REVISIONS
<br />BULLETIN #1
<br />APRIL 16, 2007
<br />SALES AREA POWER REQUIREMENT SCHEDULE
<br />SYMBOL
<br />SERVICE
<br />LOAD DESCRIPTION
<br />SOURCE
<br />CIRCUITS
<br />VOLTAGE
<br />LOAD
<br />WIRE/
<br />EXISTING PANEL
<br />REQUIRED
<br />AMPS
<br />CONDUIT SIZE
<br />FOUR (4) 20A
<br />6#10 & 1 #12 GND
<br />O
<br />DAIRY -MILK
<br />COOLERS
<br />NEAREST 120V
<br />NON-CR & NON -TIMED
<br />1-POLE, GFCI
<br />12010
<br />10.OA
<br />IN 3/4" C
<br />CITRUS
<br />BREAKERS
<br />EACH
<br />EACH
<br />SWITCHED PANEL
<br />CKTS.
<br />WALL -MOUNTED
<br />MULTIOUTLET PLUG-IN
<br />NEAREST 120V
<br />THREE (3) 20A
<br />120V 10
<br />10.OA
<br />4#12 & 2#12
<br />O
<br />ELECTRONICS
<br />STRIPS FOR TV'S, COMBO
<br />NON-CR &NON -TIMED
<br />1-POLE, CKTS.
<br />EACH
<br />EACH
<br />GND IN 3/4"C
<br />TV'S AND HDTV'S
<br />SWITCHED PANEL
<br />TV, HOME THEATRE,
<br />O
<br />ELECTRONICS
<br />VCR,DVD, HDTV'S,
<br />NEAREST 120V
<br />NON-CR & NON -TIMED
<br />FIVE (5) 20A
<br />120V 10
<br />10.0A
<br />7#12 & 1 #12
<br />INTERACTIVE DISPLAY,
<br />1-POLE CKTS.
<br />EACH
<br />EACH
<br />GND-3/4"C
<br />BOOM BOXES, VIDEO GAMES
<br />SWITCHED PANEL
<br />4A
<br />CASH REGISTER IG
<br />NEAREST 120V "CR"
<br />2#12 & 1 #12 IG A"C
<br />RECEPTACLE
<br />PANEL
<br />46
<br />ELECTRONICS
<br />SHOWCASE LIGHTING
<br />TIME -CONTROLLED
<br />ONE (1) 20A
<br />120V 10
<br />10.OA
<br />2#12 & 1 #12 GND -
<br />208Y/120V
<br />1-POLE CKT.
<br />EACH
<br />EACH
<br />1/2"C.
<br />4C
<br />GENERAL PURPOSE
<br />NEAREST 120V
<br />NON -CH & NON -TIMED
<br />2#12 & 1 #12 GND.
<br />RECEPTACLE
<br />SWITCHED PANEL
<br />-AC
<br />O
<br />ELECTRONICS
<br />MULTI -OUTLET PLUG-IN STRIPS
<br />NEAREST 120V
<br />NON-CR & NON -TIMED
<br />THREE (3)
<br />20A 1-POLE
<br />120V 10
<br />10.OA
<br />4#12 & 1#12
<br />SWITCHED PANEL
<br />CKT.
<br />EACH
<br />EACH
<br />GND-1/2"C
<br />NEAREST 120V
<br />TWO (2) 20A
<br />120V3#12
<br />10
<br />& 1#12
<br />0
<br />CORD REELS
<br />GENERAL PURPOSE
<br />NON-CR & NON -TIMED
<br />1-POLE CKT.
<br />EACH
<br />EACH
<br />GND 1/2"C
<br />RECEPTACLE
<br />SWITCHED PANEL
<br />2 REELS/ CKT
<br />EACH
<br />EACH
<br />STOCKROOM
<br />GENERAL PURPOSE
<br />NEAREST 120V
<br />ONE (1) 20A
<br />12010
<br />1&0A
<br />2#12 & 1#12
<br />O
<br />DESK
<br />RECEPTACLE
<br />NON-CR & NON -TIMED
<br />1-POLE CKT.
<br />EACH
<br />EACH
<br />GND - 1/2"C
<br />SWITCHED PANEL
<br />8O
<br />STOCKROOM
<br />IG RECEPTACLE
<br />NEAREST 120V "CR2„
<br />ONE (1) 20A
<br />1-POLE CKT.
<br />120V 10
<br />10.OA
<br />2#12 & 1#12 ,
<br />GND. & #12 ISO
<br />DESK
<br />PANEL
<br />EACH
<br />EACH
<br />GND -3/4"C
<br />(I) 20A
<br />GENERAL PURPOSE
<br />NEAREST 120V NON-CR
<br />1-POLE CKT.
<br />120V 10
<br />2#12 & 1 #12 GND
<br />9
<br />O
<br />FITNESS
<br />RECEPTACLE
<br />&NON TIMED
<br />EACH
<br />10.0A
<br />-1/2 C
<br />SWITCHED PANEL
<br />APPLIANCE
<br />GENERAL PURPOSE
<br />NEAREST 120V NON-CR
<br />ONE 1 20A
<br />120V 10
<br />2#12 & 1#12 GND
<br />10
<br />O
<br />WALL
<br />RECEPTACLE
<br />& NON -TIMED
<br />1-POLE CKT.
<br />EACH
<br />10.OA
<br />-1/2"C
<br />SWITCHED PANEL
<br />MULTI -OUTLET
<br />NEAREST 120V TIMED
<br />ONE(1) 20A
<br />120V 10
<br />2#12 & 1 #12
<br />0LAMPS
<br />PLUG-IN STRIPS
<br />SWITCHED
<br />1-POLE CKT
<br />EACH
<br />10.OA
<br />GND-1/2"C
<br />, ',*N
<br />SPORTING
<br />CASH REGISTER IG
<br />NEAREST 120V "GRi"
<br />ONE(1) 20A120V
<br />10
<br />2#12 & 1#12
<br />kzj
<br />GOODS
<br />RECEPTACLE
<br />PANEL
<br />1-POLE CKT.
<br />EACH
<br />10.OA
<br />,
<br />GND. & #12 ISO
<br />GND -3/4"C
<br />13
<br />FLOORCARE
<br />GENERAL PURPOSE
<br />NEAREST 120V NON-CR
<br />& NON
<br />ONE(1) 20A
<br />120V 10
<br />RECEPTACLE
<br />-TIMED
<br />1-POLE CKT.
<br />EACH
<br />10.0A
<br />2#12 & 1 #12
<br />SWITCHED PANEL
<br />GND.-1/2"C
<br />01
<br />GUNCASE LIGHTING CKT.
<br />NEAREST 120V NON-CR
<br />ONE(1) 20A
<br />4.OA
<br />2#12-1#12
<br />SPORTING
<br />& NON -TIMED
<br />1-POLE CKT.
<br />120V 10
<br />GRID - 1/2"C
<br />0GOODS
<br />1 120V GEN. PURPOSE CKT,
<br />SWITCHED PANEL
<br />EACH
<br />4.OA
<br />2#12 & 1 #12
<br />GND: 1/2"C
<br />GENERAL PURPOSE
<br />NEAREST 120V NON-CR
<br />ONE(1) 20A
<br />120V 10
<br />14.0A
<br />2#12 & 1 #12
<br />15
<br />MOBILE CARTS
<br />& NON -TIMED
<br />1-POLE GFCI
<br />EACH
<br />GND-1/2"C
<br />RECEPTACLE
<br />SWITCHED PANEL
<br />CKT.
<br />SMALL
<br />UNDERSHELF DISPLAY
<br />NEAREST 120V TIMED
<br />TWO (2)
<br />120V 10
<br />10.OA
<br />3#12& 1 #12
<br />ig
<br />APPLIANCES
<br />LIGHTING
<br />CKT.
<br />1-POLE CKT.
<br />EACH
<br />EACH
<br />GND: 1/2"C EACH
<br />GND.
<br />17
<br />OME APPLIANCES
<br />MULTIOUTLET
<br />NEAREST 120V
<br />FIVE (5) 20A
<br />120V 10
<br />10.OA
<br />7#12 & 2#12
<br />PLUG-IN STRIPS
<br />NON-CR & NON -TIMED
<br />1-POLE
<br />EACH
<br />EACH
<br />GND-3/4"C
<br />SWITCHED PANEL
<br />18
<br />OME APPLIANCES
<br />CASH REGISTER IG
<br />NEAREST 120V "CRV
<br />ONE (1) 20A
<br />120V 10
<br />10.OA
<br />2#12 & 1 #12 ,
<br />RECEPTACLE
<br />PANEL
<br />1-POLE
<br />EACH
<br />EACH
<br />GND. & #12 ISO
<br />GND -3/4"C
<br />19
<br />SALES AREA
<br />EXTERIOR SIGNAGE
<br />NEAREST 120V
<br />NON -OR & NON -TIMED
<br />ONE (1) 20A
<br />1-POLE
<br />120V 10
<br />5.OA
<br />2#12 & 1 #12 GND
<br />EACH
<br />1/2"C
<br />SWITCHED PANEL
<br />SALES AREA
<br />AUTOMATIC
<br />NEAREST 120V
<br />ONE (1) 20A
<br />120V 10
<br />2#12 & 1 #12 GND
<br />20
<br />DOOR OPENER
<br />NON-CR & NON -TIMED
<br />1-POLE
<br />EACH
<br />10.0A
<br />-1/2"C
<br />SWITCHED PANEL
<br />NEAREST 120V
<br />ONE (1) 20A
<br />120V 10
<br />10.OA
<br />2#12 & 1#12 GND
<br />SALES AREA
<br />EAS
<br />NON-CR & NON -TIMED
<br />1-POLE
<br />EACH
<br />-1/2"C
<br />21
<br />SWITCHED PANEL
<br />GENERAL PURPOSE
<br />NEAREST 120V NON-CR
<br />ONE (1) 20A
<br />120V 10
<br />2#12 & 1#12 GND
<br />0SALES
<br />AREA
<br />RECEPTACLE
<br />& NON -TIMED
<br />1-POLE CKT.
<br />EACH
<br />10.OA
<br />-1/2"C
<br />SWITCHED PANEL
<br />23
<br />SALES AREA
<br />IG RECEPTACLE
<br />NEAREST 120V "CR2"
<br />ONE (1) 20A
<br />1-POLE CKT.
<br />120V 10
<br />10.OA
<br />2#12 & 1 #12,
<br />GND. & #12 ISO
<br />PANEL
<br />EACH
<br />EACH
<br />GND -3/4"C
<br />24
<br />JEWELRY
<br />CASH REGISTER IG
<br />NEAREST 120V "CR"
<br />ONE (1) 20A
<br />120V 10
<br />4.0A
<br />2#12 & 1#12 ,
<br />GND. & #12 ISO
<br />RECEPTACLE
<br />PANEL
<br />1-POLE CKT.
<br />EACH
<br />GND -3/4"C
<br />0NEAREST
<br />JEWELRY
<br />120V
<br />TIMED SWITCHED
<br />ONE (1) 20A
<br />120V 10
<br />2.OA
<br />2#12 & 1 #12
<br />DISPLAY LIGHTING
<br />PANEL "K1"
<br />1-POLE CKT.
<br />EACH
<br />GND -1/2"C
<br />GENERAL PURPOSE
<br />NEAREST 120V
<br />ONE (1) 20A
<br />26
<br />JEWELRY
<br />RECEPTACLE
<br />NON-CR & NON -TIMED
<br />1 -POLE CKT.
<br />120V 10
<br />1
<br />10.OA
<br />2#12 & 1 #12
<br />SWITCHED PANEL
<br />EACH
<br />GND -1/2"C
<br />27
<br />INTERNET KIOSK,
<br />NEAREST 120V "CR"
<br />FOUR (4)
<br />120V 10
<br />10.OA
<br />6#12 & 1 #12 ,
<br />E-HIRE CONSOLE
<br />IG RECEPTACLE
<br />PANEL
<br />20A 1-POLE
<br />EACH
<br />EACH
<br />GND. & #12 ISO
<br />& GIFT REGISTRY
<br />CKT.
<br />GND -3/411C
<br />SALES AREA
<br />AUTOMATIC
<br />NEAREST 120V
<br />ONE (1) 20A
<br />120V 10
<br />10.OA
<br />2#12 & 1 #12 GND
<br />28
<br />DOOR OPENER
<br />NON-CR & NON -TIMED
<br />1-POLE
<br />EACH
<br />-1/2"C
<br />SWITCHED PANEL
<br />lL J � 440 � 0® O ® O
<br />NORTH
<br />ELECTRICAL NOTES AND SPECIFICATIONS
<br />1. INSTALLATION OF ELECTRICAL WORK SHALL CONFORM WITH LOCAL REGULATIONS AND
<br />ORDINANCES, STATE REQUIREMENTS AND THE LATEST NATIONAL ELECTRICAL CODE.
<br />2. ELECTRICAL CONTRACTOR SHALL VISIT JOB SITE AND DETERMINE EXISTING CONDITIONS AND
<br />LIMITATIONS UNDER WHICH THE WORK IS TO BE PERFORMED. THE SUBMISSION OF A BID
<br />SHALL BE CONSTRUED AS INDICATING SUCH KNOWLEDGE THAT SUCH EXAMINATION HAS
<br />BEEN MADE AND VERIFIED.
<br />3. MAKE APPLICATION FOR AND PAY ALL FEES IN CONNECTION WITH ANY PERMITS,
<br />INSPECTIONS, TESTS, ETC., THAT MAY BE REQUIRED FOR ALL JOBS.
<br />4. FURNISH AND INSTALL ALL MATERIAL AND EQUIPMENT AS SHOWN OR REQUIRED TO
<br />COMPLETE THE WORK.
<br />5. NEW INSTALLATION INCLUDING MATERIAL AND EQUIPMENT SHALL BE EQUAL TO ORIGINAL
<br />INSTALLATION.
<br />6. GUARANTEE ALL WORKMANSHIP, MATERIAL AND PERFORMANCE FOR A PERIOD OF ONE (1)
<br />YEAR FROM DATE OF FINAL ACCEPTANCE,
<br />7. ALL NEW CONDUCTORS SHALL BE COPPER TYPE THHN (ABOVE GROUND) RUN IN
<br />ELECTRICAL METALLIC TUBING (EMT/THIN WALL) AND TYPE THWN (BELOW GROUND) RUN IN
<br />RIGID CONDUIT. PROVIDE COMPRESSION TYPE FITTINGS FOR EMT.
<br />8. MATERIAL NOT SPECIFIED SHALL BE EQUAL IN QUALITY TO EXISTING MATERIAL OF LIKE KIND.
<br />9. ELECTRICAL CONTRACTOR SHALL PROVIDE TYPED -IN DIRECTORY FOR NEW PANELS AND
<br />EXISTING PANELS BEING AFFECTED BY THIS WORK.
<br />10. ALL ELECTRICAL DISTRIBUTION EQUIPMENT(i.e. PANELBOARDS etc.) ARE EXISTING TO REMAIN
<br />UNLESS NOTED AS NEW.
<br />11. PROVIDE AN INSULATED, ISOLATED GROUND SYSTEM THROUGHOUT AS INDICATED ON
<br />DRAWINGS FOR ELECTRONIC CASH REGISTER (ECR) SYSTEM. PROVIDE ONE INSULATED
<br />ISOLATED GROUND WIRE FOR EACH CIRCUIT. PLACE ONLY, A MAXIMUM OF TWO (2) ECRS ON
<br />A SINGLE ISOLATED GROUND POWER CIRCUIT,
<br />12. RECEPTACLES FOR ISOLATED GROUND CIRCUITS SHALL BE AS FOLLOWS:
<br />SINGLE - HUBBELL #IG5251 (ORANGE)
<br />DUPLEX - HUBBELL #IG5262 (ORANGE) EXCEPT AS OTHERWISE NOTED,
<br />13. PROVIDE SCREW FASTENED HANDLE LOCK -ON DEVICES AT CIRCUIT BREAKERS FOR ALL
<br />REFRIGERATION EQUIPMENT, CASH REGISTERS AND AS DIRECTED IN FIELD BY KMART
<br />PROJECT REPRESENTATIVE.
<br />COORDINATOR PRIOR TO INSTALLATION.
<br />15. HOMERUNS SHOWN SEPARATE FOR CLARITY ONLY. CIRCUITS MAY BE COMBINED FOR MOST
<br />COST EFFECTIVE INSTALLATION, BUT MUST COMPLY WITH ARTICLE #310 DEBATING FACTORS
<br />FROM THE LATEST NATIONAL ELECTRIC CODE.
<br />16, IT IS THE RESPONSIBILITY OF THIS ELECTRICAL CONTRACTOR TO VERIFY AT THE JOB
<br />SITE ACTUAL AVAILABILITY OF CIRCUITS REQUIRED. CIRCUITS INDICATED ARE
<br />TENTATIVE. DIFFERENT CIRCUITS THAT HAVE BECOME AVAILABLE IN THE CEILING
<br />SPACE DUE TO RELOCATION OF ELECTRIFIED DEVICES SUCH AS CORD REELS OR
<br />LIGHTED DISPLAYS CAN BE SUBSTITUTED TO CIRCUITS INDICATED ON THE DRAWINGS,
<br />IF THOSE CIRCUIT ARE COMING FROM SOURCE PANELS OF THE SAME ELECTRICAL
<br />CHARACTERISTICS.
<br />17. RETRACTABLE EXTENSION CORD REEL TO BE PLUGGED INTO ADJACENT FLUSH MOUNTED
<br />CEILING RECEPTACLE. CORD REELS WILL BE FURNISHED BY KMART.
<br />18. THE INTENTION OF THESE DRAWINGS IS TO INDICATE THE ROUGH IN POWER
<br />REQUIREMENTS FOR STORE MERCHANDISE FIXTURES AND CASH REGISTERS. IT SHALL BE
<br />THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY THE EXACT LOCATION
<br />OF EACH OUTLET WITH THE KMART PROJECT REPRESENTATIVE USING FINAL STORE
<br />PLANNING FIXTURE LAYOUT FOR FINAL INSTALLATION.
<br />19. ALL OUTLET BOXES FOR DROPS TO SALES AREA FIXTURES MUST BE LOCATED IN CEILING
<br />SPACE AND SECURED TO ROOF STEEL.
<br />20. ALL WIRES SHALL BE LABELED WITH AN IDENTIFICATION TAG TO INDICATE THEIR
<br />DESTINATION.
<br />21. FOR MOBILE CART (WHEEL CHAIRS) CHARGER ELECTRICAL CONTRACTOR SHALL
<br />FURNISH AND INSTALL HUBBELL #HBL5362GY RECEPTACLE IN A FLOOR -SUPPORTED
<br />CAST ALUMINUM BOX FLUSH WITH CART RAILING. PROVIDE STAINLESS STEEL PLATE.
<br />CONNECT TO A GFCI CIRCUIT FROM THE NEAREST NON-09 AND NON -TIMED SWITCHED
<br />PANEL, WHERE APPLICABLE FURNISH AND INSTALL ALUMINUM CHANNEL ALONG
<br />VESTIBULE MULLIONS FOR CONDUIT COVER.
<br />22. MINIMUM CONDUCTOR SIZE FOR HOMERUNS SHALL BE #12 THHN IN 2" CONDUIT. MAKE
<br />THE NECESSARY WIRE SIZE ADJUSTMENT TO CONFORM WITH NEC ARTICLE #210-19. FOR
<br />VOLTAGE LIMITS OF BRANCH CIRCUITS.
<br />23. THE CONTRACTOR MUST INSURE THRU COORDINATION WITH STORE MANAGER AND
<br />PROJECT REPRESENTATIVE THAT DURING CONSTRUCTION STAGES, PRIORITIES SHALL BE
<br />ESTABLISHED TO KEEP THE STORE IN OPERATION - ESPECIALLY THE ECR/POS SYSTEM.
<br />ANY ACTIVITIES AFFECTING SYSTEMS WHICH ARE VITAL TO THE CONTINUOUS OPERATION
<br />OF THE STORE SHALL BE IMPLEMENTED DURING OFF -HOURS. CONSTRUCTION DURING
<br />STORE OPERATIONS SHALL BE LIMITED TO MINIMAL INTERRUPTIONS DURING SLOW
<br />BUSINESS HOURS. MINIMUM DISTANCE NECESSARY TO ALLOW PASSAGE OF POWER
<br />POLES THRU CEILING.
<br />24. IN GENERAL, MULTI -OUTLET PLUG-IN STRIPS AND/OR AUDIO/TV TRACKS SHALL BE
<br />RELOCATED BY THIS CONTRACTOR FROM EXISTING DISPLAY FIXTURES AS IDENTIFIED
<br />AND DIRECTED BY THE KMART PROJECT COORDINATOR. WHERE NEW ONES ARE
<br />REQUIRED THIS CONTRACTOR SHALL FURNISH AND INSTALL NEW PLUG-IN STRIPS TO
<br />MATCH EXISTING, PAINT RELOCATED PLUG-IN STRIPS "OFF WHITE" AS REQUIRED TO
<br />MATCH NEW DISPLAY FIXTURES. SIMILAR TO WIREMOLD PLUGMOLD SERIES 2000 CAT. NO.
<br />20GB612. ALL MULTIOUTLET STRIPS SHALL BE HARDWIRED.
<br />25. SMALL APPLIANCES DISPLAY LUMINAIRES ARE DESIGNED TO BE MOUNTED UNDERNEATH
<br />THE SHELVES WITH MATCHING MOUNTING CLIPS. LUMINAIRES AND MOUNTING CLIPS
<br />WILL BE FURNISHED BY KMART FOR COMPLETE INSTALLATION BY ELECTRICAL
<br />CONTRACTOR. EXACT MOUNTING METHOD SHALL BE AS DIRECTED BY THE KMART
<br />PROJECT REPRESENTATIVE IN THE FIELD, DO NOT DRILL HOLES THROUGH THE
<br />LUMINAIRES TO AVOID DAMAGE TO THE INTERNAL BALLASTS.
<br />26. RELOCATION OF TELEPHONE, LAN DROPS, PA AND BA DEVICES AND WIRING WILL BE BY OTHERS.
<br />27. PAINT ALL CONDUIT DROPS TO MATCH WALL COLOR.
<br />28. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL WIRING AND CIRCUITS MATCHING RATING
<br />AND POWER REQUIREMENTS OF SPECIFIC ELECTRIFIED STORE FIXTURES, DEVICES AND EQUIPMENT
<br />NOT SHOWN ON THIS DRAWING BUT SHOWN AND INDICATED IN THE STORE PLANNING LAYOUT AS
<br />BEING RELOCATED OR NEW AS VERIFIED AND DIRECTED BY THE KMART PROJECT COORDINATOR.
<br />THESE EQUIPMENT SHALL INCLUDE BUT NOT BE LIMITED TO CHECKOUT POWER POLES COOLERS,
<br />FREEZERS, PRICE SCANNERS, MOBILE CARTS, CASH REGISTERS, MULTIOUTLET STRIPS,
<br />RECEPTACLES AND LUMINAIRES.
<br />29. ELECTRICAL CONTRACTOR SHALL UTILIZE PREVIOUS CIRCUITS AND PANELS FOR ALL RELOCATED
<br />EQUIPMENT SUCH AS COOLERS AND FREEZERS, ADJUST BRANCH FEEDER CONDUCTOR SIZES
<br />INDICATED OR UTILIZE BOOSTER TRANSFORMERS TO LIMIT VOLTAGE DROPS TO A MAXIMUM OF 3
<br />EQUIPMENT. ALL RELOCATED AND NEW RECEPTACLES SHALL MATCH EXISTING CONFIGURATION
<br />AND RATING OF EQUIPMENT. INPUT VOLTAGE TO FILM PROCESSORS UNDER FULL LOAD
<br />CONDITIONS SHALL NOT FALL BELOW 200 VOLTS,
<br />30. ELECTRICAL CONTRACTOR SHALL DISCONNECT AND REMOVE THE POWER POLES SERVING
<br />EXISTING CHECKOUTS BEING RELOCATED. POWER WIRING AND CIRCUITS SERVING THESE
<br />EQUIPMENT SHALL BE EXTENDED AND RECONNECTED AT THEIR NEW LOCATIONS. REMOVAL
<br />AND RELOCATION OF CABINET FIXTURES WILL BE BY OTHERS. SEE STORE PLANNING DRAWING
<br />FOR EXACT LOCATIONS OF CHECKOUTS.
<br />31. ELECTRICAL CONTRACTOR SHALL RELOCATE ANY EXISTING OVERHEAD LUMINAIRE(S) WHICH
<br />MAY INTERFERE WITH THE RE -INSTALLATION OF POWER POLES SERVING RELOCATED CHECKOUT
<br />FIXTURES. RELOCATION SHALL BE LIMITED TO THE BARE MINIMUM DISTANCE NECESSARY TO
<br />ALLOW PASSAGE OF POWER POLES THRU CEILING.
<br />32 PROVIDE TEN FEET OF MULTI -OUTLET STRIP PLUGMOLD 20613612 MOUNTED 18" AFF. IN SECURITY
<br />OFFICE. PROVIDE 2#12, 1 #12 GND TO SPARE 20A BREAKER TO NEAREST 120V. GENERAL PURPOSE
<br />PANEL. DISCONNECT AND REMOVE WALL -MOUNTED MAIN SWITCH FOR EXISTING PLUGMOLD IF
<br />EXISTING.
<br />33. NEW EXIT SIGN WALL MOUNTED ABOVE THE DOOR TO MATCH EXISTING CONNECT TO LOCKED -ON
<br />EMERGENCY LIGHTING CIRCUIT.
<br />34. EXTERIOR TO BE CONTROLLED BY PHOTOCELL AND A 7 DAY ASTRONOMICAL TIME SWITCH.
<br />TIME SWITCH OVERRIDES PHOTOCELL TO TURN OFF SIGNS. COORDINAT WITH SIGNAGE
<br />SUPPLIER FOR EXACT LOCATION OF OUTLET BOXES FOR EXTERIOR SIGNAGE. FINAL
<br />CONNECTION OF SIGNS TO 120V BRANCH CIRCUITS BY SIGN CONTRACTOR.
<br />�NO/
<br />C
<br />F--�
<br />F-� a C
<br />W o
<br />� CO
<br />_ Ao
<br />o�-
<br />M Cd
<br />Cn
<br />W
<br />coQ
<br />O
<br />cn
<br />x
<br />Q
<br />ryN0
<br />0
<br />J
<br />LL
<br />O0
<br />LPL
<br />J
<br /><C
<br />J_
<br />JN_
<br />ry
<br />ZD
<br />0
<br />m
<br />Lu
<br />J
<br />Fj
<br />J
<br />Z
<br />1
<br />CU
<br />V
<br />N
<br />Q
<br />J
<br />0
<br />Z
<br />=
<br />L
<br />E
<br />_0
<br />vn
<br />L0
<br />O
<br />C17
<br />0')
<br />i
<br />rr
<br />Q
<br />Co
<br />rr
<br />L1
<br />Cy.)
<br />Co
<br />QO
<br />0
<br />z
<br />S
<br />Lu
<br />nr-
<br />U
<br />rr
<br />�
<br />Cn
<br />J
<br />Y z
<br />W z Q
<br />z
<br />Q
<br />Lu
<br />rr
<br />Q
<br />Lu I_-
<br />= 0-C
<br />C" )
<br />U
<br />m � L07
<br />Q co Lo
<br />U
<br />LL
<br />Project Arch./ Engineer:
<br />JOHN LINEGAR
<br />Drawn:
<br />DENNIS CARMICHAE
<br />Checked:
<br />BRAIN BILOTTA
<br />Date:
<br />JANUARY 17, 2007
<br />FLOOR PLAN
<br />SCALE: 1/16"=1'-O"
<br />Sheet No:
<br />Em
<br />
|