GENERAL NOTES:
<br />THIS BUILDING HAS BEEN DESIGNED TO CONFORM TO THE 2020 FLORIDA BUILDING CODE
<br />7 TH EDITION
<br />ARKAY ENGINEERING, INC.; A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL
<br />ENGINEERING COMPANY, HAS APPLIED 'RATIONAL ANALYSIS" FOR THE STRUCTURAL DESIGN
<br />OF THIS STRUCTURE.
<br />THE BUILDING (INCLUDING ALL COMPONENTS AND CLADDINGS) SHALL BE DESIGNED FOR THE
<br />FOLLOWING SUPERIMPOSED LOADS:
<br />FLOOR:
<br />LIVE LOAD - 50 P.S.F.
<br />DEAD LOAD - 10 P.S.F.
<br />ROOF -
<br />LIVE LOAD (TRUSS TOP CHORD) - 20 P.S.F.
<br />DEAD LOAD (TRUSS TOP CHORD) - 10 P.S.F.
<br />DEAD LOAD (TRUSS BOTTOM CHORD) - 10 P.S.F.
<br />ASSUMED TRUSS SELF WEIGHT (DEAD LOAD) - 7 P.S.F.
<br />WIND'
<br />BUILDING IS DESIGNED TO CONFORM TO ASCE 7-16, CHAPTERS 26 THRU 31; PER 2020 FLORIDA
<br />BUILDING CODE, 7 TH EDITION - SECTION R301.2.1.1. AND 2020 FLORIDA BUILDING
<br />CODE 7 TH EDITION SECTION 1609
<br />WIND DESIGN ASSUMPTIONS:
<br />BUILDING EXPOSURE - B
<br />BUILDING RISK CATEGORY - II
<br />MEAN ROOF HEIGHT 30' OR LESS
<br />HEIGHT & EXPOSURE ADJUSTMENT
<br />COEFFICIENT = 1.0
<br />ENCLOSED BUILDING
<br />INTERNAL PRESSURE COEFFICIENT = +/- 0.18
<br />WIND SPEED SHOWN AT THE BOTTOM RIGHT
<br />CORNER OF THIS SHEET
<br />ALL STRUCTURAL ELEMENTS, EXTERIOR
<br />WALLS AND INTERIOR WALLS SHALL BE
<br />TYPE V CONSTRUCTION PER FBC 602.5
<br />SOIL BEARING & COMPACTION:
<br />COMPONENT & CLADDING WIND LOADS
<br />ALL OTHER
<br />BUILDING
<br />ROOF OVERHANG
<br />COMPONENT
<br />20NE
<br />LOADS
<br />LOADS
<br />1
<br />N/A
<br />+32.3/-35.3
<br />2
<br />-65.7
<br />+32.31-56 2
<br />3
<br />-110.6
<br />+32.3/-89.0
<br />4
<br />N/A
<br />t 35.3/-38.2
<br />11
<br />N/A
<br />+35.3/A7.2
<br />THESE PLANS WERE DRAWN BASED UPON AN ALLOWABLE SOIL BEARING CAPACITY OF 2,000 P S F.
<br />(MINIMUM). THE CONTRACTOR/PROPERTY OWNER ARE RESPONSIBLE FOR VERIFYING THAT THE SOIL
<br />ON THE SITE IS PROPERLY PREPARED & COMPACTED SUCH THAT IT CAN SUPPORT A 2,000 P.S.F.
<br />FOUNDATION LOADING.
<br />ARKAY ENGINEERING, INC.; A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL
<br />ENGINEERING COMPANY; DESIGNED THESE FOUNDATIONS WITHOUT VISITING THE CONSTRUCTION SITE
<br />NOR PERFORMING ANY SOIL TESTING.
<br />ARKAY ENGINEERING, INC. SHALL NOT BE RESPONISIBLE FOR THE SITE SOILS ABILITY TO SUPPORT
<br />THE BUILDING LOADS.
<br />FOUNDATIONS & SLAB -ON -GRADE:
<br />BUILDING SITE SHALL BE SCRAPED TO REMOVE ALL ORGANIC MATERIALS WITHIN THE BUILDING AREA.
<br />ANY ADDITIONAL FILL PLACED ON THE BUILDING PAD AREA, SHALL BE COMPACTED
<br />SUCH THAT IT CAN ADEQUATELY SUPPORT A 2,000 P.S.F. FOUNDATION LOADING.
<br />SLAB SHALL BE PLACED OVER A 6 MIL VAPOR BARRIER ON CLEAN, ADEQUATELY
<br />COMPACTED AND TERMITE POISONED SOIL.
<br />CONCRETE UTILIZED IN THE FOUNDATIONS AND SLABS SHALL HAVE A MINIMUM 28 DAY
<br />COMPRESSIVE STRENGTH OF 2,500 P.S.I.
<br />REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE
<br />WITH ASTM A-615. LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 25'
<br />FOR #5 REBAR, 30" FOR #6 REBAR & 35" FOR #7 REBAR.
<br />PLANS ARE ENGINEERED FOR A MAXIMUM STEMWALL HEIGHT OF 4 COURSES (AFTER
<br />FINAL SITE GRADING) THE CONTRACTOR OR BUILDING OWNER SHALL DETERMINE THE
<br />EXACT STEMWALL HEIGHT BASED UPON SITE CONDITIONS PRIOR TO POURING THE FOUNDATION
<br />AND CONTACT ARKAY ENGINEERING WHEN MORE THAN 4 COURSES ARE REQUIRED.
<br />A FOUNDATION SURVEY SHALL BE PERFORMED AND A COPY OF THE SURVEY SHALL BE ON THE
<br />SITE FOR THE BUILDING INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE EXPOSED AND
<br />A STRING STRETCHED FROM MARKER TO MARKER TO VERIFY THE REQUIRED BUILDING SETBACKS.
<br />MASONRY WALLS:
<br />CONCRETE MASONRY UNITS SHALL BE HOLLOW UNIT MASONRY IN ACCORDANCE WITH ASTM C-90
<br />AND SHALL HAVE A MINIMUM F'M OF 1,500 P.S.I.
<br />MORTAR SHALL CONFORM TO ASTM C-270 AND SHALL BE EITHER TYPE M OR S.
<br />REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE
<br />WITH ASTM A-615. LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 25"
<br />FOR #5 REBAR, 30" FOR #6 REBAR & 35" FOR #7 REBAR.
<br />GROUT FOR THE POURED CELLS AND LINTELS SHALL HAVE A MAXIMUM COURSE AGGREGATE SIZE
<br />OF 3/8', PLACED AT AN 8 TO 11 INCH SLUMP AND HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH
<br />OF 2,500 P.S.I. (WHEN TESTED PER ASTM C-1019),
<br />PROVIDE CLEAN -OUT OPENINGS (12 SO IN_) IN CELLS CONTAINING SPLICED REINFORCEMENT, WHEN
<br />THE GROUT POUR EXCEEDS 5 FEET IN HEIGHT.
<br />TIMBER MATERIALS
<br />ALL TIMBER MATERIALS SHALL BE AS FOLLOWS:
<br />ALL LUMBER IN CONTACT WITH MASONRY WILL BE PRESSURE TREATED
<br />MATERIALS
<br />INTERIOR STUD WALLS TO BE OF 2 X 4 #2 SPRUCE OR BETTER WITH SINGLE 2 X 4 P.T.
<br />PINE BOTTOM PLATE AND SINGLE 2 X 4 #2 SPRUCE TOP PLATE WITH STUDS SPACED
<br />MAXIMUM 24" OC. WALLS TO HAVE 112" GYPSUM BOARD EACH SIDE, WITH WALLS AT
<br />GARAGE TO HAVE MINIMUM R-11 INSULATION
<br />SOIL TERMITE TREATMENT:
<br />TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING PESTICIDES
<br />APPLIED TO SOIL, OR WOOD, BAITING SYSTEMS, OR OTHER APPROVED PROTECTION LABELED FOR
<br />USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION.
<br />A "CERTIFICATE OF COMPLIANCE" SHALL BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED
<br />PEST CONTROL COMPANY BEFORE A "CERTIFICATE OF OCCUPANCY" WILL BE ISSUED. THE CERTIFICATE
<br />SHALL STATE
<br />"THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
<br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE FLORIDA
<br />DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES-"
<br />IF A REGISTERED TERMITICIDE BAIT SYSTEM IS TO BE USED FOR SUBTERRANEAN TERMITE PREVENTION,
<br />DO NOT APPLY. A SIGNED FIVE YEAR CONTRACT FROM THE ISSUE
<br />OF THE CERTIFICATE OF OCCUPANCY ASSURING INSTALLATION, MAINTENANCE AND MONITORING OF THE
<br />BAITING SYSTEM SHALL BE PROVIDED TO THE BUILDING OFFICIAL PRIOR TO THE SLAB POUR_ THE SYSTEM
<br />MUST BE INSTALLED PRIOR TO FINAL BUILDING APPROVAL.
<br />INITIAL SOIL POISONING TREATMENT SHALL BE DONE AFTER ALL EXCAVATION,
<br />BACKFILLING & COMPACTION ARE COMPLETE
<br />ANY SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RE -TREATED
<br />(INCLUDING ANY BOXED OR FORMED AREAS) -
<br />BOXED AREAS IN THE CONCRETE SLAB FOR INSTALLATION OF TRAPS SHALL BE MADE
<br />WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT FORMS MUST BE OF AN
<br />ADEQUATE SIZE & DEPTH TO ELIMINATE ANY DISTURBANCE OF THE SOIL AFTER THE
<br />INITIAI TREATMFNI.
<br />A MINIMUM 6 MIL VAPOR BARRIER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL
<br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR BARRIER PLACEMENT, RE -TREATMENT
<br />SHALL BE REQUIRED
<br />ANY CONCRETE OVERPOUR, MORTAR OR STUCCO MATERIALS ALONG THE FOUNDATION PERIMETER
<br />MUST BE REMOVED PRIOR TO EXTERIOR SOIL TREATMENT
<br />EXTERIOR SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE
<br />WITHIN 12 INCHES OF THE STRUCTURE SIDE WALLS
<br />AN EXTERIOR VERTICAL CHEMICAL BARRIER SHALL BE INSTALLED AFTER CONSTRUCTION IS
<br />COMPLETE (INCLUDING LANDSCAPING AND IRRIGATION). ANY SOILS DISTURBED AFTER THE
<br />VERTICAL BARRIER IS APPLIED, SHALL BE RE -TREATED.
<br />CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 12 INCHES AWAY FROM THE
<br />BUILDING SIDEWALLS (PER FBC R318).
<br />AFTER ALL WORK IS COMPLETED, ANY LOOSE WOOD AND FILL MUST BE REMOVED FROM BELOW
<br />AND WITHIN 12 INCHES OF THE BUILDING. THIS SHALL INCLUDE ALL GRADE STAKES, TUB TRAP BOXES
<br />FORMS, SHORING AND ANY OTHER CELLULOSE CONTAINING MATERIALS.
<br />THE DISTANCE FROM THE EXTERIOR WALL COVERING (EXCEPTIONS: PAINT AND DECORATIVE
<br />CEMENTITIOUS FINISHES LESS THAN 5/8 INCH THICK ADHERED DIRECTLY ONTO THE FOUNDATION
<br />WALL) AND FINAL EARTH GRADE SHALL NOT BE LESS THAN 6 INCHES TO ALLOW FOR INSPECTION
<br />FOR FUTURE TERMITE INFESTATIONS
<br />TRUSSES
<br />IF THE CONTRACTOR, TRUSS MANUFACTURER OR ANY OTHER DESIGN PROFESSIONALS REVISE THE
<br />TRUSS SYSTEM LAYOUT FROM THOSE SHOWN ON THESE PLANS T_ L HANSON & ASSOCIATES IS
<br />REQUIRED TO REVIEW ALL FINAL CONSTRUCTION DOCUMENTS FOR COMPLIANCE WITH THE DESIGN
<br />INTENT PRIOR TO COMMENCEMENT OF THE PROJECT.
<br />EXTERIOR WINDOWS & DOOR ASSEMBLIES:
<br />ALL EXTERIOR WINDOW & GLASS DOORS SHALL BE TESTED IN ACCORDANCE WITH ANSI/AMMA/NWWDA
<br />101/IS2 STANDARDS AND BEAR AN AMMA OR WDMA LABEL IDENTIFYING THE MANUFACTURER,
<br />PERFORMANCE CHARACTERISTICS AND APPROVED PRODUC I I ES I ING EN 11 I Y.
<br />ALI. MULLIONS AND ADJACENT DOORIWINDOW ASSEMBLIES SHALL BE TESTED OR ENGINEERED TO
<br />TRANSFER 1.5 TIMES THE DESIGN LOADS TO THE ROUGH OPENING SUBSTRATE.
<br />INSTALL ALL WINDOW & DOOR ASSEMBLIES PER THE MANUFACTURERS ANCHORING RECOMMENDATIONS
<br />TO ACHIEVE THE DESIGN PRESSURES SPECIFIED.
<br />ELECTRICAL, PLUMBING & MECHANICAL
<br />IN ACCORDANCE WITH CHAPTER 471.003(2)(1) OF THE FLORIDA ADMINISTRATIVE CODE, ELECTRICAL,
<br />PLUMBING AND MECHANICAL SYSTEMS SHALL BE DESIGNED BY THE RESPECTIVE CONTRACTORS TO
<br />MEET ALL APPLICABLE CODES. THE ELECTRICAL, PLUMBING AND MECHANICAL SYSTEMS DRAWN HEREON
<br />ARE BASED UPON A DESIGN PROVIDED BY THE OWNER TO ADDRESS HIS/HER REQUIREMENTS.
<br />ALL ELECTRICAL OUTLETS IN BATHROOMS, KITCHEN, GARAGE AND AT
<br />EXTERIOR LOCATIONS SHALL BE WIRED INTO A GROUND -FAULT INTERRUPTER "GFI" CIRCUIT.
<br />ALL ELECTRICAL OUTLETS IN HABITABLE SPACES SHALL BE WIRED INTO AN ARC -FAULT INTERRUPTER
<br />SAFETY GLAZING:
<br />THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE PURPOSES OF
<br />GLAZING PER THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308:
<br />(1) GLAZING IN SWINGING DOORS, FIXED AND SLIDING PANELS OF SLIDING DOOR
<br />ASSEMBLIES.
<br />(2) GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM
<br />ROOMS, BATHTUBS, AND SHOWERS. GLAZING IN ANY PORTION OF A BUILDING WALL
<br />ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EDGE OF THE GLAZING IS LESS
<br />THAN 60 INCHES ABOVE THE DRAIN INLET.
<br />(3) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT A DOOR WHERE
<br />THE NEAREST VERTICAL EDGE IS WITHIN A 24 INCH RADIUS OF THE DOOR IN A
<br />CLOSED POSITION AND WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES ABOVE THE
<br />FINISHED FLOOR OR WALKING SURFACE.
<br />(4) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, OTHER THAN THOSE LOCATIONS
<br />DESCRIBED IN ITEMS (2) AND (3) ABOVE THAT MEETS ALL OF THE FOLLOWING
<br />CONDITIONS:
<br />A) EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 SQ. FT.
<br />B) BOTTOM EDGE LESS THAN 18 INCHES ABOVE THE FLOOR.
<br />C) TOP EDGE GREATER THAN 36 INCHES ABOVE THE FLOOR.
<br />D) ONE OR MORE WALKING SURFACES WITHIN 36 INCHES HORIZONTALLY OF THE
<br />PLANE OF THE GLAZING.
<br />REFER TO THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308 FOR ADDITIONAL AREAS
<br />THAT MAY BE CONSIDERED A HAZARDOUS LOCATION FOR THE PURPOSE OF GLAZING.
<br />BUILDING DESIGNS
<br />13821 U.S. HWY 98 BY PASS DADE CITY, FLORIDA 33523
<br />OFFICE 352-523-2077
<br />SHELL OFFICE BUILDING
<br />6638 DAIRY ROAD
<br />ZEPHYRHILLS, FLORIDA
<br />JOB SITE LOCATION MAP
<br />FLORIDA FIRE PREVENTION CODE 7TH EDITION
<br />7 TH EDITION 2020 FLORIDA BUILDING CODE
<br />7 TH EDITION 2020 FLORIDA ACCESSIBILITY CODE
<br />BUILDING HAS WOOD ROOF SYSTEM
<br />LIGHT FRAME CONSTRUCTION SIGN REQUIRED
<br />BUILDING DATA
<br />TOTAL AREA 3242.2 SO. FT.
<br />USE AND OCCUPANCY: BUSINESS GROUP B
<br />CONSTRUCTION TYPE : VB
<br />FIRE PROTECTION : NON SPRINKLED
<br />RYMAN CONSTRUCTION INC
<br />36413 STR RD 54
<br />ZEPHYRHILLS, FL 33541
<br />OFFICE 813-782-0825
<br />6001u_1
<br />REVIEW DATE:_�_�_2, /
<br />CITY OF ZEPHYRHILLS
<br />BUILDING OFFICIAL
<br />PLAN INDEX
<br />SITE PLAN BY OTHERS
<br />SHEET B 1: BUILDING FLOOR PLAN
<br />WINDOW AND DOOR SCHEDULE
<br />FLORIDA PRODUCT APPROVAL
<br />SHEET B 2: BUILDING ELEVATIONS
<br />SHEET B 3: BUILDING FOUNDATION PLAN
<br />DECK FOUNDATION PLAN
<br />LINTEL DETAIL
<br />LINTEL CHART
<br />DOOR BUCK DETAIL
<br />WINDOW BUCK DETAIL
<br />SHEET B 4: WALL SECTION DETAILS A & B
<br />DECK FRAMING PLAN
<br />DECK CUT SECTION DETAIL
<br />SOFFIT DETAIL
<br />WINDOW FLASHING DETAIL
<br />PLYWOOD DETAIL
<br />SHEET B 5: ROOF TRUSS PLAN
<br />TRUSS BRACE DETAIL
<br />VALLEY FRAMING DETAIL
<br />FLASHING DETAIL
<br />SHEET E 1 : ELECTRICAL PLAN
<br />RISER DETAIL
<br />ELECTRICAL LEGEND
<br />ALL WORK SHALL COMPLY WITH PREVAILING
<br />CODES FLORIDA BUILDING CODE,
<br />NATIONAL ELECTRIC CODE,
<br />AND THE CITY OF ZEPHYRHILLS
<br />ORDINANCES
<br />AFKAY EN(SINEERING INC,.
<br />structural engineers
<br />1955 E. Edgewood Drive, Lakeland FI 33803
<br />Phone 863-688-6500 Fax 863-688-655-1
<br />State of Florida Certificate of Authorization " E86341
<br />Richard L Kiddey P.E_ - Florida License M 31296
<br />ARKAY JOB # 19870