TRUSS AND FRAMING NOTES:
<br />1. TRUSSES SHALL BE DESIGNED IN ACCORDANCE WITH THE APPLICABLE
<br />PROVISIONS OF THE "NATIONAL DESIGN SPECIFICATION FOR WOOD
<br />CONSTRUCTION" OF NFPA AND WITH THE TPI "DESIGN SPECIFICATION
<br />FOR METAL PLATE CONNECTED WOOD TRUSSES". CHORD MEMBERS
<br />SHALL BE K.D. SOUTHERN PINE, SURFACED DRY, NO.2 MINIMUM.
<br />LIVE LOAD DEFLECTION SHALL BE LIMITED TO L/360. CONNECTOR
<br />PLATES SHALL BE MADE OF ASTM A446, GRADE A, HOT -DIPPED
<br />GALVANIZED (G60) STEEL AND APPLIED TO BOTH FACES OF TRUSS
<br />AT EACH JOINT. TRUSSES WITH THREE SUPPORTS SHALL PROVIDE
<br />FOR HORIZONTAL MOVEMENT AT ONE.
<br />2. ROOF TRUSS SUPPLIER SHALL BE RESPONSIBLE FOR THE DESIGN OF
<br />THE ROOF TRUSS SYSTEM. DESIGN OF THE SYSTEM SHALL BE PREPARED
<br />SIGNED AND SEALED BY A QUALIFIED FLORIDA REGISTERED PROFESSIONAL ENGINEER.
<br />COPIES OF COMPLETE SHOP DRAWINGS, INCLUDING TRUSS LAYOUT AND
<br />BRACING, SHALL BE SUBMITTED FOR THE CONTRACTOR'S REVIEW.
<br />DURATION FACTORS USED FOR DESIGN SHALL BE 1.25 FOR D+L AND
<br />1.33 FOR D+W LOADS. SUBMITTALS SHALL INDICATE UPLIFT LOADS PER
<br />PROJECT WIND SPEED AND DESIGN CRITERIA.
<br />3. TRUSSES AND RAFTERS SHALL BE SECURED TO SUPPORTS WITH HURRICANE
<br />ANCHORS AND 8d NAILS, MINIMUM. TRUSS TO TRUSS CONNECTORS SHALL
<br />BE BY THE TRUSS FABRICATOR INCLUDING VALLEY TRUSSES.
<br />4. TRUSSES SHALL BE SECURELY BRACED DURING ERECTION AND AFTER
<br />PERMANENT INSTALLATION IN ACCORDANCE WITH "BRACING WOOD TRUSSES:
<br />COMMENTARY AND RECOMMENDATIONS (BWT-85)" AS PUBLISHED BY TPI, AS
<br />CALLED FOR BY THE TRUSS FABRICATOR AND AS SHOWN ON DRAWINGS.
<br />CONSTRUCTION AND/OR PERMANENT LOADS SHALL BE PLACED ONLY ON
<br />COMPLETED NAILED SHEATHING AND BRACING.
<br />5. ALL LUMBER IN CONTACT WITH CONCRETE OR MASONRY SHALL
<br />BE PRESSURE TREATED, USING WOLMAN CC OR EQUIVALENT.
<br />6. THE CONTRACTOR SHALL COORDINATE ALL ROOF PENETRATIONS, DUCT LAYOUT
<br />AND OTHER CEILING WORK WITH TRUSS AND OTHER STRUCTURAL FRAMING.
<br />7. ALL DOORS, WINDOWS AND STOREFRONT, THEIR FRAMES, FASTENERS AND ANCHORAGES
<br />SHALL SATISFY THE 150 MPH WIND SPEED REQUIREMENTS OF RFBC 2010, CHAPTFER 3.
<br />8. PATIO DOORS SHALL BE SAFTY GLAZED PER RFBC 2010, SECTION R 308.4.
<br />ROOF SHEATHING (UNBLOCKED
<br />USE 15/32" THICK APA RATED SHEATHING, 32/16, EXPOSURE
<br />1 (OR 1 /2" OSB). USE PANEL CLIPS BETWEEN EACH SUPPORT.
<br />MINIMUM NAILING OF PLYWOOD SHALL BE WITH 8d COMMON NAILS
<br />AT 6" O.C. AT SUPPORTED EDGES. AT 12" O.C. ALONG
<br />INTERMEDIATE SUPPORTS, NAILING SHALL BE 4" O.C. FOR PERIMITERS
<br />AND HIPS, FOR A 5'-0" WIDTH. ( NO STAPLES ).
<br />FLOOR SHEATHING, GLUE -NAILED SUB -FLOORING
<br />USE 3/4" THICK APA RATED SHEATHING, 48/24, C-D, EXPOSURE I. PANELS
<br />SHALL BE TONGUE AND GROOVE EDGES. NAILING SHALL BE 8d DEFORMED
<br />NAILS ® 6" O.C. ALONG EDGES AND 12" O.C. AT INTERMEDIATE
<br />SUPPORTS FOR GLUE -NAILED FLOORS. USE ADHESIVES CONFORMING TO APA
<br />SPEC Y510J; NON -VENEERED PANELS WITH SANDED SURFACES AND EDGES
<br />SHALL USE ONLY SOLVENT BASED GLUES.
<br />WALL SHEATHING
<br />EXTERIOR AND INTERIOR BEARING STUD WALL SHEATHING SHALL BE 15/32"
<br />THICK APA RATED, EXPOSURE I OR 1 /2" OSB. NAILING OF PLYWOOD SHALL BE 8d NAILS
<br />AT 6" O.C. AT EDGES AND 12" O.C. AT INTERMEDIATE SUPPORTS, U.O.N.
<br />STRUCTURAL WOOD
<br />1. LUMBER FOR STRUCTURAL FRAMING AND STUD WALLS SHALL BE SURFACED
<br />® 15% M.C. MAX, KID, SOUTHERN YELLOW PINE MEETING OR EXCEEDING THE
<br />FOLLOWING MINIMUM GRADES:
<br />2X4 STUD WALLS - STUD GRADE
<br />2X6 AND LARGER FRAMING - NO. 2 GRADE, Fb=1200 PSI, MIN.
<br />4X4 POSTS - STUD GRADE
<br />2. MINIMUM TWO-2X STUDS UNDER ALL CONCENTRATED LOADS.
<br />3. ML = MICRO -LAM BEAMS BY "TRUSJOIST", GRADE Fb = 2925 PSI
<br />OPEN WEBB 4X2 WOOD FLOOR TRUSSES, SHALL BE 16" DEEP BY
<br />TRUSJOIST-MACILLAN WITH INSTALLATION IN ACCORDANCE WITH
<br />RECOMMENDATIONS AND GUIDLINES OF THE VENDOR. PROVIDE STRUT
<br />BRACING, BRIDGING AND BLOCKING AS REQUIRED OR SHOWN. SHOP DRAWINGS
<br />SHALL BE SUBMITTED FOR THE ENGINEERS REVIEW. PERMANANT BRACING,
<br />BRIDGING AND SHEATHING SHALL BE INSTALLED PRIOR TO FLOOR LOADS.
<br />4. ALL FRAMING CONNECTIONS SHALL BE BASED ON (USP) LUMBER CONNECTORS.
<br />NAILING REQUIEMENT LITERATURE. A CATALOG OF CONNECTORS SHALL BE
<br />KEPT ON SITE AT ALL TIMES AND REFERED TO BY THE FRAMING
<br />SUBCONTRACTOR. ALL NAILS AND CONNECTORS EXPOSED TO THE ATMOSPHERE
<br />SHALL BE GALVANIZED.
<br />5. PROVIDE WOOD FRAME SUPPORT AND ACCESS PLATFORM ABOVE BOTTOM TRUSS
<br />CHORDS AS REQUIRED BY MECHANICAL CONTRACTOR. CONTRACTOR SHALL VERIFY
<br />LOCATIONS AND PROVIDE ROOF TRUSS FABRICATOR WITH LOADS, INSTALLATION
<br />DIMENSIONS AND CLEARANCE REQUIREMENTS NECESSARY FOR TRUSS DESIGN AND
<br />MODIFICATIONS TO STANDARD TRUSSES.
<br />ASSUMED ALLOWABLE SOIL BEARING PRESSURE = 2000 PSI
<br />BUILDING SLAB AND FOOTING SUBGRADES INCLUDING ALL FILL SHALL BE COMPACTED
<br />TO 95% OF THE MODIFIED PROCTOR MAXIMUM DRY DENSITY AT OPTIMUM MOISTURE
<br />PER ASTM D-1557. SOIL SHALL BE GRANULAR MATERIAL CONTAINING LESS THAN
<br />11% OF FINES PASSING A #200 SIEVE. DENSITY TESTING AT CONTRACTORS OPTION.
<br />DESIGN CRITERIA AND STRUCTURAL NOTES
<br />1. ALL WORK SHALL BE IN ACCORDANCE WITH THE RESIDENTIAL FLORIDA BUILDING
<br />CODE 2010, LOCAL ORDINANCE AND REGULATIONS.
<br />2. LIVE LOADS
<br />ROOF = 30 PSF
<br />FLOOR = 40 PSF
<br />DEAD LOADS:
<br />ROOF -TOP CHORDS = 7.5 PSF, BOTTOM CHORD = 10 PSF
<br />FLOOR = 20 PSF
<br />3. WIND LOADS: 150 MPH WIND SPEED = 25 PSF, BASIC
<br />DESIGN PER RFBC 2010.
<br />4. MATERIALS OF CONSTRUCTION AND NOTES
<br />ALL CONCRETE TO BE IN ACCORDANCE WITH "BUILDING CODE REQUIREMENTS
<br />FOR REINFORCED CONCRETE" (ACI 318-95).
<br />ALL CONCRETE ------ f'c = 2,500 PSI, 5" SLUMP MAX, FILLED CELLS
<br />2,500 PSI, "PEAROCK CONCRETE", 9" SLUMP MAX. USE WATER OR CURING
<br />COMPOUND FOR SLAB -ON -GRADE AND PLACE NO CONSTRUCTION MATERIALS
<br />THEREON UNTIL CONCRETE HAS REACHED 2/3 OF IT'S COMPRESSIVE STRENGTH.
<br />CONCRETE TESTING AT CONTRACTOR'S OPTION.
<br />ALL REINFORCING STEEL SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000 PSI
<br />AND SHALL CONFORM TO ASTM A-615. LAP SPLICE BARS 25 TIMES.
<br />ALL WELDED WIRE FABRIC SHALL CONFORM TO ASTM A 82-02..
<br />MASONRY
<br />1. HOLLOW REGULAR WEIGHT CONCRETE MASONRY UNITS EIGHT 8 INCHES AND OVER
<br />IN WIDTH SHALL CONFORM TO STANDARD SPECIFICATIONS FOR HOLLOW LOAD -
<br />BEARING CONCRETE MASONRY UNITS, GRADE N-II CONFORMING TO ASTM C90-03,
<br />WITH A 28 DAY COMPRESSIVE STRENGTH OF NOT LESS THAN 1,500 PSI, f'm
<br />(net section area).
<br />2. BRACE HOUSE WALLS UNTIL FILL AND CONCRETE FLOOR SLAB ARE INSTALLED.
<br />3. MORTAR MIXES SHALL MEET ASTM C-270-04, PROPORTION PER THE FOLLOWING TYPES:
<br />TYPE S (1,800 PSI) OR M (2,500 PSI).
<br />4. CELLS CONTAINING VERTICAL REINFORCING BARS SHALL BE FILLED WITH 'PEAROCK"
<br />CONCRETE AT A 28 DAY COMPRESSIVE STRENGTH OF 2,500 PSI AND CONTAINING
<br />NOT LESS THAN 5 BAGS OF CEMENT PER CUBIC YARD AND A SLUMP OF
<br />9 INCHES MAXIMUM.
<br />NOTE: VARIOUS ITEMS WITHIN THE GENERAL
<br />NOTES DO NOT APPLY TO THIS PROJECT.
<br />GARDEN VILLAS
<br />FOR
<br />GARDEN VILLAS, LLC
<br />38070DAUGHTERYROAD
<br />ZEPHYRHILLS, FLORIDA 33540
<br />SECTION 2, TO u�NSHIP 2 6S, RANGE 21 E
<br />LOCATION MAP
<br />Nrs
<br />�Qq"coo"�v
<br />UTILITY COMPANIES:
<br />TELEPHONE:
<br />VERIZON
<br />27835 WESLEY CHAPEL BLVD.
<br />SUITE 100
<br />WESLEY CHAPEL, FLORIDA
<br />813-907-8511
<br />CABLE:
<br />BRIGHT HOUSE NETWORK
<br />CONSTRUCTION DEPARTMENT
<br />2728 S. FALKENBURG ROAD
<br />ZEPHYRHILLS, FLORIDA 33539
<br />813- 788- 7634
<br />ELECTIRC:
<br />DUKE ENERGY
<br />36906 EILAND BLVD.
<br />ZEPHYRHILLS, FLORIDA 33539
<br />813- 782- 7237
<br />OV3 (q/0
<br />�P
<br />.7LILIJP
<br />ALL WORK SHALL COMPLY WIT11 X11NG � �
<br />CoDES. TLORIDABl)IL
<br />PREVAILINC
<br />CODE. N �� 1DN' At. ELECTRIC CODE AND
<br />CITY OF ZE.P�iVV--'S ORDiNpNCES
<br />OWNER: GARDEN VILLAS, LLC
<br />38070 DA UGHTERY ROAD
<br />ZEPHYRHILLS, FLORIDA 33540
<br />CONTRACTOR: TO BE DETERMINED
<br />SURVEYOR: TO BE DETERMINED
<br />REVIEW UK I✓--I,--
<br />CITY OF ZEPHYRHILLS
<br />PLANS EXAMINER
<br />BEFORE DIGGING CALL
<br />SUNSHINE STATE ONE -CALL OF FLA
<br />1-800-432-4770
<br />FSS 93,240, SECTI❑NS 556.101-556,111
<br />REQUIRES MIN. OF 2 DAYS AND MAX. OF
<br />5 DAYS NOTICE BEFORE YOU EXCAVATE,
<br />3,%
<br />WA TER:
<br />CITY OF ZEPHYRHILLS
<br />5335 8th STREET
<br />ZEPHYRHILLS, FLORIDA 33542
<br />813- 780- 0008
<br />ATTN.- JOHN BOSTIC
<br />WASTE WA TER:
<br />CITY OF ZEPHYRHILLS
<br />39825 ALSOTN AVENUE
<br />ZEPHYRHILLS, FLORIDA 33542
<br />813- 780-0029
<br />ATTN.- JOHN BOSTIC
<br />DRA WING INDEX
<br />1.
<br />SITE PLAN, NOTES AND DRAWING INDEX
<br />� 2.
<br />SURVEY PLAN
<br />3.
<br />SITE PLAN WITH PHASES
<br />4.
<br />MODEL
<br />CENTER FLOOR PLANS
<br />5.
<br />MODEL
<br />CENTER FL 0 OR PLANS UNITS 7-9
<br />6.
<br />MODEL
<br />CENTER ELEVA TIONS
<br />7.
<br />MODEL
<br />CENTER ELEVATIONS
<br />8.
<br />MODEL
<br />CENTER FOUNDATION PLAN
<br />9.
<br />MODEL
<br />CENTER PLUMBING PLAN
<br />10.
<br />MODEL
<br />CENTER ELECTRIC PLAN
<br />11.
<br />MODEL
<br />CENTER MECHANICAL PLAN
<br />12.
<br />MODEL
<br />CENTER TRUSS PLAN
<br />13.
<br />CONCRETE DETAILS
<br />14.
<br />WOOD DETAILS
<br />15.
<br />FLOOR
<br />PLAN BUILDINGS 1-6
<br />16.
<br />FL 0 OR
<br />PLAN BUILDINGS 10-16
<br />DO NOT SCALE DRAWINGS
<br />The contractor shall verify all plans and existing dimensions
<br />and conditions on the job site and shall immediately notify
<br />the engineer in writing of any discrepancies before
<br />proceeding with the work or be responsible for some.
<br />Emails: rroberts.egi®gmail.com troutwein-clem®outlook.com
<br />I HEREBY CERTIFY:
<br />THAT THE CONSTRUCTION PLANS SHOWN ARE IN COMPLIA CE
<br />WITH CHAPTER 16, SECTION 1609 OF THE 2010 FLORIDA ILDIP
<br />FOR 150 MPH ULTIMATE DESIGN WIND SPEEII,� (RISK C TEGO
<br />ALONG WITH THE ENTIRE 2010 FLORIDA BUILDING COVEN RESIDENT L.
<br />EGI-ENGINEERING GREAT IDEAS, LLC
<br />William H Roberts P E
<br />C10
<br />Cr
<br />O
<br />q
<br />h
<br />a
<br />.■■.■■■■■
<br />■.■■.■■■■
<br />::
<br />_ME
<br />,
<br />i
<br />i
<br />• _
<br />• -
<br />_
<br />'
<br />ME
<br />IN
<br />■■
<br />■■
<br />■■
<br />■■
<br />.■
<br />■■
<br />■■
<br />IN
<br />■■
<br />■■
<br />.■
<br />■■
<br />.■
<br />■■
<br />■■
<br />■■
<br />■■
<br />ME
<br />ME
<br />ME
<br />M■
<br />■■
<br />.■
<br />IN
<br />ME
<br />ME
<br />■N
<br />EM
<br />■M
<br />ME
<br />ME
<br />ME
<br />MIMMMMMMM
<br />■■■■...■■
<br />- '
<br />11M
<br />I
<br />.10
<br />IN
<br />�IN
<br />.I
<br />'■
<br />■
<br />'■
<br />IN
<br />101
<br />011
<br />101
<br />IN
<br />■■■■■■■■■
<br />i
<br />DRAWN
<br />CLEM TRAUTWEIN
<br />NTS
<br />:ODE CHECKED do APPROVED
<br />II)
<br />CET 4-20-15
<br />1906 W. Thonotosassa Road ! ,
<br />Suite 2 /
<br />Plant City, Florida 33563
<br />P.E. #42712 4-28-15
<br />TEL (813) 752-7078 DATE
<br />CA #29098 (NOT VALID WITHOUT FOR SEAL OR STAMP)
<br />C 145 74A
<br />SHEET OF 16