STRUCTURAL NOTES <br />STRUCTURAL DESIGN CRITERIA G-10 GENERAL CONTRACTOR SHALL COORDINATE THE STRUCTURAL RC-14 PROVIDE THE FOLLOWING CONCRETE COVERAGE'S OVER REINFORCING, M-16 CMU CELLS INDICATED IN PLAN OR NOTES AS FILLED CELLS SHALL BE COLD FORMED STEEL (METAL STUDS OR TRUSSES) DEFINITIONS OF ABBREVIATIONS <br />DRAWINGS WITH ALL OTHER DISCIPLINES. WHERE THERE ARE GROUTED SOLID WITH 3000 psi CONCRETE GROUT (8" TO 10" SLUMP). <br />D-1 CODES: FLORIDA BUILDING CODE 2020, 7TH EDITION CONFLICTS IN INFORMATION PRESENTED IN THE DRAWINGS OR IF THE B.O. FOOTINGS & UNFORMED EDGES- 3" CLR. MS-1 ALL STUDS AND/OR JOISTS AND ACCESSORIES SHALL BE OF THE <br />DRAWINGS ARE UNCLEAR OR INSUFFICIENT IN ANY MANNER THAT MAY BEAMS &COLUMNS (TIES)- 1 1/2' CUR. M-17 SUBMIT REBAR PLACING SHOP DRAWINGS FOR REVIEW, ALSO INCLUDE TYPE, SIZE, GAUGE AND SPACING AS SHOWN ON THE DRAWINGS OR A.B. ANCHOR BOLT MISC. MISCELLANEOUS <br />D 2 DESIGN LOADS: INHIBIT THE CONTRACTORS UNDERSTANDING OF THE PROJECT, SUCH SLABS (TOP & BOT.-STEEL) LOCATION OF MASONRY CONTROL JOINTS. TABLES. ABV. ABOVE MPH MILES PER HOUR <br />LIVE LOAD ROOF: 20 PSF. CONFLICTS SHALL BE BROUGHT TO THE ARCHITECT/ENGINEER'S INTERIOR- 3/4" CLR. ACI AMERICAN CONCRETE MTL METAL <br />ATTEN ITON PRIOR TO BIDDING AND THE NECESSARY ADJUSTMENTS EXTERIOR- 1 1/2" CLR. " M-18 REINFORCING STEEL SHALL BE NEW DEFORMED BARS THAT ARE FREE MS-2 ALL STRUCTURAL MEMBERS AND CONNECTIONS SHALL BE DESIGNED IN INSTITUTE NO. NUMBER <br />D- - 3 ULTIMATE DESIGN WIND SPEED V ult 137 MPH, 3-SEC. GUST SHALL BE MADE PER THEIR INSTRUCTIONS, CONC. WALLS- AS NOTED (1 1/2 CLR. MIN.) FROM RUST, SCALE AND OIL AND CONFORM TO ASTM A615, GRADE ACCORDANCE WITH THE AMERICAN IRON AND STEEL INSTITUTE ARCH. ARCHED OR ARCHITECT <br />NOMINAL DESIGN WIND SPEED V asd = 107 MPH, 3-SEC. GUST 60, WITH MINIMUM YIELD STRENGTH = 60,000psL WHERE WELDING SPECIFICATIONS FOR THE DESIGN OF COLD FORMED STRUCTURAL STEEL ASTM AMERICAN SOCIETY OF NS.&FS. NEAR SIDE AND FAR SIDE <br />RISK CATEGORY II G-11 ONLY WRITTEN .; HANGES APPROVED BY THE ARCHITECT AND ENGINEER RC-15 SHOP DRAWINGS FOR PLACEMENT SHALL BE SUBMITTED FOR REVIEW REQUIRED ASTM A706, GRADE 60 MEMBERS, LATEST EDITION. TESTING AND MATERIALS N.T.S. NOT TO SCALE <br />EXPOSURE C SHALL BE PERMITTED. PRIOR TO REBAR FABRICATION. Q.C. ON CENTER <br />ENCLOSED BLDG, INTERNAL PRESSURE COEFFICIENT M-19 A MINIMUM OF (3) FILLED CELLS SHALL BE LOCATED AT MS-3 ALL FRAMING MEMBERS SHALL BE FORMED FROM CORROSION BLW. BELOW OHGD OVERHEAD GARAGE <br />(GCpi)=+/-0,18 RC-16 SLEEVE ALL PENETRATIONS THROUGH BEAMS AND SLABS INDIVIDUALLY CONCENTRATED LOADS ON TYPICAL WALLS. RESISTANT STEEL, CORRESPONDING TO THE REQUIREMENTS OF ASTM BM BEAM DOOR <br />NET JOIST UPLIFT SHALLOW FOUNDATIONS CORE DRILLING WILL NOT BE PERMITTED. SUBMIT LOCATION AND SIZE A-446 WITH A MINIMUM YIELD STRENGTH OF 50 ksi FOR SJ AND CJ B.O. BOTTOM OF OPG. OPENING <br />40 PSF. ZONE 3 OF SLEEVES THROUGH BEAMS TO ENGINEER FOR REVIEW PRIOR TO M-20 PROVIDE (3) FILLED CELLS AT ALL CORNERS AND ENDS OF WALLS. STYLE STUDS AND 33 ksi FOR CR RUNNERS. (U.S.G. OR EQUIVALENT). BOT. BOTTOM OSB ORIENTED STRAND BOARD <br />34 PSF. ZONE 2 SF-1 PREPARATION OF SUBGRADE SHALL BE IN STRICT ACCORDANCE CASTING CONCRETE. BRG. BEARING <br />24 PSF. ZONE 1 WITH INSTRUCTIONS OUTLINED IN THE GEOTECHNICAL REPORT M-21 LAP ALL BOND BEAMS WHERE STEPPED 2'-0'. MS-4 FASTENING OF COMPONENTS SHALL BE WITH SELF DRILLING SCREWS C.J. CONTROL JOINT P.D.F. POWER DRIVEN FASTENERS <br />15 PSF. ZONE 1'' FROM UNIVERSAL ENGINEERING SERVICES, LIES PROJECT No. RC-17 NO REINFORCING BARS SHALL BE CUT TO ACCOMMODATE THE OF SUFFICIENT, NUMBER AND SPACING TO DEVELOP THE FULL DESIGN CLR. CLEAR <br />0830.190061, REPORT No. 1677966, DATED MAY 22, 2019. INSTALLATION OF ANCHORS, EMBEDS OR OTHER ITEMS. M-22 ALL DOWELS FROM THE FOUNDATION SHALL MATCH SIZE & LOCATION CAPACITY OF THE CONNECTED MEMBERS IN ACCORDANCE WITH THE CMU CONCRETE MASONRY UNIT P.E.M.T. PRE-ENGINEERED METAL <br />D-4 SEISMIC: ZONE 0 OF THE VERTICAL REINFORCING IN MASONRY, UNLESS NOTED MANUFACTURER'S RECOMMENDATIONS. WIRE TYING OF COMPONENTS TRUSSES <br />SF-2 SOIL BELOW NEW FOOTERS SHALL BE CLEAN COMPACTED SAND IN RC-18 USE THE STRUCTURAL DRAWINGS INCLUDING REVISIONS AND ADDENDA DIFFERENTLY. EXTEND DOWEL A MIN. OF 48 BAR DIAMETERS FROM THE SHALL NOT BE PERMITTED. COL. COLUMN P.E.W.T. PRE-ENGINEERED WOOD <br />D 5 ALLOWABLE SOIL BEARING PRESSURE 2500 PSF ACCORDANCE WITH FBC. 1818.2 AND THE RECOMMENDATIONS OF THE IN CONJUNCTION WITH REVIEWED SHOP DRAWINGS FOR PLACEMENT OF FOUNDATION. CONC. CONCRETE TRUSSES <br />PROJECT SPECIFICATIONS. REINFORCING. MS-5 PROVIDE HORIZONTAL STRAP BRIDGING 1j"x20 GAUGE AT 48" O.C., CONN. CONNECTION PL PLATE <br />D-6 WIND CODE - ASCE 7-16 M-23 EXPANSION BOLTS SHALL BE "HILTI KWIK BOLT TZ2" SUPPLEMENTED BY SOLID BRIDGING AT 8'-0" O.C. MINIMUM AND AS CONT. CONTINUOUS PSF POUNDS PER SQUARE <br />SF-3 CENTER ALL FOOTINGS UNDER THEIR RESPECTIVE COLUMNS OR WALLS RC-19 AT CHANGES IN DIRECTION OF CONCRETE WALLS, BEAMS & STRIP OR APPROVED EQUAL MINIMUM EMBEDMENT SHALL BE 4Y4" FOR X4" RECOMMENDED BY THE MANUFACTURER. CVR. COVER FOOT <br />D-7 COMPONENTS AND CLADDING WIND PRESSURES UNLESS OTHERWISE SHOWN ON PLANS. MAXIMUM MISPLACEMENT OR FOOTINGS, PROVIDE CORNER BARS OF SAME SIZE AND QUANTITY " " " DIA. DIAMETER <br />DIA. 4 FOR � DIA3X� .. AND FOR � DIA. INSTALLED IN PSI POUNDS PER SQUARE <br />FOR ASD PRESSURES MULTIPLY TABLE VALUES BY 0.6 ECCENTRICITY-2'. TOLERANCE FOR MISLOCATION OF COLUMN DOWELS U.O.N. AS HORIZONTAL STEEL REFER TO TYPICAL DETAIL MS-6 SUBMIT METAL STUD AND METAL TRUSS SHOP DRAWINGS & DTL DETAIL <br />( ) ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS. DO NOT CUT INCH <br />OR ANCHOR BOLTS TO BE PER ACI OR AISC STANDARDS. EXISTING REINFORCING TO INSTALL. CALCULATIONS SIGNED AND SEALED BY AN ENGINEERED REGISTERED IN DWG. DRAWING P.T. PRESSURE TREATED <br />c RC-20 ALL EMBEDDED ITEMS SHALL BE SECURELY TIED IN PLACE PRIOR TO THE STATE OF FLORIDA.(CONNECTIONS AND STUD GAGES SHOWN TO EA. EACH <br />SF-4 HORIZONTAL JOINTS IN FOOTINGS WLL NOT BE PERMITTED. CONCRETE PLACEMENT. M-24 ADHESIVE ANCHORS SHALL BE "HILTI HIT-HY 270" OR APPROVED BE VERIFIED BY SPECIALTY ENGINEER) E.J. EXPANSION JOINT QTY. QUANTITY <br />EQUAL. MINIMUM EMBEDMENT SHALL BE 6)(4" FOR -Y; DIA., 5' FOR %" EL. ELEVATION REINF. REINFORCEMENT <br />O3 33 SF-5 WHERE VERTICAL CONSTRUCTION JOINTS OCCUR IN CONTINUOUS RC-21 EXPANSION BOLTS SMALL BE "HILTI KWIK BOLT TZ2" DIA., 4Y" FOR 7 " DIA., Wr FOR %" DIA. INSTALLED IN ACCORDANCE EMBED EMBEDMENT REQ'D REQUIRED <br />O FOOTINGS. PROVIDE A MINIMUM CONTINUOUS 2' x 4" KEY WAY OR APPROVED EQUAL. MINIMUM EMBEDMENT SHALL BE 4-" FOR X4" WITH MANUFACTURER'S RECOMMENDATIONS. DO NOT CUT EXISTING FIELD VERIFY CONDITIONS ' EXP. EXPOSURE OR EXPANSION RMD ROOF METAL DECK <br />4'-0" E7 - - ACROSS JOINT FOR EACH 12" OF DEPTH. DIA., 4' FOR W DIA. AND 3W FOR )r DIA. INSTALLED IN REINFORCING TO INSTALL FV-1 CONTRACTOR SHALL VERIFY CONDITIONS AND DIMENSIONS RELATIVE TO FF FINISHED FLOOR <br />ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. . DO NOT CUT SPF SPRUCE PINE FIR <br />- - - SF-6 CONTRACTOR TO NOTIFY ARCHITECT IF SOIL CONDITIONS ARE EXISTING REINFORCING TO INSTALLM-25 THREADED ANCHORS SHALL BE ASTM A36 OR A307 QUALITY. ALL CMU THE SAME. WHERE THERE ARE CONFLICTS BETWEEN ACTUAL FIELD FFE. FINISHED FLOOR STL STEEL <br />f I UNCOVERED THAT PREVENT THE REQUIRED SOIL BEARING PRESSURE CELLS TO RECEIVE ANCHORS SHALL BE GROUTED SOLLD. NOTIFY CONDITIONS AND DATA PRESENTED IN THE DRAWINGS, SUCH ELEVATION STRUCT. STRUCTURAL <br />I I FROM BEING OBTAINED. RC-22 DOWEL BAR SPLICERS SHALL BE A COMPLETE ASSEMBLY, INCLUDING ENGINEER PRIOR TO SUBSITUTION OF ANY BOLTS INDICATED IN THE CONDITIONS SHALL BE CALLED TO THE ARCHITECT'S ATTENTION AND FG FINISHED GRADE 1 2 _ COUPLER, FROM ATTACHMENT (WSUBMIT. SUBSTITUTE <br />HEN REQUIRED) AND THREADED BAR DRAWINGS. THE NECESSARY ADJUSTMENTS SHALL BE MADE PER THEIR fm MASONRY COMPRESSIVE <br />OIO (DO SF 7 COORDINATE PLUMBING LINES WITH FOOTING LOCATIONS FOR SUP SOUTHERN YELLOW <br />CAPABLE OF DEVELOPING THE BAR BEING SPLICED IN ACCORDANCE INSTRUCTIONS. STRENGTH PINE <br />INTERFACE. INDIVIDUAL FOOTINGS SHOULD BE LOWERED WITH THE WITH ACI 318 SECTION 12.14.3. M-26 USE OF POWER ACTUATATED FASTNERS NOT ALLOWED IN MASONRY FND. FOUNDATION <br />12'-0" 12'-0' I PRIOR APPROVAL OF THE STRUCTURAL ENGINEER. CONTINUOUS WALL FV-2 GENERAL CONTRACTOR SHALL REVIEW AND APPROVE SHOP DRAWINGS FRM FRAMING T.O. TOP OF <br />TOP AND BOTTOM <br />T.O. <br />L - - J IF I FOOTINGS SHOULD BE STEPPED AS DETAILED ON DRAWINGS. RC-23 HEADED STUD ANCHORS SHALL BE ASTM A 108, GRADE S, 1010 M-27 ALL HORIZONTAL REINFORCING ABOVE AND BELOW OPENINGS IN BEFORE SUBMITTING THEM TO THE ENGINEER, OTHERWISE THEY WILL FTG. FOOTING <br />THROUGH 1020 AS MANUFACTURED BY NELSON STUD OR APPROVED CONCRETE BLOCK WALLS SHALL EXTEND 22' MINIMUM BEYOND EACH BE REJECTED. GA GAUGE TOF TOP OF FOOTING <br />• L - Q - SF-8 EXCAVATING UNDER OR NEAR IN -PLACE FOOTINGS/FOUNDATIONS EQUIVALENT. STUD WELDING SHALL CONFORM TO AWS DO JAMB. G.C. GENERAL CONTRACTOR TOS TOP OF SLAB <br />2 WHICH DISTURBS THE COMPACTED SOIL BENEATH THE "STRUCTURAL WELDING CODE." FV-3 IF THERE ARE ANY DISCREPANCIES THE STRICTER SHALL GOVERN. H.C.A. HEADED CONCRETE TS TUBE STEEL <br />OAL <br />FOOTINGS/FOUNDATIONS WILL NOT BE PERMITTED. " ANCHOR U 0 N UNLECSS 0TUI7DUISE <br />3 3O RC-24 ADHESIVE ANCHORS SHALL BE "HILTI HIT-HY 200 OR APPROVED <br />4• SF-9 REINFORCING SHALL BE SUPPORTED ON PRECAST CONCRETE PADS, EQUAL MINIMUM EMBEDMENT SHALL BE 6W FOR -' DIA,, 5" FOR 9" <br />�i DOWELS FOR COLUMNS AND FILLED CELLS SHALL BE SECURED IN DIA., 404" FOR V DIA., %* FOR V DIA. INSTALLED IN ACCORDANCE <br />IN PLACE PRIOR TO POURING CONCRETE. USE TEMPLATES FOR SETTING WITH MANUFACTURER'S RECOMMENDATIONS. DO NOT CUT EXISTING <br />COLUMN DOWELS AND ANCHOR BOLTS. REINFORCING TO INSTALL. <br />ROOF PRESSURES IN PSF SF-10 STEPS IN WALL FOOTING SHALL NOT EXCEED A SLOPE OF (1) RC-25 PLACE CONCRETE PER ACI 304. USE INTERNAL MECHANICAL <br />MULTIPLY BY 0.6 FOR ASID PRESSURES VERTICAL TO (2) HORIZONTAL. VIBRATION FOR ALL CONCRETE. LIMIT MAXIMUM FREE FALL DROP OF <br />INTERIOR <br />PERIMETER <br />CORNER <br />TRIBUTARY AREA <br />1 <br />2 <br />3 <br />area - 20 SF <br />....._. 388 <br />173 <br />57 <br />173 <br />....... -89 fl <br />173 <br />-121.3 <br />173 <br />2D SF < area <- 50 SF <br />-38 8 <br />16 6 <br />-63 0 <br />16 6 <br />-83._ .............. <br />16.6 <br />109 9 <br />16.8 <br />- <br />50 SF < area <- 100 SF <br />38.8 <br />57:2 <br />75.7 <br />94.7 <br />16.6 <br />16.6 <br />16.6 <br />16.6 <br />100 SF < area <br />38.8 <br />-52.7 <br />70 0 <br />-83.3 <br />16.6 <br />16_6x <br />16.6 <br />16.6 <br />8'-0' <br />WALL PRESSURES IN PSF <br />MIII _nPI Y RY nE`w FCW ARn PPFfi..gIIPFC <br />INTERIOR <br />END <br />TRIBUTARY AREA <br />area <= 20 SF <br />............_ `.1.:............._ <br />...............:.::............... <br />38.2 <br />382 <br />20 SF < area <= 50 SF <br />9 7 <br />47.6 <br />354 <br />384 <br />50 SF < area <= 100 SF <br />-37 4 .. <br />.. -43 1 <br />34.2 <br />34.2 <br />100 SF < area <br />...... -357 .................................... <br />-39 7 <br />32.4 <br />32 4 <br />GENERAL NOTES <br />G-1 REVIEW ALL PROJECT DOCUMENTS PRIOR TO FABRICATION AND START <br />OF CONSTRUCTION. REPORT ANY DISCREPANCIES TO ARCHITECT OR <br />STRUCTURAL ENGINEER PRIOR TO PROCEEDING WITH WORK. <br />G-2 THE MASONRY WALLS ARE NOT DESIGNED TO WITHSTAND TEMPORARY <br />CONSTRUCTION ROADS. IT IS THE CONTRACTORS RESPONSIBILITY AT <br />ALL TIMES TO MAINTAIN WALL STABILITY DURING THE CONSTRUCTION <br />PHASE OF THIS PROJECT. <br />G-3 IT IS THE CONTRACTORS RESPONSIBILITY TO PROTECT EXISTING <br />FACILITIES, STRUCTURES AND UTILITY LINES FROM ALL DAMAGE DURING <br />CONSTRUCTION. <br />G-4 NO STRUCTURAL MEMBER SHALL BE CUT, NOTCHED OR OTHERWISE <br />REDUCED IN SIZE OR STRENGTH WITHOUT PRIOR APPROVAL IN WRITING <br />FROM THE STRUCTURAL ENGINEER. <br />G-5 COORDINATE STRUCTURAL AND OTHER DRAWINGS THAT ARE PART OF <br />THE CONTRACT DOCUMENTS FOR ANCHORED, EMBEDDED OR <br />SUPPORTED ITEMS WHICH AFFECT THE STRUCTURAL DRAWINGS. <br />G-6 ALL DETAILS AND SECTIONS ON THE DRAWINGS ARE INTENDED TO BE <br />TYPICAL AND SHALL BE CONSTRUED TO APPLY TO ANY SIMILAR <br />SITUATION ELSEWHERE ON THE PROJECT EXCEPT WHERE A SEPARATE <br />DETAIL IS SHOWN. <br />G-7 IF SPECIFIC INFORMATION IS MISSING OR IF THERE ARE ANY <br />DISCREPANCIES BETWEEN THE STRUCTURAL DRAWINGS, :.RCHITECTURAL <br />DRAWINGS, STRUCTURAL DETAILS, STRUCTURAL NOTES, THE PROJECT <br />SPECIFICATIONS, OR APPLICABLE CODES THE CONTRACTOR SHALL USE <br />A SIMILAR DETAIL AND/OR THE MORE COSTLY ITEM OF CONFLICT. <br />THE CONFLICTS SHALL BE BROUGHT TO THE ATTENTION OF THE <br />ARCHITECT. <br />G-8 PHOTOGRAPHIC REPRODUCTIONS OF THE STRUCTURAL DRAWINGS FOR <br />SHOP DRAWINGS SHALL NOT BE PERMITTED. <br />G-9 REVIEW ALL SHOP DRAWINGS FOR CONFORMANCE WITH THE CONTRACT <br />DOCUMENTS AND FOR COMPLETENESS AND ANSWER ALL CONTRACTOR <br />RELATED QUESTIONS. STAMP AND INITIAL ALL SHEETS PRIOR TO <br />SUBMITTING SHOP DRAWINGS TO ARCHITECT FOR REVIEW. <br />NONCOMPLIANCE WITH THIS REQUIREMENT WILL RESULT IN REJECTION <br />OF SUBMITTAL. <br />CONCRETE TO 6'-0" FOR #57 AGGREGATE AND 8'-0' FOR #8 <br />SF-11 CAUTION SHALL BE USED WHEN OPERATING VIBRATORY COMPACTION AGGREGATE. ALL PRECAUTIONS SHOULD BE TAKEN TO AVOID <br />EQUIPMENT NEAR EXISTING STRUCTURES TO AVOID THE RISK OF <br />Q SEGREGATION OF CONCRETE DURING PLACEMENT. <br />DAMAGING THE EXISTING STRUCTURE. <br />RC-26 PLACEMENT OF CONDUIT AND PIPES IN CONCRETE SHALL CONFORM TO <br />SF-12 ALL BACKFILL COMPACTION WORK ADJACENT TO RETAINING WALLS, ACI 318, SECTION 6.3. <br />FOUNDATION WALLS ETC. SHALL USE LIGHT DUTY HAND OPERATED <br />TAMPERS WITHIN 3'-O" DISTANCE FROM THE WALL RC-27 SLABS AND GRADE BEAMS SHALL NOT HAVE JOINTS IN A HORIZONTAL <br />PLANE. ALL REINFORCEMENT SHALL BE CONTINUOUS THROUGH ALL <br />SF-13 AT EXTERIOR CMU FOUNDATION WALLS, WHEN THE HEIGHT BETWEEN CONSTRUCTION JOINTS. <br />1 • <br />STRUCTURAL STEEL <br />S-1 FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM <br />TO THE AISC "STEEL CONSTRUCTION MANUAL", 15TH EDITION AND THE <br />AISC 360-1.6 "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS' <br />S-2 STEEL DESIGNATIONS: <br />WIDE FLANGES - ASTM A992 Fy=50k.s.i <br />ALL OTHER HOT -ROLLED SHAPES AND PLATES - ASTM A36 <br />Fy=36k.s. i <br />PIPE COLUMNS - ASTM A53, GRADE B Fy=35k.s.i <br />STRUCTURAL TUBING - ASTM 1085, Fy=50k.s.i <br />S-3 ALL HIGH -STRENGTH BOLTS SHALL MEET THE REQUIREMENTS OF THE <br />"SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 <br />BOLTS." <br />S-4 UNLESS NOTED OTHERWISE, ALL BOLTS SHALL BE 3/4" DIAMETER <br />HORIZ. HORIZONTAL ... NnTGn <br />SPECIALITY ENGINEERING REQUIREMENTS: <br />SE-1 ALL GUARDRAILS, HANDRAILS OR MISC. STEEL, FOR EXAMPLE SHIPS <br />LADDER SHALL BE DESIGNED BY THE FABRICATORS SPECIALITY <br />ENGINEER. THIS INCLUDES MISCELLANEOUS SUPPORTS AND <br />CONNECTIONS. SHOP DRAWINGS SHALL BE SUBMITTED FOR REVIEW AND <br />MUST BE SIGNED AND SEALED BY A STRUCTURAL ENGINEER. <br />SE-2 ALL LIGHT GAUGE FRAMING SHALL BE DESIGNED BY A SPECIALITY <br />ENGINEER AND SHALL INCLUDE FRAME, COVERING, AND CONNECTIONS. <br />SHOP DRAWINGS SHALL BE , SUBMITTED FOR REVIEW AND MUST BE <br />SIGNED AND SEALED BY A STRUCTURAL ENGINEER REGISTERED IN THE <br />SAME STATE AS THE PROJECT LOCATION. <br />SE-3 ALUMINUM CANOPIES SHALL BE DESIGNED BY THE FABRICATORS <br />SPECIALITY ENGINEER AND SHALL INCLUDE FOUNDATIONS, COLUMNS, <br />FRAMES, DECKING AND CONNECTIONS. SHOP DRAWINGS SHALL BE <br />SUBMITTED FOR REVIEW AND MUST BE SIGNED AND SEALED BY A <br />TOP OF SLAB AND FINISH GRADE IS GREATER THAN 3 -0 FOR A A-325 AND SHALL BE BEARING TYPE CONNECIIONS. IF A CERTAIN <br />LENGTH OF 6'-0" OR MORE, CONTRACTOR SHALL PROVIDE TEMPORARY RC-28 PROVIDE (2) #5 BARS WITH 2'-0' PROJECTION ON ALL SIDES OF ALL SITUATION IS NOT DETAILED USE A SIMIALAR DETAIL CONNECTIONS STRUCTURAL ENGINEER REGISTERED IN THE SAME STATE AS THE <br />RRAC[NA OF WA[ I unlTil 14 nAYS MINIMUM AFTFR RI AR 14 INRTAI I Fn- OPENINGS OR RE-ENTRANT CORNERS IN CONCRETE SHALL GENERALLY FOLLOW THE TYPES SHOWN IN AISC MANUAL OF PROJECT LOCATION. DESIGN LOADING(S) SHALL CONFORM TO ALL <br />REINFORCED CONCRETE <br />RC-1 ALL CONCRETE DESIGN PLACEMENT SHALL BE IN STRICT ACCORDANCE <br />WITH THE ACI "BUILDING CODE REQUIREMENTS FOR STRUCTURAL <br />CONCRETE," ACI 318-14. <br />RC-2 STRUCTURAL CONCRETE SHALL CONFORM TO ACI 301 SPECIFICATIONS. <br />ALL CONCRETE TYPE I PORTLAND CEMENT. (ASTM C 150) 3000 psi. <br />TYP COMPRESSIVE STRENGTH AT 28 DAYS (U.O.N.). 4000 psi. FOR <br />TILT -UP WALLS <br />SLUMP: <br />FOOTINGS 4" <br />COLUMNS 4' +/- 1" <br />SLABS 4' +/- 1" <br />TIE BMS & TIE COL'S 4' +/- 1" <br />WATER: POTABLE <br />CHLORIDE: NONE <br />RC-3 PROVIDE NORMAL WEIGHT AGGREGATES IN COMPLIANCE WITH THE <br />REQUIREMENTS OF ASTM C33. <br />RC-4 FLYASH WHEN USED, SHALL BE LIMITED TO 20% OF THE CEMENTITIOUS <br />MATERIAL. <br />RC-5 ALL PUMPED CONCRETE WITH #57 AGGREGATE IS TO CONTAIN A HIGH <br />RANGE WATER REDUCING AGENT. MINIMUM SIZE OF DISCHARGE TO BE <br />4" I.D. <br />RC-6 A 2" I.D. DISCHARGE MAY BE USED WITH #8 AGGREGATE. USE <br />PLASTICIZER ADMIXTURE IF NECESSARY TO INCREASE SLUMPS BEYOND <br />THAT NOTED ABOVE. <br />RC-7 CHAMFER ALL EDGES OF EXPOSED CONCRETE X4" UNLESS NOTED <br />OTHERWISE. <br />RC-5 ALL REINFORCING STEEL SHALL BE DETAILED, FABRICATED AND <br />INSTALLED IN ACCORDANCE WITH ACI 318-14 AND ACI DETAILING <br />MANUAL, ACI 315. <br />RC-9 REINFORCING STEEL SHALL BE NEW DEFORMED BARS THAT ARE FREE <br />FROM RUST, SCALE AND OIL AND CONFORM TO ASTM A615, GRADE <br />60, WITH MINIMUM YIELD STRENGTH = 60,000psi. WHERE WELDING <br />REQUIRED ASTM A706, GRADE 60 <br />RC-1U ALL SLABS ON GRADE SHALL BE REINFORCED WITH WELDED WIRE <br />FABRIC AS SHOWN IN THE DRAWINGS. <br />RC-11 WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185. <br />RC-12 LAP CONT. BOTTOM STEEL OVER SUPPORT AND CONT. TOP STEEL AT <br />MID SPAN UNLESS OTHERWISE SPECIFIED. MIN. LENGTH OF LAPPED <br />SPLICES SHALL BE AS FOLLOWS UNLESS NOTED. STAGGER SPLICES SO <br />THAT NO TWO ADJACENT BARS ARE SPLICED IN THE SAME LOCATION <br />UNLESS SHOWN OTHERWISE. WELDED WIRE FABRIC SHALL BE LAPPED <br />ONE FULL MESH AT THE SIDES AND ONE FULL MESH PLUS 2" AT THE <br />ENDS. MAKE ALL BARS CONTINUOUS AROUND CORNERS OF PROVIDE <br />CORNER BARS OF EQUAL SIZE AND SPACING. <br />BAR SIZE: SPLICE SIZE: <br />#3 16" <br />#4 22" <br />#5 27" <br />#6 35" <br />RC-13 TERMINATE ALL DISCONTINUOUS TOP BARS WITH STANDARD 90 DEGREE <br />HOOK (PLACED VERTICALLY) UNLESS NOTED OTHERWISE. <br />AM SONRY <br />M-1 <br />M-2 <br />M-3 <br />M-4 <br />M-5 <br />M-6 <br />M-7 <br />M-8 <br />M-9 <br />M-10 <br />ME <br />M-12 <br />M-13 <br />M-14 <br />M-15 <br />MASONRY CONSTRUCTION SHALL CONFORM "BUILDING CODE <br />REQUIREMENTS AND SPECIFICATIONS FOR MASONRY STRUCTURES" (TM'S <br />402/602-16) EXCEPT AS AMENDED BELOW. <br />CONTRACTOR SHALL OBTAIN COPY OF MASONRY CODE AND <br />SPECIFICATIONS FOR REFERENCE AT THE JOBSITE. <br />STRUCTURE HAS BEEN DESIGNED AS A BEARING WALL STRUCTURE. <br />ALL MASONRY UNITS SHALL BE LAID PRIOR TO CONCRETE PLACEMENT <br />OF COLUMNS, BEAMS AND SLABS FOR THE SAME STORY. <br />USE TYPE "S' MORTAR WITH MINIMUM COMPRESSIVE STRENGTH OF <br />1800psi. IN ACCORDANCE WITH ASTM C270 <br />MASONRY UNITS SHALL CONFORM TO ASTM C90, GRADE N WITH A <br />MINIMUM COMPRESSIVE STRENGTH OF 1900psi ON NET SECTION TO <br />PROVIDE NET AREA COMPRESSIVE STRENGTH OF MASONRY (F'm) OF <br />1500psi., LAID IN RUNNING BOND. <br />PROVIDE FILLED CELLS AS SHOWN ON PLANS. IN ADDITION, PROVIDE <br />FILLED CELLS W/ (1) #6 MIN. VERTICAL ADJACENT TO ALL OPENINGS, <br />AND AT ANCHORAGE OF CONNECTIONS. <br />PROVIDE FULL MORTAR BEDDING AROUND ALL FILLED CELLS WITH <br />VERTICAL REINFORCING. <br />REINFORCING FOR FILLED CELLS SHALL CONFORM TO ASTM A615, <br />GRADE 60. PROVIDE THE FOLLOWING LAP SPLICES FOR REINFORCING. <br />BAR SIZE: SPLICE SIZE: <br />#4 24" <br />#5 30" <br />#6 36" <br />ALL FILLED CELLS AND COLUMNS SHALL BE POURED AT LEAST TWO <br />(2) HOURS PRIOR TO POURING BEAMS AND LINTELS. <br />REINFORCING WALL WITH LADDER TYPE REINFORCEMENT <br />('DUR-O-WALL" OR EQUAL) IN BED JOINTS AT 16' O.C. FOR RUNNING <br />BOND MEASURED VERTICALLY. LAP SPLICE ALL HORIZONTAL WALL <br />REINFORCING 6', PROVIDE PREFABRICATED "TEE" OR CORNER SECTIONS <br />AT ALL INTERSECTING WALLS. <br />UTILIZE LOW LIFT GROUTING TECHNIQUE FOR CONSTRUCTION OF ALL <br />MASONRY WALLS. PROVIDE CLEAN -OUT HOLES AT BASE OF FILLED <br />CELLS WHEN THE CONCRETE POUR EXCEEDS 5 FEET IN HEIGHT. <br />CONCRETE FOR FILLED CELLS SHALL BE VIBRATED DURING PLACEMENT <br />USING A "PENCIL" TYPE VIBRATOR. <br />THE TYPICAL LINTELS OVER OPENINGS IN THE WALL SHALL HAVE (2) <br />#5 BARS FOR 2 COURSES ABOVE OPENING FILLED SOLID UNLESS <br />NOTED OTHERWISE PROVIDE THE FOLLOWING LINTELS OVER ALL <br />MASONRY WALL OPENINGS. <br />-PROVIDE MINIMUM END BEARING OF 8". CUT OUT BOTTOM OF <br />LINTEL AT END TO ALLOW CONTINUATION OF FILLED CELL <br />REINFORCING. <br />PROVIDE (1) 15 CONTINUOUS HORIZONTAL IN KNOCK -OUT BLOCK <br />BELOW ALL WINDOW SILLS, UNLESS NOTED OTHERWISE. <br />PROVIDE VERTICAL REINFORCEMENT IN 3000psi GROUT FILLED CMU' <br />CELL FROM FOOTING TO BEAM AT TOP OF WALL AS FOLLOWS: <br />(1) #6 VERTICAL AT 2'-0" O.C. <br />2 #5 HORIZONTAL BAR AT 8'-0' O.C. <br />HORIZONTAL JOINT REINFORCEMENT 16" O.C. <br />STEEL CONSTRUCTION. <br />S-5 USE MIN. 3/4' A-325F BOLTS WITH CLASS A CONTACT SURFACE FOR <br />SUP CRITICAL CONNECTIONS AS DESIGNATED ON PLANS BY A-325 <br />S.C. <br />S-6 ALL BOLTS CAST IN CONCRETE SHALL BE ASTM F1554 - <br />GRADE 36 <br />S-7 ALL SHOP AND FIELD WELDING SHALL BE DONE BY CURRENTLY <br />CERTIFIED WELDERS IN ACCORDANCE WITH AWS D1.1-04 "STRUCTURAL <br />WELDING CODE -STEEL' AND PROOF OF WELDER CERTIFCATION SHALL <br />BE AVAILABLE AT THE JOB SITE DURING TIMES OF INSPECTION. <br />S-8 ALL WELDS ARE TO CONFORM TO RISC STANDARDS AND LOAD <br />TABLES. USE E70XX ELECTRODES FOR ALL WELDING UNLESS NOTED <br />OTHERWISE GRIND SMOOTH ALL EXPOSED WELDS, <br />S-9 SUBMIT STRUCTURAL STEEL SHOP DRAWINGS FOR REVIEW PRIOR TO <br />FABRICATION. CLEARLY SHOW ALL PIECE MARKS, CONNECTIONS AND <br />ERECTION DRAWINGS. ANY SPLICES NOT SHOWN ON CONTRACT <br />DRAWINGS ARE TO BE CLEARLY NOTED FOR APPROVAL. <br />S-10 DO NOT WELD TO EMBEDS UNTIL CONCRETE HAS CURED AT LEAST 72 <br />HOURS. USE APPROPRIATE WELDING PROCESSES TO LIMIT HEAT <br />BUILDUP IN EMBED TO AVOID PLATE EXPANSION AND CRACKING OF <br />CONCRETE <br />S-11 WELDED CONNECTIONS SHALL DEVELOP THE FULL SHEAR AND/OR <br />MOMENT CAPACITY OF THE MEMBERS CONNECTED. AS PER AISC <br />S-12 ALL BOLTED STEEL CONNECTIONS ARE TO BE STANDARD AISC BOLTED <br />CONNECTIONS AS PER THE AISC MANUAL AND SHALL BE CAPABLE OF <br />SUPPORTING MAXIMUM ALLOWABLE UNIFORM BEAM LOADS, AS <br />DETERMINED FROM THE TABLES OF UNIFROM LOAD CONSTANTS OF THE <br />AISC MANUAL ALL BOLTS SHALL BE STRENGTH ASTM A325. <br />ROOF METAL DECK <br />RD-1 PROVIDE WIDE RIB PAINTED, METAL DECK WITH THE FOLLOWING MINIMUM <br />PROPERTIES: <br />1 1/2" MIN. DEPTH <br />22 GAUGE <br />Ip MIN. = 0.155 INr In MIN. = 0.183 IN 4 �FT <br />Sp MIN. = 0.186 IN /FT Sn MIN. = 0.193 IN /FT <br />Fy 33 ksi <br />RD-2 PROVIDE A 36/5 WELDING PATTERN WITH W DIA. PUDDLE WELDS AND <br />(5) SIDELAP FASTENERS (#10 TEK SCREWS) PER SPAN. PROVIDE <br />PUDDLE WELDS AT 6' O.C. ALONG EDGES. <br />RD-3 METAL DECK SHALL BE CONTINUOUS FOR A MINIMUM OF THREE <br />SPANS. <br />RD-4 ALL ROOF OPENINGS GREATER THAN 12"X12" SHALL BE FRAMED WITH <br />STEEL ANGLES COORDINATE WITH ROOF PLAN SEE DETAIL: <br />REQUIREMENTS OF THE BUILDING CODE (SEE GENERAL NOTES FOR <br />APPLICABLE BUILDING CODE). <br />H.S. HEADED STUD <br />IN <br />INCH(ES) <br />INT. <br />INTERIOR <br />VERT. <br />VERTICAL <br />J.B. <br />JOIST BEARING <br />W/ <br />W/C <br />NTH <br />WATER CEMENT <br />J.G. <br />JOIST GIRDER <br />yyyyF <br />WELDED WIRE FABRIC <br />JST. <br />JOIST <br />JT. <br />JOINT <br />L <br />ANGLE <br />MAX. <br />MAXIMUM <br />M/C <br />MOISTURE CONTENT <br />M.C.J. <br />MASONRY CONTROL JOINT <br />MFR. <br />MANUFACTURER <br />MIN. <br />MINIMUM <br />SPECIAL INSPECTION <br />SI-1 THE CONTRACTOR OR OWNER SHALL EMPLOY A QUALIFIED <br />INDEPENDENT INSPECTION AGENCY. THIS AGENCY (REFERRED TO AS <br />INSPECTOR HEREIN) SHALL BE RESPONSIBLE FOR VERIFYING THAT <br />PROJECT STRUCTURAL WORK IS ACCOMPLISHED IN CONFORMANCE WITH <br />THE CONTRACT DOCUMENTS. <br />SI-2 DURATION AND FREQUENCY OF JOB VISITS SHALL BE SUFFICIENT FOR <br />THE INSPECTOR TO STATE AT THE COMPLETION OF THE PROJECT <br />THAT THE STRUCTURAL WORK IS ACCOMPLISHED, AND ITS RELATED <br />ELEMENTS HAVE BEEN ERECTED IN ACCORDANCE WITH THE CONTRACT <br />DOCUMENTS. SPECIFIC SYSTEMS TO BE INSPECTED INCLUDE: <br />CONCRETE (FOUNDATION, COLUMNS & BEAMS) <br />CONCRETE (SLAB ON GRADE) <br />MASONRY <br />STRUCTURAL STEEL' (INCLUDING BAR JOISTS AND JOIST GIRDERS) <br />METAL DECK <br />LIGHT GAUGE FRAMING <br />SI-3 THE FOREGOING LIST IS NOT INTENDED TO BE ALL INCLUSIVE. THE <br />INSPECTOR SHALL USE HIS PROFESSIONAL JUDGMENT AND HIS <br />KNOWLEDGE OF THE JOB SITE CONDITIONS AND THE CONTRACTORS' <br />PERFORMANCE TO DECIDE WHICH ADDITIONAL STRUCTURAL SYSTEM OR <br />ITEMS MAY REQUIRE ATTENTION. <br />SI-4 THE INSPECTOR DOES NOT RELIEVE THE CONTRACTOR'S CONTRACTUAL <br />OR STATUTORY OBLIGATIONS. THE CONTRACTOR HAS THE SOLE <br />RESPONSIBILITY FOR ANY DEVIATIONS FROM THE OFFICIAL CONTRACT <br />DOCUMENTS. THE INSPECTOR WILL NOT REPLACE THE QUALITY <br />CONTROL PERSONNEL OF THE CONTRACTOR. <br />SI-5 ALL INSPECTION REPORTS SHALL BE FORWARD BY THE INSPECTOR TO <br />THE ENGINEER AND ARCHITECT OF RECORD. <br />SUBMITTALS <br />SB-1 CONCRETE MIX DESIGNS <br />SB-2 REBAR PLACEMENT SHOP DRAWINGS WITH FOUNDATIONS, BEAMS AND <br />WALLS <br />SB-3 SHOP DRAWINGS FOR STEEL STRUCTURE (STEEL JOIST, BEAMS, ETC.) <br />SB-4 CALCULATIONS AND SHOP DRAWINGS FOR ALL EXTERIOR LIGHT GAUGE <br />FRAMING <br />SB-5 CALCULATIONS AND SHOP DRAWINGS FOR ALUMINUM CANOPIES <br />iff ��=7 <br />BOWEN ENGINEERING <br />CORPORATION <br />1528 VASSAR STREET <br />ORLANDO, FL 32804 <br />EB 5026 <br />BEC PROJECT No. 2022.050 <br />W a <br />Associates, Inc. AA26001933 <br />Architecture • Planning Interior Design <br />1.4125 N' W. 30th Ave. Suite 303 <br />Miami Lakes, Fl. 33016 <br />T. 786-235-9097 <br />F. 305-362-4420 <br />dtiinfo@dtiarchitect.com <br />www.dtiarchitect.coni <br />H, MA rT�f'. <br />�� �'••� G E N S'•.yF ��i <br />No.54831 <br />*: Z* <br />S : <br />LU <br />000• STATE OF 0 ki ft <br />,,�I�►W *% O R -.�• �• , i a <br />I <br />Revisions: -1 I <br />U <br />Z <br />0� �M <br />�00 <br />(� Q Z o <br />00C 30LL <br />UQ �acn <br />>M <br />W <br />LIB N <br />0 <br />a <br />Job Number: <br />22008.01 <br />File name: <br />Issued Date: <br />07-25-22 <br />Drawn by: <br />G K <br />Checked by: <br />WM <br />11 SHEET NAME 1 <br />STRUCTURAL <br />NOTES <br />SHEET NUMBER <br />s-o.01 <br />