NO. DESCRIPTION DATE <br />N. <br />1. THE WORK REQUIRED UNDER THIS DIVISION SHALL INCLUDE ALL MATERIALS, LABOR, TOOLS, EQUIPMENT, TRANSPORTATION, INSURANCE, <br />TEMPORARY PROTECTION, TEMPORARY LIGHTING, SUPERVISION AND INCIDENTAL ITEMS ESSENTIAL FOR PROPER INSTALLATION AND OPERATION, <br />EVEN THOUGH NOT SPECIFICALLY MENTIONED OR INDICATED BUT WHICH ARE USUALLY PROVIDED OR ARE ESSENTIAL FOR PROPER <br />INSTALLATION AND OPERATION OF ALL ELECTRICAL SYSTEMS THE ELECTRICAL SYSTEM REQUIRED UNDER THIS DIVISION CONSISTS BASICALLY <br />OF, BUT IS NOT LIMITED TO THE FOLLOWING: LIGHTING SYSTEM, POWER SYSTEM, ALARM SYSTEM, POWER DISTRIBUTION, EQUIPMENT <br />CONNECTIONS, ACCESS PANELS, EMPTY CONDUIT SYSTEMS AND ALL REQUIRED WIRING. <br />2. GIVE ALL NOTICES, FILE ALL PLANS, PAY ALL FEES, OBTAIN ALL PERMITS, ALL LICENSES, INSPECTIONS, RE -INSPECTIONS AND APPROVALS <br />FROM AUTHORITIES HAVING JURISDICTION. INCLUDE ALL FEES IN THE BID <br />3. A. SPECIAL ATTENTION IS CALLED TO THE FACT THAT WORK INVOLVED IS IN CONNECTION WITH EXISTING BUILDINGS WHICH REMAIN IN <br />OPERATION WHILE WORK IS BEING PERFORMED. WORK MUST BE DONE IN ACCORDANCE WITH THE PRIORITY SCHEDULE. SCHEDULE <br />WORK FOR A MINIMUM OUTAGE TO OWNER. CONTRACTOR SHALL CLOSELY COORDINATE WITH THE HOSPITAL PRIOR TO COMMENCING <br />WORK AND DURING CONSTRUCTION FOR POWER ANDIOR SYSTEM OUTAGES AS WELL AS GENERAL REQUIREMENTS. RECEIVE WRITTEN <br />ACCEPTANCE FROM THE OWNER NO LATER THAN 7 DAYS IN ADVANCE OF ALL POWER OUTAGES. CONTRACTOR SHALL WORK DURING <br />OFF HOURS (EVENINGS & WEEKENDS) WHEN DEEMED NECESSARY BY THE HOSPITAL. PROTECT EXISTING BUILDINGS AND EQUIPMENT <br />DURING CONSTRUCTION. <br />B. CONTRACTOR SHALL VERIFY IF THERE IS ANY PIPING, FIXTURES OR OTHER ITEMS IN THE EXISTING BUILDING WHICH MUST BE REMOVED <br />OR RELOCATED IN ORDER TO PERFORM THE ALTERATION WORK. BID SHALL INCLUDE ALL REMOVAL AND RELOCATION REQUIRED FOR <br />COMPLETION OF THE ALTERATIONS AND THE NEW CONSTRUCTION. <br />C. ALL EXISTINGINEW CONDUIT AND CABLES WITHIN THE AREA OF RENOVATION SHALL BE PROVIDED WITH PROPER SUPPORTS. <br />D. ALL EXISTING ELECTRICAL WHICH IS DESIGNATED FOR REWORKING OR REQUIRES RELOCATION, REPAIR OR ADJUSTMENT SHALL CONFORM <br />TO ALL APPLICABLE CODES AND SHALL BE TREATED AS NEW WORK COMPLYING TO ALL PARTS OF THIS SPECIFICATION. <br />E. THE CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED PROGRAMMING FOR CONNECTION TO EXISTING SYSTEMS INCLUDING BUT NOT <br />LIMITED TO FIRE ALARM AND NURSE CALL. <br />4. ALL MATERIALS SHALL BE NEW AND FREE OF DEFECTS, AND SHALL BE U.L. LISTED, BEAR THE U.L. LABEL OR BE LABELED OR LISTED WITH <br />AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL TESTING AGENCY, WHERE NO LABELING OR LISTING SERVICE IS AVAILABLE FOR <br />CERTAIN TYPES OF EQUIPMENT, TEST DATA SHALL BE SUBMITTED TO PROVE TO THE ENGINEER THAT EQUIPMENT MEETS OR EXCEEDS <br />AVAILABLE STANDARDS, AFTER TEST DATA IS SUBMITTED AND TENTATIVELY APPROVED, THE CONTRACTOR SHALL PAY FOR ANY REQUIRED <br />FIELD LUSTING ANDIOR CORRECTIVE WORK REQUIRED BY THE FIELD LISTING INSPECTOR IF ALLOWED BY THE AHJ. <br />5. PROVIDE SHOP DRAWING SUBMITTALS TO THE ARCHITECTIENGINEER FOR APPROVAL FOR ALL MATERIAL PROVIDED UNDER THIS DIVISION. <br />EQUIPMENT SHALL NOT BE ORDERED PRIOR TO APPROVAL FROM THE ARCHITECTIENGINEER. <br />6. COORDINATION STUDY: ALL PANELBOARD AND CIRCUIT BREAKERS SHALL MATCH THE EXISTING TYPE, AIC RATING, AND MANUFACTURER. ANY <br />DISCREPANCIES OR CONFLICTS IN THE SPECIFIED EQUIPMENT SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER DURING BID FOR <br />FORMAL CLARIFICATION. <br />7. PROVIDE AND INSTALL ALL ELECTRICAL SYSTEMS AND ANY NECESSARY ACCESSORIES AS PER NEC AND LOCAL CODES WHETHER SPECIFIED <br />HEREIN OR SHOWN ON DRAWINGS OR NOT. THE CONTENT OF THESE SPECIFICATIONS (DIVISION 26) AND CONTRACT DOCUMENTS IN GENERAL <br />ONLY REFERS TO WORK REQUIRED ABOVE AND BEYOND THE REQUIREMENTS OF THE NEC AND LOCAL CODES. <br />8. DRAWINGS ARE DIAGRAMMATIC. COORDINATE FINAL EQUIPMENT LOCATIONS WITH GOVERNING ARCHITECTURAL AND STRUCTURAL DRAWINGS. <br />LAY OUT BEFORE INSTALLATION SO THAT ALL TRADES MAY INSTALL EQUIPMENT IN SPACES AVAILABLE. PROVIDE COORDINATION AS <br />REQUIRED FOR INSTALLATION IN A NEAT AND WORKMANLIKE MANNER. <br />9. CHECK SITE AND EXISTING CONDITIONS THOROUGHLY BEFORE BIDDING. ADVISE ENGINEER OF DISCREPANCIES OR QUESTIONS NOTED. WHERE <br />EXISTING CONDITIONS ARE DISCOVERED WHICH ARE NOT IN COMPLIANCE WITH THE CODES AND STANDARDS, THE CONTRACTOR SHALL <br />SUBMIT PROPER DOCUMENTATION TO THE ARCHITECT FOR CLARIFICATION AND CORRECTIVE WORK DIRECTION. EXISTING <br />CONDITIONS SHALL NOT REMAIN WHICH WILL CREATE A DISAPPROVAL OF THE RENOVATED AREA. <br />10. ALL EXISTING CONDUIT AND CABLE PENETRATIONS SHALL BE PROPERLY FIRE TREATED PER CODE AND SPECIFICATION REQUIREMENTS. THE <br />CONTRACTOR SHALL THOROUGHLY INSPECT ALL EXISTING LOCATIONS AND INCLUDE THE COST OF PATCHING AND REPAIR IN HIS PROPOSED <br />CONSTRUCTION COST. <br />11. PROVIDE FIELD SUPERINTENDENT WHO HAS HAD A MINIMUM OF FOUR (4) YEARS PREVIOUS SUCCESSFUL EXPERIENCE ON PROJECTS OF <br />COMPARABLE SIZES AND COMPLEXITY. SUPERINTENDENT SHALL BE PRESENT AT ALL TIMES THAT WORK UNDER THIS DIVISION IS BEING <br />INSTALLED OR AFFECTED. SUPERINTENDENT SHALL HAVE PASSED A PROCTORED H.H. BLOCK JOURNEYMAN EXAM WITH 75% GRADE OR <br />BETTER AND SHALL BE A LICENSED JOURNEYMAN. A RESUME OF THE SUPERINTENDENTS EXPERIENCE SHALL BE SUBMITTED TO ENGINEER <br />BEFORE STARTING WORK. AT LEAST ONE MEMBER OF THE ELECTRICAL CONTRACTING FIRM SHALL HOLD A STATE MASTER CERTIFICATE OF <br />COMPETENCY. <br />12. PROVIDE ALL REQUIRED COORDINATION AND SUPERVISION WHERE WORK CONNECTS TO OR IS AFFECTED BY WORK OF OTHERS, AND COMPLY <br />WITH ALL REQUIREMENTS AFFECTING THIS DIVISION. <br />13. SUITABLY PROTECT ALL EQUIPMENT FURNISHED UNDER THIS DIVISION DURING CONSTRUCTION. RESTORE ALL DAMAGED SURFACES AND <br />ITEMS TO 'LIKE NEW CONDITION BEFORE A REQUEST FOR SUBSTANTIAL COMPLETION INSPECTION. <br />14. THE WORK REQUIRED UNDER THIS DIVISION SHALL INCLUDE A ONE-YEAR GUARANTEE. THIS GUARANTEE SHALL BE BY THE CONTRACTOR TO <br />THE OWNER FOR ANY DEFECTIVE WORKMANSHIP OR MATERIAL WHICH HAS BEEN FURNISHED UNDER THIS CONTRACT AT NO COST TO THE <br />OWNER FOR A PERIOD OF ONE YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION OF THE SYSTEM. THIS GUARANTEE SHALL NOT <br />INCLUDE LAMPS IN SERVICE. THE PROVISIONS OF GUARANTEE TO THE OWNER AT THE "DEMONSTRATION OF COMPLETED AFTER ONE MONTH <br />FROM DATE OF SUBSTANTIAL COMPLETION OF THE SYSTEM.' <br />15. PERFORM VERIFICATION WORK AS REQUIRED TO SHOW THAT THE SYSTEM IS OPERATING CORRECTLY IN ACCORDANCE WITH CONTRACT <br />DOCUMENTS AND MANUFACTURER'S LITERATURE. ALL VERIFICATION SHALL BE DONE AFTER 3-DAY FULL OPERATIONAL PERIOD. ALL WORK <br />ON THE SYSTEM SHALL BE COMPLETED, AND ALL FORMS AND OTHER INFORMATION SHALL. BE SUBMITTED FOR APPROVAL ONE WEEK <br />BEFORE THE REQUEST FOR FINAL INSPECTION OF THE BUILDING. <br />16. WHERE THE REQUIREMENTS OF ANOTHER DIVISION, SECTION, OR PART OF THESE SPECIFICATIONS EXCEED THE REQUIREMENTS OF THIS <br />DIVISION, THOSE REQUIREMENTS SHALL GOVERN. <br />17. THE ENTIRE INSTALLATION SHALL BE IN HOT DIPPED RIGID GALVANIZED CONDUIT, OR ELECTRIC METALLIC TUBING, UNLESS SPECIFICALLY <br />NOTED OTHERWISE. RIGID METAL GALVANIZED CONDUIT SHALL BE USED IN ALL DAMP OR WET LOCATIONS OR WHERE SUBJECT TO <br />MECHANICAL DAMAGE. ELECTRIC METALLIC TUBING SHALL HAVE STEEL COMPRESSION TYPE COUPLINGS AND BE USED INSIDE OF BUILDINGS <br />AND ONLY IN DRY AREAS WHERE NOT EXPOSED TO MECHANICAL DAMAGE. MINIMUM CONDUIT SIZE FOR ALL SYSTEMS SHALL BE 3/4'. <br />PROVIDE INSULATED BUSHINGS AT ENDS OF ALL CONDUITS. ALL CONDUITS AND BACKBOXES SHALL BE COLOR CODED TO MATCH EXISTING <br />HOSPITAL STANDARDS. SUPPORT CONDUIT IN ACCORDANCE WITH THE NEC. LISTED WHIPS FOR LIGHTING FIXTURES SHALL BE ALLOWED NO <br />LONGER THAN V-0' IN LENGTH. <br />18. BRANCH CIRCUIT AND FEEDER CONDUCTORS FOR ELECTRIC POWER SHALL BE COPPER TYPE THHNITHWN INSULATION FOR BRANCH <br />CIRCUITS AND THWN INSULATION FOR FEEDERS, UNLESS SPECIFICALLY NOTED OTHERWISE. SIZES #12 AND SMALLER SHALL BE SOLID, #10 <br />AND LARGER STRANDED. NO ALUMINUM WIRING SHALL BE PERMITTED. ALL WIRE SHALL BE SIZE SHOWN ON THE DRAWINGS. IF NO SIZE IS <br />SHOWN, WIRE SHALL BE MINIMUM NO. 12, EXCEPT THAT BRANCH 'HOMERUNS' OVER 50 FT. IN LENGTH SHALL BE MINIMUM NO. 10. WIRE IN <br />VICINITY OF HEAT -PRODUCING EQUIPMENT SHALL BE TYPE XHHW INSULATION. ALL WIRING SHALL BE MANUFACTURED IN THE USA. WIRING <br />SHALL BE COLOR CODED ACCORDING TO EXISTING HOSPITAL STANDARDS. USE OF MULTI -WIRE BRANCH CIRCUIT CONFIGURATIONS ARE NOT <br />PERMITTED. ALL BRANCH CIRCUITS SPECIFIED SHALL BE PROVIDED WITH A DEDICATED NEUTRAL. CONDUCTOR EACH SIZED TO MATCH THE <br />CORRESPONDING PHASE CONDUCTORS FOR THE BRANCH CIRCUIT. <br />19. EACH THREE-PHASE CIRCUIT SHALL BE RUN IN A SEPARATE CONDUIT UNLESS OTHERWISE SHOWN ON THE DRAWINGS. CONDUIT SHALL <br />NOT BE INSTALLED EXPOSED UNLESS OTHERWISE NOTED. WHERE CIRCUITS ARE SHOWN AS 'HOME -RUNS' ALL NECESSARY FITTINGS AND <br />BOXES SHALL BE PROVIDED FOR A COMPLETE RACEWAY INSTALLATION. NEUTRAL CONDUCTORS SHALL NOT BE SHARED BETWEEN CIRCTUITS <br />AND THEREFORE ALL CIRCUITS REQUIRING A NEUTRAL CONDUCTOR SHALL EACH RECEEVE A DEDICATED NEUTRAL SIZED TO MATCH THE <br />CORRESPONDING PHASE CONDUCTORS. <br />20. OUTLET BOXES SHALL BE ONE PIECE OR PROJECTION WELDED, GALVANIZED STAMPED STEEL FOR GANG SIZES REQUIRED. SECTIONAL <br />BOXES ARE NOT ACCEPTABLE. BOXES SHALL BE 4' SQUARE AND 1-1/2' DEEP GENERALLY. LARGER BOXES SHALL BE USED AS <br />REQUIRED BY CODE. <br />21. ALL RECEPTACLES SHALL BE 20 AMP HOSPITAL GRADE, STANDARD DUPLEX GROUNDING TYPE. SWITCHES SHALL BE SPECIFICATION GRADE, <br />20 AMP,120/277 VOLT AND SHALL BE OF THE SILENT OPERATING TYPE. GFCI RECEPTACLES SHALL BE HOSPITAL GRADE, UL RATED CLASS <br />A, GROUP 1. COVER PLATES SHALL BE STAINLESS STEEL FINISHED. ALL WIRING DEVICE COVER PLATES INCLUDING BUT NOT LIMITED TO <br />RECEPTACLES AND SWITCHES SHALL BE ENGRAVED WITH THE BRANCH CIRCUIT IDENTIFICATION AS REQUIRED (I.E. 'PANELNAME'.'CIRCUIT <br />NUMBER'. COVERPLATES SHALL BE STAINLESS STEEL WITH BLACK INFILLED LETTERS FOR NORMAL BRANCH AND RED INFILLED LETTERS <br />FOR EMERGENCY BRANCHES. RECEPTACLES AND SWITCHES SHALL HAVE IVORY FINISH FOR NORMAL BRANCH DEVICES AND RED FINISH FOR <br />CRITICAL BRANCH DEVICES. APPROVED MANUFACTURER: PASS & SEYMOUR, LEVITON, HUBBELL <br />22. ALL EQUIPMENT SHALL BE FIRMLY MOUNTED USING APPROVED HANGERS ATTACHED TO STRUCTURAL PORTIONS OF THE BUILDING. <br />SUPPORTING WITH TIE WIRE IS PROHIBITED. LIGHT FIXTURES RECESSED IN CEILINGS SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE <br />INDEPENDENT OF THE CEILING SYSTEM. <br />DIVISION 26 SPECIFICATIONS <br />23. IN GENERAL, ALL ELECTRICAL EQUIPMENT (METALLIC CONDUIT, MOTOR FRAMES, PANELBOARDS, ETC.) SWILL BE BONDED TOGETHER WITH A <br />GREEN INSIAATED COPPER SYSTEM GROUNDING CONDUCTOR IN ACCORDANCE WITH SPECIFIC RULES OF ARTICLE 250 OF THE N.E.C. <br />BONDIING CONDUCTOR THROUGH THE RACEWAY SYSTEM SHNL BE CONTINUOUS FROM EACH WIRING DEVICE OR EQUIPMENT TO PANEL <br />GROUND BAR OF EACH PANELBOARD. PROVIDE GROUND BAR BOLTED TO THE CAN OF EXISTING PANELS WITHOUT A GROUND BAR ALL <br />RACEWAYS SHALL HAVE AN INSULATED COPPER SYSTEM GROUND CONDUCTOR THROUGHOUT THE ENTIRE LENGTH OF CIRCUIT INSTALLED <br />WT1M CONDUIT PER NEC 517.13. GROUNDING CONDUCTOR SHALL BE INCLUDED IN TOTAL FILL IN DETERMINING CONDUIT SIZES, EVEN <br />THOUGH NOT INCLUDED OR SHOWN ON DRAWINGS. <br />24. A. MOLM CASE CIRCUIT BREAKERS : ALL PANELBOARD BRANCH CIRCUIT BREAKERS SHALL BE BOLT -ON THERMAL -MAGNETIC MOLDED <br />CASE TYPE. BREAKERS SHALL BE 1, 2 OR 3 POLE WITH AN INTEGRAL CROSSBAR TO ASSURE SIMULTANEOUS OPENING OF ALL POLES IN <br />MULT141OLE CIRCUIT BREAKERS. BREAKERS SHALT. HAVE AN OVERCENTER,TRIP-FREE,T000LE-TYPE OPERATING MECHANISM WITH QUICK. <br />MAKE, QUICK -BREAK ACTION AND ACTIVE HANDLE INDICATION. HANDLES SWILL HAVE 'ON','OFP, AND 'TRIPPED' POSITIONS. BOLT -ON <br />CIRCUIT BREAKERS SHALL BE ABLE TO BE INSTALLED IN THE PANELBOARD WITHOUT REQUIRING ADDITIONAL MOUNTING HARDWARE. <br />120/20 VOLT CIRCUIT BREAKERS SHALL HAVE INTERRUPTING RATINGS A MINIMUM OF 10,000 IN SYMMETRICAL AMPERES AT 240VAC. <br />277MO VOLT CIRCUIT BREAKERS SHALL HAVE INTERRUPTING RATINGS A MINIMUM OF 18,000 RMS SYMMETRICAL AMPERES AT 600VAC. <br />28. RECORD DRAWINGS: AT THE COMPLETION OF WORK, CONTRACTOR SHALL PROVIDE TWO SETS OF RECORD'AS-BUILT DRAWINGS IN <br />ACCORDANCE WITH DIVISION 1, SHOWING THE ACTUAL LOCATION OF ALL EQUIPMENT INSTALLED INCLUDING UNDERGROUND CONDUITS AND <br />JUNCTION BOXES. <br />26. CONTRACTOR SHALL CLOSELY COORDINATE WITH THE HOSPITAL PRIOR TO COMMENCING WORK AND DURING CONSTRUCTION FOR POWER <br />ANDIOR SYSTEM OUTAGES AS WELL AS GENERAL REQUIREMENTS. A SEVEN (7) DAY NOTICE SHALL BE GIVEN FOR ALL POWER OUTAGES. <br />CONTRACTOR SHALL WORK DURING OFF HOURS (EVENINGS & WEEKENDS) WHEN DEEMED NECESSARY BY THE HOSPITAL. <br />27. GROUND TESTING: CONTRACTOR SHALL PERFORM A COMPLETE EQUIPOTENTIAL GROUND TEST IN ACCORDANCE WITH NFPA 99 UPON THE <br />COMPLETION OF ALL BRANCH CIRCUITS TO THE PANELS SPECIFIED. GROUND TEST SHALL BE IN A TYPED WRITTEN FORMAT FOR ISSUANCE <br />TO MCA AT THE 100% INSPECTION. TEST SHALL BE PERFORMED IN ALL AFFECTED PATIENT -CARE AREAS. <br />28. COLOR CODING : COLOR CODE ALL POWER AND LIGHTING CABLE. COLOR CODE THE WIRE BY USING COLORED PLASTIC TAPE, PAINTING THE <br />ENDS ACCESSIBLE AT JUNCTION OR PULL BOXES, OR OTHER METHOD ACCEPTABLE TO THE ENGINEER USE THE FOLLOWING CHART AS <br />APPLICABLE; <br />1201208 277/480 <br />CONDUCT VOLTS NCO DUCTOR VOLTS <br />PHASE A BLACK PHASE A BROWN <br />PHASE B RED PHASE B ORANGE <br />PHASE C BLUE PHASE C YELLOW <br />NEUTRAL WHITE NEUTRAL GRAY <br />EQUIRGROUND GREEN EQUIPAROUND GREEN <br />29. COLOR CODING OF RACEWAYSIBOXES: ALL BOXES AND ENCLOSURES SHALL BE MARKED SO AS TO BE READILY IDENTIFIED AS PART OF THE <br />SYSTEM FOR WITH IT SERVES. CONDUIT AND BOXES, INCLUDING BACK BOXES. PANELS, ETC. SHALL BE SPOT PAINTED. CONDUITS SHALL BE <br />IDENTIFIED TO WITHIN 6' OF THE BOX OR ENCLOSURE. PROVIDE SPOT PAINTING BINDS AT ALL CONDUIT COUPLING LOCATIONS OR EVERY IT-0' <br />WHICHEVER IS LESS ALONG WITHIN 6' OF EACH SIDE OF WALLS AND FLOOR THAT THE CONDUIT PENETRATES. THE FOLLOWING COLOR CODES <br />SHALL BE USED UNLESS OTHERWISE REQUIRED TO MATCH EXISTING COLOR CODING; <br />BLACK: NORMAL BROWN: MISCELLANEOUS COMMUNICATIONS <br />PURPLE: ESSENTIAL DISTRIBUTION BLUE: TELEPHONSCOMPUTER <br />YELLOW: LIFE SAFETY BRANCH WHITE: NURSE CALL <br />ORANGE: CRITICAL BRANCH LIGHT PINK: TV <br />GREEN: EQUIPMENT BRANCH GREY: PAGING <br />RED: FIRE ALARM BRANCH BEIGE: PHYSIOLOGICAL MONITORING <br />30, EQUIPMENT IDENTIFICATION: <br />LOCATIONS: PROVIDE NAMEPLATES FOR EACH UNIT OF THE FOLLOWING CATEGORIES OF ELECTRICAL WORK: <br />A. SWITCHBOARD, PANELBOARDS, ELECTRICAL CABINETS AND ENCLOSURES. <br />(1) PROVIDE A NAMEPLATE OUTSIDE ABOVE THE DOOR (IF EQUIPPED WITH ONE) LISTING ITS <br />DESIGNATION, BRANCH, VOLTAGE AND CIRCUIT NUMBER <br />(2) PROVIDE AN ENGRAVED PHENOLIC PLASTIC LAMINATE NAMEPLATE: <br />(NORMAL BRANCH: BLACK WANHITE LETTTERS) <br />(CRITICAL BRANCH: ORANGE W/WHITE LETTTERS) <br />(EQUIPMENT BRANCH: GREEN W/WHITE LETTTERS) <br />(LIFE SAFETY BRANCH: YELLOW WIWHITE LETTTERS) <br />(3) NAMEPLATE SIZE SHALL MATCH EXISTING. <br />B. ACCESS PANEUDOORS TO ELECTRICAL FACILITIES. <br />C. MOTOR STARTERS. <br />D. ALL WIRING DEVICES COVERPLATES INCLUDING BUT NOT LIMITED TO RECEPTACLES AND <br />SWITCHES SHALL BE REPLACED WITH NEW 302 STAINLESS STEEL COVERPLATES, AND ENGRAVED <br />IN BLACK FOR NORMAL AND RED FOR EMERGENCY BRANCHES WITH THE BRANCH CIRCUIT <br />IDENTIFICATIONS AS REQUIRED (I.E.'PANELNAME' - CIRCUIT NUMBERI, <br />E. ALL EXIT LIGHTS TO HAVE LABELS MADE (WHITE WIRED LETTERS) AND INSTALLED ON CANOPY <br />OF FIXTURE WITH PANELNAME - CIRCUIT NUMBER <br />F. ALL AUTOMATIC DOOR CONTROLLERS TO HAVE LABELS MADE (WHITE WIRED LETTERS) AND <br />INSTALLED BY DOOR CONTROL ENCLOSURE (LOCATED BELOW THE CEILING) WITH <br />PANELNAME - CIRCUIT NUMBER. <br />1000 <br />GDP-CB2 <br />SQUARE D, ME <br />800.0 AT/800 AP <br />Settings Phase <br />LTPU (0.5-1.0 x P) 1.0 (800A) <br />LTD (2-24 Sec.) 11 <br />STPU (2-10 x P) 6.0 (4800A) <br />STD (0.1-0.5 Sec.) .1 (1"2t Off) <br />INST (3-12 x P) 8.0 (6400A) <br />wo <br />MSB-CB4 <br />SQUARE D, ME <br />800.0 AT/800 AP <br />Settings Phase <br />LTPU (0.5-1.0 x P) 1.0 (800A) <br />LTD (2-24 Sec. ) 24 <br />STPU (2-10 x P) 3 (2400A) <br />STD (0.1-0.5 Sec.) .5 (1^2t Off) <br />10 INST (3-12 x P) 8.0 (6400A) <br />1, <br />0.10 <br />CURRENT IN AMPERES <br />1 HCBDP-CB6 <br />SQUARE D, HJ <br />150.0 AT/150 AP <br />Settings Phase <br />Ir (50-150A); tr (Fixed)125 (125A); Fixed <br />Isd (1.5 - 10 x Ir); tsd 10 (1250A); Fixed <br />Ii (1.5 - 15 x In) 12 (1800A) <br />NEW -CT -ECM <br />SQUARE D, HJ <br />150.0 AT/150 AP <br />Settings Phase <br />Ir (50-150A); tr (Fixed) 125 (125A); Fixed <br />Isd (1.5 - 10 x Ir); tsd 10 (1250A); Fixed <br />Ii (1.5 - 15 x In) 12 (1800A) <br />0.01 <br />0.5 1 <br />10 <br />100 <br />1K <br />NEW CT.tcc Ref. Voltage: 480V Current in Amps x 1 <br />10K <br />m <br />Z <br />CD <br />m <br />O <br />Z <br />CD <br />0 <br />t�D <br />A' <br />CON�N <br />d 8 9 <br />r�.-OCR. <br />Cb <br />> C <br />�Ch N 7 <br />¢U_oa <br />=O­ $ <br />pzau- <br />R <br />.O <br />L <br />N <br />W <br />Z <br />V <br />W w <br />W = <br />Z u <br />�a <br />Z� <br />o <br />W <br />rA <br />r- <br />� <br />O <br />� <br />R3 <br />M <br />N <br />rA <br />O <br />o <br />O <br />w <br />"..0 <br />�M <br />W <br />CC3 <br />p <br />co <br />H <br />W <br />U <br />d <br />•D <br />z <br />W <br />a <br />F- <br />z <br />0 <br />W <br />3 <br />U <br />�c <br />W <br />a <br />_ <br />LL <br />Q <br />W <br />w a <br />9, <br />Y <br />SEAL Christopher V. O'Hara, P. E. <br />Florida License #166504 <br />OP H ER f <br />OI <br />, <br />V:No 66504 •.'7 <br />' <br />O R I O <br />C?� , �t <br />STATE OF <br />l <br />--t,v,0 N A� ��.� <br />SHEET TITLE: <br />ELECTRICAL <br />SPECIFICATIONS <br />DATE: 10/25/17 <br />SCALE: AS SHOWN <br />SHEET NO.: <br />E3w 1 <br />