ELECTRICAL SYMBOLS
<br />LEGEND
<br />10.29.10 ES03
<br />(SYMBOLS APPLY ONLY WHEN USED ON DRAWINGS)
<br />SYMBOL
<br />DESCRIPTION
<br />O
<br />FLUORESCENT / LED OR HID FIXTURE
<br />/
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />0 _
<br />FLUORESCENT / LED FIXTURE
<br />FLUORESCENT / LED FIXTURE,
<br />e '
<br />NIGHT LIGHT
<br />VOLUMETRIC LED FIXTURE
<br />ENCLOSED FREEZER LIGHT
<br />TRACK LIGHTING
<br />/ ®
<br />EXIT FIXTURE
<br />/
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />D04
<br />EMERGENCY LIGHT
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />SINGLE POLE SWITCH
<br />$3
<br />3-WAY SWITCH
<br />$4
<br />4-WAY SWITCH
<br />$K
<br />KEYED SWITCH
<br />$D
<br />DIMMER SWITCH
<br />$VS
<br />VARIABLE SPEED SWITCH
<br />$M
<br />MANUAL MOTOR SWITCH
<br />SINGLE POLE OCCUPANCY
<br />`IDS
<br />SENSOR SWITCH
<br />$OS2
<br />DOUBLE POLE OCCUPANCY
<br />SENSOR SWITCH
<br />CEILING MOUNTED OCCUPANCY
<br />O(ED)
<br />SENSOR SWITCH
<br />RECEPTACLE,DUPLEX
<br />RECEPTACLE, DUPLEX,
<br />MOUNTED HORIZONTALLY
<br />RECEPTACLE, GFI
<br />©
<br />RECEPTACLE, DUPLEX FLUSH FLOOR
<br />RECEPTACLE, DUPLEX ISOLATED
<br />GROUND FLUSH FLOOR
<br />RECEPTACLE, DOUBLE DUPLEX
<br />RECEPTACLE, DUPLEX
<br />ISOLATED GROUND
<br />RECEPTACLE, DOUBLE DUPLEX,
<br />ISOLATED GROUND
<br />RECEPTACLE, SIMPLEX TWIST LOCK,
<br />L5-15R, LINO
<br />RECEPTACLE, SIMPLEX TWIST LOCK,
<br />ISOLATED GROUND, L5-15R, LINO
<br />RECEPTACLE, DUPLEX TWIST LOCK,
<br />L5-15R, LINO
<br />RECEPTACLE, DUPLEX TWIST LOCK,
<br />ISOLATED GROUND, L5-15R, LINO
<br />RECEPTACLE, SPECIAL
<br />RECEPTACLE, SIMPLEX
<br />RECEPTACLE, PLUG -MOLD
<br />O
<br />JUNCTION BOX
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />O
<br />THERMOSTAT
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />O
<br />ALARM JUNCTION BOX,
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />ALARM JUNCTION BOX,
<br />®
<br />FOR REMOTE TEST/RESET
<br />(WALL MOUNTED/CEILING MOUNTED)
<br />0
<br />EQUIPMENT CONNECTION POINT
<br />(PROVIDED WITH EQUIPMENT)
<br />Eh
<br />NON -FUSED DISCONNECT
<br />FUSED DISCONNECT
<br />CIRCUIT, CONCEALED IN WALLS OR
<br />CEILING, E INDICATES EXISTING
<br />WIRING
<br />CIRCUIT, CONCEALED IN SLAB FLOOR,
<br />E INDICATES EXISTING WIRING
<br />r—
<br />CIRCUIT, EXPOSED,
<br />E INDICATES EXISTING WIRING
<br />H
<br />CONDUIT SLEEVE
<br />1�
<br />FLUSH MOUNTED PANELBOARD
<br />SURFACE MOUNTED PANELBOARD
<br />�- - - — - - —
<br />MANUFACTURED WIRING SYSTEM
<br />-
<br />TELEPHONE / DATA BOX FOR ISD
<br />LOW VOLTAGE CABLE
<br />BOX FOR OTHER
<br />®
<br />TELEPHONE, FLUSH FLOOR
<br />0
<br />MOTOR
<br />0
<br />TELEPOWER POLE
<br />g
<br />PUSH BUTTON
<br />ElBUZZER
<br />SAIL SWITCH
<br />SS
<br />JUNCTION BOX
<br />SO
<br />SMOKE DETECTOR
<br />HORN/STROBE
<br />DH
<br />DOOR HOLD OPEN
<br />ABBREVIATIONS
<br />CF CEILING FAN
<br />CO CHECK OUT
<br />CW CASH/WRAP
<br />EF EXHAUST FAN
<br />ETR EXISTING TO REMAIN
<br />G GROUND
<br />GFI GROUND FAULT CIRCUIT INTERRUPTER
<br />IG ISOLATED GROUND
<br />REC REFRIGERATION ELECTRICAL CONTRACTOR
<br />RC REFRIGERATION CONTRACTOR
<br />RH RADIANT HEATER
<br />Sc SECURITY CAMERA
<br />TR TAMPER RESISTANT
<br />UH UNIT HEATER
<br />WH WATER HEATER
<br />WP WEATHER PROOF COVERPLATE
<br />WR WEATHER RESISTANT RECEPTACLE
<br />REVISE TEMPERATURE
<br />SETPOINT
<br />OGP COOLER
<br />0
<br />I
<br />I
<br />I
<br />I
<br />f --(2( -1 )
<br />1
<br />P)
<br />1 0
<br />K20A-1 ) y
<br />i
<br />o I i 16.492
<br />4
<br />I ii I
<br />I ii i
<br />I ii I
<br />EDC4 /
<br />RELOCATE LIGHT SWITCH TO
<br />WALL AND RECONNECT TO
<br />EXISTING LIGHTING CIRCUIT
<br />SEAFOOD INTERNAL HIGH POWER PLAN
<br />1 /8" = 1'-0"
<br />(: D 1 KEY PLAN
<br />16.492 E.C. SHALL COORDINATE WITH GENERAL
<br />1
<br />CONTRACTOR AND ARCHITECTURAL
<br />TELEPOWER POLE(S): MOUNT JUNCTION BOX(ES) TO TOP
<br />DEMOLITION PLANS THE EXTENT OF
<br />SIDE OF BOTTOM CHORD OF BAR JOIST. INSTALL
<br />ELECTRICAL DEMOLITION. REMOVE
<br />FURNISHED PRE -WIRED POWER POLE AND TERMINATE
<br />CONDUITS AND WIRES ALL THE WAY BACK TO
<br />PROVIDED FLEXIBLE CONDUIT AND WIRING TO JUNCTION
<br />ORIGINATING JUNCTION BOXES OR
<br />BOX. PROVIDE UNISTRUT SUPPORTS AND HARDWARE. TO
<br />PANELBOARDS. DEMOLITION SHALL NOT
<br />SECURE TELEPOWER POLE PLUMB TO BUILDING
<br />AFFECT ACTIVE CIRCUITS. LABEL
<br />STRUCTURE.
<br />DEMOLISHED CIRCUIT(S) IN PANELBOARDS
<br />AS "SPARE". COORDINATE EXACT
<br />2. PROVIDE LIQUID -TIGHT FLEXIBLE METAL CONDUIT AND
<br />REQUIREMENTS WITH EXISTING CONDITIONS
<br />WIRING FROM DISCONNECT SWITCH OR JUNCTION BOX TO
<br />PRIOR TO BID.
<br />EQUIPMENT KNOCKOUT OR ELECTRICAL CONNECTION
<br />16.W04 120 VOLT GENERAL POWER CIRCUIT(S):
<br />POINT.
<br />FURNISH AND INSTALL NEW 20 AMP, 120 VOLT
<br />3. WHERE EQUIPMENT NAMEPLATE PROTECTIVE DEVICE
<br />CIRCUIT(S), OR AS SPECIFIED ON DRAWINGS.
<br />RATING DIFFERS FROM SIZE PROVIDED, CHANGE OUT
<br />FEED FROM NEAREST 120 VOLT PANEL, WITH
<br />BRANCH CIRCUIT WIRING AND OVERCURRENT DEVICE TO
<br />ADEQUATE SPACE AND AMPACITY. A. CIRCUIT
<br />APPROPRIATE RATING PER NEC.
<br />BREAKER FOR CIRCUITS INDICATED WITH
<br />(GFI) SHALL BE GFCI TYPE FOR PERSONNEL
<br />4. ELECTRONIC FIRE PROTECTION/SECURITY ALARM BOXES
<br />PROTECTION.
<br />AND CONDUITS SHOWN ON POWER PLANS SHALL BE
<br />16.W07 208 VOLT GENERAL POWER CIRCUIT:
<br />PROVIDED UNDER THIS CONTRACT. IN ADDITION, UNLESS
<br />FURNISH AND INSTALL NEW 208 VOLT
<br />NOTED OTHERWISE, THE FOLLOWING GENERAL NOTES
<br />CIRCUIT, AS SPECIFIED ON DRAWINGS. FEED
<br />APPLY:
<br />FROM NEAREST 208 VOLT PANEL, WITH
<br />A. ALL ALARM JUNCTION BOXES SHALL BE
<br />ADEQUATE SPACE AND AMPACITY.
<br />4"X4"X2-1/8" MINIMUM.
<br />B. ALARM RACEWAYS SHALL BE 3/4" MINIMUM WITH
<br />PULL WIRE AND INSULATING BUSHINGS AT END OF
<br />VERTICAL RACEWAY RUN.
<br />C- VERTICAL RACEWAYS FROM ALARM BOXES SHALL BE
<br />EITHER CONCEALED INSIDE WALL OR SURFACE
<br />MOUNTED (TO MATCH JUNCTION BOX MOUNTING). ALL
<br />VERTICAL RUNS SHALL BE TURNED 90-DEGREES AT
<br />TOP SIDE OF BOTTOM CHORD OF BAR JOIST AND
<br />EXTENDED HORIZONTALLY TO A LOCATION ACCESSIBLE
<br />BY VERTICAL FLOOR TYPE LIFT.
<br />5. UPON COMPLETION OF ELECTRICAL INSTALLATION AND
<br />PRIOR TO ENERGIZING CIRCUIT:
<br />A. INSPECT WIRE AND CABLE FOR PHYSICAL DAMAGE.
<br />B. PERFORM CONTINUITY TEST.
<br />C- VERIFY PROPER PHASING CONNECTION TO ALL THREE
<br />PHASE MOTOR LOADS.
<br />20A WIRE SIZING SCHEDULE
<br />ALL WIRE SIZES SHOWN ON PANEL SCHEDULES AND
<br />PLANS ARE INTENDED TO BE MINIMUM ACCEPTABLE
<br />WIRE SIZE.
<br />THE FOLLOWING SCHEDULE IS TO BE USED TO SIZE
<br />WIRE FOR 20 AMP CIRCUITS (120 AND 277 VOLT).
<br />LENGTHS (IN FEET) ARE INTENDED TO BE MAXIMUM.
<br />FINAL CONNECTIONS: WHERE 20A BRANCH CIRCUITS
<br />HAVE #8 AND LARGER WIRE CALLED OUT, #10AWG WIRE
<br />MAY BE USED FOR THE FINAL CONNECTION (15- MAX.).
<br />120 VOLT
<br />#12
<br />#10
<br />#8
<br />#6
<br />1-5 AMPS
<br />200 FT.
<br />325 FT.
<br />490 FT.
<br />770 FT.
<br />6-10 AMPS
<br />100 FT.
<br />160 FT.
<br />245 FT.
<br />385 FT.
<br />11-15 AMPS
<br />70 FT.
<br />1 110 FT.
<br />165 FT.
<br />255 FT.
<br />277 VOLT
<br />#12
<br />#10
<br />#8
<br />#6
<br />1-5 AMPS
<br />480 FT.
<br />760 FT.
<br />1170 FT.
<br />1865 FT.
<br />6-10 AMPS
<br />240 FT.
<br />380 FT.
<br />585 FT.
<br />930 FT.
<br />11-15 AMPS
<br />160 FT.
<br />250 FT.
<br />390 FT.
<br />620 FT.
<br />7
<br />08.31.12 EN08
<br />1 FURNISH AND INSTALL ALL MATERIALS, EQUIPMENT, AND
<br />LABOR, FOR A COMPLETE INSTALLATION IN ALL RESPECTS,
<br />READY FOR INTENDED USE AND IN STRICT ACCORDANCE WITH
<br />NEC, NESC, STATE, AND LOCAL CODES, AND MANUFACTURER'S
<br />RECOMMENDATIONS. PAY ALL NECESSARY FEES AND PERMITS.
<br />A. NO CIRCUITRY SHALL BE ALLOWED TO BE ROUTED ACROSS
<br />THE ROOF OR THE EXTERIOR SIDE OF THE EXTERIOR
<br />WALLS.
<br />B. ALL EQUIPMENT SHALL BE UL LISTED WHERE APPLICABLE.
<br />C. ARRANGE ALL WORK TO MINIMIZE DISRUPTIONS TO STORE
<br />OPERATIONS. COORDINATE ALL DISRUPTIONS WITH
<br />WALMART CONSTRUCTION MANAGER AND STORE MANAGER.
<br />D. CONTRACTOR SHALL VERIFY ALL WALL FINISH THICKNESSES
<br />BEFORE INSTALLING BOXES. FURNISH AND INSTALL
<br />EXTENDED BOXES OR BOX EXTENDERS WHERE REQUIRED.
<br />E. CONTRACTOR SHALL VERIFY THAT ALL AFFECTED
<br />PANELBOARDS HAVE CIRCUIT BREAKER KNOCKOUTS
<br />PROPERLY COVERED AND THAT ALL TRIM IS IN GOOD
<br />CONDITION, ALLOWING NO ACCESS TO LIVE PARTS.
<br />2- PROVIDE SEALS AT RACEWAY PENETRATIONS AS FOLLOWS:
<br />A• FIRE RATED WALLS: SEAL PER SPECIFICATIONS FOR FIRE
<br />STOPPING.
<br />B. NEUTRALIZATION AREA: SEAL PER MECHANICAL DETAIL.
<br />C. FREEZER/COOLER BOXES: SEAL WITH EXPANDING FOAM
<br />SEALANT.
<br />D. EXTERIOR: REFER TO ARCHITECTURAL DOCUMENTS FOR
<br />SEALING REQUIREMENTS AT ALL EXTERIOR MOUNTED
<br />DEVICES, FIXTURES, ENCLOSURES, AND RACEWAY
<br />PENETRATIONS.
<br />3. PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR
<br />(SIZE PER NEC) IN PVC TYPE CONDUIT, POWER CIRCUITS,
<br />ISOLATED GROUND CIRCUITS, OR AS SHOWN ON PLANS.
<br />CONDUIT SHALL BE SIZED PER NEC BASED ON THWN 600
<br />VOLT COPPER SINGLE CONDUCTORS, PLUS THE EQUIPMENT
<br />GROUNDING CONDUCTOR.
<br />4. WIRING DEVICES: DEVICE MOUNTING HEIGHTS ARE FROM
<br />FINISHED FLOOR TO CENTER OF OUTLET BOX UNLESS NOTED
<br />OTHERWISE ON PLANS. COORDINATE THE STANDARD
<br />MOUNTING HEIGHTS WITH MASONRY:
<br />A. SWITCHES +46"
<br />B. RECEPTACLES +20"
<br />C. VOICE/DATA +20"
<br />5. WIRING SHALL INCLUDE FINAL CONNECTION TO ALL EQUIPMENT
<br />IN CONFORMANCE WITH EQUIPMENT SUPPLIER WIRING
<br />DIAGRAMS.
<br />6. CONTRACTOR IS RESPONSIBLE FOR PROVIDING COMPLETE
<br />PANELBOARD IDENTIFICATION SCHEDULES FOR PANELBOARDS
<br />AFFECTED BY REMODEL.
<br />7. NEW OVERCURRENT PROTECTIVE DEVICES INSTALLED IN
<br />EXISTING PANELBOARDS OR DISTRIBUTION BOARDS SHALL
<br />MATCH THE TYPE AND AIC RATING OF EXISTING OVERCURRENT
<br />PROTECTIVE DEVICES.
<br />8. BRANCH CIRCUIT CONDUCTORS SHALL BE MINIMUM #12 AWG THHN
<br />UNLESS NOTED OTHERWISE IN SCHEDULES. WHERE 20A
<br />BRANCH CIRCUITS HAVE #8 AND LARGER WIRE SPECIFIED, #10
<br />AWG WIRE SHALL BE USED FOR THE FINAL CONNECTION
<br />(15-FT MAXIMUM).
<br />9. WHERE BRANCH CIRCUITS ARE GROUPED, SIZE CONDUIT AND
<br />DERATE CURRENT CARRYING CONDUCTORS PER NEC.
<br />10. SUPPORTS FROM STRUCTURE: NO ATTACHMENT OF ANY TYPE
<br />SHALL BE MADE TO BRIDGING OR JOIST WEB MEMBERS.
<br />UTILIZE ONLY THE TOP AND BOTTOM CHORDS FOR
<br />SUPPORTING THE ELECTRICAL SYSTEM INSTALLATIONS.
<br />11. DEVICES SHOWN ON COOLER/FREEZER PANELS SHALL BE
<br />SURFACE MOUNTED UNLESS NOTED OTHERWISE. REFER TO
<br />ARCHITECTURAL DOCUMENTS FOR CONDUIT INSTALLATION AND
<br />SEALING REQUIREMENTS.
<br />12. ONLY FEEDER CIRCUITS NOTED ON THE ONE LINE DIAGRAM
<br />AND BRANCH CIRCUITS NOTED BY LEGEND SHALL BE
<br />INSTALLED UNDER SLAB. ALL OTHER FEEDER AND BRANCH
<br />CIRCUITS SHALL BE INSTALLED OVERHEAD. PROVIDE EXTERIOR
<br />COATED GRC BENDS ON ALL CONDUIT RUNS THAT HAVE 45
<br />DEGREE BENDS OR GREATER. REF SPECIFICATIONS.
<br />13. SEISMIC ZONE REQUIREMENTS: PROVIDE EXPANSION COUPLINGS
<br />AND BRACING FOR ELECTRICAL EQUIPMENT AS REQUIRED BY
<br />LOCAL CODES.
<br />14. EXISTING ELECTRICAL AND ALARM:
<br />A. WHERE DEMOLITION OR NEW CONSTRUCTION INTERRUPTS
<br />EXISTING ELECTRICAL CIRCUITS FEEDING EXISTING
<br />EQUIPMENT, DEVICES, OR LIGHTING TO REMAIN, BUT NOT
<br />SHOWN ON DRAWINGS, PROVIDE LABOR AND MATERIALS TO
<br />REWORK CIRCUITRY, AS REQUIRED, TO MAINTAIN EXISTING
<br />OPERATION.
<br />B. IF DEMOLITION OR NEW CONSTRUCTION WILL DISRUPT
<br />EXISTING UNDERGROUND SERVICES (ELECTRICAL,
<br />TELEPHONE, PARKING LOT LIGHTING CIRCUITRY, ETC.)
<br />PROVIDE ALL MATERIALS AND LABOR AS REQUIRED TO
<br />REROUTE, SLEEVE, OR OTHERWISE REWORK THESE SERVICES
<br />TO MAINTAIN THEIR EXISTING OPERATION.
<br />C. EXERCISE CAUTION AROUND ALARM AND SECURITY CABLES
<br />DURING DEMOLITION AND CONSTRUCTION. PROTECT ALARM
<br />AND SECURITY CABLES FROM ACCIDENTAL DAMAGE SO
<br />THAT SYSTEMS REMAIN OPERATIONAL AT ALL TIMES.
<br />D- DISPOSE OF ALL REMOVED MATERIALS, UNLESS OTHERWISE
<br />NOTED.
<br />15. EXISTING ELECTRICAL DEMOLITION:
<br />A. GENERAL: REMOVE OR RELOCATE EXISTING ELECTRICAL
<br />EQUIPMENT CONDUIT, AND CONDUCTORS AS INDICATED ON
<br />THE DRAWINGS, OR ONLY AS REQUIRED BY DEMOLITION.
<br />REMOVE ALL PANELBOARDS DISCONNECT SWITCHES BOXES
<br />W
<br />O
<br />w W,r,� J(Ct I-
<br />D 0 �WoF}
<br />2 � F UJw �wu o.
<br />n w z�-o0z n�
<br />Lu
<br />p F-O�FWowYZ LnF-
<br />0
<br />aF F w OpoQwwo
<br />�-o ��zoow
<br />U-
<br />uiw ro4�irawQW CO
<br />of �zza,, ma>_
<br />t��
<br />z
<br />�¢oQoul =->O �¢
<br />O
<br />QwJ Qw �fn <,U OEHO=p
<br />s-w DOzz xz� z
<br />Z
<br />MR' W : Qw U_OUQ
<br />zcan�
<br />p20,-,Z�Q,QO
<br />rnx0 c> W
<br />aW0ND Lu0
<br />a�U
<br />womvo
<br />W �2 F" Wa =goZwn
<br />5cwZ�OU—�OwaDr
<br />OQwWUW W�_
<br />t-��WrUov>aowL_jCCW¢��wr
<br />tiro
<br />M
<br />co zzo
<br />m
<br />V0W
<br />z
<br />L0
<br />w
<br />tM Q
<br />Z
<br />n 16
<br />� N
<br />Q
<br />� n
<br />J
<br />M � Q
<br />U)
<br />t N Ix
<br />z
<br />z
<br />�m;
<br />O
<br />moo
<br />U
<br />US w
<br />z
<br />w
<br />00
<br />2
<br />w
<br />C)z
<br />CD c:D
<br />0 0
<br />_I
<br />L
<br />_
<br />w
<br />L�
<br />w
<br />I,
<br />�
<br />0
<br />o
<br />O
<br />o
<br />w
<br />W
<br />rn
<br />M
<br />o
<br />!�2
<br />m
<br />�
<br />z
<br />Z
<br />W
<br />O
<br />~
<br />6 090
<br />^=
<br />I..L
<br />U)
<br />W
<br />N
<br />w
<br />m
<br />z
<br />m
<br />O
<br />ISSUE BLOCK
<br />CHECKED BY:
<br />SAG
<br />DRAWN BY:
<br />JOP
<br />FILE NAME:
<br />E1
<br />PROTO CYCLE:
<br />07/03/18
<br />DOCUMENT DATE:
<br />07/25/18
<br />RELAYS, TIME SWITCHES, LIGHTS, DEVICES, ETC., WHICH
<br />WILL NOT BE REUSED.
<br />B. SALES FLOOR: REMOVE UNUSED POWER DROP CONDUIT,
<br />CONDUCTORS AND RELATED DEVICES SERVING SALES AREA
<br />GONDOLAS BEING RELOCATED OR REMOVED. EXISTING
<br />CONDUIT AND CONDUCTORS MAY BE REUSED FOR NEW �� �/�
<br />POWER DROPS WHERE SIZE, RATING, AND CONDITION MEET g\� �1
<br />REQUIREMENTS INDICATED ON PLANS AND ALL U.L. \°`��®w,�
<br />RATINGS. REMOVE ALL UNUSED CONDUIT AND .
<br />CONDUCTORS BACK TO POINT OF ORIGIN WHENEVER 6, V
<br />FEASIBLE AND RELABEL DEMOLISHED CIRCUITS AS "SP, &.;B N 793319 t
<br />PROVIDE HANDLE DEVICE TO LOCK "SPARE" CIRCUIT = s
<br />B
<br />BREAKER IN THE "OFF" POSITION. v171 ST E 0 .°
<br />C. CONDUIT AND WIRING TO BE ABANDONED IN CEILING '�,°�.•'+�
<br />SPACES AND OTHER NON-PUBLIC AREAS (I.E., THROUGH �llj�' �"'` ��'w� AUG 0 3 2918
<br />�_
<br />STOCKROOM AREA): CUT WIRING LOOSE AND REMOVE ��//��� � ��\
<br />FROM RACEWAY(S), LEAVING RACEWAY(S) IN PLACE.
<br />CONDUIT TO BE ABANDONED IN WALLS OR FLOORS SHALL Randal C. Haase, P.E.
<br />BE REMOVED BACK TO FINISHED SURFACE AND CAPPED
<br />FL Li efiSe79#3i9
<br />INSIDE. REPAIR SURFACE(S) TO MATCH ADJACENT.
<br />D. ALL CIRCUIT BREAKERS SERVING BRANCH CIRCUITS TO BE
<br />ABANDONED OR REMOVED SHALL REMAIN IN RESPECTIVE
<br />PANELBOARD FOR FUTURE USE, UNLESS NOTED OTHERWISE
<br />ON DRAWINGS. PROVIDE HANDLE DEVICE TO LOCK "SPARE"
<br />CIRCUIT BREAKER IN THE "OFF" POSITION.
<br />E. DEMOLISHED FLUORESCENT LIGHT FIXTURES: REFER TO
<br />SELECTIVE SITE DEMOLITION SPECIFICATION FOR
<br />DISPOSAL OF LIGHT FIXTURE.
<br />F- BUILDING COMPONENTS ABANDONED BY THE SCOPE OF
<br />WORK SHALL BE SECURED TO PREVENT FALLING,
<br />LOOSENING, OR CREATING DAMAGE OF ANY KIND IN THE
<br />FUTURE.
<br />EXISTING CONDITIONS WERE TAKEN FROM
<br />ORIGINAL DRAWINGS AND MAY NOT REFLECT
<br />EXACT "AS -BUILT" CONDITIONS. CONTRACTOR
<br />SHALL FIELD VERIFY ALL EXISTING CONDITIONS
<br />PRIOR TO SUBMITTING FINAL BIDS. CONTRACTOR
<br />SHALL CAREFULLY COORDINATE NEW WORK AND
<br />DEMOLITION WITH ALL OTHER DISCIPINES AND
<br />EXISTING CONDITIONS.
<br />NOTE:
<br />RECEPTACLES, SWITCHES, DATA BOXES
<br />AND THEIR CORRESPONDING COVER
<br />PLATES SHALL BE WHITE NYLON.
<br />EACH SUBCONTRATOR IS RESPONSIBLE FOR HAVING A
<br />THOROUGH KNOWLEDGE OF ALL DRAWINGS AND
<br />SPECIFICATIONS IN THEIR RELATED FIELD. THE FAILURE
<br />TO ACQUAINT THEMSELF WITH THIS KNOWLEDGE DOES
<br />NOT RELIEVE THE RESPONSIBILITY OF PERFORMING
<br />THE WORK PROPERLY. NO ADDITIONAL
<br />COMPENSATION SHALL BE ALLOWED BECAUSE OF
<br />CONDITIONS THAT OCCUR DUE TO FAILURE TO
<br />FAMILIARIZE WORKERS WITH THIS KNOWLEDGE.
<br />ELECTRICAL
<br />PLANS
<br />SHEET:
<br />El