />LIVE LOAD (TRUSS TOP CHORD) - 20 P.S.F. <br />DEAD LOAD (TRUSS TOP CHORD) - 10 P.S.F. (15 P.S.F. WHEN TILE ROOFING IS INSTALLED) <br />DEAD LOAD (TRUSS BOTTOM CHORD) - 10 P.S.F. <br />ASSUMED TRUSS SELF WEIGHT (DEAD LOAD) - 7 P.S.F. <br />WIND: <br />BUILDING IS DESIGNED TO CONFORM TO ASCE 7-10, CHAPTERS 26 THRU 31; PER 2017 FLORIDA <br />BUILDING CODE, RESIDENTIAL 6TH EDITION- SECTION R301.2.1.1. AND 2017 FLORIDA BUILDING CODE <br />6TH EDITION SECTION 1609.1.1. <br />COMPONENT & CLADDING WIND LOADS <br />WIND DESIGN ASSUMPTIONS: <br />BUILDING EXPOSURE - B <br />BUILDING RISK CATEGORY - II <br />MEAN ROOF HEIGHT 30' OR LESS <br />HEIGHT & EXPOSURE ADJUSTMENT <br />COEFFICIENT = 1.0 <br />ENCLOSED BUILDING <br />INTERNAL PRESSURE COEFFICIENT = +/- 0.18 <br />WIND SPEED SHOWN AT THE BOTTOM RIGHT <br />CORNER OF THIS SHEET <br />ALL STRUCTURAL ELEMENTS, EXTERIOR <br />WALLS AND INTERIOR WALLS SHALL BE <br />TYPE V CONSTRUCTION PER FBC 602.5 <br />SOIL BEARING & COMPACTION: <br />ALL OTHER <br />BUILDING <br />ROOF OVERHANG <br />COMPONENT <br />ZONE <br />LOADS <br />LOADS <br />1 <br />N/A <br />+32.3/-35.3 <br />2 <br />-65.7 <br />+32.3/-56.2 <br />3 <br />-110.6 <br />+32.3/-89.0 <br />4 <br />N/A <br />+35.3/-38.2 <br />5 <br />N/A <br />+35.31-47.2 <br />THESE PLANS WERE DRAWN BASED UPON AN ALLOWABLE SOIL BEARING CAPACITY OF 2,000 P.S.F. <br />(MINIMUM). THE CONTRACTOR/PROPERTY OWNER ARE RESPONSIBLE FOR VERIFYING THAT THE SOIL <br />ON THE SITE IS PROPERLY PREPARED & COMPACTED SUCH THAT IT CAN SUPPORT A 2,000 P.S.F. <br />FOUNDATION LOADING. <br />T.L. HANSON, A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL <br />ENGINEERING COMPANY; DESIGNED THESE FOUNDATIONS WITHOUT VISITING THE CONSTRUCTION SITE <br />NOR PERFORMING ANY SOIL TESTING. <br />T.L. HANSON SHALL NOT BE RESPONISIBLE FOR THE SITE SOILS ABILITY TO SUPPORT <br />THE BUILDING LOADS. <br />FOUNDATIONS & SLAB -ON -GRADE: <br />BUILDING SITE SHALL BE SCRAPED TO REMOVE ALL ORGANIC MATERIALS WITHIN THE BUILDING AREA <br />ANY ADDITIONAL FILL PLACED ON THE BUILDING PAD AREA, SHALL BE COMPACTED <br />SUCH THAT IT CAN ADEQUATELY SUPPORT A 2,000 P.S.F. FOUNDATION LOADING. <br />SLAB SHALL BE PLACED OVER A 6 MIL VAPOR BARRIER ON CLEAN, ADEQUATELY <br />COMPACTED AND TERMITE POISONED SOIL. <br />CONCRETE UTILIZED IN THE FOUNDATIONS AND SLABS SHALL HAVE A MINIMUM 28 DAY <br />COMPRESSIVE STRENGTH OF 2,500 P.S.I. <br />REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE <br />WITH ASTM A-615. LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 25" <br />FOR #5 REBAR, 30" FOR #6 REBAR & 35" FOR #7 REBAR. <br />PLANS ARE ENGINEERED FOR A MAXIMUM STEMWALL HEIGHT OF 4 COURSES (AFTER <br />FINAL SITE GRADING). THE CONTRACTOR OR BUILDING OWNER SHALL DETERMINE THE <br />EXACT STEMWALL HEIGHT BASED UPON SITE CONDITIONS PRIOR TO POURING THE FOUNDATION <br />AND CONTACT ARKAY ENGINEERING WHEN MORE THAN 4 COURSES ARE REQUIRED. <br />A FOUNDATION SURVEY SHALL BE PERFORMED AND A COPY OF THE SURVEY SHALL BE ON THE <br />SITE FOR THE BUILDING INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE EXPOSED AND <br />A STRING STRETCHED FROM MARKER TO MARKER TO VERIFY THE REQUIRED BUILDING SETBACKS. <br />MASONRY WALLS: <br />CONCRETE MASONRY UNITS SHALL BE HOLLOW UNIT MASONRY IN ACCORDANCE WITH ASTM C-90 <br />AND SHALL HAVE A MINIMUM FM OF 1,500 P.S.I. <br />MORTAR SHALL CONFORM TO ASTM C-270 AND SHALL BE EITHER TYPE M OR S. <br />REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE <br />WITH ASTM A-615. LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 25" <br />FOR #5 REBAR, 30" FOR #6 REBAR & 35" FOR #7 REBAR. <br />GROUT FOR THE POURED CELLS AND LINTELS SHALL HAVE A MAXIMUM COURSE AGGREGATE SIZE <br />OF 3/8", PLACED AT AN 8 TO 11 INCH SLUMP AND HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH <br />OF 2,500 P.S.I. (WHEN TESTED PER ASTM C-1019). <br />PROVIDE CLEAN -OUT OPENINGS (12 SQ. IN.) IN CELLS CONTAINING SPLICED REINFORCEMENT, WHEN <br />THE GROUT POUR EXCEEDS 5 FEET IN HEIGHT. <br />TIMBER MATERIALS: <br />ALL LUMBER IN CONTACT WITH MASONRY WILL BE PRESSURE TREATED <br />MATERIALS <br />INTERIOR STUD WALLS TO BE OF 2 X 4 #2 SPRUCE OR BETTER WITH SINGLE 2 X 4 P.T. <br />PINE BOTTOM PLATE AND SINGLE 2 X 4 #2 SPRUCE TOP PLATE WITH STUDS SPACED <br />MAXIMUM 24" OC. WALLS TO HAVE 1/2" GYPSUM BOARD EACH SIDE, WITH WALLS AT <br />GARAGE TO HAVE MINIMUM R-11 INSULATION <br />DRAFTSTOPPING: <br />IN SINGLE FAMILY DWELLINGS, DRAFTSTOPPING SHALL BE PROVIDED (PARALLEL TO THE MAIN <br />FRAMIMG MEMBERS) IN FLOOR/CEILING ASSEMBLIES SEPARATING USEABLE SPACES. DRAFTSTOPPING <br />SHALL BE CONSTUCTED SUCH THAT THE FLOOR/CEILING ASSEMBLY IS BROKEN UP INTO TWO OR <br />MORE APPROXIMATE AREAS WITH NO AREA GREATER THAN 1000 SO. FT. <br />SOIL TERMITE TREATMENT: <br />TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING PESTICIDES <br />APPLIED TO SOIL, OR WOOD, BAITING SYSTEMS, OR OTHER APPROVED PROTECTION LABELED FOR <br />USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION. <br />A "CERTIFICATE OF COMPLIANCE" SHALL BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED <br />PEST CONTROL COMPANY BEFORE A "CERTIFICATE OF OCCUPANCY" WILL BE ISSUED. THE CERTIFICATE <br />SHALL STATE <br />"THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN <br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE FLORIDA <br />DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES." <br />IF A REGISTERED TERMITICIDE BAIT SYSTEM IS TO BE USED FOR SUBTERRANEAN TERMITE PREVENTION, <br />DO NOT APPLY. A SIGNED FIVE YEAR CONTRACT FROM THE ISSUE <br />OF THE CERTIFICATE OF OCCUPANCY ASSURING INSTALLATION, MAINTENANCE AND MONITORING OF THE <br />BAITING SYSTEM SHALL BE PROVIDED TO THE BUILDING OFFICIAL PRIOR TO THE SLAB POUR. THE SYSTEM <br />MUST BE INSTALLED PRIOR TO FINAL BUILDING APPROVAL. <br />INITIAL SOIL POISONING TREATMENT SHALL BE DONE AFTER ALL EXCAVATION, <br />BACKFILLING & COMPACTION ARE COMPLETE <br />ANY SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RE -TREATED <br />(INCLUDING ANY BOXED OR FORMED AREAS) - <br />BOXED AREAS IN THE CONCRETE SLAB FOR INSTALLATION OF TRAPS SHALL BE MADE <br />WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT FORMS MUST BE OF AN <br />ADEQUATE SIZE & DEPTH TO ELIMINATE ANY DISTURBANCE OF THE SOIL AFTER THE <br />INITIAL TREATMENT. <br />A MINIMUM 6 MIL VAPOR BARRIER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL <br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR BARRIER PLACEMENT, RE -TREATMENT <br />SHALL BE REQUIRED <br />ANY CONCRETE OVERPOUR, MORTAR OR STUCCO MATERIALS ALONG THE FOUNDATION PERIMETER <br />MUST BE REMOVED PRIOR TO EXTERIOR SOIL TREATMENT <br />EXTERIOR SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE <br />WITHIN 12 INCHES OF THE STRUCTURE SIDE WALLS <br />AN EXTERIOR VERTICAL CHEMICAL BARRIER SHALL BE INSTALLED AFTER CONSTRUCTION IS <br />COMPLETE (INCLUDING LANDSCAPING AND IRRIGATION). ANY SOILS DISTURBED AFTER THE <br />VERTICAL BARRIER IS APPLIED, SHALL BE RE -TREATED. <br />CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 12 INCHES AWAY FROM THE <br />BUILDING SIDEWALLS (PER FBC R318). <br />AFTER ALL WORK IS COMPLETED, ANY LOOSE WOOD AND FILL MUST BE REMOVED FROM BELOW <br />AND WITHIN 12 INCHES OF THE BUILDING. THIS SHALL INCLUDE ALL GRADE STAKES, TUB TRAP BOXES <br />FORMS, SHORING AND ANY OTHER CELLULOSE CONTAINING MATERIALS. <br />THE DISTANCE FROM THE EXTERIOR WALL COVERING (EXCEPTIONS: PAINT AND DECORATIVE <br />CEMENTITIOUS FINISHES LESS THAN 5/8 INCH THICK ADHERED DIRECTLY ONTO THE FOUNDATION <br />WALL) AND FINAL EARTH GRADE SHALL NOT BE LESS THAN 6 INCHES TO ALLOW FOR INSPECTION <br />FOR FUTURE TERMITE INFESTATIONS <br />TRUSSES: <br />IF THE CONTRACTOR, TRUSS MANUFACTURER OR ANY OTHER DESIGN PROFESSIONALS REVISE THE <br />TRUSS SYSTEM LAYOUT FROM THOSE SHOWN ON THESE PLANS T. L. HANSON & ASSOCIATES IS <br />REQUIRED TO REVIEW ALL FINAL CONSTRUCTION DOCUMENTS FOR COMPLIANCE WITH THE DESIGN <br />INTENT PRIOR TO COMMENCEMENT OF THE PROJECT. <br />EXTERIOR WINDOWS & DOOR ASSEMBLIES: <br />ALL EXTERIOR WINDOW & GLASS DOORS SHALL BE TESTED IN ACCORDANCE WITH ANSI/AMMA/NWWDA <br />101/IS2 STANDARDS AND BEAR AN AMMA OR WDMA LABEL IDENTIFYING THE MANUFACTURER, <br />PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT TESTING ENTITY, <br />ALL MULLIONS AND ADJACENT DOOR/WINDOW ASSEMBLIES SHALL BE TESTED OR ENGINEERED TO <br />TRANSFER 1.5 TIMES THE DESIGN LOADS TO THE ROUGH OPENING SUBSTRATE. <br />INSTALL ALL WINDOW & DOOR ASSEMBLIES PER THE MANUFACTURERS ANCHORING RECOMMENDATIONS <br />TO ACHEIVE THE DESIGN PRESSURES SPECIFIED. <br />ELECTRICAL, PLUMBING & MECHANICAL: <br />IN ACCORDANCE WITH CHAPTER 471.003(2)(1) OF THE FLORIDA ADMINISTRATIVE CODE; ELECTRICAL, <br />PLUMBING AND MECHANICAL SYSTEMS SHALL BE DESIGNED BY THE RESPECTIVE CONTRACTORS TO <br />MEET ALL APPLICABLE CODES. THE ELECTRICAL, PLUMBING AND MECHANICAL SYSTEMS DRAWN HEREON <br />ARE BASED UPON A DESIGN PROVIDED BY THE OWNER TO ADDRESS HIS/HER REQUIREMENTS, <br />ALL ELECTRICAL OUTLETS IN BATHROOMS, KITCHEN (WITHIN 6 FEET OF SINKS), GARAGE AND AT <br />EXTERIOR LOCATIONS SHALL BE WIRED INTO A GROUND -FAULT INTERRUPTER "GFI" CIRCUIT. <br />ALL ELECTRICAL OUTLETS IN BEDROOMS SHALL BE WIRED INTO AN ARC -FAULT INTERRUPTER <br />"AR" CIRCUIT. <br />SAFETY GLAZING: <br />THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE PURPOSES OF <br />GLAZING PER THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308: <br />(1) GLAZING IN SWINGING DOORS, FIXED AND SLIDING PANELS OF SLIDING DOOR <br />ASSEMBLIES. <br />(2) GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM <br />ROOMS, BATHTUBS, AND SHOWERS. GLAZING IN ANY PORTION OF A BUILDING WALL <br />ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EDGE OF THE GLAZING IS LESS <br />THAN 60 INCHES ABOVE THE DRAIN INLET. <br />(3) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT A DOOR WHERE <br />THE NEAREST VERTICAL EDGE IS WITHIN A 24 INCH RADIUS OF THE DOOR IN A <br />CLOSED POSITION AND WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES ABOVE THE <br />FINISHED FLOOR OR WALKING SURFACE. <br />(4) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, OTHER THAN THOSE LOCATIONS <br />DESCRIBED IN ITEMS (2) AND (3) ABOVE. THAT MEETS ALL OF THE FOLLOWING <br />CONDITIONS: <br />A) EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 SQ. FT. <br />B) BOTTOM EDGE LESS THAN 18 INCHES ABOVE THE FLOOR. <br />C) TOP EDGE GREATER THAN 36 INCHES ABOVE THE FLOOR. <br />D) ONE OR MORE WALKING SURFACES WITHIN 36 INCHES HORIZONTALLY OF THE <br />PLANE OF THE GLAZING. <br />REFER TO THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308 FOR ADDITIONAL AREAS <br />THAT MAY BE CONSIDERED A HAZARDOUS LOCATION FOR THE PURPOSE OF GLAZING. <br />BUILDING DATA: <br />USE AND OCCUPANCY: BUSINESS GROUP B <br />TYPE CONSTRUCTION: VB <br />FIRE PRO i ECTION: NON SPRINKLED <br />OCCUPANT LOAD CAPACITY: <br />BUSINESS 492 SQ. FT. 100 GROSS PER SQUARE FOOT = 5 PEOPLE <br />STORAGE 296 SQ. FT. 300 GROSS PER SQUARE FOOT = 1 PEOPLE <br />TOTAL OCCUPANCY = 6 PEOPLE <br />EXISTING PLUMBING FIXTURES MEET REQUIREMENT PER TABLE 403.1 <br />■� A IL ■ A %k ff <br />rV D E S I G N S I N C <br />BUILDING DESIGNS <br />13821 U.S. HWY 98 BY PASS DADE CITY, FLORIDA 33523 <br />OFFICE 352-523-2077 FAX 352-567-2070 <br />OFFICE AND STORAGE ADDITION FOR <br />ZEPHYRHILLS CHRISTIAN CHRUCH <br />5940 DOGWOOD STREET <br />ZEPHYRHILLS, FLORIDA <br />SITE JOB SITE LOCATION MAP <br />1 <br />L <br />6TH EDITION FLORIDA FIRE PREVENTION <br />6TH EDITION 2017 FLORIDA BUILDING CODE <br />6TH EDITION 2017 FLORIDA ACCESSIBILITY CODE <br />6TH EDITION 2017 FLORIDA ENERGY CONSERVATION CODE <br />6TH EDITION 2017 FLORIDA MECHANICAL CODE <br />6TH EDITION 2017 FLORIDA PLUMBING CODE <br />2017 NFPA 10 (STANDARD FOR PORTABLE FIRE EXTINGUISHERS) <br />2014 NATIONAL ELECTRICAL CODE (NFPA 70) <br />CONTRACTOR TO PROVIDE TACTICAL SIGNS AS REQUIRED <br />CONTRACTOR TO PROVIDE SIGNS DESIGNATING TYPE OF ROOF CONSTRUCTION <br />BUILDING HAS WOOD ROOF SYSTEM <br />LIGHT FRAME CONSTRUCTION SIGN REQUIRED <br />INTERIOR FINISHES <br />TABLE 803.11 <br />INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCY' <br />SPRINKLERED' <br />NONSPRINKLERED <br />GROUP <br />Interior exit stairways and ramps <br />„ <br />and exit passageways" <br />Corridors and <br />enclosure for exit <br />access stairways <br />ra <br />Rooms and <br />enclosed <br />spaces` <br />Interfor exit stairways <br />ramps and exit <br />passageways'' <br />Corridors and <br />enclosure for exit <br />access stairways <br />nd s <br />Rooms and <br />enclosed <br />spaces` <br />A —I & A-2 <br />B <br />B <br />C <br />-- A --- <br />Air — <br />— Bs. <br />—A <br />B, F,, N1, R—I <br />B <br />C <br />C <br />B <br />-- <br />C <br />R-4 -- <br />B <br />C <br />C <br />A <br />B <br />— B <br />lI <br />B ---- <br />B <br />C <br />A <br />A <br />B <br />i-1 <br />B <br />C <br />C <br />A <br />B <br />B <br />1-2 <br />__.._..._...__. <br />B- -- -- — <br />_ <br />— -- B <br />Bh. ' <br />— <br />A <br />A <br />B <br />13 <br />4 <br />A' <br />C <br />A <br />A <br />B <br />---I-4 <br />--- — B <br />B <br />B" ' <br />A <br />A <br />B <br />R-2 <br />_ C <br />C <br />C <br />B <br />B <br />C <br />R-3 <br />C-- <br />- C -- <br />C <br />C <br />C <br />C <br />S <br />C <br />C <br />C <br />B <br />B <br />c: <br />17 <br />_.-____ ------ <br />No restrictions <br />No restrictions <br />For Si: 1 inch = 25A nun, 1 square foot = 0.0929m2. <br />a. Class C'. interior finish materials shall he permitted for wainscotting or paneling of not more than 1,000 square feet of applied surface area in the grade lobby <br />where applied directly to a noncombustible base or over furring strips applied to a noncombustible base tmdfireblockedas required by Section 803.13.1. <br />b. In other than Group I-3 occupancies in buildin gs less than three stories above grade plane, Class B interior finish for nonsprinklered bu ldings and Ctrs C <br />interiorfinish for .spriuklcred buildings shall be permitted iir interior exit sttwe°ays and ramps. <br />c. Requirements for rooms and enclosed spaces shall be based upon spaces enclosed by partitions. Where a fire -resistance rating is required for structural <br />elements, the enclosing pai titions shrill extend from the floor co the ceiling. Partitions that do not comply with this shall be corm;idered enclosing spaces and the <br />rooms or spaces on both sides shrill be considered one. In determining the applic ibie icquiremcnts foi ronrns and enclosed spaces, the specific occupancy, <br />thereuf shall be the govcinin,g, factor regardless of the group classification of the building or stricture. <br />d_ Lobby areas in Group A-1, A-2 and A-3 occupancies shall not be less than Class B materials. <br />c. Class C interior finish materials shall be permitted in places of assembly with an occupant load of 300 persons or less. <br />f. For places of religious worship, wood used for ornamental purposes, trusses, pan.elina or chancel furnishing shah be permitted. <br />g. Class B material is required where the building exceeds two stories. <br />h. Class C interior finish materials shall be permitted in administrative spaces. <br />i. Class C interior finish materials shall be permitted in rooms with a capacity offourpetsons or less. <br />j. Class B materials shall be permitted as wainscotting extending not more that) 48 inches above the finished floor in corridors and exit access stairways and <br />ramps. <br />k. Finish materials as provided for in other sections of this code. <br />L, Applies when protected Mr an automatic sprinkler system installed in accordance. with Section 903.3.1.1 or 903.3-1.2. <br />D <br />PLAN INDEX: <br />SHEET B 1 : EXISTING FLOOR PLAN <br />SHEET B 2: PROPOSED FLOOR PLAN <br />FLORIDA APPROVAL CHART <br />DOOR AND WINDOW SCHEDULE <br />SHEET B 3: ELEVATIONS <br />ROOF SHEATHING DETAIL <br />EXTERIOR WALL SECTION <br />INTERIOR WAL SECTION <br />SHEET B 4: FOUNDATION PLAN <br />LINTEL DETAIL <br />LINTEL CHART <br />SHEET B 5: ROOF TRUSS PLAN <br />GABLE BRACE DETAIL <br />MINIMUM TRUSS BRACE DETAIL <br />VALLEY FRAMING DETAIL <br />FLASHING DETAIL <br />SHEET E M : POWER & MECHANICAL PLAN <br />DROP CEILING & LIGHTING PLAN <br />FIXTURE LEGEND <br />Pt <br />(352) 521i. <br />-5848 <br />V <br />oft � �TZ:���v <br />C +. f Z�H'YR�11I,1.�t <br />tUlt'M6 OMCIA L t,�i — <br />T, L. HAN50N <br />4 ASSOCIATES, INC, <br />CONSULTING ENGINEERS <br />ENGINEERING eUSINES5 NO, E5583O <br />Post Office Box 1128 <br />Dade Cit�i, Florida 33526 <br />THOMAS L, HANSON, PE 38ro54 <br />