Laserfiche WebLink
GENERAL ELECTRICAL NOTES <br />1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (N.E.C. 2014), <br />FLORIDA BUILDING CODE 2017 AND GOVERNING MUNICIPAL, STATE AND LOCAL CODES. ALL MATERIAL <br />SHALL BE NEW AND SHALL BEAR THE U.L. LABEL WHERE APPLICABLE. <br />2. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS <br />WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY THE <br />OWNER. <br />3. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE <br />CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM <br />AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING <br />ORDER. <br />4. CONTRACTOR SHALL MAKE ALL NECESSARY CUTTING AND DO ALL THE REPATCHING AS NECESSARY FOR <br />THE PROPER EXECUTION OF THIS WORK. <br />5. AFTER COMPLETION OF THE INSTALLATION, THE SYSTEM SHALL TEST FREE FROM SHORT CIRCUITS AND <br />GROUNDS. <br />6. WHERE ELECTRICAL CONDUCTORS ARE INSTALLED IN CONDUIT, THE CONDUIT SHALL COMPLY WITH THE <br />N.E.C. REQUIREMENTS. <br />7. ALL CONDUCTORS SHALL BE COPPER. NO CONDUCTOR SHALL BE SMALLER THAN #12 AWG AND SHALL <br />BE RATED FOR 600VOLTS THWN OR THHN INSULATION. INSTALL A GROUNDING CONDUCTOR WITH ALL <br />CIRCUITS, UNLESS NOTED OTHERWISE, SIZED PER N.E.C. 250-122. <br />8. VERIFY BREAKER AND CORRESPONDING WIRE SIZES FOR ALL ELECTRICAL EQUIPMENT.. DO NOT ORDER <br />MATERIAL BEFORE VERIFYING BREAKER & WIRE SIZE. REPORT ANY DISCREPANCY IMMEDIATELY TO THE <br />ENGINEER OF RECORD. <br />9. ALL OUTDOOR DISCONNECTS AND ELECTRICAL PANELS TO BE NEMA-3R. ALL OUTDOOR DISCONNECTS <br />AND ELECTRICAL PANELS IN A SALT SPRAY AREA TO BE NEMA-0. <br />10. PANELS SHALL BE SQUARE 'D', GENERAL ELECTRIC OR EQUAL, TYPE AND NUMBER OF BREAKERS AS <br />INDICATED ON PANEL SCHEDULE. STENCIL PANEL DESIGNATION ON INSIDE OF PANEL. ALL TWO -POLE <br />BREAKERS SHALL BE COMMON TRIP. PROVIDE TYPE WRITTEN SCHEDULE IN EACH LOAD CENTERS. <br />CONNECTION TO MAIN BUS SHALL BE WITH BURNDY ANNULAR COMPRESSION LUGS. PANELS AIC RATING <br />SHALL BE AS INDICATED ON PLANS. <br />11. PROVIDE NAMEPLATES FOR ALL PANEL BOARDS, DISCONNECTS, TRANSFORMER, TERMINAL CABINETS AND <br />ALL ELECTRICAL EQUIPMENT IDENTIFIED BY NAME ON DRAWINGS. <br />12. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN <br />APPROVED THIRD PARTY TESTING AGENCY. <br />13. LOAD DATA IS BASED ON INFORMATION GIVEN ENGINEER AT TIME OF DESIGN. VERIFY ALL EQUIPMENT <br />AND PANEL SIZES BEFORE ORDERING AND BEFORE INSTALLATION. <br />14. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE ANCHORED TO COMPLY WITH LOCAL CODE FOR WIND <br />RESISTANCE. <br />15. ALL ELECTRICAL AND COMMUNICATIONS OUTLETS TO BE AT 15" A.F.F TO BOTTOM OF OUTLET UNLESS <br />OTHERWISE NOTED, ALL LIGHT SWITCHES SHALL BE ® 48" AFF. TO TOP OF SWITCH. <br />16. TIME CLOCK FOR LIGHTING CONTROL TO BE AN ASTRONOMICAL TIME CLOCK. <br />17. THE CONTRACTOR SHALL CONTACT THE LOCAL POWER COMPANY AND OBTAIN, IN WRITING, THE AVAILABLE <br />FAULT CURRENT OF THE UTILITY TRANSFORMER. THE CONTRACTOR SHALL ENSURE THAT ALL ELECTRICAL <br />EQUIPMENT HAS AN AMP INTERRUPTING CAPACITY (AIC) GREATER THAN THE AVAILABLE FAULT CURRENT <br />AT ANY POINT IN THE ELECTRICAL DISTRIBUTION SYSTEM. <br />18. WIRING METHOD: <br />ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT) OR MC CABLE & <br />FLEXIBLE METAL CONDUIT (GREENFIELD) AS PER NEC 330-10, PROVIDED IT IS USED IN NON <br />DESTRUCTIVE OR CORROSIVE SURROUNDINGS AS SPECIFIED IN NEC 2014 330-12. ALL FITTINGS AND <br />COUPLINGS FOR EMT CONDUIT SHALL BE ALL STEEL RAIN TIGHT COMPRESSION TYPE OR ALL STEEL <br />CONCRETE TIGHT SET SCREW TYPE. SCHEDULE 40 PVC CONDUIT, WITH FITTINGS AND COUPLINGS <br />APPROPRIATE FOR THE USE, SHALL BE USED UNDERGROUND OR BELOW SLABS ON GRADE. <br />19. BRANCH -CIRCUIT WIRING, OTHER THAN 2-WIRE OR MULTIWIRE BRANCH CIRCUITS SUPPLYING POWER TO <br />LUMINAIRES CONNECTED TOGETHER, SHALL NOT BE PASSED THROUGH AN OUTLET BOX THAT IS AN <br />INTEGRAL PART OF A LUMINAIRE UNLESS THE LUMINAIRE IS IDENTIFIED FOR THROUGH -WIRING. <br />LUMINAIRES SHALL NOT BE USED AS A RACEWAY FOR CIRCUIT CONDUCTORS UNLESS LISTED AND <br />MARKED FOR USE AS A RACEWAY. PROVIDE J-BOXES AS REQUIRED. <br />20. SEAL ALL NEW CONDUIT PENETRATIONS THROUGH FIRE RATED WALLS, CEILINGS, FLOORS, ETC., TO <br />MAINTAIN EXISTING FIRE RATING CONDITIONS. FURNISH AND INSTALL FIRE RATED ENCLOSURES FOR ALL <br />EQUIPMENTS PENETRATING FIRE RATED ENVELOPES, SPACES, ECT. <br />21, ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE WIRING FOR HVAC SYSTEM: A/C EQUIPMENT(S), <br />SMOKE DETECTORS, THERMOSTATS, TEST STATIONS, MOTORIZED VOLUME DAMPERS, ETC. ELECTRICAL <br />CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AND PROVIDE ALL NECESSARY CONTROL <br />WIRING. ELECTRICAL CONTRACTOR TO THOROUGHLY REVIEW MECHANICAL PLANS AND PROVIDE POWER TO <br />ANY MECHANICAL EQUIPMENT OR DEVICE THAT IS NOT SHOWN ON ELECTRICAL PLANS BUT IS SHOWN ON <br />MECHANICAL PLANS. <br />22. INSTALL "GFCI" GROUND FAULT INTERRUPTER RECEPTACLES WITH WEATHERPROOF COVER WITHIN 25 FT <br />OF HVAC EQUIPMENT, MOUNT RECEPTACLE ON UNISTRUT (UNLESS HVAC EQUIPMENT IS SPECIFIED WITH <br />FACTORY INSTALLED CONVENIENT RECEPTACLE) . <br />23. WHEN NEW ELECTRIC SERVICE IS BEING INSTALLED, IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY <br />TO COORDINATE WITH FPL/FPL ENGINEERS ON THE SIZE OF THE FPL TRANSFORMER THAT IS REQUIRED <br />TO PROVIDE THE NEW ELECTRIC SERVICE SHOWN ON ELECTRIC PLANS, GC HAS TO INFORM THE OWNER <br />ABOUT ANY EXTRA FPL CHARGES THAT MIGHT OCCUR IN ORDER TO PULL NEW SERVICE. THIS HAS TO <br />BE DONE AS EARLY AS POSSIBLE DURING THE BIDDING PROCESS. <br />24. ELECTRICAL SERVICE EQUIPMENT MUST BE 3' ABOVE MSL, AND 8' ABOVE N.V.G.D. VERIFY AT SITE. ALL <br />ELECTRICAL EQUIPMENTS SHALL BE INSTALLED ABOVE FLOOD LEVEL. <br />25. CONTRACTOR MUST VISIT THE SITE PRIOR TO BID OR CONSTRUCTION TO VERIFY ALL EXISTING <br />CONDITIONS. BEFORE SUBMITTING BID, BECOME THOROUGHLY FAMILIAR WITH ACTUAL EXISTING CONDITIONS <br />AT THE BUILDING SITE. THE INTENT OF THE WORK IS SHOWN ON THE DRAWINGS AND DESCRIBED <br />HEREINAFTER. BY THE ACT OF SUBMITTING A BID PROPOSAL FOR WORK, THE CONTRACTOR SHALL BE <br />DEEMED TO HAVE MADE SUCH STUDY AND EXAMINATION AND TO ACCEPT ALL CONDITIONS PRESENT AT <br />THE SITE. NO REQUEST FOR ADDITIONAL PAYMENT SHALL BE CONSIDERED AS VALID, DUE TO THE <br />FAILURE TO ALLOW FOR CONDITIONS WHICH MAY EXIST. CONTRACTOR TO REPLACE ANY EXISTING DEVICE <br />OR COMPONENT THAT IS CALLED AS EXISTING IF IT IS NOT FULLY OPERATIONAL. <br />26. WIRING METHODS IN ALL PATIENT CARE AREAS TO BE IN COMPLIANCE WITH REDUNDANT GROUNDING <br />REQUIREMENTS OF NEC 2014 SECTION 517.13. <br />27. ALL DIMMING MECHANISMS HAVE TO BE COMPATIBLE WITH FIXTURE DIMMING REQUIREMENTS. CONTRACTOR <br />MUST VERIFY ALL DIMMING MECHANISM AND FIXTURE DIMMING REQUIREMENTS BEFORE ANY ORDERING, <br />INSTALLING, OR WIRING OF ANY DIMMING MECHANISMS AND FIXTURES. <br />28, ALL OUTDOOR RECEPTACLES TO BE GFCI & WEATHER PROOF, <br />29. CONTRACTOR MUST REVIEW THE OWNER WORK LETTERS AND PROTOTYPE DRAWINGS PRIOR TO BID OR <br />CONSTRUCTION TO VERIFY ALL REQUIREMENTS. BEFORE SUBMITTING BID, BECOME THOROUGHLY FAMILIAR <br />WITH THE OWNER WORK LETTERS AND PROTOTYPE DRAWINGS. THE INTENT OF THE WORK IS SHOWN ON <br />THE DRAWINGS AND DESCRIBED HEREINAFTER. BY THE ACT OF SUBMITTING A BID PROPOSAL FOR WORK, <br />THE CONTRACTOR SHALL BE DEEMED TO HAVE MADE SUCH STUDY AND EXAMINATION PROVIDED IN <br />WRITING TO THE ENGINEER/ARCHITECT ANY DISCREPANCIES. NO REQUEST FOR ADDITIONAL PAYMENT <br />SHALL BE CONSIDERED AS VALID DUE TO THE FAILURE TO ALLOW FOR COORDINATION. CONTRACTOR TO <br />PROVIDE THE TENANT WITH ALL REQUIRED ITEMS. <br />PER FLORIDA BUILDING CODE 2017 ENERGY CONSERVATION: <br />405.6.3 VOLTAGE DROP, <br />405.6.3 THE CONDUCTORS FOR FEEDERS AND BRANCH CIRCUITS COMBINED SHALL BE SIZED FOR <br />A MAXIMUM OF 5 PERCENT VOLTAGE DROP TOTAL. <br />405.6.4 COMPLETION REQUIREMENTS. <br />405.6.4.1 DRAWINGS. CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30 DAYS AFTER <br />THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE <br />PROVIDED TO THE BUILDING OWNER, INCLUDING: <br />1. A SINGLE -LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND <br />2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION. <br />405.6.4.2 MANUALS. CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING MANUAL <br />AND MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING OWNER. THE MANUALS SHALL <br />INCLUDE, AT A MINIMUM, THE FOLLOWING: <br />1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF <br />EQUIPMENT REQUIRING MAINTENANCE. <br />2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING <br />MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED. <br />3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY. <br />NOTE: ENFORCEMENT AGENCIES SHOULD ONLY CHECK TO BE <br />SURE THAT THE CONSTRUCTION DOCUMENTS REQUIRE THIS INFORMATION TO BE TRANSMITTED TO <br />THE OWNER AND SHOULD NOT EXPECT COPIES OF ANY OF THE MATERIALS. <br />AIC CALCULATIONS <br />AT 800A MAIN <br />L '= LENGTH OF CIRCUIT TO FAULT IN FT = 100 FT <br />I = AVAILABLE AIC AT CIRCUIT = 62,000 AMPS <br />c = CONSTANT FROM TABLE = 28,033 <br />n= NUMBER OF'\MRES PER PHASE 2 <br />C = CONSTANT c * n 56,066 <br />V = VOLTS 208 VOLTS <br />F=1.732*L*ITC*V 0.921 <br />M=11(1+F) = 0.521 <br />AIC = I * M F 32,278 AMPS <br />* THESE CALCULATIONS ARE BASED ON AN ESTIMATED DISTANCE FROM <br />TRANSFORMER TO 1ST MEANS OF DISCONNECT AND FEEDER WIRE SIZE.. <br />IF LARGER WIRE IS USED OR THE DISTANCE (L) IS LESS THAT 100 FEET <br />THEN THE AIC VALUES WILL BE LARGER_ CONTACT ENGINEER FOR NEW CALLS_ <br />2 SETS OF 4#600MCM CU <br />IAI A" PAKIF)I NT I Arru crT <br />RISER DIAGRAM <br />SCALE: NTS <br />TWO 10' LONG <br />5/8"0 CU. CLAD <br />GROUND RODS <br />4`a`aot®��es1po�a®®rirrso <br />U�l..ss ,, <br />y\ N' <br />No. 916 <br />CI <br />�\ <br />L <br />JUL 2 2 222 <br />BUCHANAN RE CONSULTING INC. <br />ELECTRICAL * MECHANICAL * PLUMBING <br />ENGINEERING <br />6191 W. ATLANTIC BLVD, SUITE# 2 MARGATE, FL 33063 <br />Phi 954-590-3300 Faxi 954-590-2232 <br />Emo,ili BUCHANAN@MEPENGINEERS.COM <br />CERTIFICATE OF AUTHORIZATION # 8842 <br />❑RAJA BUCHANAN RE # 48916 <br />n t <br />ernationdt, <br />Associates, Inc. AA26001933 <br />Architecture • Planning • Interior Design <br />14125 N.W. 80th Ave. Suite 303 <br />Miami Lakes, FI.33016 <br />T. 786-235-9097 <br />F. 305-362-4420 <br />Otiicifo@dtiarchitect.com <br />www.dtiarchitect.com <br />II Carlos Pizarro, R.A. II <br />AR - 0013079 <br />Revisions: I I <br />Z <br />0 <br />w <br />WD <br />M. <br />V <br />W� <br />j <br />LU <br />H <br />Z <br />N <br />w <br />p <br />LU <br />W <br />HV <br />Q <br />LU <br />LU <br />= <br />a <br />W <br />m <br />0 <br />0 <br />V2 <br />w <br />Z­ <br />0 <br />Z <br />W <br />IL <br />- <br />0 <br />0 <br />W- <br />- N r <br />Z <br />040 aM <br />Q <br />2', 000 <br />LU <br />V QZ0 <br />0 �0LL <br />vQ 0av� <br />�a = � <br />N�� <br />_> <br />a 0 06 <br />0 W N <br />W N <br />0 <br />L <br />n <br />Job Number: 22008.01 <br />File name: <br />Issued Date: <br />Drawn by: <br />Checked by: <br />SHEET NAME II <br />ELECTRICAL <br />RISER DIAGRAM <br />SHEET NUMBER <br />E-2 <br />