(VIA PHOTOCELL) <br />GARAGE BUILDING ELECT I AL PLAN - <br />SCALE: 1 /4"=1'-O" 0 2' 4' 8' <br />PLAN KEY NOTES: <br />0 1 /2" PLYWOOD PAINTED. ALL PLYWOOD <br />TO BE PLACED BETWEEN HEIGHT 3'-0" <br />AND 7'-0". <br />BATTERY CHARGER. (VERIFY LOCATION <br />WITH OWNER). <br />1. 3-J3, THWN Cu, 1-1 /4'C. <br />2. 3-#3, 1-#8 GND, THWN Cu, 1-1/4"C. <br />3. 100 AMP, 2P, S/N ENCLOSED CIRCUIT BREAKER, <br />NEMA 3R ENCLOSURE. <br />4. 1-4 THWN Cu, GREEN GROUND WIRE, IN 1 /2"C. <br />5. 5/8"0 x 101 COPPERCLAD" GROUND ROD. <br />INSTALL ADDITIONAL GROUND RODS AS REQUIRED <br />TO PROVIDE MAX. OF 25 OHMS RESISTANCE TO <br />GROUND. <br />6. 3-#3, 1-#8 GND, THWN Cu, 1-1 /4"C. <br />MAIN <br />BREAKER <br />TO POWER <br />CO. XFMR <br />(120/240V, <br />1 PH, 3W <br />SERVICE) <br />POWER RISER DIAGRAM <br />NOT TO SCALE <br />C.W.P. <br />PANEL G SERMCE 120/24OV-10-3W MINIMUM BREAKER AIC 10,000A <br />LOCATION MAIN GARAGE ROOM RATING 100A M.L.O. MOUNTING SURFACE / NEMA-1 <br />LOAD DESCRIP11ON <br />BKR <br />KVA <br />CKT. <br />NO. <br />KVA <br />BKR <br />LOAD DESCRIPTION <br />TRIP <br />POLES <br />OA <br />OB <br />OA <br />OB <br />TRIP <br />POLES <br />L-LIGHTS <br />20 <br />1 <br />0.5 <br />1 <br />2 <br />1.2 <br />20 <br />1 <br />R-EQUIPMENT-CABLE ROOM <br />L-LIGHTS (1) <br />20 <br />1 <br />.15 <br />3 <br />41 <br />1.2 <br />20 <br />1 <br />R-EQUIPMENT-CABLE ROOM <br />R-RECEPTACLES <br />20 <br />1 <br />0.9 <br />5 <br />6 <br />1.0 <br />20 <br />1 <br />R-EQUIPMENT-CABLE ROOM <br />L-SITE UGHTING <br />20 <br />1 <br />0.8 <br />7 <br />8 <br />1.5 <br />20 <br />1 <br />E-CHARGER <br />M-EF-1 <br />20 <br />1 <br />0.2 <br />9 <br />10 <br />0.8 <br />20 <br />1 <br />E-GARAGE DOOR OPENER <br />S-SPARE <br />20 <br />1 <br />0.1 <br />11 <br />12 <br />.36 <br />20 <br />1 <br />R-RECEPTACLES <br />E-EQUIPMENT RACK <br />20 <br />1 <br />.50 <br />131141 <br />.36 <br />20 <br />1 1 <br />R-RECEPTACLES <br />R-RECEPTACLES <br />20 <br />1 <br />0.40 <br />1516 <br />.36 <br />20 <br />1 <br />R-RECEPTACLES <br />SPACE <br />- <br />1 <br />0.0 <br />1718 <br />- <br />- <br />1 <br />SPACE <br />SPACE <br />- <br />1 <br />- <br />19 <br />20 <br />- <br />- <br />1 <br />SPACE <br />SPACE <br />- <br />1 <br />- <br />2122 <br />- <br />- <br />1 <br />SPACE <br />SPACE <br />- <br />1 <br />- <br />23 <br />24 <br />- <br />- <br />1 <br />SPACE <br />SPACE <br />125 <br />26 <br />- <br />- <br />1 <br />SPACE <br />SPACE <br />- <br />1 <br />- <br />27 <br />28 <br />- <br />- <br />1 <br />SPACE <br />SPACE <br />1 <br />291301 <br />- <br />- <br />1 <br />SPACE <br />1 X, <br />r <br />>,- <br />35 <br />41 <br />36 <br />40 <br />42 <br />TOTALS <br />2.1 <br />1.4 <br />3.4 <br />3.4 <br />SERVES <br />CONN. LOAD - KVA <br />D.F. <br />CALC. DEMAND - KVA <br />NOTES: <br />1. THIS CIRCUIT CONTROLLED <br />BY PHOTOCELL. <br />LIGHTING <br />1.45 <br />1.25 <br />1.81 <br />RECEPTACLES - 1ST 10 KVA <br />5.78 <br />1.00 <br />5.78 <br />RECEPTACLES - ABOVE 10 KVA <br />0.00 <br />0.50 <br />0.00 <br />MECHANICAL <br />0.00 <br />1.00 <br />0.00 <br />EQUIPMENT <br />2.80 <br />1.00 <br />2.80 <br />APPLIANCE <br />0.00 <br />0.75 <br />0.00 <br />SPARE/SPACE <br />0.20 <br />1.00 <br />0.20 <br />OTHER <br />0.00 <br />1.00 <br />0.00 <br />TOTALS <br />10.23 <br />10.59 <br />CALCULATED AMPS: 44 <br />LIGHTING FDCTURE SCHEDULE <br />TYPE <br />DESCRIPTION <br />VOLTAGE <br />LAMPS <br />REMARKS <br />AC <br />FLUORESCENT STRIP FIXTURE, ELECTRONIC BALLAST <br />120 <br />2-2T8 <br />GARAGE BUILDING <br />COOPER METALUX 1424 STRIP UGHT 48" <br />EXTERIOR WALL LANTERN <br />18W <br />AD <br />INCON 304H-18QE <br />120 <br />1- PL <br />TRASH COMPACTOR, GARAGE BLDG. <br />CHLORIDE <br />CONNECT TO UNSWITCH LEG <br />` <br />CEL <br />120 <br />OF ROOM LIGHTING CIRCUIT <br />AX <br />CHLORIDE <br />CONNECT TO UNSWITCHED LEG <br />EIXT SIGN RLNIRA <br />120 <br />OF ROOM LIGHTING CIRCUIT <br />GROUNDING <br />BAR <br />BONDING JUMPER <br />NEUTRAL <br />BUS <br />ENCLOSURE <br />( <br />TYP <br />FULL SIZE FULL SIZE GROUNDING ELECTRODE CONDUCTOR <br />(SEE RISER DIAGRAM FOR SIZE) <br />PANEL MAIN UNDERGROUND METAL WATER PIPE <br />G (BOND TO PIPING PIPING ISINSTALLED)LY WHEN METAL <br />FL/GRADE <br />FOOTER STEEL <br />FULL <br />5/8"x10' <br />GROUND RODS <br />GROUNDING DETAIL <br />NOT TO SCALE <br />.vot IltlWo... <br />MAP <br />:".cENSF �SGM ENGINEERING, INC. <br />•. FACILITIES CONSULTING ENGINEERS <br />* : _ 935 Lake Baldwin Lane TEL- (407) 767-5188 <br />• Baldwin Park, FAX: (407) 767-5772 <br />TAT � Orlando, Florida 32814 $r CA_00006208 <br />' •.,• (� Project number. 2010-090 <br />r www.sgmengineenng.com <br />- FL61756 Copyright ©2010 SGM Engineering, Inc. <br />FORUME <br />ARCHITECTURE & <br />INTERIOR DESIGN, INC. <br />PLANNING I ARCHITECTURE I INTERIOR DESIGN <br />i <br />745 orienta avenue, suite 1121 <br />altamonte springs, fl 32701 <br />phone: 407.830.1400 <br />fax: 407.830.4143 <br />AA0002731 <br />I www.forumarchitecture.com <br />Fort King <br />Colony <br />Apartments <br />City of Zephyrhills, FL <br />Q SHEET REVISIONS: <br />EDITED BY: NDM <br />z PROJECT NO. 10-2651 <br />414L;.W111117,A1 Lr Ira. 11. d. u._ .T� 11- _. _-I � II. - -I <br />IIllll11`• <br />