NO. DESCRIPTION DATE
<br />N.
<br />1. THE WORK REQUIRED UNDER THIS DIVISION SHALL INCLUDE ALL MATERIALS, LABOR, TOOLS, EQUIPMENT, TRANSPORTATION, INSURANCE,
<br />TEMPORARY PROTECTION, TEMPORARY LIGHTING, SUPERVISION AND INCIDENTAL ITEMS ESSENTIAL FOR PROPER INSTALLATION AND OPERATION,
<br />EVEN THOUGH NOT SPECIFICALLY MENTIONED OR INDICATED BUT WHICH ARE USUALLY PROVIDED OR ARE ESSENTIAL FOR PROPER
<br />INSTALLATION AND OPERATION OF ALL ELECTRICAL SYSTEMS THE ELECTRICAL SYSTEM REQUIRED UNDER THIS DIVISION CONSISTS BASICALLY
<br />OF, BUT IS NOT LIMITED TO THE FOLLOWING: LIGHTING SYSTEM, POWER SYSTEM, ALARM SYSTEM, POWER DISTRIBUTION, EQUIPMENT
<br />CONNECTIONS, ACCESS PANELS, EMPTY CONDUIT SYSTEMS AND ALL REQUIRED WIRING.
<br />2. GIVE ALL NOTICES, FILE ALL PLANS, PAY ALL FEES, OBTAIN ALL PERMITS, ALL LICENSES, INSPECTIONS, RE -INSPECTIONS AND APPROVALS
<br />FROM AUTHORITIES HAVING JURISDICTION. INCLUDE ALL FEES IN THE BID
<br />3. A. SPECIAL ATTENTION IS CALLED TO THE FACT THAT WORK INVOLVED IS IN CONNECTION WITH EXISTING BUILDINGS WHICH REMAIN IN
<br />OPERATION WHILE WORK IS BEING PERFORMED. WORK MUST BE DONE IN ACCORDANCE WITH THE PRIORITY SCHEDULE. SCHEDULE
<br />WORK FOR A MINIMUM OUTAGE TO OWNER. CONTRACTOR SHALL CLOSELY COORDINATE WITH THE HOSPITAL PRIOR TO COMMENCING
<br />WORK AND DURING CONSTRUCTION FOR POWER ANDIOR SYSTEM OUTAGES AS WELL AS GENERAL REQUIREMENTS. RECEIVE WRITTEN
<br />ACCEPTANCE FROM THE OWNER NO LATER THAN 7 DAYS IN ADVANCE OF ALL POWER OUTAGES. CONTRACTOR SHALL WORK DURING
<br />OFF HOURS (EVENINGS & WEEKENDS) WHEN DEEMED NECESSARY BY THE HOSPITAL. PROTECT EXISTING BUILDINGS AND EQUIPMENT
<br />DURING CONSTRUCTION.
<br />B. CONTRACTOR SHALL VERIFY IF THERE IS ANY PIPING, FIXTURES OR OTHER ITEMS IN THE EXISTING BUILDING WHICH MUST BE REMOVED
<br />OR RELOCATED IN ORDER TO PERFORM THE ALTERATION WORK. BID SHALL INCLUDE ALL REMOVAL AND RELOCATION REQUIRED FOR
<br />COMPLETION OF THE ALTERATIONS AND THE NEW CONSTRUCTION.
<br />C. ALL EXISTINGINEW CONDUIT AND CABLES WITHIN THE AREA OF RENOVATION SHALL BE PROVIDED WITH PROPER SUPPORTS.
<br />D. ALL EXISTING ELECTRICAL WHICH IS DESIGNATED FOR REWORKING OR REQUIRES RELOCATION, REPAIR OR ADJUSTMENT SHALL CONFORM
<br />TO ALL APPLICABLE CODES AND SHALL BE TREATED AS NEW WORK COMPLYING TO ALL PARTS OF THIS SPECIFICATION.
<br />E. THE CONTRACTOR IS RESPONSIBLE FOR ALL REQUIRED PROGRAMMING FOR CONNECTION TO EXISTING SYSTEMS INCLUDING BUT NOT
<br />LIMITED TO FIRE ALARM AND NURSE CALL.
<br />4. ALL MATERIALS SHALL BE NEW AND FREE OF DEFECTS, AND SHALL BE U.L. LISTED, BEAR THE U.L. LABEL OR BE LABELED OR LISTED WITH
<br />AN APPROVED, NATIONALLY RECOGNIZED ELECTRICAL TESTING AGENCY, WHERE NO LABELING OR LISTING SERVICE IS AVAILABLE FOR
<br />CERTAIN TYPES OF EQUIPMENT, TEST DATA SHALL BE SUBMITTED TO PROVE TO THE ENGINEER THAT EQUIPMENT MEETS OR EXCEEDS
<br />AVAILABLE STANDARDS, AFTER TEST DATA IS SUBMITTED AND TENTATIVELY APPROVED, THE CONTRACTOR SHALL PAY FOR ANY REQUIRED
<br />FIELD LUSTING ANDIOR CORRECTIVE WORK REQUIRED BY THE FIELD LISTING INSPECTOR IF ALLOWED BY THE AHJ.
<br />5. PROVIDE SHOP DRAWING SUBMITTALS TO THE ARCHITECTIENGINEER FOR APPROVAL FOR ALL MATERIAL PROVIDED UNDER THIS DIVISION.
<br />EQUIPMENT SHALL NOT BE ORDERED PRIOR TO APPROVAL FROM THE ARCHITECTIENGINEER.
<br />6. COORDINATION STUDY: ALL PANELBOARD AND CIRCUIT BREAKERS SHALL MATCH THE EXISTING TYPE, AIC RATING, AND MANUFACTURER. ANY
<br />DISCREPANCIES OR CONFLICTS IN THE SPECIFIED EQUIPMENT SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER DURING BID FOR
<br />FORMAL CLARIFICATION.
<br />7. PROVIDE AND INSTALL ALL ELECTRICAL SYSTEMS AND ANY NECESSARY ACCESSORIES AS PER NEC AND LOCAL CODES WHETHER SPECIFIED
<br />HEREIN OR SHOWN ON DRAWINGS OR NOT. THE CONTENT OF THESE SPECIFICATIONS (DIVISION 26) AND CONTRACT DOCUMENTS IN GENERAL
<br />ONLY REFERS TO WORK REQUIRED ABOVE AND BEYOND THE REQUIREMENTS OF THE NEC AND LOCAL CODES.
<br />8. DRAWINGS ARE DIAGRAMMATIC. COORDINATE FINAL EQUIPMENT LOCATIONS WITH GOVERNING ARCHITECTURAL AND STRUCTURAL DRAWINGS.
<br />LAY OUT BEFORE INSTALLATION SO THAT ALL TRADES MAY INSTALL EQUIPMENT IN SPACES AVAILABLE. PROVIDE COORDINATION AS
<br />REQUIRED FOR INSTALLATION IN A NEAT AND WORKMANLIKE MANNER.
<br />9. CHECK SITE AND EXISTING CONDITIONS THOROUGHLY BEFORE BIDDING. ADVISE ENGINEER OF DISCREPANCIES OR QUESTIONS NOTED. WHERE
<br />EXISTING CONDITIONS ARE DISCOVERED WHICH ARE NOT IN COMPLIANCE WITH THE CODES AND STANDARDS, THE CONTRACTOR SHALL
<br />SUBMIT PROPER DOCUMENTATION TO THE ARCHITECT FOR CLARIFICATION AND CORRECTIVE WORK DIRECTION. EXISTING
<br />CONDITIONS SHALL NOT REMAIN WHICH WILL CREATE A DISAPPROVAL OF THE RENOVATED AREA.
<br />10. ALL EXISTING CONDUIT AND CABLE PENETRATIONS SHALL BE PROPERLY FIRE TREATED PER CODE AND SPECIFICATION REQUIREMENTS. THE
<br />CONTRACTOR SHALL THOROUGHLY INSPECT ALL EXISTING LOCATIONS AND INCLUDE THE COST OF PATCHING AND REPAIR IN HIS PROPOSED
<br />CONSTRUCTION COST.
<br />11. PROVIDE FIELD SUPERINTENDENT WHO HAS HAD A MINIMUM OF FOUR (4) YEARS PREVIOUS SUCCESSFUL EXPERIENCE ON PROJECTS OF
<br />COMPARABLE SIZES AND COMPLEXITY. SUPERINTENDENT SHALL BE PRESENT AT ALL TIMES THAT WORK UNDER THIS DIVISION IS BEING
<br />INSTALLED OR AFFECTED. SUPERINTENDENT SHALL HAVE PASSED A PROCTORED H.H. BLOCK JOURNEYMAN EXAM WITH 75% GRADE OR
<br />BETTER AND SHALL BE A LICENSED JOURNEYMAN. A RESUME OF THE SUPERINTENDENTS EXPERIENCE SHALL BE SUBMITTED TO ENGINEER
<br />BEFORE STARTING WORK. AT LEAST ONE MEMBER OF THE ELECTRICAL CONTRACTING FIRM SHALL HOLD A STATE MASTER CERTIFICATE OF
<br />COMPETENCY.
<br />12. PROVIDE ALL REQUIRED COORDINATION AND SUPERVISION WHERE WORK CONNECTS TO OR IS AFFECTED BY WORK OF OTHERS, AND COMPLY
<br />WITH ALL REQUIREMENTS AFFECTING THIS DIVISION.
<br />13. SUITABLY PROTECT ALL EQUIPMENT FURNISHED UNDER THIS DIVISION DURING CONSTRUCTION. RESTORE ALL DAMAGED SURFACES AND
<br />ITEMS TO 'LIKE NEW CONDITION BEFORE A REQUEST FOR SUBSTANTIAL COMPLETION INSPECTION.
<br />14. THE WORK REQUIRED UNDER THIS DIVISION SHALL INCLUDE A ONE-YEAR GUARANTEE. THIS GUARANTEE SHALL BE BY THE CONTRACTOR TO
<br />THE OWNER FOR ANY DEFECTIVE WORKMANSHIP OR MATERIAL WHICH HAS BEEN FURNISHED UNDER THIS CONTRACT AT NO COST TO THE
<br />OWNER FOR A PERIOD OF ONE YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION OF THE SYSTEM. THIS GUARANTEE SHALL NOT
<br />INCLUDE LAMPS IN SERVICE. THE PROVISIONS OF GUARANTEE TO THE OWNER AT THE "DEMONSTRATION OF COMPLETED AFTER ONE MONTH
<br />FROM DATE OF SUBSTANTIAL COMPLETION OF THE SYSTEM.'
<br />15. PERFORM VERIFICATION WORK AS REQUIRED TO SHOW THAT THE SYSTEM IS OPERATING CORRECTLY IN ACCORDANCE WITH CONTRACT
<br />DOCUMENTS AND MANUFACTURER'S LITERATURE. ALL VERIFICATION SHALL BE DONE AFTER 3-DAY FULL OPERATIONAL PERIOD. ALL WORK
<br />ON THE SYSTEM SHALL BE COMPLETED, AND ALL FORMS AND OTHER INFORMATION SHALL. BE SUBMITTED FOR APPROVAL ONE WEEK
<br />BEFORE THE REQUEST FOR FINAL INSPECTION OF THE BUILDING.
<br />16. WHERE THE REQUIREMENTS OF ANOTHER DIVISION, SECTION, OR PART OF THESE SPECIFICATIONS EXCEED THE REQUIREMENTS OF THIS
<br />DIVISION, THOSE REQUIREMENTS SHALL GOVERN.
<br />17. THE ENTIRE INSTALLATION SHALL BE IN HOT DIPPED RIGID GALVANIZED CONDUIT, OR ELECTRIC METALLIC TUBING, UNLESS SPECIFICALLY
<br />NOTED OTHERWISE. RIGID METAL GALVANIZED CONDUIT SHALL BE USED IN ALL DAMP OR WET LOCATIONS OR WHERE SUBJECT TO
<br />MECHANICAL DAMAGE. ELECTRIC METALLIC TUBING SHALL HAVE STEEL COMPRESSION TYPE COUPLINGS AND BE USED INSIDE OF BUILDINGS
<br />AND ONLY IN DRY AREAS WHERE NOT EXPOSED TO MECHANICAL DAMAGE. MINIMUM CONDUIT SIZE FOR ALL SYSTEMS SHALL BE 3/4'.
<br />PROVIDE INSULATED BUSHINGS AT ENDS OF ALL CONDUITS. ALL CONDUITS AND BACKBOXES SHALL BE COLOR CODED TO MATCH EXISTING
<br />HOSPITAL STANDARDS. SUPPORT CONDUIT IN ACCORDANCE WITH THE NEC. LISTED WHIPS FOR LIGHTING FIXTURES SHALL BE ALLOWED NO
<br />LONGER THAN V-0' IN LENGTH.
<br />18. BRANCH CIRCUIT AND FEEDER CONDUCTORS FOR ELECTRIC POWER SHALL BE COPPER TYPE THHNITHWN INSULATION FOR BRANCH
<br />CIRCUITS AND THWN INSULATION FOR FEEDERS, UNLESS SPECIFICALLY NOTED OTHERWISE. SIZES #12 AND SMALLER SHALL BE SOLID, #10
<br />AND LARGER STRANDED. NO ALUMINUM WIRING SHALL BE PERMITTED. ALL WIRE SHALL BE SIZE SHOWN ON THE DRAWINGS. IF NO SIZE IS
<br />SHOWN, WIRE SHALL BE MINIMUM NO. 12, EXCEPT THAT BRANCH 'HOMERUNS' OVER 50 FT. IN LENGTH SHALL BE MINIMUM NO. 10. WIRE IN
<br />VICINITY OF HEAT -PRODUCING EQUIPMENT SHALL BE TYPE XHHW INSULATION. ALL WIRING SHALL BE MANUFACTURED IN THE USA. WIRING
<br />SHALL BE COLOR CODED ACCORDING TO EXISTING HOSPITAL STANDARDS. USE OF MULTI -WIRE BRANCH CIRCUIT CONFIGURATIONS ARE NOT
<br />PERMITTED. ALL BRANCH CIRCUITS SPECIFIED SHALL BE PROVIDED WITH A DEDICATED NEUTRAL. CONDUCTOR EACH SIZED TO MATCH THE
<br />CORRESPONDING PHASE CONDUCTORS FOR THE BRANCH CIRCUIT.
<br />19. EACH THREE-PHASE CIRCUIT SHALL BE RUN IN A SEPARATE CONDUIT UNLESS OTHERWISE SHOWN ON THE DRAWINGS. CONDUIT SHALL
<br />NOT BE INSTALLED EXPOSED UNLESS OTHERWISE NOTED. WHERE CIRCUITS ARE SHOWN AS 'HOME -RUNS' ALL NECESSARY FITTINGS AND
<br />BOXES SHALL BE PROVIDED FOR A COMPLETE RACEWAY INSTALLATION. NEUTRAL CONDUCTORS SHALL NOT BE SHARED BETWEEN CIRCTUITS
<br />AND THEREFORE ALL CIRCUITS REQUIRING A NEUTRAL CONDUCTOR SHALL EACH RECEEVE A DEDICATED NEUTRAL SIZED TO MATCH THE
<br />CORRESPONDING PHASE CONDUCTORS.
<br />20. OUTLET BOXES SHALL BE ONE PIECE OR PROJECTION WELDED, GALVANIZED STAMPED STEEL FOR GANG SIZES REQUIRED. SECTIONAL
<br />BOXES ARE NOT ACCEPTABLE. BOXES SHALL BE 4' SQUARE AND 1-1/2' DEEP GENERALLY. LARGER BOXES SHALL BE USED AS
<br />REQUIRED BY CODE.
<br />21. ALL RECEPTACLES SHALL BE 20 AMP HOSPITAL GRADE, STANDARD DUPLEX GROUNDING TYPE. SWITCHES SHALL BE SPECIFICATION GRADE,
<br />20 AMP,120/277 VOLT AND SHALL BE OF THE SILENT OPERATING TYPE. GFCI RECEPTACLES SHALL BE HOSPITAL GRADE, UL RATED CLASS
<br />A, GROUP 1. COVER PLATES SHALL BE STAINLESS STEEL FINISHED. ALL WIRING DEVICE COVER PLATES INCLUDING BUT NOT LIMITED TO
<br />RECEPTACLES AND SWITCHES SHALL BE ENGRAVED WITH THE BRANCH CIRCUIT IDENTIFICATION AS REQUIRED (I.E. 'PANELNAME'.'CIRCUIT
<br />NUMBER'. COVERPLATES SHALL BE STAINLESS STEEL WITH BLACK INFILLED LETTERS FOR NORMAL BRANCH AND RED INFILLED LETTERS
<br />FOR EMERGENCY BRANCHES. RECEPTACLES AND SWITCHES SHALL HAVE IVORY FINISH FOR NORMAL BRANCH DEVICES AND RED FINISH FOR
<br />CRITICAL BRANCH DEVICES. APPROVED MANUFACTURER: PASS & SEYMOUR, LEVITON, HUBBELL
<br />22. ALL EQUIPMENT SHALL BE FIRMLY MOUNTED USING APPROVED HANGERS ATTACHED TO STRUCTURAL PORTIONS OF THE BUILDING.
<br />SUPPORTING WITH TIE WIRE IS PROHIBITED. LIGHT FIXTURES RECESSED IN CEILINGS SHALL BE SUPPORTED FROM THE BUILDING STRUCTURE
<br />INDEPENDENT OF THE CEILING SYSTEM.
<br />DIVISION 26 SPECIFICATIONS
<br />23. IN GENERAL, ALL ELECTRICAL EQUIPMENT (METALLIC CONDUIT, MOTOR FRAMES, PANELBOARDS, ETC.) SWILL BE BONDED TOGETHER WITH A
<br />GREEN INSIAATED COPPER SYSTEM GROUNDING CONDUCTOR IN ACCORDANCE WITH SPECIFIC RULES OF ARTICLE 250 OF THE N.E.C.
<br />BONDIING CONDUCTOR THROUGH THE RACEWAY SYSTEM SHNL BE CONTINUOUS FROM EACH WIRING DEVICE OR EQUIPMENT TO PANEL
<br />GROUND BAR OF EACH PANELBOARD. PROVIDE GROUND BAR BOLTED TO THE CAN OF EXISTING PANELS WITHOUT A GROUND BAR ALL
<br />RACEWAYS SHALL HAVE AN INSULATED COPPER SYSTEM GROUND CONDUCTOR THROUGHOUT THE ENTIRE LENGTH OF CIRCUIT INSTALLED
<br />WT1M CONDUIT PER NEC 517.13. GROUNDING CONDUCTOR SHALL BE INCLUDED IN TOTAL FILL IN DETERMINING CONDUIT SIZES, EVEN
<br />THOUGH NOT INCLUDED OR SHOWN ON DRAWINGS.
<br />24. A. MOLM CASE CIRCUIT BREAKERS : ALL PANELBOARD BRANCH CIRCUIT BREAKERS SHALL BE BOLT -ON THERMAL -MAGNETIC MOLDED
<br />CASE TYPE. BREAKERS SHALL BE 1, 2 OR 3 POLE WITH AN INTEGRAL CROSSBAR TO ASSURE SIMULTANEOUS OPENING OF ALL POLES IN
<br />MULT141OLE CIRCUIT BREAKERS. BREAKERS SHALT. HAVE AN OVERCENTER,TRIP-FREE,T000LE-TYPE OPERATING MECHANISM WITH QUICK.
<br />MAKE, QUICK -BREAK ACTION AND ACTIVE HANDLE INDICATION. HANDLES SWILL HAVE 'ON','OFP, AND 'TRIPPED' POSITIONS. BOLT -ON
<br />CIRCUIT BREAKERS SHALL BE ABLE TO BE INSTALLED IN THE PANELBOARD WITHOUT REQUIRING ADDITIONAL MOUNTING HARDWARE.
<br />120/20 VOLT CIRCUIT BREAKERS SHALL HAVE INTERRUPTING RATINGS A MINIMUM OF 10,000 IN SYMMETRICAL AMPERES AT 240VAC.
<br />277MO VOLT CIRCUIT BREAKERS SHALL HAVE INTERRUPTING RATINGS A MINIMUM OF 18,000 RMS SYMMETRICAL AMPERES AT 600VAC.
<br />28. RECORD DRAWINGS: AT THE COMPLETION OF WORK, CONTRACTOR SHALL PROVIDE TWO SETS OF RECORD'AS-BUILT DRAWINGS IN
<br />ACCORDANCE WITH DIVISION 1, SHOWING THE ACTUAL LOCATION OF ALL EQUIPMENT INSTALLED INCLUDING UNDERGROUND CONDUITS AND
<br />JUNCTION BOXES.
<br />26. CONTRACTOR SHALL CLOSELY COORDINATE WITH THE HOSPITAL PRIOR TO COMMENCING WORK AND DURING CONSTRUCTION FOR POWER
<br />ANDIOR SYSTEM OUTAGES AS WELL AS GENERAL REQUIREMENTS. A SEVEN (7) DAY NOTICE SHALL BE GIVEN FOR ALL POWER OUTAGES.
<br />CONTRACTOR SHALL WORK DURING OFF HOURS (EVENINGS & WEEKENDS) WHEN DEEMED NECESSARY BY THE HOSPITAL.
<br />27. GROUND TESTING: CONTRACTOR SHALL PERFORM A COMPLETE EQUIPOTENTIAL GROUND TEST IN ACCORDANCE WITH NFPA 99 UPON THE
<br />COMPLETION OF ALL BRANCH CIRCUITS TO THE PANELS SPECIFIED. GROUND TEST SHALL BE IN A TYPED WRITTEN FORMAT FOR ISSUANCE
<br />TO MCA AT THE 100% INSPECTION. TEST SHALL BE PERFORMED IN ALL AFFECTED PATIENT -CARE AREAS.
<br />28. COLOR CODING : COLOR CODE ALL POWER AND LIGHTING CABLE. COLOR CODE THE WIRE BY USING COLORED PLASTIC TAPE, PAINTING THE
<br />ENDS ACCESSIBLE AT JUNCTION OR PULL BOXES, OR OTHER METHOD ACCEPTABLE TO THE ENGINEER USE THE FOLLOWING CHART AS
<br />APPLICABLE;
<br />1201208 277/480
<br />CONDUCT VOLTS NCO DUCTOR VOLTS
<br />PHASE A BLACK PHASE A BROWN
<br />PHASE B RED PHASE B ORANGE
<br />PHASE C BLUE PHASE C YELLOW
<br />NEUTRAL WHITE NEUTRAL GRAY
<br />EQUIRGROUND GREEN EQUIPAROUND GREEN
<br />29. COLOR CODING OF RACEWAYSIBOXES: ALL BOXES AND ENCLOSURES SHALL BE MARKED SO AS TO BE READILY IDENTIFIED AS PART OF THE
<br />SYSTEM FOR WITH IT SERVES. CONDUIT AND BOXES, INCLUDING BACK BOXES. PANELS, ETC. SHALL BE SPOT PAINTED. CONDUITS SHALL BE
<br />IDENTIFIED TO WITHIN 6' OF THE BOX OR ENCLOSURE. PROVIDE SPOT PAINTING BINDS AT ALL CONDUIT COUPLING LOCATIONS OR EVERY IT-0'
<br />WHICHEVER IS LESS ALONG WITHIN 6' OF EACH SIDE OF WALLS AND FLOOR THAT THE CONDUIT PENETRATES. THE FOLLOWING COLOR CODES
<br />SHALL BE USED UNLESS OTHERWISE REQUIRED TO MATCH EXISTING COLOR CODING;
<br />BLACK: NORMAL BROWN: MISCELLANEOUS COMMUNICATIONS
<br />PURPLE: ESSENTIAL DISTRIBUTION BLUE: TELEPHONSCOMPUTER
<br />YELLOW: LIFE SAFETY BRANCH WHITE: NURSE CALL
<br />ORANGE: CRITICAL BRANCH LIGHT PINK: TV
<br />GREEN: EQUIPMENT BRANCH GREY: PAGING
<br />RED: FIRE ALARM BRANCH BEIGE: PHYSIOLOGICAL MONITORING
<br />30, EQUIPMENT IDENTIFICATION:
<br />LOCATIONS: PROVIDE NAMEPLATES FOR EACH UNIT OF THE FOLLOWING CATEGORIES OF ELECTRICAL WORK:
<br />A. SWITCHBOARD, PANELBOARDS, ELECTRICAL CABINETS AND ENCLOSURES.
<br />(1) PROVIDE A NAMEPLATE OUTSIDE ABOVE THE DOOR (IF EQUIPPED WITH ONE) LISTING ITS
<br />DESIGNATION, BRANCH, VOLTAGE AND CIRCUIT NUMBER
<br />(2) PROVIDE AN ENGRAVED PHENOLIC PLASTIC LAMINATE NAMEPLATE:
<br />(NORMAL BRANCH: BLACK WANHITE LETTTERS)
<br />(CRITICAL BRANCH: ORANGE W/WHITE LETTTERS)
<br />(EQUIPMENT BRANCH: GREEN W/WHITE LETTTERS)
<br />(LIFE SAFETY BRANCH: YELLOW WIWHITE LETTTERS)
<br />(3) NAMEPLATE SIZE SHALL MATCH EXISTING.
<br />B. ACCESS PANEUDOORS TO ELECTRICAL FACILITIES.
<br />C. MOTOR STARTERS.
<br />D. ALL WIRING DEVICES COVERPLATES INCLUDING BUT NOT LIMITED TO RECEPTACLES AND
<br />SWITCHES SHALL BE REPLACED WITH NEW 302 STAINLESS STEEL COVERPLATES, AND ENGRAVED
<br />IN BLACK FOR NORMAL AND RED FOR EMERGENCY BRANCHES WITH THE BRANCH CIRCUIT
<br />IDENTIFICATIONS AS REQUIRED (I.E.'PANELNAME' - CIRCUIT NUMBERI,
<br />E. ALL EXIT LIGHTS TO HAVE LABELS MADE (WHITE WIRED LETTERS) AND INSTALLED ON CANOPY
<br />OF FIXTURE WITH PANELNAME - CIRCUIT NUMBER
<br />F. ALL AUTOMATIC DOOR CONTROLLERS TO HAVE LABELS MADE (WHITE WIRED LETTERS) AND
<br />INSTALLED BY DOOR CONTROL ENCLOSURE (LOCATED BELOW THE CEILING) WITH
<br />PANELNAME - CIRCUIT NUMBER.
<br />1000
<br />GDP-CB2
<br />SQUARE D, ME
<br />800.0 AT/800 AP
<br />Settings Phase
<br />LTPU (0.5-1.0 x P) 1.0 (800A)
<br />LTD (2-24 Sec.) 11
<br />STPU (2-10 x P) 6.0 (4800A)
<br />STD (0.1-0.5 Sec.) .1 (1"2t Off)
<br />INST (3-12 x P) 8.0 (6400A)
<br />wo
<br />MSB-CB4
<br />SQUARE D, ME
<br />800.0 AT/800 AP
<br />Settings Phase
<br />LTPU (0.5-1.0 x P) 1.0 (800A)
<br />LTD (2-24 Sec. ) 24
<br />STPU (2-10 x P) 3 (2400A)
<br />STD (0.1-0.5 Sec.) .5 (1^2t Off)
<br />10 INST (3-12 x P) 8.0 (6400A)
<br />1,
<br />0.10
<br />CURRENT IN AMPERES
<br />1 HCBDP-CB6
<br />SQUARE D, HJ
<br />150.0 AT/150 AP
<br />Settings Phase
<br />Ir (50-150A); tr (Fixed)125 (125A); Fixed
<br />Isd (1.5 - 10 x Ir); tsd 10 (1250A); Fixed
<br />Ii (1.5 - 15 x In) 12 (1800A)
<br />NEW -CT -ECM
<br />SQUARE D, HJ
<br />150.0 AT/150 AP
<br />Settings Phase
<br />Ir (50-150A); tr (Fixed) 125 (125A); Fixed
<br />Isd (1.5 - 10 x Ir); tsd 10 (1250A); Fixed
<br />Ii (1.5 - 15 x In) 12 (1800A)
<br />0.01
<br />0.5 1
<br />10
<br />100
<br />1K
<br />NEW CT.tcc Ref. Voltage: 480V Current in Amps x 1
<br />10K
<br />m
<br />Z
<br />CD
<br />m
<br />O
<br />Z
<br />CD
<br />0
<br />t�D
<br />A'
<br />CON�N
<br />d 8 9
<br />r�.-OCR.
<br />Cb
<br />> C
<br />�Ch N 7
<br />¢U_oa
<br />=O $
<br />pzau-
<br />R
<br />.O
<br />L
<br />N
<br />W
<br />Z
<br />V
<br />W w
<br />W =
<br />Z u
<br />�a
<br />Z�
<br />o
<br />W
<br />rA
<br />r-
<br />�
<br />O
<br />�
<br />R3
<br />M
<br />N
<br />rA
<br />O
<br />o
<br />O
<br />w
<br />"..0
<br />�M
<br />W
<br />CC3
<br />p
<br />co
<br />H
<br />W
<br />U
<br />d
<br />•D
<br />z
<br />W
<br />a
<br />F-
<br />z
<br />0
<br />W
<br />3
<br />U
<br />�c
<br />W
<br />a
<br />_
<br />LL
<br />Q
<br />W
<br />w a
<br />9,
<br />Y
<br />SEAL Christopher V. O'Hara, P. E.
<br />Florida License #166504
<br />OP H ER f
<br />OI
<br />,
<br />V:No 66504 •.'7
<br />'
<br />O R I O
<br />C?� , �t
<br />STATE OF
<br />l
<br />--t,v,0 N A� ��.�
<br />SHEET TITLE:
<br />ELECTRICAL
<br />SPECIFICATIONS
<br />DATE: 10/25/17
<br />SCALE: AS SHOWN
<br />SHEET NO.:
<br />E3w 1
<br />
|