GENERAL ELECTRICAL NOTES <br />1. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (N.E.C. 2008) AND <br />GOVERNING MUNICIPAL, STATE AND LOCAL CODES. ALL MATERIAL SHALL BE NEW AND SHALL BEAR THE <br />U.L LABEL WHERE APPLICABLE. <br />2. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS <br />WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY THE <br />OWNER. <br />3. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE <br />CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM <br />AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING <br />ORDER. <br />4. CONTRACTOR SHALL MAKE ALL NECESSARY CUTTING AND DO ALL THE REPATCHING AS NECESSARY FOR <br />THE PROPER EXECUTION OF THIS WORK. <br />5. AFTER COMPLETION OF THE INSTALLATION, THE SYSTEM SHALL TEST FREE FROM SHORT CIRCUITS AND <br />GROUNDS. <br />6. WHERE ELECTRICAL CONDUCTORS ARE INSTALLED IN CONDUIT, THE CONDUIT SHALL COMPLY WITH THE <br />N.E.C. REQUIREMENTS. <br />7. ALL CONDUCTORS SHALL BE COPPER. NO CONDUCTOR SHALL BE SMALLER THAN #12 AWG AND SHALL <br />BE RATED FOR 600VOLTS THWN OR THHN INSULATION. INSTALL A GROUNDING CONDUCTOR WITH ALL <br />CIRCUITS, UNLESS NOTED OTHERWISE, SIZED PER N.E.C. 250-122. <br />8. VERIFY BREAKER AND CORRESPONDING WIRE SIZES FOR ALL ELECTRICAL EQUIPMENT. DO NOT ORDER <br />MATERIAL BEFORE VERIFYING BREAKER & WIRE SIZE. REPORT ANY DISCREPANCY IMMEDIATELY TO THE <br />ENGINEER OF RECORD. <br />9. SAFETY SWITCHES SHALL BE SQUARE 'D', GENERAL ELECTRIC, OR WESTINGHOUSE, FUSED OR <br />NON -FUSED AND SIZED AS INDICATED. NEMA 3R WHEN EXPOSED TO WEATHER <br />10. PANELS SHALL BE SQUARE 'D', GENERAL ELECTRIC OR EQUAL, TYPE AND NUMBER OF BREAKERS AS <br />INDICATED ON PANEL SCHEDULE. STENCIL PANEL DESIGNATION ON INSIDE OF PANEL ALL TWO -POLE <br />BREAKERS SHALL BE COMMON TRIP. PROVIDE TYPE WRITTEN SCHEDULE IN EACH LOAD CENTERS. <br />CONNECTION TO MAIN BUS SHALL BE WITH BURNDY ANNULAR COMPRESSION LUGS, PANELS AIC RATING <br />SHALL BE AS INDICATED ON PLANS. <br />11. PROVIDE NAMEPLATES FOR ALL PANEL BOARDS, DISCONNECTS, TRANSFORMER, TERMINAL CABINETS AND <br />ALL ELECTRICAL EQUIPMENT IDENTIFIED BY NAME ON DRAWINGS. <br />12. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN <br />APPROVED THIRD PARTY TESTING AGENCY. <br />13. LOAD DATA IS BASED ON INFORMATION GIVEN ENGINEER AT 11ME OF DESIGN. VERIFY ALL EQUIPMENT <br />AND PANEL SIZES BEFORE ORDERING AND BEFORE INSTALLATION, <br />14. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE ANCHORED TO COMPLY WITH LOCAL CODE FOR WIND <br />RESISTANCE. <br />15. ALL ELECTRICAL AND COMMUNICATIONS OUTLETS TO BE AT 15" A.F.F TO BOTTOM OF OUTLET UNLESS <br />OTHERWISE NOTED, ALL LIGHT SWITCHES SHALL BE 0 48" AFF. TO TOP OF SWITCH. <br />16. TIME CLOCK FOR LIGHTING CONTROL TO BE AN ASTRONOMICAL TIME CLOCK. <br />17. THE CONTRACTOR SHALL CONTACT THE LOCAL POWER COMPANY AND OBTAIN, IN WRITING, THE AVAILABLE <br />FAULT CURRENT OF THE UTILITY TRANSFORMER. THE CONTRACTOR SHALL ENSURE THAT ALL ELECTRICAL <br />EQUIPMENT HAS AN AMP INTERRUPTING CAPACITY (AIC) GREATER THAN THE AVAILABLE FAULT CURRENT <br />AT ANY POINT IN THE ELECTRICAL DISTRIBUTION SYSTEM. <br />18. WIRING METHOD: <br />ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT) UNLESS OTHERWISE <br />NOTED. ALL FITTINGS AND COUPLINGS FOR EMT CONDUIT SHALL BE ALL STEEL RAIN TIGHT <br />COMPRESSION TYPE OR ALL STEEL CONCRETE TIGHT SET SCREW TYPE. <br />SCHEDULE 40 PVC CONDUIT, WITH FITTINGS AND COUPLINGS APPROPRIATE FOR THE USE, SHALL BE <br />USED UNDERGROUND OR BELOW SLABS ON GRADE. <br />19. SEAL ALL NEW CQNDUIf PENETRATIONS THROUGH FIRE RATED WALLS, CEILINGS, FLOORS, ETC., TO <br />MAINTAIN EXISTING FIRE RATING CONDITIONS. FURNISH AND INSTALL FIRE RATED ENCLOSURES FOR ALL <br />EQUIPMENTS PENETRATING FIRE RATED ENVELOPES, SPACES, ECT. <br />I <br />I <br />20. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE WIRING FOR HVAC SYSTEM: A/C EQUIPMENT(S), <br />SMOKE DETECTORS, THERMOSTATS, TEST STATIONS, MOTORIZED VOLUME DAMPERS, ETC. ELECTRICAL <br />CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AND PROVIDE ALL NECESSARY CONTROL <br />WIRING. ELECTRICAL CONTRACTOR TO THOROUGHLY REVIEW MECHANICAL PLANS AND PROVIDE POWER TO <br />ANY MECHANICAL EQUIPMENT OR DEVICE THAT IS NOT SHOWN ON ELECTRICAL PLANS BUT IS SHOWN ON <br />MECHANICAL PLANS. <br />21. INSTALL "GFCI" GROUND FAULT INTERRUPTER RECEPTACLES WITH WEATHERPROOF COVER WITHIN 25 FT <br />OF HVAC EQUIPMENT, MOUNT RECEPTACLE ON UNISTRUT (UNLESS HVAC EQUIPMENT IS SPECIFIED WITH <br />FACTORY INSTALLED CONVENIENT RECEPTACLE) . <br />22. WHEN NEW ELECTRIC SERVICE IS BEING INSTALLED, IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY <br />TO COORDINATE WITH FPL/FPL ENGINEERS ON THE SIZE OF THE FPL TRANSFORMER THAT IS REQUIRED <br />TO PROVIDE THE NEW ELECTRIC SERVICE SHOWN ON ELECTRIC PLANS, GC HAS TO INFORM THE OWNER <br />ABOUT ANY EXTRA FPL CHARGES THAT MIGHT OCCUR IN ORDER TO PULL NEW SERVICE. THIS HAS TO <br />BE DONE AS EARLY AS POSSIBLE DURING THE BIDDING PROCESS. <br />23. ELECTRICAL SERVICE EQUIPMENT MUST BE 3' ABOVE MSL, AND 8' ABOVE N.V.G.D. VERIFY AT SITE. ALL <br />ELECTRICAL EQUIPMENTS SHALL BE INSTALLED ABOVE FLOOD LEVEL. <br />24, CONTRACTOR MUST VISIT THE SITE PRIOR TO BID OR CONSTRUCTION TO VERIFY ALL EXISTING <br />CONDITIONS. BEFORE SUBMITTING BID, BECOME THOROUGHLY FAMILIAR WITH ACTUAL EXISTING CONDITIONS <br />AT THE BUILDING SITE. THE INTENT OF THE WORK IS SHOWN ON THE DRAWINGS AND DESCRIBED <br />HEREINAFTER. BY THE ACT OF SUBMITTING A BID PROPOSAL FOR WORK, THE CONTRACTOR SHALL BE <br />DEEMED TO HAVE MADE SUCH STUDY AND EXAMINATION AND TO ACCEPT ALL CONDITIONS PRESENT AT <br />THE SITE. NO REQUEST FOR ADDITIONAL PAYMENT SHALL BE CONSIDERED AS VALID, DUE TO THE <br />FAILURE TO ALLOW FOR CONDITIONS WHICH MAY EXIST. CONTRACTOR TO REPLACE ANY EXISTING DEVICE <br />OR COMPONENT THAT IS CALLED AS EXISTING IF IT IS NOT FULLY OPERATIONAL <br />25. WIRING METHODS IN ALL PATIENT CARE AREAS TO BE IN COMPLIANCE WITH REDUNDANT GROUNDING <br />REQUIREMENTS OF NEC 2008 SECTION 517.13, <br />26. ALL DIMMING MECHANISMS HAVE TO BE COMPATIBLE WITH FIXTURE DIMMING REQUIREMENTS. CONTRACTOR <br />MUST VERIFY ALL DIMMING MECHANISM AND FIXTURE DIMMING REQUIREMENTS BEFORE ANY ORDERING, <br />INSTALLING, OR WIRING OF ANY DIMMING MECHANISMS AND FIXTURES. <br />27. ALL OUTDOOR RECEPTACLES TO BE GFCI & WEATHER PROOF. <br />28. ALL OUTDOOR DISCONNECTS AND ELECTRICAL PANELS TO BE NEMA-3R. ALL OUTDOOR DISCONNECTS <br />AND ELECTRICAL PANELS IN A SALT SPRAY AREA TO BE NEMA-0. <br />PER FLORIDA BUILDING CODE 2010 ENERGY CONSERVATION: <br />505.7.3 VOLTAGE DROP. <br />505.7.3.1 FEEDERS AND CUSTOMER OWNED SERVICE CONDUCTORS. <br />FEEDER AND CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE <br />DROP OF 2 PERCENT AT DESIGN LOAD. <br />505.7.3.2 BRANCH CIRCUITS. BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM <br />VOLTAGE DROP OF 3 PERCENT AT DESIGN LOAD. <br />505.7.4 COMPLETION REQUIREMENTS. <br />505.7.4.1 DRAWINGS. CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30 DAYS AFTER <br />THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE <br />PROVIDED TO THE BUILDING OWNER, INCLUDING: <br />1. A SINGLE -LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND <br />2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION. <br />505.7.4.2 MANUALS. CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING MANUAL <br />AND MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING OWNER. THE MANUALS SHALL <br />INCLUDE, AT A MINIMUM, THE FOLLOWING: <br />1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF <br />EQUIPMENT REQUIRING MAINTENANCE. <br />2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING <br />MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED. <br />3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY. <br />NOTE: ENFORCEMENT AGENCIES SHOULD ONLY CHECK TO BE <br />SURE THAT THE CONSTRUCTION DOCUMENTS REQUIRE THIS INFORMATION TO BE TRANSMITTED TO <br />THE OWNER AND SHOULD NOT EXPECT COPIES OF ANY OF THE MATERIALS, <br />505.3 TANDEM WIRING: <br />LUMINAIRES DESIGNED FOR USE WITH ONE OR THREE LINEAR FLUORESCENT LAMPS GREATER THAN <br />30 W EACH SHALL BE TANDEM WIRED WHEN TWO OR MORE LUMINAIRES ARE IN THE SAME SPACE <br />AND ON THE SAME CONTROL DEVICE. <br />EXCEPTIONS: <br />1. RECESSED LUMINAIRES MORE THAN 10 FEET APART MEASURED CENTER TO CENTER. <br />2. SURFACE -MOUNTED OR PENDANT LUMINAIRES THAT ARE NOT CONTINUOUS. <br />3. LUMINAIRES USING THREE -LAMP HIGH -FREQUENCY ELECTRONIC OR THREE -LAMP <br />ELECTROMAGNETIC BALLASTS. <br />4. RECESSED LUMINAIRES MORE THAN 10 FEET APART MEASURED CENTER TO CENTER. <br />5. SURFACE -MOUNTED OR PENDANT LUMINAIRES THAT ARE NOT CONTINUOUS. <br />6. LUMINAIRES USING THREE -LAMP HIGH -FREQUENCY ELECTRONIC OR THREE -LAMP <br />ELECTROMAGNETIC BALLASTS. <br />NOTE: <br />PER FLORIDA BUILDING CODE 2010 SEC. 505.2 <br />AREAS ENCLOSED BY CEILING HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE <br />SWITCH TO CONTROL LIGHTING WITHIN THE SPACE AS SHOWN. THESE SWITCHES <br />ARE EQUIPPED WITH OCCUPANT SENSORS THAT WILL TURN THE LIGHTS OFF <br />WITHIN 30 MINUTES OF OCCUPANT LEAVING A SPACE REGULAR SWITCHES CAN <br />BE USED WHEN A CEILING OCCUPANT SENSOR IS USED SEE PLAN. <br />ALL EMERGENCY AND EXIT LIGHTS TO BE CONNECTED AHEAD OF ANY SWITCH <br />OR TIME CLOCK <br />OCCUPANCY SENSOR SWITCHES OR CEILING MOUNT TURN POWER ON WHEN <br />OCCUPANT IS DETECTED FOR 30 MINUTES AND TURN POWER OFF WITHIN 30 <br />MINUTES AFTER AN OCCUPANT LEAVES THE M01ION DETECTOR VICINITY. <br />POSITION OF THE SWITCH (ON/OFF) DOES NOT EFFECT OCCUPANCY SENSOR <br />CONTROL. <br />BRANCH CIRCUIT VOLTAGE DROP <br />MAXIMUM 3% PER 2010 FBC <br />ENERGY CONSERVATION CODE <br />SECTION 505.7.3.2 <br />CIRCUIT LOAD <br />IN AMPS <br />WIRE SIZE <br />COPPER <br />MAXIMUM <br />LENGTH <br />IN FEET <br />5 AMPS OR LESS <br />180 <br />6 AMPS <br />150 <br />7 AMPS <br />130 <br />8 AMPS <br />115 <br />9 AMPS <br />100 <br />10 AMPS <br />90 <br />11 AMPS <br />j12 AWG <br />83 <br />12 AMPS <br />#12 AWG <br />75 <br />13 AMPS <br />70 <br />14 AMPS <br />65 <br />15 AMPS <br />#12 AWG <br />60 <br />16 AMPS <br />57 <br />17 AMPS <br />#12 G <br />54 <br />18 AMPS <br />#12 AWG <br />51 <br />19 AMPS <br />j12 AWG <br />48 <br />20 AMPS <br />#12 AWG <br />45 <br />NOTE: <br />THE LIGHTING SPECIFICATIONS WERE SUPPLIED BY OTHERS. <br />CONTRACTOR TO COORDINATE WITH OWNER/OWNER REP OR <br />OWNER'S INTERIOR DESIGNER. VERIFY THAT THE <br />SPECIFICATIONS ON THIS PLAN ARE WHAT THE OWNER i <br />ASKED FOR AND PROPERLY WIRE CONTROLS PER <br />MANUFACTURER SPECIFICATIONS. ELECTRICAL CONTRACTOR <br />TO CHECK MANUFACTURER SPECIFICATIONS AND <br />INSTALLATION INSTRUCTIONS FOR LIGHTS AND CONTROLS <br />FOR LIGHTS PRIOR TO ORDERING AND ROUGH -IN. <br />NOTE: <br />FOR FLUORESCENT LUMINAIRES, PROVIDE <br />DISCONNECTS AS PER NEC 410.130(G). <br />ACE T TENANT <br />RUN 2# 12 CU + 1# 12 <br />CU GROUND MC CABLE <br />BETWEEN ALL JBOXES OF <br />FUTURE LIGHTS THEN <br />CONNECT TO NEAREST JBOX <br />AS LABELED <br />� J-BOX 1 - <br />I� <br />i=1i=1 n rnnRnitieTl= � I <br />i <br />FUTURE LIGHTING S <br />- E <br />D.1 <br />\_ J <br />N <br />HELL PLAN <br />SCALE: 1 /8" = 1'-0" <br />SCOPE OF WORD: <br />PROVIDE J-BOXES AS SHOWN ON PLANS FOR FRONT CANOPY LIGHTS SIGNS AND CAMERAS. <br />PROVIDE WIRING BETWEEN J-BOXES FOR SCONCE AND HI HATS LIGHTS AS SHOWN ON PLANS. <br />PROVIDE 1 /2" EMT CONDUIT CONNECTING LIGHTS AND SIGN J-BOXES AS SHOWN ON PLANS. <br />PROVIDE 3/4" CONDUIT FOR DOME CAMERAS JBOXES. <br />ROSS PLANS WILL PROVIDE MAIN RUNS OF POWER AND CAMERA CABLES TO THESE JBOXES. <br />ONLY FUTURE SCONCES AND HI HATS WILL HAVE MC WIRING TO JBOXES 1 , 2 AND 3, ROSS <br />PLANS WILL PROVIDE POWER FROM PANELS TO JBOXES 1 , 2 AND 3 AND CONNECT THE MC <br />CABLE WIRING PROVIDED ON THESE PLANS. <br />I <br />ROSS WILL PROVIDE THE LIGHTS ON THEIR PERMIT, NO LIGHTS WILL BE INSTALLED ON THIS <br />PERMIT ONLY JBOXES WILL BE INSTALLED. <br />FUTURE LIGHTING LEGEND <br />EXTERIOR DOCK LIGHTING - 'LUMARK' WPS15-MV-PE-PC <br />150W HPS LAMPS ON PHOTO CELL, SHIELDED <br />a EXTERIOR ROSS OPERATIONS LIGHTING - 'LUMARK' WPS15-MV-L-PE <br />150W HIPS LAMPS ON PHOTO CELL, NON -SHIELDED <br />FEATURE ARCHITECTURAL LIGHTING, OR CENTER STANDARD IF APPROVED BY ROSS <br />STORES). IF NOT OTHERWISE SPECIFIED, NOVA MODEL #071938 B, QUARTER SPHERE <br />SCONCE WITH 10OW MH TAMP AND FACTORY FINISHED SHELL TO MATCH FASCIA COLOR <br />(U.ON.). THIS EXAMPLE IS TO ESTABLISH INTENDED LEVEL OF QUALITY & TYPE OF LIGHT <br />TO BE USED, CONTACT AWL FOR SITE SPECIFIC LIGHT FIXTURE. CONTRACTOR MUST <br />SPECIFY SCONCE FINISH COLOR WHEN PLACING ORDER. NO EXCEPTION. <br />UNDER CANOPY DOWN LIGHTING, (OR CENTER STANDARD MAY BE UTILIZED IF APPROVED <br />BY ROSS STORES). IF NOT OTHERWISE SPECIFIED, PORTFOLIO MODEL #M78-100-80LI, <br />100 WATT, METAL HALIDE DOWNLIGHT, DAMP LABEL FIXTURE. THIS EXAMPLE IS TO <br />ESTABLISH INTENDED LEVEL OF QUALITY & TYPE OF LIGHT TO BE USED, CONTACT AWL <br />FOR SITE SPECIFIC LIGHT FIXTURE. <br />W <br />W PAGING/MUSIC SYSTEM SPEAKERS PROVIDED AND INSTALLED BY ROSS AFTER TURNOVER. <br />IN THE EVENT THAT LOCAL CODE REQUIRES LOW VOLTAGE WIRING TO BE INSTALLED IN <br />CONDUIT, THEN 3/4" CONDUIT WITH PULL STRINGS IN PLACE LINKING SPEAKER <br />LOCATIONS TO PAGING/MUSIC DATA BOX IN MANAGER'S OFFICE IS TO BE PROVIDED AND <br />PLACED BY G.C. PRIOR TO CONSTRUCTION TURNOVER. CONFIRM SPEAKER LOCATIONS <br />THROUGH ROSS CONSTRUCTION REPRESENTATIVE. 18 TO 20 LOCATIONS, TYP. CEILING <br />MOUNTED UNLESS MARKED "W„ FOR WALL MOUNTED <br />■ PRE -FINISHED POWER POLE PROVIDED AS PART OF FRONT END MODULAR SYSTEM <br />PROVIDED AND INSTALLED BY ROSS FIXTURE VENDOR. <br />17-77-7-771 <br />GYPSUM BOARD CEILING <br />SUSPENDED ACOUSTICAL CEILING TILE <br />Pro j. Mer. <br />JU <br />Job. Capt. <br />SG <br />Drawn by <br />JT <br />RON <br />BARR, <br />A.I.A. <br />Revd by <br />STATE <br />OF FLORIDA <br />I@S <br />AR 0016160 <br />U <br />W <br />U <br />H <br />z <br />O <br />F- <br />W <br />> <br />Q 2: <br />n <br />w <br />W <br />Iw- <br />F=-- 2 <br />= <br />U <br />F- <br />o❑~ <br />W <br />'0'O <br />2 <br />w <br />4] <br />0 <br />07 <br />- <br />❑�� <br />- <br />w <br />OXa <br />- <br />U <br />asOQ <br />W <br />❑ <br />KZzW <br />MXO <br />p <br />WW°Oi <br />¢ U= <br />wz <br />O <br />� ( <br />w <br />~ <br />a}v <br />ZZzQ-ZOU <br />F <br />F <br />0wo <br />V''oo <br />a <br />� <br />°WQ <br />U <br />=R0' <br />oz <br />XW <br />01 <br />O <br />(n <br />d <br />¢ <br />2 <br />o, <br />U❑ <br />z= <br />W <br />a <br />y <br />z <br />Wa <br />(n <br />w <br />2 <br />w <br />W <br />Q <br />2 <br />W <br />o <br />of <br />= <br />2 <br />m° <br />oZ <br />_ <br />o <br />w <br />2XXo <br />Z <br />F- <br />Q d U <br />W <br />Z) <br />Z <br />� <br />O <br />F- Z <br />o <br />Z <br />z <br />O <br />_ <br />? J <br />° <br />❑ <br />U W <br />O tL F- <br />° <br />❑ <br />2 <br />W <br />z O <br />0 Z <br />Z❑ <br />W <br />Z U= <br />z d W <br />O <br />F <br />W w¢ <br />2 <br />2 <br />W W <br />O <br />2 <br />Z 0 <br />2 <br />F- <br />a W a <br />2 <br />r¢ <br />0 <br />�- <br />o❑ <br />0 <br />o <br />2 r <br />Z?� <br />0 <br />Q U <br />© <br />COPYRIGHT <br />2012 <br />BARR ARCHITECTURAL STUDIO <br />f <br />V <br />� w <br />�f <br />� <br />nib <br />f <br />"' <br />;I <br />Y <br />1 <br />I � <br />PA �; <br />I <br />o <br />V,.hL2� <br />Revis Ions: <br />CADFILE No. <br />d' <br />� <br />M <br />� <br />M <br />O <br />� <br />H <br />1 <br />f� <br />f <br />�^ f� <br />h� <br />O <br />� <br />N <br />Sheet Title <br />LIGHTING <br />PLAN <br />sca le: <br />Date: <br />Z.J. <br />Sheet No. <br />BUCHANAN P.E. CONSULTING INC" <br />-- <br />AL <br />A A B ANA <br />ELECTRICAL * MECHANICAL * PLUMBING <br />Project No. <br />ENGINEERING <br />6191 W. ATLANTIC BLVD., SUITE #2 <br />`# <br />E3-0 <br />MARGATE, FL 33063 <br />Ph: 954-590-3300 Fax: 954-590-2232 <br />Email: mepengineers@aol.com <br />RAJA BUCHANAN FL P.E # 48916 <br />CERTIFICATE OF AUTHORIZATION # 8842 <br />MAY 0 5 201412-027 <br />DATE: <br />3 OF 3 <br />--------r---------------- - <br />-----�:.f.,,-r-----r-rrfr�-----i--r-- --r- - <br />