DEVICE INSTALLATION DETAIL
<br />CEILING
<br />E ALARM
<br />N/STROBE
<br />FIRE ALARM
<br />ANNUNCIATOR
<br />f PANEL
<br />FIRE ALARM
<br />44-1/8 MANUAL
<br />BOX PULL STATION
<br />M
<br />48" TO CENTER
<br />FINISHES
<br />- FLOOR
<br />80" TO
<br />BOTTOM
<br />OF LENS
<br />SMOKE DETECTOR INSTALLATION DETAIL
<br />411 CEILING
<br />1••••_�INEVER IN THIS ARE4
<br />i�CEILING MOUNTED SMOX(E
<br />DETECTOR BEAT
<br />LEAST / • WALL AND I
<br />J FROM ANY AIR DUCT
<br />MOUNTEDWALL •
<br />DETECTOR MUST BEAT
<br />AL�AST 4" BELOW CEILING
<br />BUT NO LOWER
<br />TO TOP OF •
<br />WIRING LEGEND
<br />MARK NUMBER OF WIRES CIRCUIT DESCRIPTION RECOMMENDED COLOR CODE A
<br />SIZE AND WIRE TYPE
<br />2 #18 FPLR
<br />S UNSHIELDED ADDRESSABLE DATA LOOP RED JACKET B
<br />P 2#14THHN SOUNDER BASE POWER WHITE JACKET C
<br />D
<br />E
<br />F
<br />G
<br />H
<br />J
<br />CONDUITOPP DETAIL \\
<br />System No, W-L-1148
<br />F Ratings - 1 and 2 Hr
<br />T Rating - 0 Hr
<br />F_A
<br />L_A
<br />1. Wall Assembly - The fire -rated gypsum wallboard/stud wall assembly
<br />shall be constructed of the materials and in the manner specified in the
<br />individual U30D or U400 Series Wall and Partition Designs in the Fire
<br />Resistance Directory and shall include the following construction features:
<br />A Studs - Wall framing shall consist of either wood studs or channel
<br />shaped steel studs. Wood studs to consist of 2 by 4 in. lumber spaced
<br />16 in. OC. Steel studs to be min 2-1/2 in. wide, fabricated from min
<br />25 MSG galvanized steel, spaced max 24 in. OC.
<br />B. Wallboard, Gypsum' - 5/8 in. thick, 4 ft wide with square or tapered
<br />edges. The gypsum wallboard type, number of layers and sheet
<br />orientation shall be as specified in the Individual U300 or U400 Series
<br />Designs in the UL Fire Resistance Directory. Max diam of opening is 13
<br />in.
<br />The hourly F Rating of the firestop system is equal to the hourly fire
<br />rating of the wall assembly in which it is installed.
<br />2. Through Penetrants - One metallic pipe, conduit or tubing to be installed
<br />either concentrically or eccentrically within the f"estop system. Pipe,
<br />conduit or tubing to be rigidly supported on both sides of the assembly.
<br />The following types and sizes of metallic pipes, conduits or tubing may
<br />be used:
<br />A Steel Pipe - Nom 8 in. diam (or smaller) Schedule 10 (or heavier)
<br />steel pipe.
<br />B. Iron Pipe - Nom 8 in. diam (or smaller) cast or ductile iron pipe.
<br />C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing
<br />or steel conduit.
<br />3. Pipe Covering - Nom 2 in. thick hollow cylindrical heavy density (min
<br />3.5 pcf) fiberglass pipe covering with an all -service jacket. Pipe covering
<br />material to be min 9 in. long and installed on penetrant to extend 2 in.
<br />beyond both sides of wall surface. Longitudinal joints sealed with metal
<br />fasteners or factory-oppl'ied self-sealing lap (SSL) tape. The annular space
<br />between the pipe covering and periphery of opening shall be min 0 in.
<br />(point contact) to max 3/8 in.
<br />See Pipe and Equipment Covering -Materials (BRGU) category in the
<br />Building Materiels Directory for names of manufacturers. Any pipe
<br />covering material meeting the above specifications and bearing the
<br />UL Classification Marking with a Flame Spread Index of 25 or less and
<br />a Smoke Developed Index of 50 or less may be used.
<br />4. Fill, Void or Cavity Moteri0 - Sealant - In 1 hr assemblies, min 5/8 in.
<br />thickness of fill material applied within annulus Hush with both surfaces
<br />of wall. In 2 hr assemblies, min 1-1/4 in. thickness of fill material
<br />applied within annulus flush with both surfaces of wall. For both 1 and
<br />2 hr assemblies, at point contact location between insulation and
<br />gypsum, a min 1/2 in. bead of fill material shall be applied on both sides
<br />of wail.
<br />r r
<br />STOPPINGFREEWIRE FIRE DETAIL
<br />System No. W-L-3065
<br />F Ratings --1 and 2 Hr (See Item 1)
<br />T Rating -- 0 Hr
<br />SECTION A -A
<br />1. Wall Assembly - The 1 or 2 fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in
<br />the individual U300, U400 or V600 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following
<br />construction features:
<br />A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in.
<br />OC. Steel studs to be min 2-1/2 in. wide and spaced max 24 in. OC.
<br />B. Gypsum Board* - Nom 5/8 in. thick gypsum board, with square or tapered edges. The gypsum board type, thickness, number of layers,
<br />fastener type and sheet orientation shall be as specified in the individual U300, U400 or V600 Series Design in the UL Fire Resistance
<br />Directory. Max diam of opening is 5-1/2 in. when sleeve (item 2) is employed. Max diam of opening is 4 in. when sleeve (item 2) is not
<br />employed.
<br />The F Rating of the firestop system is equal to the fire rating of the wall assembly.
<br />2. Metallic Sleeve - (Optional) - Nom 4 in, diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016
<br />in, thick (28 ga) galv steel sleeve installed flush with wall surfaces. The annular space between steel sleeve and periphery of opening shall be min
<br />0 in. (point contact) to max 1 in. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces.
<br />3. Cables -- Aggregate cross -sectional area of cable in opening to be max 45 percent of the cross -sectional area of the opening. The annular space
<br />between the cable bundle and the periphery of the opening to be min 0 in. to max 1 in. Cables to be rigidly supported on both sides of the wall
<br />assembly. Any combination of the following types and sizes of copper conductor cables may be used:
<br />A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.
<br />B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket.
<br />C. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of % in.
<br />D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in.
<br />E. Through Penetrating Products*-- Max three copper conductor No. 8 AWG . Metal -Clad Cable+.
<br />AFC CABLE SYSTEMS INC
<br />F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing.
<br />4. Fill, Void or Cavity Material*- Sealant -- Fill material applied within the annulus, flush with each end of the steel sleeve or wall surface. Fill
<br />material installed symmetrically on both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating . An additional 1 /2
<br />in. diam bead of fill material shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall.
<br />HILTI CONSTRUCTION CHEMCIALS, DIV OF HILTI INC -- CP601 S, CP606 or FS-One Sealant
<br />*Bearing the UL Classification Mark
<br />BACK BOX LEGEND
<br />4"x4"x2-1/8"
<br />SYMBOL
<br />DESCRIPTION
<br />BACK BOX
<br />MOUNTING
<br />SYMBOL
<br />DESCRIPTION
<br />4"x4" WITH 1-1/2"EXTENTION RING
<br />FACP
<br />FIRE ALARM CONTROL PANEL
<br />PROVIDED
<br />72" TO TOP
<br />C=
<br />DUCT SMOKE DETECTOR
<br />BLANK PLATE
<br />IED
<br />NAC POWER SUPPLY
<br />PROVIDED
<br />72" TO TOP
<br />Q
<br />SMOKE DETECTOR
<br />SINGLE GANG
<br />FAAP
<br />FIRE ALARM ANNUNCIATOR PANEL
<br />PROVIDED
<br />60" TO CENTER
<br />Ql
<br />HEAT DETECTOR
<br />4-11/16"X 4-11/16" x 2-1/8"
<br />FPWR
<br />AUXILIARY POWER SUPPLY
<br />PROVIDED
<br />72" TO TOP
<br />SMOKE DETECTOR W/SOUNDER BASE
<br />4-11/16"x4-11/16" WITH 1-1/2"EXTENTION RING
<br />DACT
<br />DIGITAL ALARM COMMUNICATOR/TRANSMITTER
<br />PROVIDED
<br />72" TO TOP
<br />0
<br />MONITOR MODULE
<br />4" OCTAGON
<br />EVAC
<br />VOICE EVACUATION PANEL
<br />PROVIDED
<br />72" TO TOP
<br />CR
<br />CONTROL RELAY
<br />SINGLE GANG PLASTER RING
<br />EBB
<br />EXTERNAL BATTERY BOX
<br />PROVIDED
<br />ADJ TO FACP
<br />©
<br />CONTROL MODULE
<br />DOUBLE GANG PLASTER RING
<br />RMIC
<br />VOICE REMOTE MICROPHONE
<br />PROVIDED
<br />60" TO CENTER
<br />RTs
<br />REMOTE TEST SWITCH
<br />SQUARE TO ROUND PLASTER RING
<br />FATC
<br />FIRE ALARM TERMINAL CAN
<br />BY ELEC
<br />PER DWG
<br />0
<br />ANSUL HOOD SUPPRESSION SYSTEM
<br />xPNOR
<br />FIRE ALARM TRANSPONDER
<br />PROVIDED
<br />72" TO TOP
<br />0
<br />MANUAL PULL STATION
<br />SEQUENCE OF OPERATION
<br />SEQUENCE OF OPERATION (TYPICAL)
<br />A. Manual: Refer to Fire Alarm Matrix
<br />B. Automatic: Refer to Fire Alarm Matrix
<br />C. Annunciation: Refer to Fire Alarm Matrix.
<br />D. Supervisory. System supervisory faults, such as shorts, opens, and grounds in conductors, operating power failure, or faults
<br />within supervised devices, shall cause an audible and visual trouble indication at the control panel. It shall be possible to silence
<br />the audible trouble signal. Once the trouble is corrected, the signal shall again sound until the silence switch is restored to its
<br />normal position.
<br />Fire Alarm Matrix
<br />INITIATION
<br />NOTIFICATION
<br />ALARM SIGNAL
<br />AT FACP
<br />SUPERVISORY
<br />SIGNAL
<br />AT FACP
<br />TRANSMITS TO
<br />MONITORING
<br />STATION
<br />AUDIO AND VISUAL
<br />CIRCUITS ON ALL
<br />FLOORS
<br />ACTIVATE IN ROOM
<br />SOUNDER BASES
<br />(LOCAL EXCEPT
<br />DURING ALARM)
<br />SHUTDOWN
<br />ASSOCIATED
<br />AHU UNITS
<br />SHUTDOWN ALL
<br />AHU UNITS
<br />RECALL ALL
<br />ELEVATORS
<br />SHUTDOWN
<br />AFFECTED
<br />ELEVATOR
<br />POWER
<br />RELEASE ALL
<br />DOORS BEING HELD
<br />LOCKED BY ACCESS
<br />CONTROL SYSTEM
<br />ALL FLOORS
<br />-PULL STATIONS
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />-SUPERVISORY SIGNAL FROM TAMPER SWITCHES
<br />X
<br />X
<br />-ALARM SIGNAL FROM WATER FLOW SWATCH
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />-ELEVATOR LOBBY SMOKE DETECTOR
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />-ANY OTHER SMOKE OR HEAT DETECTOR
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />-DUCT MOUNTED SMOKE DETECTORS
<br />X
<br />X
<br />X
<br />X
<br />-ELEVATOR SHAFT HEAT DETECTOR
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />-IN-ROOM SMOKE DETECTOR
<br />X
<br />X
<br />ELEVATOR MACHINE ROOM
<br />-ANY SMOKE DETECTOR
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />-ANY HEAT DETECTOR
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />X
<br />NOTESGENERAL �\
<br />GENERAL NOTES
<br />DYNAFIRE'S SCOPE OF WORK ON THIS PROJECT IS TO ADD SYSTEM
<br />QSMOKE DETECTORS W/ SOUNDER BASES TO ALL BEDROOMS. TO
<br />ACCOMPLISH THIS WE WILL CHANGE OUT THE EXISTING FACP TO A
<br />NEW FACP THAT IS CAPABLE OF HANDLING THE ADDITIONAL DEVICES.
<br />QSHOP DRAWINGS ARE BASED ON CONTRACT DRAWINGS THAT
<br />ARE DATED 8/31 /12
<br />FIRE ALARM SYSTEM INSTALLATION IN ACCORDANCE WITH NFPA 72
<br />Q 2007 EDITION, 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN,
<br />AND WIRING UNDER N.E.C., NFPA-70
<br />SYMBOL/BACK
<br />BOX/MOUNTING LEGEND
<br />BACK BOX
<br />MOUNTING
<br />SYMBOL
<br />DESCRIPTION
<br />BACK BOX
<br />MOUNTING
<br />SYMBOL
<br />DESCRIPTION
<br />PROVIDED
<br />MOUNTED BY
<br />MECHCONTRACTOR
<br />ss
<br />120v SURGE SUPPRESSION MODULE
<br />NONE NEEDED
<br />ON EQUIPMENT
<br />BEINGMONITORED
<br />00
<br />CARBON MONOXIDE DETECTOR
<br />A J
<br />CEILING
<br />tas required)
<br />Ls
<br />❑
<br />30V SURGE SUPPRESSION MODULE
<br />A,C
<br />AT INT OF CONDUIT
<br />ENTRYFROMT
<br />❑
<br />FIREMANS PHONE JACK
<br />A J
<br />CEILING
<br />(as required)
<br />s
<br />®
<br />POWER SUPERVISION MODULE
<br />A,C
<br />AT END LOCATION
<br />OF CIRCUIT
<br />WP
<br />WEATHERPROOF RATED
<br />A
<br />s" DOWN FROM CEILING
<br />Fs
<br />WATER FLOW SWITCH
<br />A
<br />ADJACENT TO
<br />EX
<br />EXPLOSION PROOF RATED
<br />TO CENTER OF BOX
<br />FLOW SWITCH
<br />A
<br />ADJACENT TO EQUIP
<br />Ts
<br />TAMPER FLOW SWITCH
<br />A
<br />ADJACENT TO
<br />WG
<br />WIRE GUARD
<br />BEING MONITORED
<br />TAMPER SWITCH
<br />A
<br />W/IN T OF ITEM
<br />Ps
<br />PRESSURE SWITCH
<br />A
<br />ADJACENT TO
<br />ET
<br />EXISTING TO REMAIN
<br />BEING CONTROLLED
<br />TAMPER SWITCH
<br />A
<br />ADJACENT TO EQUIP
<br />©
<br />SYNCHRONIZATION MODULE
<br />E
<br />ADJACENT TO
<br />04
<br />BEAM DETECTOR TRANSMITTER
<br />BEING CONTROLLED
<br />NAG PANEL
<br />A,H
<br />ADJACENT TO
<br />LB
<br />LOCK BOX
<br />PROVIDED
<br />PER AHJ
<br />R�
<br />BEAM DETECTOR RECEIVER
<br />AIR HANDLER UNIT
<br />A
<br />ADJACENT TO EQUIP
<br />DH
<br />DOOR HOLDER
<br />A,H
<br />PER DRAWING
<br />®
<br />WALL MOUNT STROBE
<br />BEING MONITORED
<br />A,H
<br />48" AFF TO CENTER
<br />©
<br />OUTDOOR FIRE BELL
<br />BY OTHERS I
<br />BY OTHERS
<br />®�
<br />CEILING MOUNT STROBE
<br />BACK BOX
<br />MOUNTING
<br />SYMBOL
<br />A,H
<br />PER DRAWING
<br />Ell
<br />A,H
<br />48" AFF TO CENTER
<br />N/A
<br />N/A
<br />Ell
<br />N/A
<br />N/A
<br />D4
<br />N/A
<br />N/A
<br />04
<br />N/A
<br />N/A
<br />Oq
<br />A,H
<br />PER DRAWING
<br />❑C Q
<br />A,H
<br />PER DRAWING
<br />EC Q
<br />a
<br />A
<br />80" AFF TO
<br />BOTTOM OF LENS
<br />S
<br />A
<br />CEILING
<br />(as required)
<br />El,
<br />DESCRIPTION
<br />BACK BOX
<br />MOUNTING
<br />WALL MOUNT HORN STROBE
<br />A
<br />ao" AFF
<br />OF L
<br />BOTTOM OF LENS
<br />CEILING MOUNT HORN STROBE
<br />A
<br />CEILING
<br />(as required) 9
<br />WALL MOUNT SPEAKER STROBE
<br />A
<br />as"AFFTO
<br />BOTTOM OF LEN
<br />CEILING MOUNT SPEAKER STROBE
<br />A
<br />CEILING ® e
<br />(as required) ,
<br />WALL MOUNT HORN
<br />A
<br />F TO
<br />aTOM
<br />BOTTOM OF
<br />OF BOW,
<br />WALL MOUNT MINI HORN
<br />A,H
<br />ao"AFF
<br />B
<br />BOTTOM OF O
<br />WALL MOUNT CHIME STROBE
<br />A
<br />80"AFF TO
<br />°
<br />BOTTOM OF LENS
<br />CEILING MOUNT CHIME STROBE
<br />A
<br />CEILING
<br />(as required)
<br />WALL MOUNT SPEAKER ONLY
<br />A
<br />F TO
<br />aoOM
<br />BOTTOM OF
<br />OF BOX
<br />CEILING MOUNT SPEAKER ONLY
<br />A
<br />CEILING r
<br />(as required)
<br />DYNAFIRE INC.
<br />PHONE (407) 830-6500 - FAX (407) 831-1347
<br />1099 Concord Drive
<br />CASSELBERRY, FLORIDA 32707
<br />E-MAIL: dynafire@dynafire.us
<br />Qualifier: STEVEN HATCH
<br />STATE LICENCE # EF20000528
<br />Z
<br />O
<br />Z
<br />0
<br />0
<br />U
<br />w
<br />x
<br />Y
<br />it
<br />sm-
<br />O li
<br />F O
<br />n
<br />0
<br />� U
<br />Z CO
<br />Z O p
<br />Q 0
<br />~ O Cl)
<br />a D�
<br />o
<br />NUJ W
<br />w
<br />in Q
<br />N Cl)
<br />LU O O
<br />� N N
<br />Q N 00
<br />o r
<br />w
<br />aia
<br />N
<br />0
<br />Z
<br />O
<br />a
<br />w
<br />0�
<br />Ll
<br />;a,
<br />nn
<br />W
<br />J
<br />J
<br />2
<br />W
<br />N
<br />DYNAFIRE, INC.
<br />ENGINEERING SERVICES
<br />P.E. No.33868
<br />Robert Munroe
<br />John Creamer
<br />W
<br />co
<br />to
<br />Q
<br />J
<br />Q
<br />W
<br />0�
<br />LL
<br />CASSELBERRY, FLORIDA
<br />407-830-6500
<br />JOB NUMBER:
<br />ISSUE DATE:
<br />DRAWN BY:
<br />CHECKED BY:
<br />2643
<br />12/5/2012
<br />Cory Abbott
<br />Steven Hatch
<br />Fire Alarm
<br />,p,, rawings
<br />FO
<br />u
<br />
|