<br />INTERIOR UNIT
<br />1.5" FIBERGLASS SUPPLY DUCT R-6
<br />CROWN SPIN -IN FITTING
<br />WITH DAMPER
<br />i
<br />ROUND METAL DUCT R-6
<br />(EXTERNAL INSULATION)
<br />CEILING
<br />INSULATED ROUND R-6
<br />FLEXIBLE DUCT
<br />(MAX. 10'-0" LONG)
<br />ATTACH WITH
<br />PANDUIT STRAP 6 TAPE PER CODE
<br />PRE -INSULATED TITUS
<br />2x2 SUPPLY DIFFUSER
<br />CEILING DIFFUSER
<br />CEILING DIFFUSER RUNOUT DETAIL
<br />NOT TO SCALE
<br />INTERIOR UNITS - HVAC NOTES
<br />DETAILS AND SCHEDULES
<br />SYSTEM DESCRIPTION" 2.0 Ton Split System With Heat Pump
<br />EQUIPMENT SCHEDULE: GOODMAN
<br />15 SEER HEAT PUMP SYSTEM with "R-41OA" Refrigerant
<br />CU MD #RQPL-B048-JK010AA Heat Pump
<br />BTUH COOLING CAPACITY 24,000 SEER 15.00 HSPF 7.8
<br />BTUH HEATING CAPACITY 24,000
<br />BLOWER SPEED CFM ® .3" WC Cooling 800 Heating 800
<br />ELECTRICAL REQUIREMENTS
<br />CU-1 MCA 35 MOCP 60 AMPS VOLTS 120 240 1 60
<br />AH-1 MINIMUM AAPACITY 28.4 MAX FUSE 40 AMPS
<br />PIPING SIZE 3 8" LIQUID 1 1 8" SUCTION w 1 2" INSULATION
<br />3 4" CONDENSATE DRAIN
<br />CONTROLS: Programmable Thermostat
<br />FILTER TYPE: 1" pleated throw -a -ways
<br />DUCT SYSTEM: R-6 fiberglass/foil-flex w/Crown #1580 register boxes,
<br />damper collars, and Air Mate grilles. All joints sealed with Fasson #0801
<br />pressure sensitive tape.
<br />All work shall conform to the requirements of the Current Florida Unified
<br />Mechanical Code, 2008 National Electrical Code, and all Pasco
<br />Country Codes.
<br />Note: General Contractor has the option of utilizing an Equivalent Manufacturers HVAC
<br />Package Heat Pump System.
<br />GENERAL A/C NOTES:
<br />1. PLANS INDICATE THE GENERAL LAYOUT AND LOCATION OF THE MECHANICAL SYSTEM COMPONENTS.
<br />UNLESS SPECIFIED DIMENSIONS ARE NOTED, THE ACTUAL LOCATION OF THOSE COMPONENTS SHALL BE
<br />DETERMINED IN THE FIELD IN COORDINATION WITH THE WORK OF OTHER TRADES, THE USE OF
<br />MANUFACTURER'S SHOP DRAWINGS AND SIMILAR CERTIFIED DATA.
<br />2. CONSTRUCTION SHALL COMPLY WITH LOCAL BUILDING CODES ADOPTED AT THE TIME OF PERMIT
<br />APPLICATION AND THE 2010 FLORIDA UNIFIED BUILDING CODE, FLORIDA MECHANICAL AND
<br />ENERGY CODES.
<br />3. SUBMIT SHOP DRAWINGS OF ALL EQUIPMENT AND MATERIAL FOR REVIEW. INSTALL AND TEST ALL
<br />EQUIPMENT AND MATERIAL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS.
<br />4. DUCTWORK, AIR DEVICES AND OTHER ITEMS OF THE AIR DISTRIBUTION SYSTEM SHALL BE SUPPORTED
<br />DIRECTLY FROM THE BUILDING STRUCTURE AND NOT TO THE CEILING OR CEILING SUSPENSION SYSTEM.
<br />COORDINATE LOCATION OF ALL AIR DEVICES, WALL CAPS, ROOF CAPS AND LOUVERS WITH ELECTRICAL,
<br />ARCHITECTURAL AND PLUMBING WORK.
<br />5. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF
<br />"SMACNA" DUCT CONSTRUCTION STANDARDS AND COMPLY WITH THE LATEST "NFPA" 90A REQUIREMENTS.
<br />6. ALL DUCT DIMENSION AS SHOWN ON THE DRAWINGS ARE CLEAR INSIDE DIMENSIONS. ADD 3" FOR
<br />EXTERIOR DUCT DIMENSIONS.
<br />7. ALL FLEXIBLE DUCT SHALL BE CLASS 1 R-6 INSULATED REINFORCED METAUZED JACKET, AIR -TIGHT,
<br />INNER CORE, WITH ENCAPSULATED WIRE HELIX.
<br />8. ALL WALL MOUNTED THERMOSTATS SHALL BE INSTALLED AT A CENTER LINE ELEVATION OF 54" ABOVE
<br />FINISHED FLOOR UNLESS NOTED ON DRAWINGS. LOCATION OF THERMOSTAT SHALL BE COORDINATED WITH
<br />OTHER TRADES FOR A NEAT APPEARANCE. FINAL LOCATION OF THE THERMOSTAT SHALL BE SUBJECT TO
<br />APPROVAL OF THE ARCHITECT OR HIS REPRESENTATIVE IN THE FIELD.
<br />9. PROVIDE A CONDENSATE DRAIN SYSTEM PER THE 2001 FLORIDA MECHANICAL CODE SECTION 307.
<br />a. PROVIDE P-TRAPS AT ALL CONDENSATE DRAIN LINES. SLOPE DRAIN LINES TOWARD THE POINT OF DISCHARGE.
<br />b. (MINIMUM 1 /8" PER FOOT). INSULATE DRAIN LINES WITH 1 /2" THICK CLOSED CELL
<br />RUBBER PIPE INSULATION.
<br />c. CONDENSATE LINES TO BE PVC. LINES TO BE A MINIMUM OF 3/4" diameter.
<br />EXTEND TERMINATION OF DRAINS 12" FROM THE EXTERIOR WALL TO GREEN AREA.
<br />10. PROVIDE REINFORCED CONCRETE EQUIPMENT PADS FOR THE CONDENSINIG UNITS. PADS TO BE SIZED
<br />AND SPACED TO PROVIDE MANUFACTURER'S REQUIRED SERVICE CLEARANCES.
<br />Elements of Load
<br />Insulation / R-value
<br />Area lin.ft.
<br />U-Value I Heat Loss
<br />Heat Gain
<br />Gross Wall
<br />1580
<br />GLASS Solar Gain
<br />2093
<br />Glass 1
<br />Single
<br />48
<br />0.42
<br />487
<br />Glass 2
<br />Select
<br />0
<br />Skylight
<br />Select
<br />0
<br />Doors
<br />Insulated or Storm
<br />40
<br />0.4
<br />384
<br />368
<br />Net Walls
<br />R-5
<br />1492
<br />0.06
<br />2148
<br />2059
<br />Ceilings
<br />R-30
<br />929
<br />0.033
<br />736
<br />1380
<br />Floors
<br />Select
<br />0
<br />0
<br />Open Floors
<br />Select
<br />0
<br />0
<br />Slab Floors
<br />No Insulation
<br />929
<br />0.8
<br />17,837
<br />0
<br />Volume of your Building or Zone (cu.ft.)
<br />18,084
<br />3208
<br />1384
<br />VARIFS
<br />TYPICAL A& SLAB
<br />People
<br />750
<br />Appliances
<br />3000
<br />Sub Total
<br />24,800
<br />14,426
<br />Duct Loss Gain
<br />2658
<br />4411
<br />Sensible Load
<br />27,457
<br />18,837
<br />Latent Load
<br />1843
<br />TOTAL BTUH
<br />27,457
<br />20,680
<br />SLAB TO BE 4"
<br />WIDER THEN THE
<br />UNIT.
<br />LEGEND:
<br />SumMary
<br />BTUH
<br />Tons
<br />Total Heating Load
<br />27,457
<br />Total Cooling Load
<br />20,680
<br />1.7
<br />206 crm 10"X10" SUPPLY AIR GRILL
<br />AND AIR FLOW CFM
<br />80 CFM 6"X1O" SUPPLY AIR GRILL
<br />AND AIR FLOW CFM
<br />10"4
<br />�- SUPPLY AIR DUCT (R-6)
<br />AND DUCT SIZE
<br />12"X14"
<br />- - - RETURN AIR DUCT (R-6)
<br />AND DUCT SIZE
<br />® 24"SQ. RETURN AIR GRILLE
<br />A/C AREA = 929 S.F.
<br />END UNIT
<br />HVAC NOTES
<br />1 All equipment is new, air handlers located on steel channell, supported from deck above with concrete deck anchors.
<br />Bottom of plenum box of return held 2" off bottom of stand with emergency condensate drain pan extending out 3" on all
<br />four sides with emergency overflow shut down switch on condensate overflow mounted on emergency part
<br />2. Rectangular ductwork to be 1.5" fiberous ductboard, Joints to be sealed with pressure sensitive "UL" 181 silver tape and
<br />staples as recommended by manufacuterer. Round ductwork to be R-6 flex duct using silver tape, "UL" 181 and nylon panduit
<br />straps at Crown dampened collar.
<br />3. All duct sizes are clear inside dimensions, allow for 1.5" R-6 fiberglass ductwork
<br />4. Rectangular ductwork to be hung with 2" u-channel 6 minimum 12-gauge wire on 6' centers and flex duct to be hung with 2"
<br />metal strap on 5' centers and at elbow down to air distribution as needed. All duct materials and installation of same to comply
<br />with section 503 of Florida Energy code for Building Construction effective March 1, 2002.
<br />5. Smoke detectors shall be installed in return duct to shut down system, located prior to introduction of ventilation outside air.
<br />6. Coordinate location of air distribution with ceiling grid and lights.
<br />7. Contractor test and balance of systems to within 10% of design airflows shown and submit air balance report and equipment
<br />performance to owner upon completion.
<br />8. Thermostats to be mounted at 52" AFF.
<br />CONC.
<br />SLAB
<br />'CONNECT
<br />END UNITS - HVAC NOTES
<br />DETAILS AND SCHEDULES
<br />SYSTEM DESCRIPTION" 2.0 Ton Split System With Heat Pump
<br />EQUIPMENT SCHEDULE: GOODMAN
<br />15 SEER HEAT PUMP SYSTEM with "R-410A" Refrigerant
<br />CU MD #RQPL-B048-JK010AA Heat Pump
<br />BTUH COOLING CAPACITY 24,000 SEER 15.00 HSPF 7.8
<br />BTUH HEATING CAPACITY 24,000
<br />BLOWER SPEED CFM ® .3" WC Cooling 800 Heating 800
<br />ELECTRICAL REQUIREMENTS
<br />CU-1 MCA 35 MOCP 60 AMPS VOLTS 120 240 1 60
<br />AH-1 MINIMUM AAPACITY 28.4 MAX FUSE 40 AMPS
<br />PIPING SIZE 3 8" LIQUID 1 1 8" SUCTION wl 1 2" INSULATION
<br />3 4" CONDENSATE DRAIN
<br />CONTROLS: Programmable Thermostat
<br />FILTER TYPE: 1" pleated throw -a -ways
<br />DUCT SYSTEM: R-6 fiberglass/foil-flex w/Crown #1580 register boxes,
<br />damper collars, and Air Mate grilles. All joints sealed with Fasson #0801
<br />pressure sensitive tape.
<br />All work shall conform to the requirements of the Current Florida Unified
<br />Mechanical Code, 2008 National Electrical Code, and all Pasco
<br />Country Codes.
<br />Note: General Contractor has the option of utilizing an Equivalent Manufacturers HVAC
<br />Package Heat Pump System.
<br />GENERAL A/C NOTES:
<br />1. PLANS INDICATE THE GENERAL LAYOUT AND LOCATION OF THE MECHANICAL SYSTEM COMPONENTS.
<br />UNLESS SPECIFIED DIMENSIONS ARE NOTED, THE ACTUAL LOCATION OF THOSE COMPONENTS SHALL BE
<br />DETERMINED IN THE FIELD IN COORDINATION WITH THE WORK OF OTHER TRADES, THE USE OF
<br />MANUFACTURER'S SHOP DRAWINGS AND SIMILAR CERTIFIED DATA.
<br />2. CONSTRUCTION SHALL COMPLY WITH LOCAL BUILDING CODES ADOPTED AT THE TIME OF PERMIT
<br />APPLICATION AND THE 2010 FLORIDA UNIFIED BUILDING CODE, FLORIDA MECHANICAL AND
<br />ENERGY CODES.
<br />3. SUBMIT SHOP DRAWINGS OF ALL EQUIPMENT AND MATERIAL FOR REVIEW. INSTALL AND TEST ALL
<br />EQUIPMENT AND MATERIAL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND RECOMMENDATIONS.
<br />4. DUCTWORK, AIR DEVICES AND OTHER ITEMS OF THE AIR DISTRIBUTION SYSTEM SHALL BE SUPPORTED
<br />DIRECTLY FROM THE BUILDING STRUCTURE AND NOT TO THE CEILING OR CEILING SUSPENSION SYSTEM.
<br />COORDINATE LOCATION OF ALL AIR DEVICES, WALL CAPS, ROOF CAPS AND LOUVERS WITH ELECTRICAL,
<br />ARCHITECTURAL AND PLUMBING WORK.
<br />5. ALL DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH THE LATEST EDITION OF
<br />"SMACNA" DUCT CONSTRUCTION STANDARDS AND COMPLY WITH THE LATEST "NFPA" 90A REQUIREMENTS.
<br />6. ALL DUCT DIMENSION AS SHOWN ON THE DRAWINGS ARE CLEAR INSIDE DIMENSIONS. ADD 3" FOR
<br />EXTERIOR DUCT DIMENSIONS.
<br />7. ALL FLEXIBLE DUCT SHALL BE CLASS 1 R-6 INSULATED REINFORCED METALIZED JACKET, AIR -TIGHT,
<br />INNER CORE, WITH ENCAPSULATED WIRE HELIX.
<br />8. ALL WALL MOUNTED THERMOSTATS SHALL BE INSTALLED AT A CENTER LINE ELEVATION OF 54" ABOVE
<br />FINISHED FLOOR UNLESS NOTED ON DRAWINGS. LOCATION OF THERMOSTAT SHALL BE COORDINATED WITH
<br />OTHER TRADES FOR A NEAT APPEARANCE. FINAL LOCATION OF THE THERMOSTAT SHALL BE SUBJECT TO
<br />APPROVAL OF THE ARCHITECT OR HIS REPRESENTATIVE IN THE FIELD.
<br />9. PROVIDE A CONDENSATE DRAIN SYSTEM PER THE 2001 FLORIDA MECHANICAL CODE SECTION 307.
<br />a. PROVIDE P-TRAPS AT ALL CONDENSATE DRAIN LINES. SLOPE DRAIN LINES TOWARD THE POINT OF DISCHARGE.
<br />b. (MINIMUM 1/8" PER FOOT). INSULATE DRAIN LINES WITH 1/2" THICK CLOSED CELL
<br />RUBBER PIPE INSULATION.
<br />c. CONDENSATE LINES TO BE PVC. LINES TO BE A MINIMUM OF 3/4" diameter.
<br />EXTEND TERMINATION OF DRAINS 12" FROM THE EXTERIOR WALL TO GREEN AREA.
<br />10. PROVIDE REINFORCED CONCRETE EQUIPMENT PADS FOR THE CONDENSINIG UNITS. PADS TO BE SIZED
<br />AND SPACED TO PROVIDE MANUFACTURER'S REQUIRED SERVICE CLEARANCES.
<br />Elements of Load
<br />Insulation / R-Value
<br />Area/lin.ft.
<br />U-Value I Heat Loss
<br />Heat Gain
<br />Gross Wall
<br />1593
<br />GLASS Solar Gain
<br />3477
<br />Glass 1
<br />Single
<br />64
<br />0.42
<br />649
<br />Glass 2
<br />Select
<br />0.06
<br />0
<br />Skylight
<br />Select
<br />0
<br />Doors
<br />Insulated or Storm
<br />40
<br />0.4
<br />384
<br />1 368
<br />Net Walls
<br />R-19
<br />1489
<br />0.06
<br />2144
<br />2054
<br />Ceilings
<br />R-30
<br />994
<br />0.033
<br />787
<br />1476
<br />Floors
<br />Select
<br />0
<br />0
<br />Open Floors
<br />Select
<br />0
<br />0
<br />Slab Floors
<br />No Insulation
<br />994
<br />0.8
<br />19,085
<br />0
<br />Volume of your Building or Zone (cu.ft.)
<br />9,277
<br />3432
<br />1480
<br />VARIES
<br />_
<br />People
<br />750
<br />Appliances
<br />3000
<br />Sub Total
<br />26,481
<br />15,999
<br />Duct Loss Gain
<br />2907
<br />4954
<br />Sensible Load
<br />29,368
<br />20,953
<br />Latent Load
<br />1939
<br />TOTAL BTUH
<br />29,388
<br />22,893
<br />TYPICAL ABC SLAB
<br />SLAB TO BE 4"
<br />WIDER THEN THE
<br />UNIT.
<br />I C/%CAIrI.
<br />Tot,fl Cooling Load
<br />2a10"X10" SUPPLY AIR GRILL
<br />AND AIR FLOW CFM
<br />SUPPLY AIR GRILL
<br />AND AIR FLOW CFM
<br />0 0 SUPPLY AIR DUCT (R-6)
<br />AND DUCT SIZE
<br />12"X14"
<br />- - - RETURN AIR DUCT (R-6)
<br />AND DUCT SIZE
<br />® RETURN AIR GRILLE
<br />A/C AREA = 994 S.F.
<br />DO NOT SCALE DRAWINGS
<br />The contractor shall verify all plans and existing dimensions
<br />and conditions on the job site and shall immediately notify
<br />the engineer in writing of any discrepancies before
<br />proceeding with the work or be responsible for same.
<br />Emails: rroberts.egi©gmail.com trautwein_clem@outlook.com
<br />1 HEREBY CERTIFY:
<br />THAT THE CONSTRUCTION PLANS SHOWN ARE IN COMPLIANC
<br />WITH CHAPTER 16, SECTION 1609 OF THE 2010 FLORIDA B D E
<br />FOR 150 MPH ULTIMATE DESIGN WIND SPEED (RISK C E )
<br />ALONG WITH THE ENTIRE 2010 FLORIDA BUILDING CODE, RESIDEN
<br />EGI-ENGINEERING GREAT IDEAS, LLC
<br />William H. Roberts, P.E.
<br />1906 W. Thonotosassa Road
<br />Suite 2 ?
<br />Plant City, Florida 33563
<br />P.E. #42712
<br />TEL (813) 752-7078 DATE
<br />CA #29098 (NOT VALID WITHOUT FOR SEAL OR STAMP)
<br />0
<br />w
<br />��
<br />2
<br />b
<br />U
<br />0
<br />q
<br />h
<br />x
<br />a
<br />■■■■■■■,
<br />.■■■■■■■■
<br />■■■■■MIME■
<br />■■
<br />•
<br />::
<br />•
<br />:
<br />, _
<br />-
<br />_
<br />_
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />�■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />■■
<br />no
<br />■■
<br />■■
<br />■■
<br />no
<br />■■■■■■■■■
<br />,�rl
<br />�
<br />•
<br />_
<br />��_.�
<br />I�
<br />■1
<br />IN
<br />■I
<br />'■ III
<br />■�
<br />'■
<br />■
<br />1■
<br />■
<br />IN
<br />■�
<br />IN
<br />MIL------�■'
<br />1
<br />J
<br />DRAWN
<br />CLEM TRAUTWEIN
<br />SCAM-
<br />1/4" = 1'-0"
<br />CHECKED & APPROVED
<br />CET 4-20-15
<br />C 145 74A
<br />SHEET 1OF 16
<br />
|