<br />THIS DOCUMENT MATERIALS OR PRESENTATION WHETHER OFFERED ONLINE OR PRESENTED IN HARD COPY "ADT INFORMATIONAL TOOLS" IS FOR INFORMATIONAL PURPOSES ONLY. ADT PROVIDES THESE ADT INFORMATIONAL TOOLS "A$ IS' WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING, BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF MERCHANTABILITY OR V II NKS I OR A PARTICULAR PURPOSE. THE ADT INFORMATIONAL TOOLS CONTAIN ADT PROPRIETARY AND CONFIDENTIAL MATERIALS. NO PART OF THE ADT INFORMATIONAI C.L, RE MOD t ,
<br />tiF T 4� '� i � RECIPIENT T Y PART F H STATEMENT
<br />I MAY N 1 T Y'IiNIrA'. INA(.CURACI,_ � OR TYPOGRAPHICAL ERRORS. ACTUAL SAVINGS OR RESULTS ACHIEVED MAY BE DIFFERENT FROM THOSE OUTLINED IN THE ADT INFORMATIONAL TOOLS . RtC. TENT SHALL NO ALTER OR REMOVE AN O THIS S E
<br />INTO A RETRIEVAL SYSTEM, OR TRANSMITTED IN ANY FORM OR BY ANY MEANS (ELECTRONIC, MECHANICAL PHOTOCOPYING, RECORDING, OR OTHERWISE), WIT THE PRIOR WRITTEN PERMISSION OF ADT, EXCEPT A$ OTHERWISE PERMITTED BY LAW. PRIOR TO PUBLICATION, REASONABLE EFFORT WAS MADE TO VALIDATE THIS WFORMATION. THE ADT INFORMATION TOOLS MA I CLl Dt t . i
<br />AIDT("
<br />Commercial
<br />FIRE ALARM DRAWING INDEX
<br />SHEET NO. SHEET DESCRIPTION
<br />FA1 SCOPE OF WORK, EQUIPMENT LEGEND, NOTES, BATTERY CALCULATION & MATRIX
<br />FA2 ORIGINAL AS -BUILT DRAWING
<br />- SCOPE OF WORK -
<br />• ADDITION OF A NEW CELLULAR SOLE PATH COMMUNICATOR TO THE
<br />EXISTING PREVIOUSLY APPROVED FIRE ALARM SYSTEM TO REPLACE
<br />POTS LINES.
<br />• NO OTHER CHANGES TO THE FIRE ALARM SYSTEM SHALL TAKE PLACE
<br />UNDER THIS PERMIT.
<br />• MONITORING SERVICE AND MONITORING CENTER SHALL REMAIN
<br />UNCHANGED.
<br />• NO CHANGES TO THE OCCUPANCY TYPE OR OCCUPANT LOAD SHALL
<br />BE MADE.
<br />• NO OTHER CONSTRUCTION OR CHANGES TO THE STRUCTURE SHALL
<br />TAKE PLACE UNDER THIS PERMIT.
<br />- CABLE SYMBOL LEGEND -
<br />SYMBOL I CIRCUIT TYPE I CABLE DESCRIPTION
<br />ALL EXISTING TO REMAIN
<br />UPGRADE -"
<br />7325
<br />GALOL.. V A�
<br />541
<br />- FIRE ALARM EQUIPMENT LEGEND -
<br />SYMBOL DEVICE DESCRIPTION MANUFACTURER BACK -BOX -- NOTES
<br />lfAC]B-444/6450 CELLULAR COMMUNICATOR BOSCH FRCP SOLE PATH
<br />1FACpj D9412GV4 FIRE ALARM CONTROL PANEL BOSCH EXI.` TING UPDATED BATTERY
<br />CALCULATION BELOW
<br />- FIRE ALARM PANEL BATTERY C-ALCULATION -
<br />Bosch D9412GV4 Existin4 Fire ,Alarm Panel
<br />QUANTITY I Devices
<br />I EACH J. TOTAL„
<br />I EACH I TOTAL
<br />Fire Alarm Control Panel
<br />1
<br />D9412GV4. CONTROL PANS..
<br />0.225000
<br />0.225000
<br />0300000
<br />0.300000
<br />2
<br />01255R ANNLN aATOR
<br />0.104000
<br />6.208000
<br />0.048000
<br />0,206000
<br />0,412000
<br />1
<br />D8125. ROPEX MODULE
<br />0.048000
<br />0.048000
<br />0.048000
<br />1
<br />D125B. POVufftHa LOOP INTERFACE MODULE
<br />0.012000
<br />0.012000
<br />0.075000
<br />0.075000
<br />1
<br />D192G. N011FICATIONAPPLIANCE MODULE
<br />0.005000
<br />0.005000
<br />0.100000
<br />0.100000
<br />1
<br />B444-V,CELLULAR COMMUNICATOR
<br />0.035000
<br />0.035000
<br />0.100000
<br />0.100000
<br />1
<br />B450. PLUG•INCOMvANVICATORINTERFACE•`"
<br />0.060000
<br />0.060000
<br />0.180000
<br />0.180000
<br />(Added) 9.593000 1,216000
<br />Conventional devices
<br />1
<br />BG-12. PULL STATION
<br />0.000000
<br />0.000000
<br />0.000000
<br />0.000000
<br />1
<br />_
<br />2W-B. SYSTEM SENSOR SMOKE DETECTOR
<br />0.000500
<br />0 000800
<br />0 130000
<br />0.130000
<br />Addressable devices
<br />17 D9127U. POPIT MODULE 0.000800 - i 13GUD 0 000800 0.013800
<br />3013600 1 0.013600
<br />Notification circuts (see additional sheet for circuit cunfiguration)
<br />1 Circuit # 1 NAC Tugger 0.006�507 0 006500 0.006b00 1 0.006500
<br />Total stand by current
<br />0.61310
<br />X Stand by hours
<br />24
<br />Stand by amp/hours
<br />14,71440
<br />Total Alarm Current
<br />1.23510
<br />X alarm Minutes (5)/60
<br />0.08333
<br />Alarm Total amplhours _
<br />0.10293
<br />Total Ampthours
<br />14.81733
<br />X Derating factor of 20%
<br />1.2
<br />_ _
<br />Minimum Battery Size
<br />17.78
<br />Battery Selected 'r 2V / 18Ah
<br />SYSTEM OUTPUTS
<br />GENERAL NOTES:
<br />QTY. ADDITIONAL NOTES 1. ALL WORK SHALL BE IN ACCORDANCE WITH NFPA STANDARDS
<br />AND ALL LOCAL ADOPTED CODES.
<br />1 NEW
<br />2. SEE WIRING LEGEND FOR CABLE TYPES AND SIZES.
<br />1 EXISTING TO REMAIN 3. FIRE ALARM CABLING SHALL BE PLENUM RATE( AND RED.
<br />4. FIRE ALARM CABLING SHALL NOT BE PAINTED.
<br />5. FIRE ALARM CABLING SHALL BE ACCEPTABLE TO THE FIRE
<br />ALARM EQUIPMENT MANUFACTURER FOR THE INTENDED
<br />PURPOSE.
<br />6. CABLE ROUTING SHALL BE COORDINATED WITH OTHER TRADES IN
<br />THE FIELD. FOLLOW DRAWING NOTES FOR SPECIFIC AND
<br />ACCEPTABLE INSTALLATION METHODS.
<br />REQUIRED
<br />CONTROL UNIT
<br />FIRE SAFETY
<br />SUPPLE
<br />ANNUNCIATION
<br />NOTIFICATION
<br />CONTROL
<br />MENTARY
<br />SYSTEM INPUTS
<br />1
<br />MANUAL PULL STATIONS
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•!
<br />1
<br />2
<br />3
<br />SMOKE DETECTORS
<br />IN -DUCT SMOKE DETECTORS
<br />•
<br />•
<br />•
<br />•
<br />00101
<br />•
<br />•
<br />•1
<br />Ii
<br />2
<br />3
<br />4
<br />WATERFLOW
<br />•
<br />•
<br />•
<br />•
<br />•
<br />•
<br />I
<br />4
<br />5
<br />SPRINKLER CONTROL VALVE
<br />•
<br />•
<br />•
<br />•
<br />5
<br />6
<br />FIRE ALARM AC POWER FAILURE
<br />•
<br />•
<br />•
<br />(
<br />6
<br />7
<br />FIRE ALARM SYSTEM LOW BATTERY
<br />•
<br />•
<br />•
<br />7
<br />8
<br />OPEN CIRCUIT
<br />•8
<br />9
<br />GROUND FAULT
<br />toe",
<br />•
<br />9
<br />10
<br />NOTIFICATION APPLIANCE CIRCUIT SHORT
<br />•
<br />10
<br />IAI8ICID IEIFIGIHIIIJIKILIMIN 0 P
<br />I -INDIVIDUAL HVAC SHUTDOWN
<br />7, ALL FIRE ALARM CONDUIT, FITTINGS, AND BACK BOXES SHALL BE
<br />PROVIDED BY THE ELECTRICAL CONTRACTOR. THE FIRE ALARM
<br />CONTRACTOR SHALL COORDINATE WITH THE ELECTRICAL
<br />CONTRACTOR TO DETERMINE THE EXTENT OF ALL FIRE ALARM
<br />CONDUIT AND BACKBOX REQUIREMENTS.
<br />8. ALL CABLE RUNS SHALL BE NEATLY BUNDLED, WRAPPED TIGHT
<br />AND PROPERLY SECURED. ANY CABLING NOT (NS- ALLED IN A
<br />NEAT MANNER SHALL BE PULLED OUT AND RE -RUN BY
<br />INSTALLER.
<br />9. CONTRACTOR RUNNING CABLING MUST MARK BOTH ENDS OF
<br />CABLING. PROVIDE A WIRE LEGEND FOR ALL LOCATIONS AND
<br />PROVIDE A CONTINUITY TEST LOG FOR EACH CABLE.
<br />10. EXPOSED CABLING SHALL BE RUN PARALLEL AND PERPENDICULAR
<br />TO BUILDING STRUCTURE. EXPOSED CABLING SHALL NOT BE RUN
<br />IN A "SPAN" FASHION BETWEEN BAR JOISTS OR BEAMS
<br />(I.E.:CABLING SHALL BE ROUTED ALONG PATH OF JOISTS AND
<br />BEAMS). ALL CABLING SHALL BE SECURED TO THE STRUCTURAL
<br />CEILING BETWEEN JOISTS OR BEAMS.
<br />11. CABLING SHALL NOT BE STRAPPED TO THE UNDERSIDE OF THE
<br />STRUCTURAL MEMBERS.
<br />12. ALL CABLING SHALL BE SUPPORTED FROM BUILDING STRUCTURE
<br />AND NOT FROM GRID, TILES, OR SUPPORT WIRES. EXPOSED
<br />CABLING SHALL BE SUPPORTED BY BUILDING STRUCTURE AT NO
<br />MORE THAN FIVE (5) FOOT INTERVALS.
<br />13, ALL JUNCTION BOXES AND ADDRESSABLE MODULES SHALL BE
<br />INSTALLED TIGHT TO STRUCTURE OR AT THE BOTTOM OF
<br />STRUCTURE JOISTS. ALL JUNCTION BOXES AND CABLE SPLICES
<br />SHALL BE ACCESSIBLE FOR SERVICE. PROVIDE ANY REQUIRED
<br />ACCESS PANELS.
<br />14. ALL WIRING CONDUCTORS FOR THE FIRE ALARM SYSTEM SEVEN
<br />FEET OR LESS ABOVE THE FINISHED FLOOR, CONCEALED IN
<br />CEILINGS OR PARTITIONS, SUBJECT TO PHYSICAL DAMAGE, NON
<br />POWER LIMITED, OR WHERE REQUIRED BY APPLICABLE CODES
<br />SHALL BE INSTALLED IN CONDUIT.
<br />15. ALL FIRE ALARM CABLING RISERS SHALL BE INSTALLED IN
<br />METALLIC CONDUIT.
<br />16. ALL FIRE ALARM CABLING IN FINISHED AREAS SHALL BE
<br />CONCEALED.
<br />17. COORDINATE DRILLING OF ANY HOLES (I.E. COLUMN
<br />PENETRATIONS) WITH THE GENERAL CONTRACTOR AND ALL
<br />OTHER TRADES PRIOR TO INSTALLATION.
<br />18. ALL CABLING, CONDUIT, AND BACK BOXES SHALL BE PROPERLY
<br />SUPPORTED AND SEISMICALLY BRACED, AS REQUIRED BY ALL
<br />APPLICABLE CODES AND THE LOCAL JURISDICTION.
<br />19. THE FIRE ALARM CONTRACTOR SHALL PROVIDE TRAINING OF
<br />AVAILABLE STORE MANAGEMENT STAFF ON SYSTEM OPERATIONS.
<br />Commercial
<br />INSTALLING BRANCH:
<br />#66874
<br />180 SCARLET BLVD.
<br />OLDSMAR, FL. 34677
<br />WEB: ADT.COM/COMMERCIAL
<br />HOBBY LOBBY #0567
<br />7325 GALL BLVD.
<br />ZEPHYRHILLS, FL. 33541
<br />FIRE ALARM SYSTEM CELL
<br />COMMUNICATOR ADDITION
<br />PROJECT, EQUIPMENT,
<br />APPLICATION, AND SYSTEM
<br />LAYOUT REVIEWED.
<br />DATED: 02/10/2023
<br />S IG N E D:���-u- J-1�:�1`
<br />DONALD J. TAYLOf , SET
<br />NICET * 116320
<br />NICET LEVEL IV
<br />FIRE ALARM SYSTEMS
<br />EXPIRES 04/01/2024
<br />Id +e u
<br />UCOM
<br />UNNWard V.Tani,Rom.MW
<br />REVISIONS
<br />NO.
<br />DATE
<br />REVISION
<br />02/10/2023
<br />ISSUED FOR PERMIT
<br />BY: DJT
<br />%2.
<br />BY:
<br />'3 ..
<br />BY:
<br />CODES ADOPTED BY LOCAL AHJ
<br />7TH EDITION-2020 FL BUILDING CODE
<br />7TH EDITION-2020 FL FIRE PREV. CODE
<br />7TH EDITION-2020 FL MECH. CODE
<br />7TH EDITION-2020 FL PLUMBING CODE
<br />NFPA 1, 2018 EDITION
<br />NFPA 70, NEC 2017 EDITION
<br />NFPA 72, 2016 EDITION
<br />NFPA 101, 2018 EDITION
<br />BUILDING INFORMATION
<br />OCCUPANCY TYPE = 'M' MERCANTILE
<br />NO CHANGE TO SQUARE FOOTAGE
<br />FULLY SPRINKLERED
<br />ONE STORY
<br />®
<br />N
<br />NOT TO SCALE
<br />PREPARED BY: AFA
<br />CHECKED BY: DJT
<br />PROJECT MANAGER: 66874
<br />DATE: 02/10/2023
<br />PROJECT NO: 281800128
<br />TITLE:
<br />COVER PAGE
<br />E
<br />SHEET:
<br />FA1