GENERAL ELECTRICAL TOTES
<br />1, ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (N.E.C. 2008) AND
<br />GOVERNING MUNICIPAL, STATE AND LOCAL CODES. ALL MATERIAL SHALL BE NEW AND SHALL BEAR THE
<br />U.L, LABEL WHERE APPLICABLE.
<br />2. ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN A FIRST CLASS
<br />WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY OPERATIVE AND ACCEPTED BY THE
<br />OWNER.
<br />3. IT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE
<br />CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM
<br />AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING
<br />ORDER.
<br />4. CONTRACTOR SHALL MAKE ALL NECESSARY CUTTING AND DO ALL THE REPATCHING AS NECESSARY FOR
<br />THE PROPER EXECUTION OF THIS WORK.
<br />5. AFTER COMPLETION OF THE INSTALLATION, THE SYSTEM SHALL TEST FREE FROM SHORT CIRCUITS AND
<br />GROUNDS.
<br />6. WHERE ELECTRICAL CONDUCTORS ARE INSTALLED IN CONDUIT, THE CONDUIT SHALL COMPLY WITH THE
<br />N.E.C. REQUIREMENTS.
<br />7. ALL CONDUCTORS SHALL BE COPPER. NO CONDUCTOR SHALL BE SMALLER THAN #12 AWG AND SHALL
<br />BE RATED FOR 600VOLTS THWN OR THHN INSULATION. INSTALL A GROUNDING CONDUCTOR WITH ALL
<br />CIRCUITS, UNLESS NOTED OTHERWISE, SIZED PER N.E.C. 250-122.
<br />8. VERIFY BREAKER AND CORRESPONDING WIRE SIZES FOR ALL ELECTRICAL EQUIPMENT. DO NOT ORDER
<br />MATERIAL BEFORE VERIFYING BREAKER & WIRE SIZE. REPORT ANY DISCREPANCY IMMEDIATELY TO THE
<br />ENGINEER OF RECORD.
<br />9. SAFETY SWITCHES SHALL BE SQUARE 'D', GENERAL ELECTRIC, OR WESTINGHOUSE, FUSED OR
<br />NON -FUSED AND SIZED AS INDICATED. NEMA 3R WHEN EXPOSED TO WEATHER
<br />10. PANELS SHALL BE SQUARE 'D', GENERAL ELECTRIC OR EQUAL, TYPE AND NUMBER OF BREAKERS AS
<br />INDICATED ON PANEL SCHEDULE. STENCIL PANEL DESIGNATION ON INSIDE OF PANEL. ALL TWO -POLE
<br />BREAKERS SHALL BE COMMON TRIP, PROVIDE TYPE WRITTEN SCHEDULE IN EACH LOAD CENTERS.
<br />CONNECTION TO MAIN BUS SHALL BE WITH BURNDY ANNULAR COMPRESSION LUGS. PANELS AIC RATING
<br />SHALL BE AS INDICATED ON PLANS.
<br />11. PROVIDE NAMEPLATES FOR ALL PANEL BOARDS, DISCONNECTS, TRANSFORMER, TERMINAL CABINETS AND
<br />ALL ELECTRICAL EQUIPMENT IDENTIFIED BY NAME ON DRAWINGS.
<br />12. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN
<br />APPROVED THIRD PARTY TESTING AGENCY.
<br />13. LOAD DATA IS BASED ON INFORMATION GIVEN ENGINEER AT TIME OF DESIGN. VERIFY ALL EQUIPMENT
<br />AND PANEL SIZES BEFORE ORDERING AND BEFORE INSTALLATION.
<br />14. ALL EXTERIOR ELECTRICAL EQUIPMENT SHALL BE ANCHORED TO COMPLY WITH LOCAL CODE FOR WIND
<br />RESISTANCE.
<br />15. ALL ELECTRICAL AND COMMUNICATIONS OUTLETS TO BE AT 15" A.F.F TO BOTTOM OF OUTLET UNLESS
<br />OTHERWISE NOTED, ALL LIGHT SWITCHES SHALL BE 0 48" AFF. TO TOP OF SWITCH.
<br />16. TIME CLOCK FOR LIGHTING CONTROL TO BE AN ASTRONOMICAL TIME CLOCK.
<br />17. THE CONTRACTOR SHALL CONTACT THE LOCAL POWER COMPANY AND OBTAIN, IN WRITING, THE AVAILABLE
<br />FAULT CURRENT OF THE UTILITY TRANSFORMER. THE CONTRACTOR SHALL ENSURE THAT ALL ELECTRICAL
<br />EQUIPMENT HAS AN AMP INTERRUPTING CAPACITY (AIC) GREATER THAN THE AVAILABLE FAULT CURRENT
<br />AT ANY POINT IN THE ELECTRICAL DISTRIBUTION SYSTEM.
<br />18. WIRING METHOD:
<br />ALL CONDUCTORS SHALL BE INSTALLED IN ELECTRICAL METALLIC TUBING (EMT) UNLESS OTHERWISE
<br />NOTED. ALL FITTINGS AND COUPLINGS FOR EMT CONDUIT SHALL BE ALL STEEL RAIN TIGHT
<br />COMPRESSION TYPE OR ALL STEEL CONCRETE TIGHT SET SCREW TYPE.
<br />SCHEDULE 40 PVC CONDUIT, WITH FITTINGS AND COUPLINGS APPROPRIATE FOR THE USE, SHALL BE
<br />USED UNDERGROUND OR BELOW SLABS ON GRADE.
<br />19. SEAL ALL NEW CONDUIT PENETRATIONS THROUGH FIRE RATEDWALLS, CEILINGS, FLOORS, ETC., TO
<br />MAINTAIN EXISTING FIRE RATING CONDITIONS. FURNISH AND INSTALL FIRE RATED ENCLOSURES FOR ALL
<br />EQUIPMENTS PENETRATING FIRE RATED ENVELOPES, SPACES, ECT.
<br />20. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE WIRING FOR HVAC SYSTEM: A/C EQUIPMENT(S),
<br />SMOKE DETECTORS, THERMOSTATS, TEST STATIONS, MOTORIZED VOLUME DAMPERS, ETC. ELECTRICAL
<br />CONTRACTOR SHALL COORDINATE WITH MECHANICAL DRAWINGS AND PROVIDE ALL NECESSARY CONTROL
<br />WIRING. ELECTRICAL CONTRACTOR TO THOROUGHLY REVIEW MECHANICAL PLANS AND PROVIDE POWER TO
<br />ANY MECHANICAL EQUIPMENT OR DEVICE THAT IS NOT SHOWN ON ELECTRICAL PLANS BUT IS SHOWN ON
<br />MECHANICAL PLANS.
<br />21. INSTALL "GFCI" GROUND FAULT INTERRUPTER RECEPTACLES WITH WEATHERPROOF COVER WITHIN 25 FT
<br />OF HVAC EQUIPMENT, MOUNT RECEPTACLE ON UNISTRUT (UNLESS HVAC EQUIPMENT IS SPECIFIED WITH
<br />FACTORY INSTALLED CONVENIENT RECEPTACLE) .
<br />22. WHEN NEW ELECTRIC SERVICE IS BEING INSTALLED, IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY
<br />TO COORDINATE WITH FPL/FPL ENGINEERS ON THE SIZE OF THE FPL TRANSFORMER THAT IS REQUIRED
<br />TO PROVIDE THE NEW ELECTRIC SERVICE SHOWN ON ELECTRIC PLANS, GC HAS TO INFORM THE OWNER
<br />ABOUT ANY EXTRA FPL CHARGES THAT MIGHT OCCUR IN ORDER TO PULL NEW SERVICE. THIS HAS TO
<br />BE DONE AS EARLY AS POSSIBLE DURING THE BIDDING PROCESS.
<br />23, ELECTRICAL SERVICE EQUIPMENT MUST BE 3' ABOVE MSL, AND 8' ABOVE N.V.G.D. VERIFY AT SITE. ALL
<br />ELECTRICAL EQUIPMENTS SHALL BE INSTALLED ABOVE FLOOD LEVEL.
<br />24. CONTRACTOR MUST VISIT THE SITE PRIOR TO BID OR CONSTRUCTION TO VERIFY ALL EXISTING
<br />CONDITIONS. BEFORE SUBMITTING BID, BECOME THOROUGHLY FAMILIAR WITH ACTUAL EXISTING CONDITIONS
<br />AT THE BUILDING SITE. THE INTENT OF THE WORK IS SHOWN ON THE DRAWINGS AND DESCRIBED
<br />HEREINAFTER. BY THE ACT OF SUBMITTING A BID PROPOSAL FOR WORK, THE CONTRACTOR SHALL BE
<br />DEEMED TO HAVE MADE SUCH STUDY AND EXAMINATION AND TO ACCEPT ALL CONDITIONS PRESENT AT
<br />THE SITE. NO REQUEST FOR ADDITIONAL PAYMENT SHALL BE CONSIDERED AS VALID, DUE TO THE
<br />FAILURE TO ALLOW FOR CONDITIONS WHICH MAY EXIST. CONTRACTOR TO REPLACE ANY EXISTING DEVICE
<br />OR COMPONENT THAT IS CALLED AS EXISTING IF IT IS NOT FULLY OPERATIONAL
<br />25. WIRING METHODS IN ALL PATIENT CARE AREAS TO BE IN COMPLIANCE WITH REDUNDANT GROUNDING
<br />REQUIREMENTS OF NEC 2008 SECTION 517,13.
<br />26, ALL DIMMING MECHANISMS HAVE TO BE COMPATIBLE WITH FIXTURE DIMMING REQUIREMENTS. CONTRACTOR
<br />MUST VERIFY ALL DIMMING MECHANISM AND FIXTURE DIMMING REQUIREMENTS BEFORE ANY ORDERING,
<br />INSTALLING, OR WIRING OF ANY DIMMING MECHANISMS AND FIXTURES.
<br />27. ALL OUTDOOR RECEPTACLES TO BE GFCI& WEATHER PROOF.
<br />28. ALL OUTDOOR DISCONNECTS AND ELECTRICAL PANELS TO BE NEMA-3R. ALL OUTDOOR DISCONNECTS
<br />AND ELECTRICAL PANELS IN A SALT SPRAY AREA TO BE NEMA-4X.
<br />PER FLORIDA BUILDING CODE 2010 ENERGY CONSERVATION:
<br />505.7.3 VOLTAGE DROP.
<br />505.7.3.1 FEEDERS AND CUSTOMER OWNED SERVICE CONDUCTORS.
<br />FEEDER AND CUSTOMER OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM VOLTAGE
<br />DROP OF 2 PERCENT AT DESIGN LOAD.
<br />505.7.3.2 BRANCH CIRCUITS. BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
<br />VOLTAGE DROP OF 3 PERCENT AT DESIGN LOAD.
<br />505.7.4 COMPLETION REQUIREMENTS.
<br />505.7.4.1 DRAWINGS. CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT WITHIN 30 DAYS AFTER
<br />THE DATE OF SYSTEM ACCEPTANCE, RECORD DRAWINGS OF THE ACTUAL INSTALLATION SHALL BE
<br />PROVIDED TO THE BUILDING OWNER, INCLUDING:
<br />1. A SINGLE -LINE DIAGRAM OF THE BUILDING ELECTRICAL DISTRIBUTION SYSTEM AND
<br />2. FLOOR PLANS INDICATING LOCATION AND AREA SERVED FOR ALL DISTRIBUTION.
<br />505.7.4.2 MANUALS. CONSTRUCTION DOCUMENTS SHALL REQUIRE THAT AN OPERATING MANUAL
<br />AND MAINTENANCE MANUAL BE PROVIDED TO THE BUILDING OWNER. THE MANUALS SHALL
<br />INCLUDE, AT A MINIMUM, THE FOLLOWING:
<br />1. SUBMITTAL DATA STATING EQUIPMENT RATING AND SELECTED OPTIONS FOR EACH PIECE OF
<br />EQUIPMENT REQUIRING MAINTENANCE.
<br />2. OPERATION MANUALS AND MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING
<br />MAINTENANCE. REQUIRED ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED.
<br />3. NAMES AND ADDRESSES OF AT LEAST ONE QUALIFIED SERVICE AGENCY.
<br />NOTE: ENFORCEMENT AGENCIES SHOULD ONLY CHECK TO BE
<br />SURE THAT THE CONSTRUCTION DOCUMENTS REQUIRE THIS INFORMATION TO BE TRANSMITTED TO
<br />THE OWNER AND SHOULD NOT EXPECT COPIES OF ANY OF THE MATERIALS.
<br />505.3 TANDEM WIRING:
<br />LUMINAIRES DESIGNED FOR USE WITH ONE OR THREE LINEAR FLUORESCENT LAMPS GREATER THAN
<br />30 W EACH SHALL BE TANDEM WIRED WHEN TWO OR MORE LUMINAIRES ARE IN THE SAME SPACE
<br />AND ON THE SAME CONTROL DEVICE.
<br />EXCEPTIONS:
<br />1. RECESSED LUMINAIRES MORE THAN 10 FEET APART MEASURED CENTER TO CENTER.
<br />2. SURFACE -MOUNTED OR PENDANT LUMINAIRES THAT ARE NOT CONTINUOUS.
<br />3. LUMINAIRES USING THREE -LAMP HIGH -FREQUENCY ELECTRONIC OR THREE -LAMP
<br />ELECTROMAGNETIC BALLASTS.
<br />4. RECESSED LUMINAIRES MORE THAN 10 FEET APART MEASURED CENTER TO CENTER.
<br />5. SURFACE -MOUNTED OR PENDANT LUMINAIRES THAT ARE NOT CONTINUOUS.
<br />6. LUMINAIRES USING THREE -LAMP HIGH -FREQUENCY ELECTRONIC OR THREE -LAMP
<br />ELECTROMAGNETIC BALLASTS.
<br />NOTE:
<br />PER FLORIDA BUILDING CODE 2010 SEC. 505.2
<br />AREAS ENCLOSED BY CEILING HEIGHT PARTITIONS SHALL HAVE AT LEAST ONE
<br />SWITCH TO CONTROL LIGHTING WITHIN THE SPACE AS SHOWN. THESE SWITCHES
<br />ARE EQUIPPED WITH OCCUPANT SENSORS THAT WILL TURN THE LIGHTS OFF
<br />WITHIN 30 MINUTES OF OCCUPANT LEAVING A SPACE. REGULAR SWITCHES CAN
<br />BE USED WHEN A CEILING OCCUPANT SENSOR IS USED SEE PLAN.
<br />ALL EMERGENCY AND EXIT LIGHTS TO BE CONNECTED AHEAD OF ANY SWITCH
<br />OR TIME CLOCK
<br />OCCUPANCY SENSOR SWITCHES OR CEILING MOUNT TURN POWER ON WHEN
<br />OCCUPANT IS DETECTED FOR 30 MINUTES AND TURN POWER OFF WITHIN 30
<br />MINUTES AFTER AN OCCUPANT LEAVES THE MOTION DETECTOR VICINITY.
<br />POSITION OF THE SWITCH (ON/OFF) DOES NOT EFFECT OCCUPANCY SENSOR
<br />CONTROL.
<br />BRANCH CIRCUIT VOLTAGE DROP
<br />MAXIMUM 3% PER 2010 FBC
<br />ENERGY CONSERVATION CODE
<br />SECTION 505.7.3.2
<br />CIRCUIT LOAD
<br />IN AMPS
<br />WIRE SIZE
<br />COPPER
<br />MAXIMUM
<br />LENGTH
<br />IN FEET
<br />5 AMPS OR LESS
<br />180
<br />6 AMPS
<br />150
<br />7 AMPS
<br />130
<br />8 AMPS
<br />�i q An,
<br />115
<br />9 8MPS
<br />L '
<br />100
<br />10 AMPS
<br />J12 AWG
<br />90
<br />11 AMPS
<br />j 12 AWG
<br />83
<br />12 AMPS
<br />#12 AWG
<br />75
<br />13 AMPS
<br />70
<br />14 AMPS
<br />W12 AWG
<br />65
<br />15 AMPS
<br />60
<br />16 AMPS
<br />#12 AWG
<br />57
<br />17 AMPS
<br />#12 AWG
<br />54
<br />18 AMPS
<br />#12 AWG
<br />51
<br />19 AMPS
<br />#12 AWG
<br />48
<br />20 AMPS
<br />#12 AWG
<br />45
<br />NOTE:
<br />THE LIGHTING SPECIFICATIONS WERE SUPPLIED BY OTHERS.
<br />CONTRACTOR TO COORDINATE WITH OWNER/OWNER REP OR
<br />OWNER'S INTERIOR DESIGNER. VERIFY THAT THE
<br />SPECIFICATIONS ON THIS PLAN ARE WHAT THE OWNER
<br />ASKED FOR AND PROPERLY WIRE CONTROLS PER
<br />MANUFACTURER SPECIFICATIONS. ELECTRICAL CONTRACTOR
<br />TO CHECK MANUFACTURER SPECIFICATIONS AND
<br />INSTALLATION INSTRUCTIONS FOR LIGHTS AND CONTROLS
<br />FOR LIGHTS PRIOR TO ORDERING AND ROUGH -IN.
<br />NOTE:
<br />FOR FLUORESCENT LUMINAIRES, PROVIDE
<br />DISCONNECTS AS PER NEC 410.130(G).
<br />-------
<br />---------------- - A
<br />I
<br />N
<br />LIGHTING SHELL PLAN Af--\
<br />SCOPE OF WORK:
<br />PROVIDE J-BOXES AS SHOWN ON PLANS FOR FRONT CANOPY LIGHTS SIGNS AND CAMERAS.
<br />PROVIDE WIRING BETWEEN J-BOXES FOR SCONCE AND HI HATS LIGHTS AS SHOWN ON PLANS.
<br />PROVIDE 1 /2" EMT CONDUIT CONNECTING LIGHTS AND SIGN J-BOXES AS SHOWN ON PLANS.
<br />PROVIDE 3/4" CONDUIT FOR DOME CAMERAS JBOXES.
<br />ROSS PLANS WILL PROVIDE MAIN RUNS OF POWER AND CAMERA CABLES TO THESE JBOXES.
<br />ONLY FUTURE SCONCES AND HI HATS WILL HAVE MC WIRING TO JBOXES 1 , 2 AND 3, ROSS
<br />PLANS WILL PROVIDE POWER FROM PANELS TO JBOXES 1 , 2 AND 3 AND CONNECT THE MC
<br />CABLE WIRING PROVIDED ON THESE PLANS.
<br />ROSS WILL PROVIDE THE LIGHTS ON THEIR PERMIT, NO LIGHTS WILL BE INSTALLED ON THIS
<br />PERMIT ONLY JBOXES WILL BE INSTALLED.
<br />FUTURE LIGHTING LEGEND
<br />EXTERIOR DOCK LIGHTING 'LUMARK' WPS15-MV-PE-PC
<br />150W HPS LAMPS ON PHOTO CELL, SHIELDED
<br />EXTERIOR ROSS OPERATIONS LIGHTING - 'LUMARK' WPS15-MV-L-PE
<br />150W HPS LAMPS ON PHOTO CELL, NON -SHIELDED
<br />FEATURE ARCHITECTURAL LIGHTING, (OR CENTER STANDARD IF APPROVED BY ROSS
<br />STORES). IF NOT OTHERWISE SPECIFIED, NOVA MODEL #071938-13, QUARTER SPHERE
<br />SCONCE WITH 10OW MH LAMP AND FACTORY FINISHED SHELL TO MATCH FASCIA COLOR
<br />(U.ON.). THIS EXAMPLE IS TO ESTABLISH INTENDED LEVEL OF QUALITY & TYPE OF LIGHT
<br />TO BE USED, CONTACT AWL FOR SITE SPECIFIC LIGHT FIXTURE. CONTRACTOR MUST
<br />SPECIFY SCONCE FINISH COLOR WHEN PLACING ORDER. NO EXCEPTION.
<br />0 (� UNDER CANOPY DOWN LIGHTING, (OR CENTER STANDARD MAY BE UTILIZED IF APPROVED
<br />BY ROSS STORES). IF NOT OTHERWISE SPECIFIED, PORTFOLIO MODEL #M78-100-80LI,
<br />100 WATT, METAL HALIDE DOWNLIGHT, DAMP LABEL FIXTURE. THIS EXAMPLE IS TO
<br />ESTABLISH INTENDED LEVEL OF QUALITY & TYPE OF LIGHT TO BE USED, CONTACT AWL
<br />FOR SITE SPECIFIC LIGHT FIXTURE.
<br />W
<br />PAGING/MUSIC SYSTEM SPEAKERS PROVIDED AND INSTALLED BY ROSS AFTER TURNOVER.
<br />17 IN THE EVENT THAT LOCAL CODE REQUIRES LOW VOLTAGE WIRING TO BE INSTALLED IN
<br />CONDUIT, THEN 3/4" CONDUIT WITH PULL STRINGS IN PLACE LINKING SPEAKER
<br />LOCATIONS TO PAGING/MUSIC DATA BOX IN MANAGER'S OFFICE IS TO BE PROVIDED AND
<br />PLACED BY G.C. PRIOR TO CONSTRUCTION TURNOVER. CONFIRM SPEAKER LOCATIONS
<br />THROUGH ROSS CONSTRUCTION REPRESENTATIVE. 18 TO 20 LOCATIONS,_ TYP. CEILING
<br />MOUNTED UNLESS MARKED "W" FOR WALL MOUNTED
<br />■ PRE -FINISHED POWER POLE PROVIDED AS PART OF FRONT END MODULAR SYSTEM
<br />PROVIDED AND INSTALLED BY ROSS FIXTURE VENDOR.
<br />GYPSUM BOARD CEILING
<br />SUSPENDED ACOUSTICAL CEILING TILE
<br />Froj. Mgr.
<br />JU
<br />Job. Capt.
<br />SG
<br />Drawn bg
<br />JT RON PARR A I A
<br />, . . .
<br />Revd by STATE OF FLORIDA
<br />Re I AR 0016160
<br />F- W L Z Z = VJ
<br />U W W O w¢ r W W
<br />W 2:x r w 0 00
<br />U p 7~ d' W O
<br />U5 O m Q 6 0 L O O U O Fx- r~n
<br />Z U O F- F- to W H O
<br />W a Q z¢ O= w W_
<br />w� m x 0 F'= U U O
<br />m X p Z w~ Q z w Q 0
<br />O 0 z W' WU' Q Q OU , T O w O
<br />U) lW 0}0 W U Z Z ZQ I~- Z O U
<br />W=2 U 0 g O O O. O¢ D O
<br />U Z
<br />O
<br />a. z Q W Ow z x x a Z F
<br />`n v r U z F w a x
<br />w
<br />w o W Q ? ° m o 0 z W
<br />(� Z w Q Q U Z x
<br />�¢ a Q z O H Z ,' 0 z p-
<br />U wW IL
<br />U Z�~ 0 x? OU z �. Z O
<br />U O W U U QU W W- 0 U �- F- Z U
<br />2 Z d X x U W O W- W O 0 Q U
<br />r¢ W a �-¢ Q 0 0 W P Z z M
<br />COPYRIGHT 2012
<br />BARR ARCHITECTURAL STUDIO
<br />Rsvfs Eons:
<br />CADFILE No.
<br />�i1
<br />O_
<br />co
<br />CM
<br />N c
<br />o N
<br />N �
<br />W > d'
<br />o Lo
<br />~o E
<br />.� 4
<br />c 4c:
<br />V =3� E
<br />Lo
<br />O W i
<br />0
<br />r O
<br />U
<br />� N
<br />L/��J L
<br />4--+
<br />U
<br />N
<br />L a
<br />01 Qf
<br />Sheet Title
<br />LIGHTING
<br />PLAN
<br />Scale:
<br />Date: Sheet No.
<br />B UCHANAN P.E. CONS UL T/NG INC. SEAL > D, { ___
<br />ELECTRICAL * MECHANICAL* PLUMBING RAJA BUCHANAN
<br />ENGINEERING Fr a.e �assis Project No, E3-0
<br />6191 W. ATLANTIC BLVD., SUITE #2 MARGATE, FL 33063 G 2-027
<br />Ph: 954-590-3300 Fax: 954-590-2232 f L
<br />Email: mepengineers@aol.com Z3 OF 3
<br />0s
<br />RAJA BUCHANAN FL RE # 48916
<br />CERTIFICATE OF AUTHORIZATION # 8842 DATE:
<br />!i