<br />FIRE ALARM SPECIFICATIONS & GENERAL NOTES
<br />FIRE ALARM SYSTEM TESTING, INSPECTION, INSTRUCTION
<br />r_
<br />E
<br />I. GENERAL SCOPE:
<br />A. THIS PROJECT WILL REQUIRE THE INSTALLATION OF A SILENT KNIGHT 6808 ADDRESSABLE FIRE ALARM SYSTEM FOR A 3 - STORY SELF STORAGE FACILITY. AS INDICATED ON THESE PLANS A
<br />NON-PROPRIETARY SYSTEM SHALL BE INSTALLED. THE FIRE ALARM SYSTEM SHALL MONITOR THE FIRE SPRINKLER SYSTEMS, BDA SYSTEM, AND INTERFACE WITH THE ELEVATORS FOR ELEVATOR
<br />RECALL AND SHUT DOWN AS REQUIRED BY NFPA 72,
<br />11. REQUIREMENTS
<br />A. THE INSTALLATION SHALL CONFORM TO THE INTENT OF NFPA 72 (2016 ED.), FLORIDA FIRE PREVENTION CODE (2020 ED.), THESE PLANS, AND APPLICABLE REFERENCED DOCUMENTS.
<br />B. SECONDARY POWER SHALL CONSIST OF RECHARGEABLE BATTERIES HAVING A CAPACITY TO POWER THE ALARM SYSTEM FOR A PERIOD OF 24 HOURS IN A STANDBY MODE AND OPERATE ALL
<br />NOTIFICATION APPLIANCES FOR 5 MINUTES AT THE END OF THE 24 HOUR PERIOD.
<br />C. ALL CIRCUITS SHALL BE "POWER LIMITED". THE CIRCUIT TYPES SHALL BE INSTALLED AS INDICATED BELOW:
<br />SIGNALING LINE LOOP: CLASS "B"
<br />INITIATION DEVICE CIRCUITS (IDC'S): CLASS "B"
<br />NOTIFICATION ALARM CIRCUITS (NAC'S): CLASS "B"
<br />D. WALL -MOUNTED NOTIFICATION HORN/STROBES ARE TO BE MOUNTED SO THAT THE ENTIRE LENS OF THE DEVICE IS NO LESS THAT 80" AFF AND NO GREATER THAN 96" AFF. CEILING -MOUNTED
<br />NOTIFICATION DEVICES ARE TO BE MOUNTED AT A MAXIMUM HEIGHT OF 30 FT. (AS INDICATED ON THE PLANS)
<br />E. ALL NEW PULL STATIONS SHALL BE INSTALLED AT 48 INCHES ABOVE THE FINISH FLOOR.
<br />F. ALL WIRING CONNECTIONS ARE TO BE IN SINGLE, DOUBLE, TRIPLE OR 4 INCH ELECTRICAL BOXES, AS NEEDED. WIRING CONNECTIONS OUTSIDE OF ELECTRICAL BOXES WILL NOT BE ALLOWED.
<br />G. ALL WIRING ON THE INITIATION AND NOTIFICATION CIRCUITS ARE SUPERVISED POWER LIMITED.
<br />H. SURGE SUPPRESSION DEVICES SHALL BE INSTALLED ON ALL CIRCUITS THAT ENTER OR EXIT THE BUILDING. TYPICAL DEVICES ARE LISTED BELOW:
<br />PANEL POWER: DITEK MODEL DTK-120HW, EDCO (OR EQUAL)
<br />INITIATING CKTS: DITEK MODEL DTK-2LVLP-F, EDCO (OR EQUAL)
<br />PHONE LINES: DITEK MODEL DTK-MRJ3ISXCPWP, EDCO (OR EQUAL)
<br />I. STROBE CIRCUITS SHALL BE SYNCHRONIZED EITHER THROUGH THE MAIN FACP OR SEPARATE SYNCHRONIZATION MODULES (AS NECESSARY).
<br />J. FIRE ALARM PATHWAY SURVIVABILITY REQUIRED FOR THIS PROJECT (NFPA 72, CHAPTER 12):
<br />PATHWAY LEVEL 1 REQUIRED FOR:
<br />PANEL POWER CONDUCTORS (120 VAC)
<br />NETWORK\COMMUNICATIONS BETWEEN PANELS
<br />PATHWAY LEVEL 0 REQUIRED FOR:
<br />SIGNALING LINE LOOP CIRCUITS (SLC)
<br />INITIATION DEVICE CIRCUITS (IDC)
<br />NOTIFICATION APPLIANCE CIRCUITS (NAC)
<br />DEVICE POWER TO NOTIFICATION OR INITIATION DEVICES
<br />111. CONDUIT AND WIRE
<br />A. CONDUIT:
<br />1. CONDUIT INSTALLATION SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC), LOCAL AND STATE REQUIREMENTS.
<br />2. CONDUIT FILL WILL NOT EXCEED 40 PERCENT OF INTERIOR CROSS SECTIONAL AREA WHERE THREE OR MORE CABLES ARE CONTAINED WITHIN A SINGLE CONDUIT.
<br />3. CABLE MUST BE SEPARATED FROM ANY OPEN CONDUCTORS OF POWER, OR CLASS 1 CIRCUITS, AND SHALL NOT BE PLACED IN ANY CONDUIT, JUNCTION BOX OR RACEWAY CONTAINING THESE
<br />CONDUCTORS.
<br />B. WIRE:
<br />1. ALL FREE -WIRED FIRE ALARM WIRING SHALL BE FPL TYPE CABLE. WIRING INSTALLED IN CONDUIT SHALL BE A MINIMUM OF THHN. UNDERGROUND WIRE SHALL BE INSTALLED IN
<br />CONDUIT AND SHALL BE A MINIMUM OF THWN.
<br />2. WIRING WILL BE IN ACCORDANCE WITH LOCAL, STATE AND NATIONAL CODES (E.G., NEC ARTICLE 760). THE NUMBER AND SIZE OF CONDUCTORS SHALL BE AS INDICATED ON THESE PLANS,
<br />BUT SHALL NOT BE LESS THAN #18 AWG FOR INITIATING DEVICE CIRCUITS (INCLUDING SIGNALING LINE CIRCUITS) AND #16 AWG FOR NOTIFICATION DEVICE CIRCUITS.
<br />3. ALL FIELD WIRING OF INITIATION AND NOTIFICATION CIRCUITS ARE TO BE COMPLETELY SUPERVISED BY END OF LINE DEVICES, PER THE MANUFACTURER'S LITERATURE.
<br />4. HORIZONTAL WIRE RUNS ABOVE CEILINGS: HORIZONTAL WIRE RUNS IN AREAS CONTAINING DROP CEILINGS MAY BE 'FREE -WIRED' IF SUPPORTED BY THE BUILDING STRUCTURE. LAYING WIRE ON
<br />THE CEILING OR INADEQUATE SUPPORT OF WIRING FROM THE STRUCTURE WILL NOT BE ALLOWED.
<br />5. VERTICAL AND HORIZONTAL WIRE RUNS IN OPEN STRUCTURE AREAS: ALL WIRING IN "OPEN STRUCTURE AREAS" ON THIS PROJECT SHALL BE INSTALLED IN CONDUIT.
<br />6. VERTICAL WIRE RUNS: VERTICAL WIRE RUNS TO DEVICES, PANELS, ANNUNCIATORS, ETC. SHALL BE INSTALLED IN CONDUIT PER THE NATIONAL ELECTRICAL CODE.
<br />C. TERMINAL BOXES, JUNCTION BOXES AND CABINETS: ALL BOXES AND CABINETS SHALL BE UL LISTED FOR THEIR USE AND PURPOSE.
<br />D. THE FIRE ALARM CONTROL PANEL IS TO BE CONNECTED TO A SEPARATE DEDICATED BRANCH CIRCUIT, MAXIMUM 20 AMPERES. THIS CIRCUIT SHALL BE LABELED AT THE MAIN POWER
<br />DISTRIBUTION PANEL AS FIRE ALARM. FIRE ALARM CONTROL PANEL PRIMARY POWER WIRING SHALL BE 12 AWG. THE CONTROL PANEL ',CABINET SHALL BE GROUNDED SECURELY TO
<br />EITHER A COLD WATER PIPE OR GROUNDING ROD. A 120 VOLT SURGE SUPPRESSER SHALL BE INSTALLED ON THE AC POWER AND GROUNDED PRIOR TO ENTERING THE FIRE ALARM
<br />CONTROL PANEL. THE BREAKER FOR THE ALARM CIRCUIT SHALL BE RED IN COLOR, OR PAINTED RED, SHALL BE ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL, AND SHALL BE
<br />IDENTIFIED WITH A PERMANENT LABEL AS "FIRE ALARM CIRCUIT". THE LOCATION OF THE DISCONNECTING MEANS SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL
<br />UNIT VIA A LABEL INSIDE THE FACP COVER.
<br />IV. EXECUTION
<br />A. INSTALLATION:
<br />1. INSTALLATION SHALL BE IN ACCORDANCE WITH THE NEC, NFPA 72, LOCAL AND STATE CODES, AS SHOWN ON THE DRAWINGS, AND AS RECOMMENDED BY THE MAJOR EQUIPMENT
<br />MANUFACTURER.
<br />2. DURING CONSTRUCTION MEASURES SHALL BE TAKEN TO IPROTECT SMOKE DETECTORS FROM CONTAMINATION AND PHYSICAL DAMAGE UNTIL CONSTRUCTION ACTIVITIES ARE COMPLETE.
<br />V. PROGRAMMING
<br />1. A BASELINE PROGRAMMING MATRIX HAS BEEN INCLUDED ON THESE PLANS.
<br />2. ALL SMOKE DETECTORS SHALL BE PROGRAMMED FOR ALARM VERIFICATION.
<br />VI. TESTING & FINAL INSPECTION
<br />1. SEE "FIRE ALARM SYSTEM TESTING, INSPECTION, INSTRUCTION" NOTES ON THIS SHEET FOR MINIMUM REQUIREMENTS.
<br />VII. SYSTEM MONITORING
<br />1. ALARM, SUPERVISORY, AND TROUBLE SHALL BE MONITORED VIA A REMOTE SUPERVISING STATION, AS INDICATED ON THESE PLANS.
<br />VIII. GENERAL
<br />1. THE VOLTAGE DROP CALCULATIONS SHOWN ON THE PLANS ARE BASED ON THE CIRCUIT ROUTING SHOWN. MAJOR CHANGES TO THE CIRCUIT ROUTING SHOWN MAY NEED TO BE JUSTIFIED BY
<br />THE FIRE ALARM CONTRACTOR WITH ADDITIONAL CALCULATIONS.
<br />2. THE ALARM CONTRACTOR WILL BE REQUIRED TO SUBMIT A "RECORD OF COMPLETION", PER NFPA 72, TO THE OWNER PRIOR TO FINAL PAYMENT.
<br />3. THE FIRE ALARM CONTRACTOR IS REQUIRED TO MAINTAIN A COMPLETE AND ACCURATE AS -BUILT DRAWING SET. UPON FINAL COMPLETION OF THE PROJECT, THE FIRE ALARM CONTRACTOR SHALL
<br />SUPPLY THE OWNER WITH AN AS -BUILT SET. AS-BUILTS SHALL INDICATE ALL CHANGES TO THE ORIGINAL LAYOUT INCLUDING, BUT NOT
<br />NECESSARY LIMITED TO, AS -BUILT DEVICE LOCATIONS, PANEL LOCATIONS, CIRCUIT ROUTING, CONDUIT ROUTING, JUNCTION BOX LOCATIONS, PANEL CIRCUIT BREAKER LOCATIONS, ETC.
<br />4. ALL CONDUIT AND WIRING PENETRATIONS THROUGH FIRE RATED BARRIERS (INCLUDING WALLS AND FLOORS), AND SMOKE BARRIERS THAT EXTEND FROM FLOOR TO CEILING, SHALL BE SEALED
<br />WITH A UL LISTED FIRESTOPPING PENETRATION SYSTEM. THE MINIMUM PENETRATION RATING FOR FIRE RATED BARRIERS SHALL MATCH THE RATING OF THE WALL \ FLOOR \ BARRIER. SMOKE
<br />BARRIERS SIMPLY NEED TO BE SEALED TO PREVENT THE PASSAGE OF SMOKE THROUGH THE ASSEMBLY.
<br />5. PRIOR TO FINAL PROJECT COMPLETION, ALL DEVICES SHALL BE LABELED ON THEIR EXTERIOR HOUSING SO THAT THE DEVICE NUMBER CAN BE DETERMINED BY VISUAL INSPECTION. ALL FIRE
<br />ALARM DEVICES, INCLUDING BUT NOT LIMITED TO DETECTORS, MODULES, HORNS, SPEAKERS, AND STROBES, $HALL HAVE A LABEL AFFIXED TO THEIR FRONT SURFACE. THESE LABELS SHALL
<br />CONFORM TO THE FOLLOWING:
<br />I. THE LABELS SHALL HAVE LETTERS AT LEAST 1/4" HIGH.
<br />II. THE LABELS SHALL MATCH THE DEVICE NUMBER SHOWN ON THE AS -BUILT DRAWINGS.
<br />111. THE LABELS SHALL BE IDENTICAL TO THE DEVICE NUMBER PROGRAMMED INTO AND DISPLAYED ON THE FACP AND ALL REMOTE ANNUNCIATORS.
<br />AT THE FINAL INSPECTION A FACTORY TRAINED REPRESENTATIVE OF THE INSTALLER SHALL DEMONSTRATE THAT THE SYSTEMS FUNCTION PROPERLY IN EVERY RESPECT. ALL TESTING SHALL
<br />BE COMPLETED IN ACCORDANCE WITH NFPA 72. THE LOCAL FIRE AUTHORITY HAVING JURISDICTION, OR THEIR ASSIGNED REPRESENTATIVE, SHALL WITNESS THE SYSTEM TESTING.
<br />FIRE ALARM SYSTEM TESTING
<br />A. PROVIDE THE SERVICE OF A COMPETENT, FACTORY -TRAINED ENGINEER OR TECHNICIAN AUTHORIZED BY THE MANUFACTURER OF THE FIRE ALARM EQUIPMENT TO TECHNICALLY
<br />SUPERVISE AND PARTICIPATE DURING ALL OF THE ADJUSTMENTS AND TESTS FOR THE SYSTEM. REPRESENTATIVE MUST BE STATE CERTIFIED FIRE ALARM CONTRACTOR/INSTALLER.
<br />1. BEFORE ENERGIZING THE CABLES AND WIRES, CHECK FOR CORRECT CONNECTIONS AND TEST FOR SHORT CIRCUITS, GROUND FAULTS, CONTINUITY, AND INSULATION.
<br />2. CLOSE EACH SPRINKLER SYSTEM FLOW VALVE AND VERIFY PROPER SUPERVISORY ALARM AT THE FACP.
<br />3. VERIFY ACTIVATION OF ALL FLOW SWITCHES.
<br />4. OPEN INITIATING DEVICE CIRCUITS AND VERIFY THAT THE TROUBLE SIGNAL ACTUATES.
<br />5. OPEN AND SHORT SIGNALING LINE CIRCUITS AND VERIFY THAT THE TROUBLE SIGNAL ACTUATES.
<br />6. OPEN AND SHORT INDICATING APPLIANCE CIRCUITS AND VERIFY THAT TROUBLE SIGNAL ACTUATES.
<br />7. GROUND ALL CIRCUITS AND VERIFY RESPONSE OF TROUBLE SIGNALS.
<br />8. CHECK PRESENCE AND AUDIBILITY OF TONE AT ALL ALARM NOTIFICATION DEVICES.
<br />9. CHECK EACH STROBE DEVICE TO VERIFY THAT THE SELECTABLE STROBE OUTPUT HAS BE SET AT THE PROPER CANDELA RATING, AS SHOWN ON THE PLANS.
<br />10. CHECK INSTALLATION, SUPERVISION, AND OPERATION OF ALL INTELLIGENT SMOKE DETECTORS USING THE WALK TEST.
<br />11. POWER LOSS TESTING SHALL BE PERFORMED IN ACCORDANCE WITH NFPA 72. TEST LOSS OF PRIMARY POWER AND SYSTEM RESPONSE, AS REQUIRED BY NFPA 72 (2016),
<br />CHAPTER 14.
<br />12. EACH OF THE ALARM CONDITIONS THAT THE SYSTEM IS REQUIRED TO DETECT SHOULD BE INTRODUCED ON THE SYSTEM. VERIFY THE PROPER RECEIPT AND THE PROPER
<br />PROCESSING OF THE SIGNAL AT THE FACP AND THE CORRECT ACTIVATION OF THE CONTROL POINTS.
<br />13. WHEN THE SYSTEM IS EQUIPPED WITH OPTIONAL FEATURES, THE MANUFACTURER'S MANUAL SHOULD BE CONSULTED TO DETERMINE THE PROPER TESTING PROCEDURES. THIS IS
<br />INTENDED TO ADDRESS SUCH ITEMS AS VERIFYING CONTROLS PERFORMED BY INDIVIDUALLY ADDRESSED OR GROUPED DEVICES, SENSITIVITY MONITORING, VERIFICATION
<br />FUNCTIONALITY AND SIMILAR.
<br />14. FINAL TESTING SHALL BE IN THE PRESENCE OF THE LOCAL FIRE MARSHALL, OR FIRE INSPECTOR, AND WARRANTY SHALL BEGIN ON DATE OF ACCEPTANCE BY LOCAL FIRE
<br />MARSHALL.
<br />FINAL INSPECTION
<br />A. AT THE FINAL INSPECTION A FACTORY TRAINED REPRESENTATIVE OF THE MANUFACTURER OF THE [MAJOR EQUIPMENT SHALL DEMONSTRATE THAT THE SYSTEMS FUNCTION PROPERLY
<br />IN EVERY RESPECT. REPRESENTATIVE SHALL BE A STATE CERTIFIED FIRE ALARM CONTRACTOR/INSTALLER.
<br />INSTRUCTION
<br />A.PROVIDE INSTRUCTION, AS REQUIRED, FOR OPERATING THE SYSTEM. "HANDS-ON" DEMONSTRATION OF THE OPERATION OF ALL SYSTEM COMPONENTS SHALL BE PROVIDED.
<br />B. THE CONTRACTOR, AND/OR THE SYSTEMS MANUFACTURER'S REPRESENTATIVE, SHALL PROVIDE A TYPE WRITTEN "SEQUENCE OF OPERATION" TO THE OWNER. PROVIDE A COPY OF
<br />THE "SEQUENCE OF OPERATION" AT EACH FACP LOCATION.
<br />C. THE CONTRACTOR SHALL PROVIDE A DEVICE LAYOUT SKETCH AT AT EACH FIRE ALARM CONTROL PANEL, TO INDICATE FLOOR PLAN, FIRE ALARM DEVICE LOCATION, ADDRESS AND
<br />DEVICE LEGEND FOR EASE OF ALARM LOCATION. THE FIRE ALARM FLOOR PLAN SHALL BE MOUNTED IN A FRAME.
<br />FIRE ALARM DEVICE LEGEND
<br />SYMBOL
<br />QTY
<br />DEVICE DESCRIPTION
<br />MAKE / MODES
<br />DEVICE SPECIFIC NOTES
<br />CIO
<br />w
<br />Z
<br />m
<br />U
<br />FACP
<br />1
<br />FIRE ALARM CONTROL PANEL
<br />SILENT KNIGHT 6808
<br />Z
<br />®
<br />1
<br />CELL / ID COMMUNICATOR
<br />NAPCO STARLINK
<br />DIALER PROVIDED BY OTHERS
<br />a
<br />z
<br />0
<br />Q
<br />1
<br />WEATHERPROOF
<br />P2RK
<br />DEVICE TO BE 'RED'
<br />I
<br />WP
<br />HORN / STROBE (WALL MOUNTED)
<br />O
<br />z
<br />0
<br />Of
<br />2
<br />MANUAL PULL STATION
<br />SK-PULL-SA
<br />INSTALL AT 48" AFF
<br />z
<br />0
<br />v_
<br />11
<br />PHOTOELECTRIC SMOKE DETECTOR
<br />SK-PHOTO-W
<br />CEILING MOUNTED DEVICES TO BE 'WHITE'
<br />Z
<br />`''P
<br />Q�F
<br />2
<br />135' FIXED HEAT DETECTOR
<br />SK-HEAT-W
<br />CEILING MOUNTED DEVICES TO BE 'WHITE'
<br />Z
<br />®WP
<br />2
<br />WEATHERPROOF 135' FIXED HEAT
<br />302 SERIES
<br />INSTALLED IN ELEVATOR PIT
<br />F
<br />DETECTOR
<br />AIM
<br />16
<br />ADDRESSABLE MONITOR MODULE
<br />SK-MONITOR, SK-MONITOR2
<br />MOUNT WITH -IN 3 FEET OF INTERFACE POINT
<br />O®
<br />8
<br />ADDRESSABLE RELAY MODULE
<br />SK-RELAY
<br />MOUNT WITH -IN 3 FEET OF AHU INTERFACE POINT
<br />C3
<br />p
<br />FLOW SWITCH
<br />TAMPER SWITCH
<br />-JVVL-
<br />END -OF -LINE RESISTOR (EOL)
<br />SUPPLIED BY PRODUCT VENDOR INSTALLED AT END OF CIRCUIT LINE
<br />8-0
<br />SURGE SUPPRESSOR
<br />❑K
<br />KNOX BOX
<br />❑J
<br />JUNCTION BOX
<br />FIRE ALARM ABBREVIATIONS LEGEND
<br />AH
<br />= AIR HANDLER
<br />MAX = MAXIMUM
<br />C
<br />= CEILING MOUNTED
<br />MIN = MINIMUM
<br />COR
<br />= CONTRACTING OFFICER REPRESENTATIVE
<br />MNS = MASS NOTIFICATION SYSTEM
<br />EXT
<br />= EXISTING
<br />N/A = NOT APPLICABLE
<br />WP
<br />= WEATHERPROOF
<br />NAC = NOTIFICATION APPUANCE CIRCUIT
<br />XP
<br />= EXPLOSION PROOF
<br />NDU = NETWORK DISPLAY UNIT
<br />AFF
<br />= ABOVE FINISHED FLOOR
<br />NEC = NATIONAL ELECTRIC CODE
<br />AHJ
<br />= AUTHORITY HAVING JURISDICTION
<br />NFPA = NATIONAL FIRE PROTECTION ASSOCIATION
<br />ALM
<br />= ALARM
<br />NIC = NOT IN CONTRACT
<br />ANN
<br />= ANNUNCIATOR
<br />NTS = NOT TO SCALE
<br />BMS
<br />= BUILDING MANAGEMENT SYSTEM
<br />PAP = PRE -ACTION PANEL
<br />CD
<br />= (eg. 15CD) CANDELA
<br />PED = PHOTOELECTRIC SMOKE DETECTOR
<br />CSFM
<br />= CALIFORNIA STATE FIRE MARSHAL
<br />SLC = SIGNALING LINE CIRCUIT
<br />DET
<br />= DETECTOR
<br />SMK = SMOKE
<br />EOL
<br />= END OF LINE
<br />SUPV = SUPERVISORY
<br />EPO
<br />= EMERGENCY POWER OFF
<br />TRBL = TROUBLE
<br />FACP
<br />= FIRE ALARM CONTROL PANEL
<br />IS = TAMPER SWITCH
<br />FATC
<br />= FIRE ALARM TERMINAL CABINET
<br />TYP = TYPICAL
<br />FBO
<br />= FURNISHED BY OTHERS
<br />UFC = UNIFIED FACILITIES CRITERIA
<br />FCC
<br />= FIRE COMMAND CENTER
<br />LINO = UNLESS NOTED OTHERWISE
<br />FAA
<br />= FIRE ALARM ANNUNCIATOR
<br />VCC = VOICE COMMAND CENTER
<br />FSD
<br />= FIRE SMOKE DAMPER
<br />WF = WATER FLOW
<br />HT
<br />= HEIGHT
<br />W = WATT
<br />HVAC
<br />= HEATING, VENTILATION, & AIR CONDITIONING
<br />W/ = WITH
<br />IDC
<br />= INITIATION DEVICE CIRCUIT
<br />W/O = WITHOUT
<br />IMS
<br />= INFORMATION MANAGEMENT SYSTEM
<br />z
<br />O
<br />In
<br />Li
<br />O_
<br />w
<br />Q
<br />0
<br />O
<br />z
<br />�ocs a���.,,
<br />••''
<br />�''•��2'
<br />=Z
<br />*
<br />W
<br />:U
<br />Q O'Z=
<br />F
<br />tn
<br />v C:4-
<br />N O
<br />O
<br />m
<br />0 O O
<br />.a1
<br />Li
<br />>, V
<br />N
<br />O
<br />ro 4- T
<br />!V �
<br />`-
<br />Q
<br />W
<br />0
<br />O
<br />z
<br />a �F zrzwa�}�.,
<br />N o�z��wWNau'
<br />2w�¢ Ou, o a�OU
<br />s
<br />zowz
<br />w} Z z O
<br />c-7 °'wwazwo¢ =n�F
<br />zz��ozw�>u
<br />z 3 z m
<br />w -'n�_z �mw w=
<br />_8 o
<br />�I
<br />of
<br />rt
<br />a
<br />U
<br />Z
<br />Q
<br />a
<br />m
<br />L
<br />V'
<br />Y ^ n
<br />Z
<br />LL
<br />�I
<br />Fy
<br />_J
<br />LLI
<br />p9
<br />ui
<br />Z
<br />Z a
<br />R
<br />mh b^
<br />�E�
<br />m
<br />a
<br />NSb�
<br />nyOti
<br />U
<br />w
<br />a
<br />U
<br />Z
<br />Z
<br />U
<br />w
<br />n
<br />lb
<br />g
<br />t
<br /><
<br />m`°Q.°'
<br />%
<br />T
<br />y�i I"
<br />2m
<br />r'l
<br />WN�N^
<br />O
<br />q,
<br />T
<br />m
<br />U
<br />C
<br />w
<br />w
<br />F
<br />3Cim�
<br />ii
<br />U
<br />a
<br />[
<br />w
<br />3
<br />a
<br />w
<br />0
<br />V
<br />z
<br />� n �
<br />morn
<br />3!*
<br />n*
<br />om
<br />T 7
<br />O�
<br />myrn
<br />S
<br />n
<br />�>
<br />MrNl�
<br />>7
<br />m
<br />-�4 O
<br />fV
<br />r it
<br />Ip Ip -
<br />2
<br />ni
<br />Q
<br />,� rlll
<br />Q
<br />M
<br />W m U_
<br />M
<br />Q,>rn
<br />03 4t m 11,
<br />1- m A
<br />0
<br />Jza 0
<br />a.. m
<br />w
<br />Q �
<br />OLn
<br />O
<br />T M J
<br />fV O
<br />rZ
<br />a
<br />0
<br />U
<br />Z
<br />0
<br />Q
<br />0
<br />L0
<br />w
<br />O
<br />EL
<br />EL
<br />Ld
<br />FIRE ALARM DRAWING LEGEND
<br />SHEET #
<br />DESCRIPTION
<br />FAO
<br />FIRE ALARM GENERAL NOTES AND SPECIFICATIONS
<br />FAt
<br />FIRE ALARM PLAN FIRST FLOOR
<br />FA2
<br />FIRE ALARM PLAN SECOND FLOOR
<br />FA3
<br />FIRE ALARM PLAN THIRD FLOOR
<br />FA4
<br />FIRE ALARM DETAILS
<br />FA5
<br />FIRE ALARM RISER DIAGRAM AND •CALCULATIONS
<br />Lw
<br />(10
<br />Ld
<br />Z
<br />LLI
<br />I -
<br />O
<br />zz
<br />a
<br />O Q
<br />�
<br />>M
<br />�0
<br />LLI
<br />LL,Q
<br />F-
<br />j -�
<br />o u-
<br />W U
<br />m
<br />Z
<br />o
<br />_j_
<br />a=
<br />Ld -
<br />Caw
<br />o
<br />(D
<br />N =
<br />c�°
<br />LLI
<br />g
<br />fb �
<br />Q Q
<br />T
<br />J
<br />LLI
<br />LL_
<br />u
<br />w
<br />U
<br />C W
<br />a p
<br />DESIGNED BY
<br />AGO
<br />DRAWN BY
<br />AGO
<br />CHECKED BY
<br />RWL
<br />PROJECT NO./CAD CODE
<br />2023-2601
<br />DATE
<br />06/27/2023 i
<br />DRAWING NO.
<br />FAO
<br />ME
<br />w