Laserfiche WebLink
Design No. U419 <br />Nonbearing Wall Rating - 1, 2, 3 OR 4 HR. <br />For Number of Layers 4 <br />and Hourly Ratings <br />See Item 4 <br />3 3A 2 <br />1 4 <br />1. Floor and Ceiling Runners - (Not shown) -- Channel shaped, fabricated from min. 25 MSG (min. 20 MSG <br />when Item 4A is used) corrosion -protected steel, min. width to accomodate stud size, with min. 1 in. long <br />legs, attached to floor and ceiling with fasteners 24 in. OC max. <br />2, Steel Studs -- Channel shaped, fabricated from min. 25 MSG (min. 20 MSG when Item 4A is used) <br />corrosion -protected steel, min. width as indicated under Item 4, min. 1-1/4 in. flanges and 1/4 in. return, <br />spaced a max of 24 in. OC. Studs to be cut 318 to 3/4 in. less than assembly height. <br />3. Batts and Blankets* -- (Required as indicated under Item 4) - Mineral wool batts, friction fitted between <br />studs and runners. Min. nom, thickness as indicated under Item 4. See Batts and Blankets (BKNV or <br />BZJZ) Categories for names of classified companies. <br />4. Gypsum Board* -- Gypsum panels with beveled, square or tapered edges, applied vertically or horizontally. <br />Vertical joints centered over studs and staggered one stud cavity on opposite sides of studs. Vertical joints <br />in adjacent layers (multilayer systems) staggered one stud cavity. Horizontal joints need not be backed by <br />steel framing. Horizontal edge joints and horizontal butt joints on opposite sides of studs need not be <br />staggered. Horizontal edge joints and horizontal butt joints in adjacent layers (multilayer systems) staggered <br />a min. of 12 in. The thickness and number of layers for the 1 hr, 2 hr, 3 hr, and 4 hr ratings are as follows: <br />Wallboard Protection on Each Side of Wall <br />Rating Min. Stud Depth No. of Layers and Min. Thickness of <br />Thickness of Panel Insulation (Rem 3) <br />1 3-1/2 1 layer, 518 in. thick Optional <br />1 2-1/2 1 layer, 1/2 in. thick 1-1/2 in. <br />1 1-5/8 1 layer, 314 In. thick Optional <br />2 1-5/8 2layers, 1/2 in. thick Optional <br />2 1-5/8 2 layers, 5/8 in. thick Optional <br />2 3-1/2 1 layer, 3/4 in. thick 3 in. <br />3 1-5/8 3 layers ,112 in. thick Optional <br />3 1-5/8 2 layers, 3/4 in. thick Optional <br />3 1-5/8 3 layers, 5/8 in. thick Optional <br />4 1-5/8 4 layers, 5/8 in. thick Optional <br />4 1-5/8 4layers, 112 in, thick Optional <br />4 2-1/2 2 layers, 314 in. thick 2 in. <br />UL DESIGN NO. U419 <br />SCALE: NOT TO SCALE <br />1-hr. Fire Rated Assembly <br />(seen NER 258) <br />USG Steel J-Runner <br />1" SHEETROCK Brand <br />gypsum shaft wall liner <br />Power -actuated <br />fasteners 24" O.C. USG steel C-H <br />(300-I. shear) stud 24" o.c. <br />I <br />—518" SHEETROCK <br />Brand gypsum panels. <br />Sealant FIRECODE C core <br />U.S.G. CORP. <br />NER 258 <br />SCALE: NOT TO SCALE <br />Design No. U437 <br />Nonbearing Wall Rating -1 or 2 HR. (See Item 5) <br />Horizontal Section <br />7-7 <br />0 <br />Oat/ <br />J O <br />I /� <br />Vertical Section <br />1. Floor and Ceiling Runners — "J"-shaped runner, min 4 in. deep with unequal legs of 1 in. and 2 in., fabricated <br />from 20 MSG galv steel. Runners positioned with short leg toward finished side of wall. Runners attached to <br />structural supports with steel fasteners located not greater than 2 in. from ends and spaced no more than 24 in. <br />OC. <br />2, Vertical Runners — "J"-shaped runner, min 4 in. deep with unequal legs of 1 in. and 2 in., fabricated from 20 <br />MSG galv steel. Vertical runners positioned at each end of the wall with short leg toward finished side of wall. <br />Runners attached to structural supports with steel fasteners located not greater than 2 in. from ends and spaced <br />no more than 24 in. OC. <br />3. Steel Studs — "C-H" -shaped studs, min 4 in. deep, with 1-1/2 in. wide flanges, fabricated from 20 MSG galv <br />steel. Installed horizontally, with the "C" section of the studs facing down, friction fitted in the vertical "J"-shaped <br />runners resting upon 2 by 2 in. by 20 ga. steel angles which are fastened to the side "J"-shaped runners. Studs cut <br />to lengths to allow a 3/8 to 1/2 in. gap at each end of the wall, and spaced vertically 24 in. or 600 mm OC. As an <br />option, the studs may be screw attached to the side "J"-shaped runners. A total of four 112 in. long pan -head steel <br />screws are to be installed, one at each end of the stud on each side of the wall. <br />4. Gypsum Board* —1 in. thick gypsum wallboard liner panels, supplied in nom 24 in. or 600 mm (for metric <br />spacing) widths. Panels cut to lengths 1 in. less than the width of the wall. Once between the vertical "J"-shaped <br />runners, the panels are centered to split equally at each end the 1 in. gap. Installed horizontally, with the long <br />edges inserted in the "H" section of the "C-H"-shaped studs. The top edge of the liner panel shall be cut 1 in. less <br />than opening height to allow installation past the 1 in. leg of J-runner. Free edge of panels attached to the long leg <br />of the top and bottom "J" -runners with 1-5/8 in. long Type S or S-12 steel screws spaced no more than 12 in. OC. <br />The width of the wall is limited to the length of the liner panels (no butt joints in the liner panels). <br />CANADIAN GYPSUM COMPANY — Type SLX <br />UNITED STATES GYPSUM CO — Type SLX <br />USG MEXICO S A DE C V — Type SLX <br />5. Gypsum Board* — 518 in. thick, 24 to 54 in. wide gypsum panels applied vertically in one (1-hr system) or two <br />(2-hr system) layers. Vertical joints between panels need not be backed by framing. Vertical joints between layers <br />staggered a minimum of 12 in. Horizontal joints centered over studs and staggered a minimum of 24 in. in adjacent <br />courses and 24 in, between layers. 1-Hr System: Single layer attached to studs and vertical and horizontal <br />"J"-shaped runners with 1 in. long Type S or S-12 steel screws spaced 8 in. OC. Joints covered with paper tape <br />and joint compound. Exposed screw heads covered with joint compound. Joint tape and compound may be <br />omitted when square edge panels are used. 2-Hr System: Base or inner layer attached to studs and vertical and <br />horizontal "J"-shaped runners with 1 in. long Type S or SA 2 steel screws spaced 12 in. OC. Outer or face layer <br />attached to studs and vertical and horizontal "J"-shaped runners with 1-5/8 in. long Type S or S-12 steel screws <br />spaced 8 in. OC. Outer layer joints covered with paper tape and joint compound. Exposed screw heads covered <br />with joint compound. Joint tape and compound may be omitted when square edge panels are used. <br />CANADIAN GYPSUM COMPANY — Type AR, IP-AR, IP-X1, SCX or WRX <br />UNITED STATES GYPSUM CO — Type AR, IP-AR, IP-X1, SCX, WRX or <br />FRX-G <br />USG MEXICO S A DE C V — Type AR, IP-AR, IP-X1, SCX or WRX <br />6. Batts and Blankets* — (Optional - Not shown) — Mineral wool or glass fiber batts partially or completely filling <br />stud cavity. Any mineral wool or glass fiber batt material bearing the UL Classification Marking as to Surface <br />Burning Characteristics and/or Fire Resistance. <br />*Bearing the UL Classification Mark <br />UL DESIGN NO. U437 I <br />SCALE: NOT TO SCALE <br />Design No. U905 <br />Bearing Wall Rating -- 2 Hr. <br />Nonbearing Wall Rating -- 2 Hr. <br />�14— — — — — — — — — — — — — — — — — — — — — <br />n o. 0 <br />3 Min. <br />2 4 <br />Horizontal Section <br />1. Concrete Blocks* -- Various designs. Classification D-2 (2 hr). See Concrete Blocks category for list of <br />eligible manufacturers. <br />2. Mortar - Blocks laid in full bed of mortar, nom. 3/8 in. thick, of not less than 2-1/4 and not more than 3-1/2 <br />parts of clean sharp sand to 1 part Portland cement (proportioned by volume) and not more than 50 <br />percent hydrated lime (by cement volume). Vertical joints staggered. <br />3. Portland Cement Stucco or Gypsum Plaster - Add 1/2 hr. to classification if used. Where combustible <br />members are framed in wall, plaster or stucco must be applied on the face opposite framing to achieve a <br />max. Classification of 1-1/2 hr. Attached to concrete blocks (Item 1). <br />4. Loose Masonry Fill -- If all core spaces are filled with loose dry expanded slag, expanded clay or shale <br />(Rotary Kiln Process), water repellant vermiculite masonry fill insulation, or silicone treated perlite loose fill <br />insulation add 2 hr. to classification. <br />5. Foamed Plastic* -- (Optional - Not Shown) -1-1/2 in. thick max, 4 ft. wide sheathing attached to concrete <br />blocks (item 1). <br />THE DOW CHEMICAL CO -- Type Thermax <br />*Bearing the UL Classification Mark <br />UL DESIGN NO. U905 I <br />SCALE: NOT TO SCALE <br />Furr, <br />Wegman & <br />Banks <br />Architects, P.A. AR0006480 <br />625 EAST ORANGE ST. <br />LAKELAND, FL 33801 <br />E-MAIL: INFO@FWBARCHITECTS.COM <br />WWW.FWBARCHITECTS.COM <br />PH. 863.688.1211 <br />0 COPYRIGHT 2021 <br />FURR, WEGMAN & BANKS ARCHITECTS, PA <br />THE DESIGN AND CONCEPTS DEPICTED HEREWITH ARE THE SOLE <br />PROPERTY OF FURR. WEGMAN & BANKS ARCHITECTS, PA. <br />NO REPRODUCTION, REVISION OR REUSE OF THIS DRAWING IS <br />AUTHORIZED WITHOUT SPECIFIC WRITTEN PERMISSION. <br />ALL RIGHTS RESERVED. <br />Lrl <br />(n to <br />14 DO <br />Z Q <br />a (T <br />co <br />O E.9 <br />v._\ <br />a <br />Z W 1� <br />FY <br />a _ <br />U <br />d' <br />a <br />J <br />Z <br />O <br />I— <br />Lu <br />Lu <br />rn <br />_ <br />I— <br />z <br />0 <br />0 <br />LLl <br />0 <br />z <br />0 <br />Lu <br />W <br />0 <br />aN co v LO cfl t` <br />N <br />O <br />N <br />ti <br />N <br />OD <br />0 <br />W <br />H <br />Q <br />H <br />U) z <br />(D W <br />V <br />z <br />~ 0 <br />Z Z <br />J J_J O <br />f J� C) <br />F z z Z <br />LLl U) U <br />C0 O <br />LL D 0 <br />0�u C)C0 3:~10� Z J <br />w 20 W <br />LL > 0 a <br />J U) Q (0N <br />PROJ MGR: CKD 17 <br />ACT MAB <br />JOB NUMBER: <br />21-19 <br />SHEET NUMBER: <br />L S 10 1 <br />