SCOPE OF WORK:
<br />TO INSTALL A ROOF MOUNTED SOLAR PHOTOVOLTAIC
<br />SYSTEM AT THE OWNER COMMERCIAL BUILDING LOCATED AT
<br />6911 GALL BLVD., ZEPHYRHILLS, FL 33542, USA.
<br />THE POWER GENERATED BY THE PV SYSTEM WILL BE
<br />INTERCONNECTED WITH THE UTILITY GRID THROUGH THE
<br />EXISTING ELECTRICAL SERVICE EQUIPMENT.
<br />THE PV SYSTEM DOES NOT INCLUDE STORAGE BATTERIES
<br />SYSTEM SUMMARY
<br />96 MISSION SOLAR MSE395SX9R (395W) MODULES
<br />96 ENPHASE IQ8H-3P-72-E-US MICROINVERTERS
<br />PROJECT DESCRIPTION:
<br />96 X 395 MISSION SOLAR MSE395SX9R (395W) MODULES
<br />ROOF MOUNTED SOLAR PHOTOVOLTAIC MODULES
<br />SYSTEM SIZE: 36.48 kW AC STC
<br />SYSTEM SIZE:37.92 kW DC STC
<br />ARRAY AREA: ROOF#1 - 1038.24 SQ FT
<br />ARRAY AREA: ROOF#2 - 1038.24 SQ FT
<br />AUTHORITIES HAVING JURISDICTION
<br />BUILDING : HILLSBOROUGH COUNTY
<br />ZONING : HILLSBOROUGH COUNTY
<br />UTILITY : N/A
<br />GENERAL NOTES:
<br />• THESE CONSTRUCTION DOCUMENTS HAVE BEEN BASED ON FIELD INSPECTIONS AND
<br />OTHER INFORMATION AVAILABLE AT THE TIME. ACTUAL FIELD CONDITIONS MAY REQUIRE
<br />MODIFICATIONS IN CONSTRUCTION DETAILS.
<br />• ARCHITECT HAS NOT BEEN RETAINED TO SUPERVISE ANY CONSTRUCTION OR
<br />INSTALLATION OF ANY EQUIPMENT AT SITE.
<br />• CONTRACTOR SHALL FURNISH ALL LABOR, MATERIAL, EQUIPMENT, TOOLS, OBTAINS ALL
<br />PERMITS, LICENSES AND PAY ALL REQUIRED FEES AND COMPLETE INSTALLATION.
<br />• CONTRACTOR HAS THE FULL RESPONSIBILITY TO CHECK AND VERIFY ALL DIMENSIONS
<br />AND EXISTING CONDITIONS. ANY DISCREPANCIES SHALL BE REPORTED TO THE ENGINEER
<br />BEFORE PROCEEDING WITH THE WORK. ANY WORK STARTED BEFORE CONSULTATION
<br />AND ACCEPTANCE BY THE ENGINEER SHALL BE THE SOLE RESPONSIBILITY OF THE
<br />CONTRACTOR AND SHALL BE SUBJECT TO CORRECTION BY THEM WITHOUT ADDITIONAL
<br />COMPENSATION.
<br />• DAMAGE CAUSED TO THE EXISTING STRUCTURE, PIPES, DUCTS, WINDOWS, WALL,
<br />FLOORS, ETC. SHALL BE REPAIRED TO THE ORIGINAL CONDITION OR REPLACED BY THE
<br />CONTRACTOR AT NO ADDITIONAL COST.
<br />• THE CONTRACTOR SHALL BE HELD RESPONSIBLE FOR THE PROPER INSTALLATION AND
<br />COMPLETION OF THE WORK WITH APPROVED MATERIALS.
<br />• NO CHANGES ARE TO BE MADE WITHOUT THE CONSULTATION AND APPROVAL OF THE
<br />ARCHITECT.
<br />• CONTRACTOR SHALL OBTAIN BUILDING PERMIT. NO WORK TO START UNLESS BUILDING
<br />PERMIT IS PROPERLY DISPLAYED.
<br />• ALL WORKMANSHIP AND MATERIALS SHALL BE OF FIRST QUALITY AND IN COMPLIANCE
<br />WITH THE REQUIREMENTS OF THE FL BUILDING CODE, THE DEPARTMENT OF
<br />ENVIRONMENTAL PROTECTION AND ALL PERTINENT AGENCIES.
<br />• IT IS ESSENTIAL THAT ALL WORK PROCEED WITH THE MAXIMUM COOPERATION OF ALL
<br />PARTIES AND WITH MINIMUM INTERFERENCE TO THE OCCUPANTS WITHIN THE BUILDING.
<br />THE OWNER'S DIRECTIONS IN THIS REGARD SHALL BE FULLY COMPLIED WITH.
<br />• ALL EXPOSED PLUMBING, HVAC, ELECTRICAL DUCTWORK, PIPING AND CONDUITS ARE TO
<br />BE PAINTED BY GENERAL CONTRACTOR.
<br />• THE CONTRACTOR SHALL PERFORM THE WORK IN STRICT CONFORMANCE WITH THE
<br />LOCAL LAWS, REGULATIONS AND THE NATIONAL ELECTRIC CODE.
<br />• THE CONTRACTOR SHALL OBTAIN ALL PERMITS, APPROVALS, AFFIDAVITS,
<br />CERTIFICATIONS, ETC. AND PAY ALL FEES AS REQUIRED BY THE LOCAL AUTHORITIES.
<br />• CONTRACTORS SHALL OBTAIN FIRE CERTIF. UPON COMPLETION OF WORK.
<br />APPLICABLE CODES & STANDARDS:
<br />2023 FLORIDA BUILDING CODE: BUILDING
<br />2023 FLORIDA BUILDING CODE: RESIDENTIAL
<br />2023 FLORIDA BUILDING CODE: EXISTING BUILDING
<br />2020 NATIONAL ELECTRICAL CODE (NEC)
<br />DESIGN CRITERIA
<br />WIND SPEED
<br />138 MPH VULT
<br />EXPOSURE CATEGORY
<br />C
<br />RISK CATEGORY
<br />II
<br />MOUNTING METHOD
<br />ROOF MOUNT
<br />GROUND SNOW LOAD
<br />3 PSF
<br />WIRING AND CONDUIT NOTES:
<br />• ALL CONDUIT SIZES AND TYPES, SHALL BE LISTED FOR ITS
<br />PURPOSE AND APPROVED FOR THE SITE APPLICATIONS
<br />• ALL PV CABLES AND HOMERUN WIRES BE #10AWG *USE-2, PV
<br />WIRE, OR PROPRIETARY SOLAR CABLING SPECIFIED BY M FR,
<br />OR EQUIVALENT; ROUTED TO SOURCE CIRCUIT COMBINER
<br />BOXES AS REQUIRED
<br />• ALL CONDUCTORS AND OCPD SIZES AND TYPES SPECIFIED
<br />ACCORDING TO [NEC 690.8 (A)(1) & (13)(1)], [NEC 240] [NEC
<br />690.7] FOR MULTIPLE CONDUCTORS
<br />• ALL PV DC CONDUCTORS IN CONDUIT EXPOSED TO SUNLIGHT
<br />SHALL BE DERATED ACCORDING TO [NEC TABLE 310.15
<br />(13)(2)(C)] BLACK ONLY**
<br />• EXPOSED ROOF PV DC CONDUCTORS SHALL BE USE-2, 900C
<br />RATED, WET AND UV RESISTANT, AND UL LISTED RATED FOR
<br />60OV, UV RATED SPIRAL WRAP SHALL BE USED TO PROTECT
<br />WIRE FROM SHARP EDGES
<br />• 4-WIRE DELTA CONNECTED SYSTEMS HAVE THE PHASE WITH
<br />THE HIGHER VOLTAGE TO GROUND MARKED ORANGE OR
<br />IDENTIFIED BY OTHER EFFECTIVE MEANS
<br />• ALL SOURCE CIRCUITS SHALL HAVE INDIVIDUAL SOURCE
<br />CIRCUIT PROTECTION
<br />• VOLTAGE DROP LIMITED TO 2%
<br />• AC CONDUCTORS >4AWG COLOR CODED OR MARKED: PHASE
<br />A OR L1- BLACK, PHASE B OR L2- RED, PHASE C OR L3- BLUE,
<br />NEUTRAL- WHITE/GRAY
<br />ELECTRICAL NOTES:
<br />• THE EQUIPMENT AND ALL ASSOCIATED WIRING AND INTERCONNECTION SHALL BE INSTALLED ONLY BY QUALIFIED PEOPLE. A QUALIFIED PERSON IS
<br />ONE WHO HAS SKILLS AND KNOWLEDGE RELATED TO THE CONSTRUCTION AND OPERATION OF THE ELECTRICAL EQUIPMENT AND INSTALLATIONS
<br />AND HAS RECEIVED SAFETY TRAINING TO RECOGNIZE AND AVOID THE HAZARDS INVOLVED. (NEC 690.4(C), NEC 2020)
<br />• LOCAL UTILITY PROVIDER SHALL BE NOTIFIED PRIOR TO USE AND ACTIVATION OF ANY SOLAR PHOTOVOLTAIC INSTALLATION. FOR A LINE SIDE TAP
<br />CONNECTION, UTILITY NEEDS TO BE NOTIFIED WELL IN ADVANCE TO COORDINATE BUILDING ELECTRICAL SHUT OFF.
<br />• NEW CONDUIT ROUTING SHOWN IS ESSENTIALLY SCHEMATIC. SUBCONTRACTOR SHALL LAY OUT RUNS TO SUIT FIELD CONDITIONS AND THE
<br />COORDINATION REQUIREMENTS OF OTHER TRADES.
<br />• ARRAY WIRING SHOULD NOT BE READILY ACCESSIBLE EXCEPT TO QUALIFIED PERSONNEL.
<br />• ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE WATERTIGHT AND APPROVED FOR USE IN WET LOCATIONS. (NEC 690), NEC 2020.
<br />• WIRING METHODS FOR PV SYSTEM CONDUCTORS AREN'T PERMITTED WITHIN 10 IN. OF THE ROOF DECKING OR SHEATHING EXCEPT WHERE LOCATED
<br />DIRECTLY BELOW THE ROOF SURFACE THAT'S COVERED BY PV MODULES AND ASSOCIATED EQUIPMENT WIRING
<br />• BACK -FED BREAKER MUST BE AT THE OPPOSITE END OF BUS BAR FROM THE MAIN BREAKER OR MAIN LUG SUPPLYING CURRENT FROM THE UTILITIES.
<br />• ALL CONDUCTORS AND WIRE TIES EXPOSED TO SUNLIGHT ARE LISTED AS UV RESISTANT.
<br />• CONTRACTOR SHALL FOLLOW ALL ELECTRICAL EQUIPMENT LABELING REQUIREMENTS IN NEC 690
<br />• PV SOURCE, OUTPUT AND INVERTER CIRCUITS SHALL BE IDENTIFIED AT ALL POINTS OF TERMINATION, CONNECTION, AND SPLICES. THE MEANS OF ID
<br />CAN BE SEPARATE COLOR CODING, MARKING TAPE, TAGGING ETC. (NEC 690.4), NEC 2020.
<br />• MEASURE THE LINE -TO -LINE AND LINE -TO -NEUTRAL VOLTAGE OF ALL SERVICE ENTRANCE CONDUCTORS PRIOR TO INSTALLING ANY SOLAR
<br />EQUIPMENT. THE VOLTAGES FOR THE 208VAC RATED.
<br />N
<br />s
<br />0
<br />SHEET INDEX
<br />PV-0
<br />PV-1
<br />PV-2
<br />PV-2A
<br />PV-3
<br />PV-4
<br />PV-5
<br />PV-6
<br />PV-7
<br />to 13
<br />COVER SHEET
<br />PLOT PLAN
<br />ROOF PLAN & MODULES
<br />BRANCH LAYOUT
<br />ATTACHMENT DETAIL
<br />ELECTRICAL LINE DIAGRAM
<br />WIRING CALCULATIONS
<br />WARNING LABELS & PLACARD
<br />EQUIPMENT SPECIFICATIONS
<br />1 I COMMERCIAL BUILDING PHOTO
<br />PV-0
<br />SCALE: NTS
<br />PROJECT SITE
<br />'g8
<br />Richland
<br />6911 GALL BLVD.,
<br />ZEPHYRMILLS, FL 33542
<br />.000waft, (54)
<br />Zephyrhills LIJ)PHillsbor�
<br />Zephyrhills
<br />So�tti
<br />2 I VICINITY MAP
<br />PV-0
<br />Wildli
<br />SCALE: NTS
<br />TAM PA BAY
<br />Lj
<br />of,""4 rx
<br />POWERING THE SUNSHINE STATE
<br />6002 E. ADAMO DR., TAMPA,
<br />FL,33619
<br />PH. NO.: (813) 398-3687
<br />Email : info@tampabaysolar.com
<br />REVISIONS
<br />DESCRIPTION
<br />DATE
<br />REV
<br />ELECTRICAL
<br />01/15/2024
<br />#1
<br />CHANCES
<br />SETBACK
<br />01/17/2024
<br />#2
<br />GIVEN
<br />CHANGED
<br />INVFRTFR TYPE
<br />02/13/2024
<br />#3
<br />CALCULATION
<br />ADDED
<br />02/15/2024
<br />#4
<br />SIGNATURE WITH SEAL
<br />DATE: 02/15/2024
<br />PROJECT NAME &ADDRESS
<br />V
<br />Z
<br />N
<br />0
<br />�
<br />J
<br />_
<br />�CY)
<br />Q
<br />M
<br />Q
<br />m
<br />CO�
<br />J
<br />J
<br />J
<br />J
<br />�_
<br />_j
<br />w
<br />V
<br />Q
<br />w
<br />��
<br />�
<br />w
<br />N
<br />0
<br />SHEET NAME
<br />COVER SHEET
<br />SHEET SIZE
<br />ANSI B
<br />11 " X 17"
<br />SHEET NUMBER
<br />PV-0
<br />
|