Project Name: SVB Housing Standby Hours: 24
<br />Alarm Minn, 5
<br />AFC-100 Installed BylFlorida Low Voltage Systems Efficiency Factor: 20%
<br />Battery & Voltage Drop Designed B lorida Low Voltage Systems SLC Type Class B
<br />Calculations Date: 1012022 NAC Source Voltage: 20.4 _
<br />Model #: AFC-100 Max Panel Current (amps): 5
<br />Panel ID:FACP User assumes all responsibility to ensure the quantities and current draw
<br />values in this worksheet are accurate prior to submittal.
<br />Locatiomist Floor Electrical/Mechanical Room
<br />DescriptionAddressable Fire Panel Standby (amps) 4404�*OPS)
<br />1 AFC-100 Analog Addressable FRCP 0.130 0.130 0.220 0.220
<br />Panel Standby: 0.130 Panel Alarm: 0.220
<br />1 UO-2000 / UD-1000 DACT Card
<br />0.016
<br />0.016
<br />0.023
<br />0.023
<br />RA-6075R LCD Annunciator
<br />0.020
<br />0.025
<br />1-650OR(F) Flush Mount LCD Annunciator
<br />0.020
<br />0.020
<br />0.050
<br />0.050
<br />LED-16(F) Flush Mount LED Annunciator
<br />0.025
<br />0.025
<br />LED-16 LED Annunciator LED Power*
<br />0.015
<br />0.210
<br />CA-6075 Class A Module
<br />0.012
<br />0.044
<br />3 P N-1000(E) Power Expander
<br />0.015
<br />0.045
<br />0.015
<br />0.045
<br />PAD100-SLCE-127 SLC Expander
<br />0.060
<br />0.060
<br />1 NOHMI-SLCE-127** SLC Expander
<br />0.060
<br />0.060
<br />0.060
<br />0.060
<br />**REQUIRED IF USING N_OHMI PROTOCOL SLC DEVICES_
<br />(Maximum current draw on P-Link limited to 1 Amp)
<br />P-LINK Standby:
<br />0.141
<br />P-LINK Alarm:
<br />0.178
<br />*Only enter quantity if PLINK power is being used to power devices
<br />SLC Devices
<br />Standby
<br />AFC / ARC Series
<br />19 PAD-PD Analog Photo Smoke
<br />0.000300
<br />0.005700
<br />0.000300
<br />0.005700
<br />PAD-PHD Analog Photo Smoke/Heat
<br />0.000300
<br />0.000300
<br />2 P D-HD Analog Fixed Temp Heat
<br />0.000300
<br />0.000600
<br />0.000300
<br />0.000600
<br />PAD -CD Analog Carbon Monoxide Detector
<br />0.000300
<br />0.000300
<br />1 P D-DUCT Addressable Duct Detector
<br />0.000300
<br />0.000300
<br />0.000300
<br />0.000300
<br />PAD-DUCTR* Add. Dud Detector w/Relay
<br />0.000500
<br />0.000500
<br />PAD100-DRTS Dud Remote Test Switch
<br />0.010000
<br />0.015000
<br />17 D100-PSSA/PSDA Add. Pull Station Single/Dual Action
<br />0.000200
<br />0.003400
<br />0.000200
<br />0.003400
<br />PAD100-MIM Micro Input Module
<br />0.000200
<br />0.000200
<br />1 P D100-SIM Single Input Module
<br />0.000240
<br />0.000240
<br />0.000240
<br />0.000240
<br />1 P, D100-DIM Dual Input Module
<br />0.000240
<br />0.000240
<br />0.000240
<br />0.000240
<br />6 AD100-RM Relay Module
<br />0.000240
<br />0.001440
<br />0.000240
<br />0.001440
<br />SLC Loop Alarm LED Current
<br />0,000000
<br />0.000000
<br />0.036000
<br />0.180000
<br />Requires Aux Power (Configure Below)
<br />SLC Standby:
<br />0.011920
<br />SLC Alarm:
<br />0.191920
<br />** See the installation manual for special considerations when installing AIB, SCI
<br />devices on Class B loops.
<br />ConfigurationNAC Circuits (See NAC below)
<br />Description1
<br />0.00000
<br />0.00000
<br />2
<br />0.00000
<br />0.00000
<br />NAC Standby:
<br />0.00000
<br />NAC Alarm:
<br />0.00000
<br />2
<br />0.00000
<br />UO Standby: 0.00000 1/0 Alarm:
<br />0.00000
<br />0.00000
<br />CalculationBattery
<br />•.
<br />e
<br />Panel Current: 0.13000
<br />0.22000
<br />P-Link Current: 0.14100
<br />0.17800
<br />SLC Device Current: 0.01192
<br />0.19192
<br />NAC Circuit Current: 0.00000
<br />0.00000
<br />1/0 Circuit Current: 0.00000
<br />0.00000
<br />SLC Loop Type: Class B
<br />Total Stand b M'`'a e" _,. Total Alarm •fi wilt
<br />;101
<br />Device Addresses U m
<br />Standby Hours: 24 Alarm Mins:
<br />5
<br />Device Addresses Available: 100
<br />AH Required: 6.80 AH Required:
<br />0.05
<br />Total Combined Standby & Alarm AmpHours Required:
<br />6.85
<br />Safety Margin:
<br />20%
<br />Required Battery AmpHours:
<br />8.22
<br />Battery AmpHours Provided:
<br />12
<br />Note: The cabinet will house two 8 AH or 18 AH batteries. The charging circuit is rated for up to
<br />two 55 AH
<br />batteries.
<br />Total Standb R`L9 Total Alarm ,' ;�
<br />1 Oft
<br />Project Name SVB Housing Standby Hours: 24
<br />Alarm Minn 5 -- --
<br />PSN-1000(E) Installed By orida Low Voltage Systems Efficiency Factor. 2oX_- --- -
<br />Battery & Voltage Drop Designed Low Voltage Systems SLC Type; Class B
<br />calculations Date: 1012022 NAC source voltage: 20.4---
<br />Model #: PSN-1000(E) Max Panel Current (amps): 10
<br />Panel Ili
<br />User assumes all responsibility to ensure the quantities and current draw
<br />Location l FL ElecbicgVMechaolcal Room values in this worksheet am accurate briar to submittal.
<br />Circuits (Sea NAC Contifiguration
<br />below)
<br />Panel Standby:
<br />0.060 Panel Alarm:- - -
<br />Standby (amps) All
<br />0.200
<br />(amps)
<br />Ckt use
<br />1 Notification
<br />DescriptionNAC
<br />1FL CKT#1
<br />Claw
<br />0,00000
<br />2.84480
<br />2 Notification
<br />1FL CKT#2
<br />Class B
<br />0.00000
<br />1.69CAO
<br />3 Notification
<br />1FL CKT #3
<br />Class B
<br />0.00000
<br />1.94860
<br />4 Notification
<br />2FL CKT #4
<br />Class B
<br />0.00000
<br />1.03860
<br />5 Notification
<br />2FL CKT #5
<br />Class B
<br />0.00000
<br />0.49700
<br />6
<br />class B
<br />0.00000
<br />0.00000
<br />NAC Standby:
<br />0.00000 NAC Alarm:
<br />8,02540
<br />Panel Current:
<br />0.06000
<br />0.20000
<br />Plink Current:
<br />0.00000
<br />0.00000
<br />SLC Device Current:
<br />0.00000
<br />0.00000
<br />NAC Circuit Current
<br />0.00000
<br />8.02540
<br />Total Stand,
<br />,•; •'""' ` Total Alarm
<br />`'`; •�
<br />Standby Hours:
<br />24 Alarm Mins:
<br />5
<br />AH Required:
<br />1.44 AH Required:
<br />0.69
<br />Total Combined Standby & Alarm AmpHours Required:
<br />2.13
<br />Safety Margin:
<br />20%
<br />Required Battery AmpHours:
<br />2,56
<br />_
<br />Battery AmpHours Provided:
<br />71
<br />Note: The cabinet will house two 8 AH or 18 AH batteries. The charging circuit is rated for up to two 55 AH batteries.
<br />NAC Circuit Configuration &
<br />#14 Solid 3.19 200 1 276 2.845 16.77 16
<br />6 H
<br />Strobes
<br />---
<br />5
<br />Potter LFHS-110 Temporal 3 Normal db
<br />Potter 5-24 Strobe, 110ed
<br />Gentex GHLF L ors, emporal 3 Norm
<br />0.000000 0 000000
<br />0.000000 0 000000
<br />0.000000 0000000
<br />0.280000 1.680C
<br />0 161000 0.966C
<br />0.099400 0.198E
<br />6 S
<br />Total Standb .. .. . - ---
<br />Total Alarm `c ....`. >..,
<br />Class Class6 Usage Notification Description 1FL CKT#2
<br />#14 Solid 3 19 190 _ 1.212 1.G96 18.34 16
<br />Potter HS-24, 75cd. Hi db 0. 0.000000 0.144000 0.7201
<br />Potter SH-24H-WP 95cd, Med db 0. 0.000000 0. 181000 0.161
<br />;Potter S24 Strobe, 75cd 0.000000 0.000000 0. 116000 0.696000
<br />Potter LFH-24 LF Hom, Temporal 3 0.000 100 0.000000 0099400 0099400
<br />Total Standb, Total Alarm(_ , , „ l,r
<br />Class Class
<br />Usage Notification
<br />Description
<br />1FL CKT#3
<br />#14 Solid
<br />3.19 160
<br />1.021 1
<br />1.949
<br />18.41
<br />16
<br />4 Ham Strobes
<br />Potter HS-24, 75W, Hi db
<br />0.00000
<br />0.
<br />0.144000
<br />0.576000
<br />2 Hom Strobes
<br />_
<br />Potter SH-24H-WP 95cd, Mod d6_ -
<br />_
<br />0.00000
<br />_
<br />0 -
<br />-0.181000
<br />0.362000
<br />1 Strobes
<br />Potter S24 Strobe, 75cd
<br />0.000000
<br />_
<br />0.000009_
<br />_ _-
<br />0.1160�
<br />0.116000
<br />9 Horns
<br />Potter LFH-24 LF Ham, Temporal 3 Norm
<br />0.00000
<br />0.
<br />0.099406
<br />0.894604
<br />- --
<br />Total Star lb
<br />,�, a:s
<br />Total Alarm
<br />NAC Circuit Configuration & Voltage Drop (cont'd)
<br />classl Class B Usage Notification Description 2FL CKT #4
<br />#14 Solid 3 19 160 1.021 1.039 19.34 16
<br />9 Horns Gentex GHLF LF Horn. Temporal 3 Norm 0.000000 0.000000 0.099400 0.E
<br />-
<br />j 1 Hqm Strobes Potter HS-24, 75cd, HI db 0.000000 G 000000 0.144000 0.1
<br />- Total Standby Total Alarm
<br />Project Name: SVB Housing Standby Hour>r: 24 I
<br />Alarm lifi l5 -�
<br />PSN-1000(E) Installed ByFll Low Volage Systems \ Efficiency Facto -�
<br />Battery & Voltage Drop Designed Low Voltage Systems SLC T pass B
<br />Calculations Date: 10/20Y2 NAG Source Voita�
<br />Model #: PSN-1000(E) Max Panel Current (amps): 10
<br />Panel ID. FCPS #2
<br />-- User a<sumes all responsibility to ensure the quantities and current draw
<br />Location 1FL ElectricaVMechanlcal Room values in this worksheet are accurate odor to submittal.
<br />1 PSN-100l
<br />Int6ftent Power Expander
<br />0.050
<br />0,060
<br />0.200
<br />0.200
<br />(See NAC Configuration
<br />be"
<br />Panel Standby:
<br />Standby
<br />0.060
<br />wipe,
<br />Panel Alarm:
<br />0.200
<br />Amwi� Use
<br />1 Notification
<br />Description
<br />2FL CKT #6
<br />Class
<br />Class B
<br />TOW
<br />O.D0000
<br />Total
<br />1.25580
<br />2 Notification
<br />2FL CKT #7
<br />Class B
<br />0.00000
<br />1. 12780
<br />3 Notification
<br />3FL CKT #8
<br />Class B
<br />0.00000
<br />1.03860
<br />4 Notification
<br />3FL CKT #9
<br />Class B
<br />0.00000
<br />0.49700
<br />5 Notification
<br />3FLCKT#10
<br />Class
<br />0.00000
<br />0.98380
<br />6 Notification
<br />3FL CKT #11
<br />Class B
<br />0.00000
<br />1.12780
<br />-
<br />- -
<br />NAC Standby:
<br />_ _
<br />0.00000
<br />NAC Alarm:
<br />6.03080
<br />Panel Current:
<br />0.01
<br />0.20000
<br />P-Link Current:
<br />0.00000
<br />0.00000
<br />SLC Device Current:
<br />0.00000
<br />0.00000
<br />NAC Circuit Current:
<br />0.00000
<br />C.03080
<br />Total Standb
<br />Total Alarm
<br />Standby Hours:
<br />24
<br />Alarm Mins:
<br />5
<br />AH Required:
<br />1.44
<br />AH Required:
<br />0.52
<br />Total Combined
<br />Standby & Alarm AmpHours Required:
<br />1.96
<br />Safety Margin:
<br />20%
<br />Required
<br />Battery AmpHours:
<br />2.35
<br />Battery AmpHours Provided:
<br />71
<br />Note: The cabinet will house two 8 AH or 18 AH batteries. The charging
<br />circuit is rated for up to two 55 AH batteries.
<br />NAC Circuit Configuration
<br />8 Voltage Drop
<br />SVB housing
<br />2110/2022
<br />Clawl Class B
<br />Usage Notification
<br />_
<br />Descriptioll2FL
<br />CKT #6
<br />#14 Solid
<br />3.19 180
<br />1.148
<br />1.256
<br />18.96 16
<br />2 Horn
<br />l do 00000
<br />0.000000
<br />0280000
<br />0
<br />7 Horns
<br />potter LFH 24 LFH m,oTelmpo al
<br />Potter
<br />3allonn_ 00000
<br />0.000000
<br />0.000000
<br />0.099400
<br />0 655800
<br />-
<br />_
<br />Total Stantl6
<br />,,>-JWJJJJ
<br />_
<br />Total AlarmE`,
<br />9.
<br />Class Class B Usage Notification Descnptio 2FL CKT #7
<br />414 Solid 3.19 180 1.148 1.128 19.10 16
<br />3 Horn Strobes Potter HS24 75cd, Hi db 0,000000 0,000000 0. 144000 043200
<br />Q
<br />7 Horns Potter LFH-24 LF Ham, Temporal 3 Norm 0.000000 0000000 0.099400 0 65580
<br />4
<br />Total Standblj; OAS - Total Alarm s, 11
<br />MAX Circuit Current lamps): 3 Source volta" Used tvocj4;F7
<br />Class ClassB Usagel Notification Descr(ptlonl 3FL CKT#8
<br />#14 Solid 3.19 - 200 1.276 1.039 19.07 16
<br />1 Horn Strobes Potter HS-24, 75cd, Ht db 0.000000 0.000300 0. 144000 0. 144000
<br />i 9 Horns Potter LFH-24 LF Hom, Temporal 3 dorm 0.000000 1) 100000 0.099400 0 tr94600
<br />Total Standby;; 0,EK160f1 Total Alarm: 1.¢
<br />li
<br />clawl Class B
<br />usagel Notification
<br />Descriptlo
<br />3FL CKT #9
<br />#14 Solid
<br />3.19 200
<br />1 276
<br />0 497
<br />1977
<br />16
<br />5 Horns
<br />Clawl Class B
<br />Potter LFH-24 LF Ham, Temporal 3 Norm
<br />Usage Notification
<br />0000000
<br />Total Standb: .._
<br />0 000003
<br />0001iG0
<br />Description
<br />0 099400
<br />Total Alarm
<br />3FL CKT #10
<br />0.497000
<br />O,A9TOf�
<br />#14 Solid
<br />3.19 170
<br />1,085
<br />0.994
<br />19 33
<br />16
<br />2 Horn Strobes
<br />7 H ins _
<br />Power HS24, 75cd, Hi db
<br />IPatter LFH•24 LF Ham, Temporal 3 Cllorm
<br />0.000000 0.000000
<br />0000000 0000000
<br />Total Standb, (
<br />0,144000
<br />0,099400
<br />Total Alarms >,
<br />0.288009
<br />0,6958
<br />Class Class B Usage Notification
<br />D.scriptioll
<br />3FL CKT #11
<br />#14 Solid 3.19 200
<br />1.276
<br />1.128
<br />18.96
<br />16
<br />3 Horn Strobes Potter HS24, 75cd, Hi db
<br />7 Horns Potter LFH24 LF Horn. Temporal 3 Norm
<br />0.000000
<br />0 000000.
<br />Total Standby(: _:
<br />0,000000
<br />0 000000
<br />0,01(0@q
<br />0. 144000
<br />0.099400
<br />Total Alarm
<br />043200
<br />0695800
<br />1.1278t1
<br />tat
<br />THIS ITEM HAS BEEN ELECTRONICALLY SIGNED AND SEALED BY SAMUEL P.
<br />DEAN, P.E. ON 104.26.20221 USING A SHA-1 AUTHENTICATION CODE.
<br />PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND
<br />SEALED AND THE SHA-1 AUTHENTICATION CODE MUST BE VERIFIED ON
<br />ANY ELECTRONIC COPIES.
<br />FLORIDA LOW VOLTAGE SYSTEMS
<br />4020 W CAYUGA ST.
<br />TAMPA, FL 33614
<br />813-353-0831
<br />EC 13010771
<br />EF 20001786
<br />L0
<br />in
<br />M
<br />M
<br />0
<br />Z
<br />C0
<br />-�
<br />U.
<br />Cl
<br />Z
<br />n
<br />=)
<br />0
<br />Ci
<br />0
<br />�_
<br />J
<br />a.
<br />LLI
<br />CAD DATE: 2/10/2022
<br />NO. ISSUE/REVISION DATE
<br />No 83 15
<br />'0
<br />p.' S O
<br />441,
<br />0
<br />t
<br />! ��/llllil►� ��
<br />APR 2 6 2022
<br />SAMUEL P. DEAN P.E.
<br />CONSULTING ENGINEER
<br />REGISTRATION NUMBER 83915
<br />CA # 29694
<br />1503-A WEST BUSCH BLVD.
<br />TAMPA FLORIDA 33612
<br />PHONE: (813) 961-3075
<br />FAX: (813) 961-1031
<br />email: sdean@beltengineering.com
<br />I CERTIFY THAT TO THE BEST OF MY KNOWLEDGE
<br />AND BELIEF ALL OF THE FIRE ALARM ELEMENTS
<br />FOR THIS STRUCTURE HAVE BEEN DESIGNED TO
<br />BE IN COMPLIANCE WITH THE FLORIDA BUILDING
<br />CODE 7TH EDITION 2020. ALL OTHER ELEMENTS,
<br />SYSTEMS AND ASSEMBLIES ARE THE TOTAL
<br />RESPONSIBILITY OF OTHERS.
<br />SHEET:
<br />FA-6
<br />
|