Laserfiche WebLink
FS <br />PROJECT SPECIFIC NOTES: <br />1. RELAY MODULES HAVE BEEN PROVIDED IN THE ELEVATOR EQUIPMENT ROOM FOR ELEVATOR CONTROL FUNCTIONS. SEE THE PLAN VIEW LAYOUT FOR DEVICE COUNT. <br />2. ALL SMOKE DETECTORS ARE TO BE PROGRAMMED WITH ALARM VERIFICATION. <br />3. THIS CHART IS TO BE USED AS A BASIC PROGRAMMING GUIDE ONLY. ALL OTHER PANEL PROGRAMMING FEATURES SHALL COMPLY WITH NFPA 72 AND THE MANUFACTURERS INSTRUCTIONS. <br />1 & 2 HOUR GYPSUM WALL <br />PENETRATION DETAIL <br />(NOT TO SCALE) <br />HILTI System No. W-L-1054 F Ratings - 1 and 2 Hr (See Items 1 and 3) T Rating - <br />0 Hr L Rating At Ambient - Less Than 1 CFM/Sq Ft L Rating At 400 F - 4 CFM/Sq Ft <br />1. Wall Assembly -- The 1 or 2 hr fire —rated gypsum wallboard/stud wall assembly shall be <br />constructed of the materials and in the manner specified in the individual U300 or U400 <br />Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the <br />following construction features: A <br />A. Studs -- Wall framing may consist of either wood studs or steel channel studs. Wood <br />studs to consist of nom 2 by 4 in. lumber spaced 16 in. OC. Steel studs to be min <br />2-1/2 in. wide and spaced max 24 in. OC. When steel studs are used and the diam of <br />opening exceeds the width of stud cavity, the opening shall be framed on all sides using <br />lengths of steel stud installed between the vertical studs and screw —attached to the steel 3 <br />studs at each end. The framed opening in the wall shall be 4 to 6 in, wider and 4 to 6 <br />in. higher than the diam of the penetrating item such that, when the penetrating item is <br />installed in the opening, a 2 to 3 in. clearance is present between the penetrating item <br />and the framing on all four sides. <br />B. Gypsum Board* -- 5/8 in. thick, 4 It wide with square or tapered edges. The gypsum <br />board type, thickness, number of layers, fastener type and sheet orientation sholl be as <br />specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. 2 <br />Max diam of opening is 32-1/4 in. for steel stud walls. Max diam of opening is 14-1/2 <br />in, for wood stud walls. <br />The F Rating of the firestop system is equal to the fire rating of the wall assembly. <br />A <br />2. Through —Penetrants -- One metallic pipe, conduit or tubing to be installed either <br />concentrically or eccentrically within the firestop system- The annular space shall be min 0 <br />in. to max 2-1/4 in. Pipe may be installed with continuous point contact. Pipe, conduit <br />or tubing may be installed at an angle not greater then 45 degrees from perpendicular. <br />Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The <br />following types and sizes of metallic pipes, conduits or tubing may be used: <br />A. Steel Pipe -- Nom 30 in diam (or smaller) Schedule 10 (or heavier) steel pipe. <br />B. Iron Pipe -- Nom 30 in. diam (or smaller) cast or ductile iron pipe. <br />C. Conduit -- Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam <br />steel conduit. <br />D. Copper Tubing -- Nam 6 in. diam (or smaller) Type L (or heavier) copper tubing. <br />E. Copper Pipe -- Nam 6 in. diam (or smaller) regular (or heavier) copper pipe. <br />3. Fill, Void or Cavity Material* -- Sealant -- Min 5/8 in, thickness of fill material applied <br />within the annulus, flush with troth surfaces of wall. At the point or continuous contact <br />locations between pipe and wall, a min 1/2 in. diam bead of fill material shall be applied <br />at the pipe wall interface on both surfaces of wall. <br />HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- FS—One Sealant <br />*Bearing the UL Classification Mark <br />UNDERGROUND FIRE ALARM WIRING ENTRANCE <br />DETAIL (BACKFLOW PREVENTER) <br />(NOT TO SCALE) <br />SURGE SUPPRESSOR W/GROUND IN <br />4JUNCTION BOX <br />--90 DEGREE PVC ELECTRICAL WIRE PULL BOX BACKFLOW DEVICE <br />SEE CIVIL DWGS <br />FOR DESIGN INFO. <br />1­_o ATERPROOF PENETRATION WEATHERPROOF PVC ELECTRICAL BOX <br />of WITH UV RESISTANT SILICONE <br />ti <br />1­_ TAMPER SWITCH X 2 <br />U ----GRAY UV RESISTANT NON-METALLIC PVC CONDUIT <br />Z J --PVC STRAP ANCHORED WITH TAPCON SCREWS INTO MASONRY WALL <br />U <br />o s DROP CONDUIT AROUND FOOTER IF 24 INCH <br />_ COVER CAN NOT BE MAINTAINED <br />BOX MUST BE WITHIN <br />q AVING BACKFLOW HOUSE <br />CU0 ¢ KEEPING SLAB <br />f <br />xw <br />ce <br />FF w <br />X <br />w Z <br />O <br />I <br />BLDG FOOT <br />ER <br />DTK- <br />GENERAL NOTES <br />1, <br />THE FIRE ALARM CABLE MUST BE <br />INSTALLED PER NFPA 70 TABLE <br />300.5. <br />2, <br />ALL WIRING USED UNDERGROUND <br />SHALL BE WEST PENN AQUASEAL <br />TYPE MOISTURE RESISTANT FPL, <br />UL RATED DIRECT BURY OR THWN <br />TYPE INSULATED WIRE, <br />3. <br />DIRECT BURIAL TYPE CABLE <br />SHALL NOT BE INSTALLED <br />WITHOUT RIGID NON METALLIC <br />CONDUIT. VALUE ENGINEERING <br />WILL NOT BE PERMITTED TO <br />OMIT THIS FEATURE, <br />4, <br />ALL CONDUIT IS TO RIDGID <br />NON-METALLIC CONDUIT (RNC) <br />CONSTRUCTED OF PVC WITH <br />SOLVENT FITTING CONNECTIONS. <br />ONLY SOLVENT GLUE LISTED FOR <br />USE WITH THE RMC SHALL BE <br />USED.ALL PIPE SHALL BE <br />CLEANED PRIOR TO MAKING THE <br />SOLVENT JOINTS. <br />5, <br />INSTALL PULL STRING IN <br />CONDUIT TO FACILITATE WIRE <br />REPLACEMENT. <br />FIRE ALARM SURGE PROTECTION DIAGRAM <br />(NOT TO SCALE) <br />1 1 KEYNOTES: <br />1 1O HIGH SURGE RISK CONNECTION, TYPICAL <br />PROTECTED COPPER CONNECTION, TYPICAL MINIMUM 3' TO <br />() o <br />a� o <br />12ovAe o' ,� a <br />POWER ) °' <br />SUPPLY o � <br />0 <br />0 <br />DTK-120SRD a o e <br />(SERIES CONNECTION) <br />E � <br />o c 120V AC <br />JL 1t TO FRCP <br />12OV AC-1 SINGLE <br />POLE 25 AMP MAX TO FRCP AUX <br />BRFNCER, TO BE CONTACTS OR <br />FIELD VERIFIED ADDRESSABLE <br />MONITOR MODULE <br />EXAMPLE MWWTORING CIRCUff <br />120VAC <br />NEUTRAL (-) <br />i. <br />LOAD: 48VDC, 0.6AMP <br />0 <br />2 <br />FIRE <br />ALARM <br />CONTROL <br />PANEL <br />O PROTECTED EQUIPMENT. <br />NETWORK SURGE PROTECTION NOTES: <br />1. TO KEEP SURGES FROM ENTERING THE BUILDING AND NETWORK, IT <br />IS RECOMMENDED TO PROVIDE A LAYER OF SURGE PROTECTION. THIS <br />(HARDWIRED) <br />HEAD END PROTECTION POINT IS THE ONLY WAY TO REDUCE THE <br />- DTK-2MHTP <br />RISKS ASSOCIATED WITH METALLIC CONDUCTORS CONNECTING <br />EXTERNAL DEVICES TO INTERNAL NETWORK COMPONENTS. <br />- DTK-2MHLPB-WB <br />(SHORTS TO GROUND) <br />2.ITIS RECOMMENDED TO PROTECT EACH EXTERNALLY -MOUNTED <br />DTK-2MHLPF-WB <br />DEVICE FROM SURGES THAT ARE INTRODUCED ON THE METALLIC <br />(OPENS CIRCUIT) <br />CONDUCTORS. <br />3. FAILURE TO INSTALL SURGE PROTECTION DEVICES PLACES ALL <br />INTERNAL NETWORK CONNECTED EQUIPMENT AT RISK. <br />4. MUST BE GROUNDED AND INSTALLED PER MANUFACTURERS <br />INSTALLATION INSTRUCTIONS. <br />5. ALL CABLING ROUTED IN PLENUM SPACE SHALL BE <br />PLENUM -RATED CABLE. <br />6. ALL DIRECT BURIED CABLE SHALL BE GEL FILLED <br />CEILING GRID ELECTRICAL BACK -BOX <br />ATTACHMENT <br />(NOT TO SCALE) <br />"CADDY" T-GRID BOX HANGER <br />SUPPORT, OR EQUAL. "CADDY'—' <br />REFERENCE NO. CEC 30-302(3). <br />ELECTRICAL MOUNTING BOX <br />FOR THE CEILING MOUNTED <br />NOTIFICATION DEVICES. <br />ACOUSTICAL TILE CEILING <br />GRID SUPPORT FRAMING. <br />FIRE ALARM DEVICE MOUNTING GUIDE <br />(NOT TO SCALE) <br />CEILING MOUNTED <br />24" MIN HANDICAP <br />BEDROOM STROBE <br />MORE THAN TWO APPLIANCES <br />IN THE SAME ROOM OR ADJACENT <br />SPACE WITHIN THE FIELD OF VIEW <br />SHALL FLASH IN SYNCHRONIZATION. <br />80" MIN <br />96" MAX <br />NFPA 72 2016 <br />(72: 18.5.5) <br />(ADAAG) <br />80" ABOVE HIGHEST FLOOR <br />LEVEL OR 6" BELOW CEILING <br />TO THE BOTTOM OF THE <br />STROBE. WHICHEVER IS LOWER. <br />FINISHED <br />FLOOR <br />DETAIL NOTES: <br />3 (MIN) <br />PER NFPA 72 <br />A/C SUPPLY DIFFUSER <br />AUDIO/VISUAL <br />3r VISUAL -ONLY <br />DEVICES CEILING MOUNTED NOTIFICATION <br />DEVICE (TO BE WHITE). <br />SEE PLAN FOR LOCATION. <br />MANUAL <br />PULL <br />STATION <br />ACCEPTABLE HERE,' <br />DO NOT INSTALL <br />IN THIS AREA <br />WALL MOUNTED <br />HEAT DETECTOR — <br />TO THE BOTTOM. <br />WALL MOUNTED <br />5'-0 SMOKE DETECTOR — <br />MAX FROM EXrr DOOR TO THE TOP. <br />MAGNETIC <br />D00 <br />HOLDER <br />48" (ADO) I o w <br />TO THE WORKING MECHANISM a o <br />48" ALSO MEETS THE <br />REQUIREMENTS OF NFPA 72 ,�01 <br />(72: 17.14.5) <br />A. NOT ALL DEVICES SHOWN ON THIS DETAIL APPLY TO THIS PROJECT. SEE THE PLAN VIEW LAYOUT OF THE FIRE ALARM <br />SYSTEM TO VERIFY WHICH DEVICES APPLY, AND WHICH DO NOT. <br />B. CHECK WITH MANUFACTURER'S INSTALLATION SHEET FOR THE EXACT ROUGH -IN HEIGHTS, LOCATION OF BACK -BOXES, AND <br />WIRING REQUIREMENTS. <br />PANEL MOUNTING ON EXTERIOR WALL <br />(NOT TO SCALE) <br />FOR PANELS MOUNTED ON AN <br />EXTERIOR WALL. PROVIDE A 3/4" <br />PLYWOOD BACK BOARD LAYER <br />BETWEEN THE EXTERIOR WALL AND <br />THE FIRE ALARM PANEL <br />EXTEND PLYWOOD BACK BOARD <br />�\ FOR ADJACENT POWER SUPPLIES <br />\\ \ OR SUB -PANELS AS REQUIRED <br />\ \ <br />I Etl III <br />ai 111 <br />I I III <br />III <br />\\ I J 11 <br />\� 11 <br />\ \ II <br />\\ II <br />\ \ II <br />LiJ <br />F- <br />S <br />jam. <br />. <br />S <br />v jz <br />5 <br />a <br />�+ <br />C: <br />4J <br />r, o <br />+�+ N O <br />Ei 0) rf3 O O <br />_1 <br />O .N i <br />rv'1 0., <br />z <br />0 <br />(14 �6 <br />o <br />w <br />i31 <br />LP) <br />r- <br />rr <br />i <br />w <br />U <br />w��xZwoZ�Y <br />o�zz��awa= <br />w <br />o wo-6.0 <br />a= LL a 0 <br />w o Z N 0 U <br />� <br />1a_ <br />�-a`"�z <br />gym- <br />Z zlaOZo <br />�i <br />to <br />= W NaO¢ <br />l7 Z5 <br />ZW <br />Q <br />a <br />U� <br />m <br />Z <br />tWL <br />7� <br />h� <br />UUJI <br />W <br />Z <br />PN o^ <br />m E <br />b .. <br />U <br />W .0ncnp� <br />o <br />Z �Uj <br />a <br />0 <br />W <br />o�om o c <br />L <br />0 <br />C <br />h •i u <br />UJ <br /><' <br />F o <br />N <br />y'�nN m <br />ro <br />U <br />U <br />ro <br />a <br />2� <br />Nat,� ° <br />4Z <br />Z Q <br />* b <br />/ <br />cah <br />a —Lt <br />n <br />U- <br />ICSI <br />tJ <br />V <br />Z <br />N <br />V) <br />Ln <br />c, M <br />:::E <br />> M <br />W <br />C0 U_ r14 <br />M <br />urno� <br />VI <br />Q > o� <br />In <br />m�m� <br />H = M <br />p <br />�=a o <br />Lnn <br />W <br />W <br />a m w <br />Q O 1- <br />_Z <br />O Vi <br />U <br />M --1 <br />nl <br />z <br />d <br />Q <br />0 <br />� r <br />z Q <br />O <br />U <br />0 <br />rr <br />a <br />W <br />LIR! <br />V <br />Z0 <br />O <br />' <br />J <br />LLJ> <br />M <br />—J _j <br />U>j J <br />J <br />5 �'- <br />W <br />W <br />m vi <br />.�_I J <br />CC <br />G <br />Wo <br />�� <br />M � <br />g <br />0 1— LU <br />10 W <br />N <br />w <br />J <br />U <br />F <br />U <br />w <br />O <br />U <br />it w <br />CL p <br />DESIGNED BY <br />AGO <br />DRAWN BY <br />AGO <br />CHECKED BY <br />RWL <br />PROJECT NO./CAD CODE <br />2023-2601 <br />ri <br />DATE <br />06/27/2023 <br />DRAWING NO. <br />FA4 <br />