r <br />n <br />DEVICE INSTALLATION DETAIL <br />CEILING <br />E ALARM <br />N/STROBE <br />FIRE ALARM <br />ANNUNCIATOR <br />PANEL <br />FIRE ALARM <br />44-118 MANUAL <br />Box PULL STATION <br />60" <br />48" TO CENTER <br />FINISHED <br />- FLOOR <br />80" TO <br />BOTTOM <br />OF LENS <br />SMOKE DETECTOR INSTALLATION DETAIL <br />x <br />;•=•=•=•=•- Ili <br />IN THIS AREA <br />SMOKENEVER <br />CEILING MOUNTED <br />MUST BEAT <br />LEASTDETECTOR <br />I <br />I FROMWALLAND <br />LEAST 36" FROMANY I • DUCT <br />MOUNTED SMOKE <br />DETECTORWALL <br />MUST BEAT 7 <br />ALEAST I BELOW CEILING <br />BUT NO LOWER THAN 1211 <br />TO OP OF DETECTOR <br />Ill <br />CONDUIT FIRE STOPPING DETAIL <br />o <br />F_A <br />L_A <br />System No. W-L-1148 <br />F Ratings - I and 2 Hr <br />T Rating - 0 Hr <br />SECTION A -A <br />1. Well Assembly - The fire -row gypsum waboad/skid walf assembly <br />shall be constructed of the materials and in D¢ manner specified in the <br />individual U300 or U40D Series Wit and Partition Designs in the Fire <br />Resistance Directory and shall include the following construction features: <br />A Studs - Wit framing shot consist of either wood studs or channel <br />shaped steel skids. Wood skids to area of 2 by 4 in. lumber spaced <br />16 in. OC. Sled shots be be min 2-1/2 in. wide, fabricated from min <br />25 MSG galvanized steel, spaced max 24 a OC. <br />B. Wallboard, Gypsum' - 5/8 in. thick, 4 ft wide with square or tapered <br />edges. The %Vsrn waboard type, number of byers and street <br />orientation shot be as specified in the indiviAd U300 or U40D Series <br />Designs in the UL Fire 1isabauce Directory. Max dam of opening is 13 <br />in. <br />�1 The hourly F Rating of the Srestop slrsten is equal to the hourly fire <br />rating of the wd assembly in which i is installed. <br />2. Through Penetrants - One rmndaic pipe, cordil or tubing to be installed <br />either concentrically or ecmdrioaly within the fiesfop system. Pine, <br />conduit or tubing to be rigidly supported on bath sides of the assembly. <br />The following types and saes of metallic pipes, conduits or tubing may <br />be used: <br />A Steel Pipe - Nan 8 in. elan (or smaler) Schedule 10 (or heavier) <br />steel pipe. <br />B. Iron Pipe - Nam 8 rt dian (or smiler) cad or ductile iron pipe. <br />C. Conduit - Norn 4 in dam (or smaller) sted electrical metdfic tubing <br />or steel condul <br />3. Pipe Covering - Nom 2 in. thick hollow q*dicd heavy density (min <br />3.5 pcf) fiberglass pipe covering with an at -service jacket. Pipe covering <br />material to be min 9 in. long acl installed an penetrant to extend 2 in. <br />beyond both sides of wit suface. Longlndnd jolts sealed with metal <br />fasteners or fadory-applied 90-sealing lap (SSL) tape. The annulor space <br />between the pipe covering ad periphery of opening shot be min 0 in. <br />(point contact) to max 3/8 in <br />See Pipe and Equipment Covering-Mderiab (BRGU) category in the <br />Building Materiels Directory for names of mawAachxas. Any pipe <br />covering material meeting the above Spedmtiors and hearing the <br />UL Classification Waling with a name Sprsad Index of 25 or less and <br />a Smoke Developed Irdes of 50 or less may be used. <br />4. Fill, Void or Cavity Martial' - Sealant - In 1 hr asemblies, min 5/8 in. <br />thickness of fill material applied within arms flesh with both surfaces <br />of walL In 2 hr assembies, min 1-1/4 in. thickness of fill material <br />applied within ormks flesh with both sofas of wag. Far both 1 and <br />2 hr assemblies, at point contact location between isolation and <br />gypsum, a min 1/2 in. bead of NI mateid shot be applied on both sides <br />of wall. <br />FREEWIRE FIRE STOPPING DETAIL <br />System No. W-L-3065 <br />F Ratings —1 and 2 Hr (See Item 1) <br />T Rating -- 0 Hr <br />cF:rrTinu a-e <br />1. Wall Assembly - The 1 or 2 fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in <br />the individual U300, U400 or V600 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following <br />construction features: <br />A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. <br />OC. Steel studs to be min 2-1/2 in . wide and spaced max 24 in. OC. <br />B. Gypsum Board* - Nom 518 in. thick gypsum board, with square or tapered edges. The gypsum board type, thickness, number of layers, <br />fastener type and sheet orientation shall be as specified in the individual U300, U400 or V600 Series Design in the UL Fire Resistance <br />Directory. Max diam of opening is 5-1/2 in. when sleeve (item 2) is employed. Max diam of opening is 4 in. when sleeve (item 2) is not <br />employed. <br />The F Rating of the firestop system is equal to the fire rating of the wall assembly. <br />2. Metallic Sleeve - (Optional) - Nom 4 in, diam (or smaller) steel electrical metallic tubing (EMT) or Schedule 5 (or heavier) steel pipe or min 0.016 <br />in. thick (28 ga) gals steel sleeve installed flush with wall surfaces. The annular space between steel sleeve and periphery of opening shall be min <br />0 in. (point contact) to max 1 in. When Schedule 5 steel pipe or EMT is used, sleeve may extend up to 18 in. beyond the wall surfaces. <br />3. Cables - Aggregate cross -sectional area of cable in opening to be max 45 percent of the cross -sectional area of the opening. The annular space <br />between the cable bundle and the periphery of the opening to be min 0 in. to max 1 in. Cables to be rigidly supported on both sides of the wall <br />assembly. Any combination of the following types and sizes of copper conductor cables may be used: <br />A. Max 7/C No.12 AWG with polyvinyl chloride (PVC) insulation and jacket. <br />B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket. <br />C. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of Y2 in. <br />D. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 518 in. <br />E. Through Penetrating Products"-- Max three copper conductor No. 8 AWG. Metal -Clad Cable+. <br />AFC CABLE SYSTEMS INC <br />F. Max 3/C (with ground)(or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing. <br />4. Fill, Void or Cavity Material*-- Sealant -- Fill material applied within the annulus, flush with each end of the steel sleeve or wall surface. Fill <br />material installed symmetrically on both sides of the wall. A min 5/8 in. thickness of sealant is required for the 1 or 2 hr F Rating . An additional 1 /2 <br />in. diam bead of fill material shall be applied around the perimeter of sleeve on both sides of the wall when sleeve extends beyond surface of wall. <br />HILTI CONSTRUCTION CHEMCIALS, DIV OF HILTI INC -- CP601 S, CP606 or FS-One Sealant <br />*Bearing the UL Classification Mark <br />SEQUENCE OF OPERATION <br />SEQUENCE OF OPERATION (TYPICAL) <br />A. Manual: Refer to Fire Alarm Matra <br />B. Automatic: Refer to Fire Alarm Matrix <br />C. Annunciation: Refer to Fire Alarm Matrix. <br />D. Supervisory. System supervisory faults, such as shorts, opens, and grounds in conductors, operating power failure, or faults <br />within supervised devices, shall cause an audible and visual trouble indication at the control panel. It shall be possible to silence <br />the audible trouble signal. Once the trouble is corrected, the signal shall again sound until the silence switch is restored to its <br />normal position. <br />Fire Alarm Matrix <br />INITIATION <br />NOTIFICATION <br />ALARM SIGNAL <br />AT FACP <br />SUPERVISORY <br />SIGNAL <br />AT FACP <br />TRANSMITS TO <br />MONITORING <br />STATION <br />AUDIO AND VISUAL <br />CIRCUITS ON ALL <br />FLOORS <br />SHUTDOWN <br />ASSOCIATED <br />AHU UNITS <br />SHUTDOWN ALL <br />AHU UNITS <br />RECALL ALL <br />ELEVATORS <br />SHUTDOWN <br />AFFECTED <br />ELEVATOR <br />POWER <br />RELEASE ALL <br />DOORS BEING HELD <br />LOCKED BY ACCESS <br />CONTROL SYSTEM <br />ALL FLOORS <br />-PULL STATIONS <br />X <br />X <br />X <br />X <br />X <br />-SUPERVISORY SIGNAL FROM TAMPER SWITCHES <br />X <br />X <br />-ALARM SIGNAL FROM WATER FLOW SWITCH <br />X <br />X <br />x <br />X <br />X <br />-ELEVATOR LOBBY SMOKE DETECTOR <br />X <br />X <br />X <br />X <br />X <br />X <br />-ANY OTHER SMOKE OR HEAT DETECTOR <br />X <br />X <br />X <br />X <br />X <br />-DUCT MOUNTED SMOKE DETECTORS <br />X <br />X <br />X <br />X <br />-ELEVATOR SHAFT HEAT DETECTOR <br />X <br />X <br />X <br />X <br />X <br />ELEVATOR MACHINE ROOM <br />-ANY SMOKE DETECTOR <br />X <br />X <br />X <br />X <br />X <br />X <br />-ANY HEAT DETECTOR <br />X <br />X <br />X <br />X <br />X <br />X <br />GENERAL NOTES <br />GENERAL NOTES <br />DYNAFIRE'S SCOPE OF WORK ON THIS PROJECT IS TO ADD 3 SMOKE <br />Q DETECTORS TO THE EXISTING NOTIFIER NFS-320 FACP. NEW SMOKE <br />DETECTORS ARE BEING ADDED TO ROOMS 238, 238A, & 236. <br />QSHOP DRAWINGS ARE BASED ON CONTRACT DRAWINGS THAT <br />ARE DATED 8/31 /12 <br />FIRE ALARM SYSTEM INSTALLATION IN ACCORDANCE WITH NFPA 72 <br />2007 EDITION, 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN, <br />AND WIRING UNDER N.E.C., NFPA-70 <br />WIRING LEGEND <br />BACK BOX LEGEND <br />SYMBOL/BACK <br />BOX/MOUNTING LEGEND <br />MARK <br />NUMBER OF WIRES <br />SIZE AND WIRE TYPE <br />CIRCUIT DESCRIPTION <br />RECOMMENDED COLOR CODE <br />A <br />4"x4"x2-1/8" <br />SYMBOL <br />DESCRIPTION <br />BACK BOX <br />MOUNTING <br />SYMBOL <br />DESCRIPTION <br />BACK BOX <br />MOUNTING <br />SYMBOL <br />DESCRIPTION <br />BACK BOX <br />MOUNTING <br />SYMBOL <br />DESCRIPTION <br />BACK BOX <br />MOUNTING <br />SYMBOL <br />DESCRIPTION <br />BACK BOX <br />MOUNTING <br />S <br />FPLR <br />UNSHIELDED <br />UNSHIELDED <br />ADDRESSABLE DATA LOOP <br />RED JACKET <br />B <br />4"x4" WITH 1-1/2"EXTENTION RING <br />FACP <br />FIRE ALARM CONTROL PANEL <br />PROVIDED <br />72" TO TOP <br />Q-- <br />DUCT SMOKE DETECTOR <br />PROVIDED <br />MOUNTED C <br />MECH CONTRACTOR <br />ss <br />120v SURGE SUPPRESSION MODULE <br />NONE NEEDED <br />ON EQUIPMENT <br />BEING MONITORED <br />�o <br />CARBON MONOXIDE DETECTOR <br />A,H <br />PER DRAWING <br />f r f-1 <br />WALL MOUNT HORN STROBE <br />A <br />BOTTOM OF LENS <br />70M O L <br />C <br />BLANK PLATE <br />NAc <br />NAC POWER SUPPLY <br />PROVIDED <br />72" TO TOP <br />2 <br />Q <br />SMOKE DETECTOR <br />A,J <br />CEILING <br />(as required) <br />Ls <br />❑ <br />30v SURGE SUPPRESSION MODULE <br />A,C <br />ENTRY FROM OUTDOORS <br />T <br />❑ <br />FIREMANS PHONE JACK <br />A,H <br />48ATPOINTOFGONDUI"AFF TO CENTER <br />F a <br />� <br />CEILING MOUNT HORN STROBE <br />A <br />CEILING <br />(as required) <br />D <br />SINGLE GANG <br />FAAP <br />FIRE ALARM ANNUNCIATOR PANEL <br />PROVIDED <br />60" TO CENTER <br />Ql <br />HEAT DETECTOR <br />A,J <br />CEILING <br />(as required) <br />S <br />® <br />POWER SUPERVISION MODULE <br />A,C <br />AT END LOCATION <br />OF CIRCUIT <br />WP <br />WEATHERPROOF RATED <br />N/A <br />NIA <br />s <br />WALL MOUNT SPEAKER STROBE <br />A <br />80"AFF TO <br />BOTTOM OF LENS <br />E <br />4-11/16"X 4-11/16" x 2-1/8" <br />PwR <br />AUXILIARY POWER SUPPLY <br />PROVIDED <br />72" TO TOP <br />2 <br />® <br />SMOKE DETECTOR W/SOUNDER BASE <br />A <br />I" DOWN TERFROOF BOX <br />TO CENTER OF BOX <br />Fs <br />❑ <br />WATER FLOW SWITCH <br />A <br />FLOWADJACETO <br />TCH <br />FLOW SWITCH <br />EX <br />EXPLOSION PROOF RATED <br />NIA <br />N/A <br />s <br />� <br />CEILING MOUNT SPEAKER STROBE <br />A <br />CEILING <br />(as required) <br />F <br />4-11/16"x4-11/16" WITH 1-1/2"EXTENTION RING <br />DACT <br />DIGITAL ALARM COMMUNICATOR/TRANSMITTER <br />PROVIDED <br />72" TO TOP <br />❑M <br />MONITOR MODULE <br />A <br />ADJACENT TO EQUIP <br />BEING MONITORED <br />Ts <br />TAMPER FLOW SWITCH <br />A <br />ADJACENT TO <br />TAMPER SWITCH <br />WG <br />WIRE GUARD <br />N/A <br />N/A <br />04 <br />WALL MOUNT HORN <br />A <br />Ba"AFFTO <br />BOTTOM OF BOX <br />G <br />4" OCTAGON <br />EVAC <br />VOICE EVACUATION PANEL <br />PROVIDED <br />72" TO TOP <br />cR <br />CONTROL RELAY <br />A <br />WAN 3'OFITEM <br />BEING CONTROLLED <br />Ps <br />PRESSURE SWITCH <br />A <br />ADJACENT TO <br />TAMPER SWITCH <br />ETR <br />EXISTING TO REMAIN <br />N/A <br />N/A <br />Ell <br />WALL MOUNT MINI HORN <br />A,H <br />80"AFF TO <br />BOTTOM OF BOX <br />H <br />SINGLE GANG PLASTER RING <br />EBB <br />EXTERNAL BATTERY BOX <br />PROVIDED <br />ADJ TO FRCP <br />® <br />CONTROL MODULE <br />A <br />ADJACENT TO EQUIP <br />BEING CONTROLLED <br />QM <br />SYNCHRONIZATION MODULE <br />E <br />ADJACENT TO <br />NAC PANEL <br />T� <br />BEAM DETECTOR TRANSMITTER <br />A,H <br />PER DRAWING <br />❑C Q <br />WALL MOUNT CHIME STROBE <br />A <br />80" AFF TO <br />BOTTOM OF LENS <br />DOUBLE GANG PLASTER RING <br />RMIc <br />VOICE REMOTE MICROPHONE <br />PROVIDED <br />60" TO CENTER <br />RTs <br />REMOTE TEST SWITCH <br />A,H <br />ADJACENT TO <br />AIR HANDLER UNIT <br />LB <br />LOCK BOX <br />PROVIDED <br />PER <br />01 <br />BEAM DETECTOR RECEIVER <br />A,H <br />PER DRAWING <br />0.1 <br />CEILING MOUNT CHIME STROBE <br />A <br />CEILING <br />(as required} <br />J <br />SQUARE TO ROUND PLASTER RING <br />FATC <br />FIRE ALARM TERMINAL CAN <br />BY ELEC <br />PER DWG <br />El <br />ANSUL HOOD SUPPRESSION SYSTEM <br />p <br />MTO EQUIP <br />ADJACENT BEING <br />BEING MONITORED <br />DH <br />DOOR HOLDER <br />A,H <br />PER DRAWING <br />® <br />WALL MOUNT STROBE <br />A <br />Bo°AFF L <br />BOTTOM OF LENS <br />WALL MOUNT SPEAKER ONLY <br />A <br />Bo"AFF TO <br />BOTTOM OF BOX <br />XPNDR <br />FIRE ALARM TRANSPONDER <br />PROVIDED <br />72" TO TOP <br />F <br />❑ <br />MANUAL PULL STATION <br />A,H <br />48"AFF TO CENTER <br />B <br />❑ <br />OUTDOOR FIRE BELL <br />BY OTHERS <br />BY OTHERS <br />5 <br />❑a <br />CEILING MOUNT STROBE <br />A <br />CEILING <br />(as required) <br />s <br />❑c <br />CEILING MOUNT SPEAKER ONLY <br />A <br />CEILING <br />(as required) <br />qy.�a F i re <br />DYNAFIRE INC. <br />PHONE (407) 830-6500 - FAX (407) 831-1347 <br />109B Concord Drive <br />CASSELBERRY, FLORIDA 32707 <br />E-MAIL dynafire@dynafire.us <br />Qualifier: STEVEN HATCH <br />STATE LICENCE # EF20000528 <br />omm" <br />Z Q <br />O� <br />�— 0 w <br />W <br />OU) <br />wwww J <br />LL <br />Z ., <br />W W 75; <br />p r <br />wwwwwr� <br />w <br />Z 0,5 ry <br />Q <br />O C) W <br />f-y <br />Z <br />>- <br />W LL <br />O N <br />U — <br />W Q <br />Z <br />O <br />l'- <br />O <br />tY <br />H <br />Z o <br />O <br />� p <br />U � <br />w U) <br />N_ <br />[L1 O <br />� N <br />0 N <br />�k <br />LLI <br />a <br />JOB NUMBER: 2643 <br />ISSUE DATE: 12/5/2012 <br />DRAWN BY: Cory Abbott <br />CHECKED BY: Steven Hatch <br />Fire Alarm <br />Shop Drawings <br />FA-1 <br />L <br />