Laserfiche WebLink
DESIGN CRITERIA <br />BASIS OF DESIGN: <br />ALL CONSTRUCTION IS DESIGNED AS FOLLOWS: <br />FLORIDA BUILDING CODE 7TH EDITION 2020 <br />DEAD LOADS <br />ROOF 15 PSF <br />LIVE LOADS <br />FLOOR 40 PSF <br />ROOF 20 PSF <br />WIND LOADS <br />ASCE 7-16, 138 MPH WIND (ULTIMATE), 106 MPH (NOMINAL) <br />BUILDINGS OF ALL HEIGHTS ANALYTICAL METHOD <br />RISK CATEGORY II <br />EXPOSURE CATEGORY"B" <br />ROOF SLOPE: 4.5:12 <br />INTERNAL PRESSURE COEFFICIENTS: <br />GCpi = +/- .18, ENCLOSED STRUCTURE <br />BASIC WIND PRESSURE:q=29.0 P.S.F. (C&C) <br />EDGE DISTANCE: a= 4 FT. <br />STRENGTH OF MATERIALS: <br />REINFORCING STEEL - - - - - ----------------fy = 60,000 psi <br />CONCRETE SLAB, BEAMS AND FOOTINGS = 3,000 psi <br />REINFORCED MASONRY = 1,500 psi <br />MASONRY GROUT ---------- -f� = 3,000 psi <br />SOIL BEARING (ASSUMED, TO BE VERIFIED) -------------- Sb = 2,000 psf <br />STRUCTURAL STEEL SHAPES --------- --- -- fy = 36,000 psi <br />STRUCTURAL STEEL SHAPES (HSS) ---------- fy = 46,000 psi <br />FRAMING LUMBER --------- ------- #2 SYP <br />BOLTS FOR WOOD AND STEEL CONNECTIONS - - A307 <br />LVL-------------------------------- Fb=2850,2.0E <br />SHEATHING DIAPHRAGM (ROOF ZONE 2 & 3) --- 19/32 APA RATED SHEATHING <br />UNBLOCKED PANEL DIAPHRAGM _----- ALLOWABLE SHEAR = 300 LBS. PER FOOT <br />10d DEFORMED NAILS SPACED @ 4" O.C. AT ALL ENDS, EDGES, CUTS AND <br />TERMINATIONS, AND @ 4" O.C. AT INTERIOR SUPPORTS. <br />SHEATHING DIAPHRAGM (ROOF ZONE 1) -- 19/32 APA RATED SHEATHING <br />UNBLOCKED PANEL DIAPHRAGM ----- ALLOWABLE SHEAR = 300 LBS. PER FOOT <br />10d DEFORMED NAILS SPACED @ 6" O.C. AT ALL ENDS, EDGES, CUTS AND <br />TERMINATIONS, AND @ 6" O.C. AT INTERIOR SUPPORTS. <br />SHEATHING DIAPHRAGM (WALLS) - -- - 15132 APA RATED SHEATHING <br />BLOCKED PANEL DIAPHRAGM --- ALLOWABLE SHEAR = 310 LBS. PER FOOT <br />10d DEFORMED NAILS SPACED @ 6" O.C, AT ALL ENDS, EDGES, CUTS AND <br />TERMINATIONS, AND @ 12" O.C. AT INTERIOR SUPPORTS. <br />SHEATHING DIAPHRAGM (WALLS) ------- 5/8 GYPSUM BOARD <br />BLOCKED PANEL DIAPHRAGM ALLOWABLE SHEAR = 145 LBS. PER FOOT <br />6d COOLER NAILS SPACED @ 7" O.C. AT ALL ENDS, EDGES, CUTS AND <br />TERMINATIONS, AND @ 12" O.C. AT INTERIOR SUPPORTS. <br />DECK DIAPHRAGM (FLOORS) ------- 23/32 APA RATED SHEATHING <br />UNBLOCKED PANEL DIAPHRAGM -- ALLOWABLE SHEAR = 320 LBS. PER FOOT <br />CONSTRUCTION ADHESIVE AND 10d DEFORMED NAILS SPACED @ 6" O.C. AT ALL <br />ENDS, EDGES, CUTS AND TERMINATIONS, AND @ 12" O.C. AT INTERIOR SUPPORTS. <br />GENERAL NOTES: <br />1. THE FOLLOWING SPECIFICATIONS ARE AN OUTLINE OF MINIMUM MATERIAL REQUIREMENTS AND THEIR <br />APPLICATION. MANUFACTURER SPECIFICATION AND LOCAL CODE REQUIREMENTS, WHEN IN EXCESS OF <br />MINIMUM SPECIFICATION SHALL CONTROL. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REVIEW AND SUBMIT <br />ALL SHOP DRAWINGS AND REPORT ALL DOCUMENT DISCREPANCIES TO THE STRUCTURAL ENGINEER PRIOR TO <br />FABRICATION OR ERECTION. <br />2. AT CONSTRUCTION ISSUE, THESE DRAWINGS REPRESENT STRUCTURAL COMPONENTS IN THEIR FINAL AND <br />FINISHED STATE. CONSTRUCTION PROCEDURES, BRACING, METHODS SAFETY PRECAUTIONS OR MECHANICAL <br />REQUIREMENTS USED TO ERECT THEM ARE THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR OR <br />SUBCONTRACTOR DOING THE WORK. <br />3. VERIFY ALL DETAILS AND DIMENSIONS WITH EXISTING CONDITIONS, ARCHITECTURAL DOCUMENTS AND <br />PROPERLY COORDINATED, APPROVED SHOP DRAWINGS. <br />4. NO COMMENT, NOTE OR DETAIL IN THESE STRUCTURAL DOCUMENTS SHOULD BE MISCONSTRUED AS A <br />DESIGN FOR WATERPROOFING OR DAMPPROOFING. SPECIFIC DESIGN FOR MOISTURE CONTROL AND <br />PERMANENT PROTECTION OF STRUCTURAL MATERIALS FROM THE ELEMENTS IS TO BE COMPLETED BY OTHERS <br />AND COORDINATED WITH THE STRUCTURAL DOCUMENTS. <br />FOUNDATION NOTES: <br />1. FOOTINGS SHALL BEAR ON SOIL SUITABLE FOR SUPPORTING 2000 P.S. NET ALLOWABLE BEARING. IF <br />QUESTIONABLE SOIL IS ENCOUNTERED, THE STRUCTURAL ENGINEER SHALL BE NOTIFIED IMMEDIATELY. <br />2. FOOTINGS SHALL BE POURED IMMEDIATELY AFTER EXCAVATION. <br />3. EXPANSION AND CONTROL JOINTS ARE TO BE PLACED PER A.C.I. RECOMMENDATIONS. PREPARE A CRACK <br />CONTROL PLAN BASED ON CONSTRUCTION SEQUENCING AND PROPOSED ACTUAL FLOOR AND WALL FINISHES, <br />AND SUBMIT TO THE ARCHITECT/ENGINEER FOR APPROVAL PRIOR TO CONSTRUCTION, <br />3.1 NO CONTROL JOIN SHALL INTERSECT AN ADJACENT CONTROL JOINT AT AN ANGLE <90 <br />3.2 CONTROL JOINTS SHALL ONLY INTERSECT A CURB OR OTHER STRUCTURAL MEMBER AT ANGLE OF <br />90". <br />4. ALL REINFORCING STEEL MARKED "CONTINUOUS" SHALL BE LAPPED PER "REINFORCING STEEL SPLICE NOTES". <br />5. LAP TOP BARS AT CENTER OF SPAN; LAP BOTTOM BARS AT SUPPORTS, U.N.O. <br />6. THERE SHALL BE NO PLUMBING LINES RUNNING PARALLEL TO, WITHIN OR UNDER ANY FOUNDATION BEAM. <br />7. PLACE A 10 MIL VAPOR RETARDER OF POLYETHYLENE UNDER ALL CONCRETE SLABS, U.N.O. <br />8. ALL FOOTING BOTTOMS MUST BE PLACED A MINIMUM OF 12" BELOW FINISH GRADE. <br />SITE WORK NOTES: <br />1. PERFORM EXCAVATION, ACCORDING TO GOOD COMMON CONSTRUCTION PRACTICES, TO THE LINES, GRADES, <br />ELEVATIONS INDICATED ON THE DRAWINGS AND ACCORDING TO RECOMMENDATIONS FOUND IN SUB SURFACE <br />REPORT BY GEOTECHNICAL ENGINEER. <br />2. ALL FILL UNDER SLABS AND FOUNDATIONS SHALL BE COMPACTED TO 98% OF MAXIMUM DENSITY (MODIFIED <br />PROCTOR TEST) AT OPTIMUM MOISTURE CONTENT. A COMPACTION REPORT FROM QUALIFIED SOILS ENGINEER <br />SHALL BE TAKEN AND SUBMITTED TO ENGINEER OF RECORD. <br />3. PROVIDE SOIL POISONING TO CONTROL TERMITES AS REQUIRED BY GOVERNING CODES. <br />WOOD FRAMING NOTES: <br />1. VERIFY SHEATHING TYPE AND THICKNESS WITH ROOF MATERIAL MANUFACTURER'S REQUIREMENTS FOR WIND <br />RESISTANCE ATTACHMENT. <br />2. PRE-ENGINEERED WOOD TRUSS ERECTOR IS REQUIRED TO HANDLE AD INSTALL TRUSSES PER <br />MANUFACTURER'S INSTRUCTIONS. AS A MINIMUM, INSTALL BRACING IN ACCORDANCE WITH ACSI 1-03, AND <br />LEAVE PERMANENTLY IN PLACE. MOVE TO OPPOSITE SIDE OF CHORD IF NECESSARY DUE TO INTERFERENCE <br />WITH SHEATHING OR CEILING MATERIALS. TOP AND BOTTOM CHORD MEMBERS OR PRE-ENGINEERED TRUSS <br />SYSTEM FOR THE COMPLETED STRUCTURE ARE INTENDED TO BE CONTINUOUSLY BRACED BY SHEATHING AND <br />CEILING FINISHES. THE ROOF TRUSS SYSTEM IS NOT COMPLETE UNTIL ALL BRACING, SHEATHING AND FINISHES <br />ARE PERMANENTLY ATTACHED. SOLID BLOCKING IS REQUIRED AT ALL EVES, EDGES, VALLEYS, RIDGES AND <br />TRANSITIONS. <br />3. ENGINEER MUST REVIEW AND APPROVE TRUSS SHOP DRAWINGS PRIOR TO FABRICATION. TRUSS ATTACHMENT <br />HARDWARE MAY BE MODIFIED IF REQUIRED. <br />4. ALL TRUSS TO TRUSS AND OVER FRAMING CONNECTIONS ARE TO BE SPECIFIED BY TRUSS MANUFACTURER. <br />5. ALL CONNECTORS AND FASTENERS THROUGH OR ADJACENT TO PRESERVATIVE TREATED LUMBER ARE TO BE <br />HOT DIPPED GALVANIZED, STAINLESS STEEL OR SPECIFICALLY APPROVED FOR SUCH USAGE BY THE <br />MANUFACTURER. <br />6. ALL WOOD SUBJECT TO MOISTURE EXPOSURE OR ADJACENT TO CONCRETE OR MASONRY SHALL BE OF AN <br />APPROVED NATURALLY DURABLE SPECIES OR PRESERVATIVE TREATED APPROPRIATELY FOR ITS INTENDED <br />USE. <br />7. ALL WOOD WHICH IS TO BE LEFT EXPOSED TO VIEW SHALL BE SELECTED FOR APPEARANCE AND PROPERLY <br />PREPARED FOR FINISHES. <br />8. THE CONTRACTOR SHALL REVIEW AND APPROVE THE TRUSS PLACEMENT PLAN AND EACH TRUSS DESIGN <br />DRAWING FOR CONFORMANCE WITH THE REQUIREMENTS AND INTENT OF THE CONSTRUCTION DESIGN <br />DOCUMENTS, AND THE EFFECT OF THE TRUSS PLACEMENT PLAN AND EACH TRUSS DRAWING ON OTHER <br />TRADES INVOLVED IN THE CONSTRUCTION OF THE STRUCTURE AND THE EFFECT OF THE OTHER TRADES ON <br />THE TRUSSES. <br />9. TRUSSES SHALL BE SHIPPED AND STORED IN SUCH AWAY AS TO PREVENT DAMAGE, WARPING AND PROLONGED <br />EXPOSURE TO WEATHER ELEMENTS THAT CAN REDUCE THE STRUCTURAL INTEGRITY OF THE TRUSSES. <br />11. ALL WOOD NAILS SHALL MEET THE FOLLOWING MINIMUM DIMENSIONS U.N.O. SEE NAIL SIZE CHART. <br />WOOD PRESERVATIVE TREATMENT REQUIREMENTS: <br />1. AWPA USE CATEGORY UC4B <br />ALL WOOD USED FOR PERMANENT WOOD FOUNDATION OR REQUIRING HEAVY DUTY PROTECTION. <br />2. AWPA USE CATEGORY UC4A <br />ALL WOOD IN CONTACT WITH OR WITHIN 8" OF THE GROUND. <br />3. AWPA USE CATEGORY UC3B <br />ALL OTHER EXTERIOR (OR EXPOSED TO THE WEATHER IN ANY FASHION) WOOD MEMBERS. <br />4. AWPA USE CATEGORY UC3A <br />ALL OTHER WOOD THAT IS REQUIRED BY CODE TO BE PRESERVATIVE TREATED OR OF A NATURALLY DURABLE <br />SPECIES. <br />TERMITE NOTES: <br />1. A PERMANENT SIGN WHICH IDENTIFIES THE TERMITE TREATMENT PROVIDER AND NEED FOR RE -INSPECTION <br />AND TREATMENT CONTRACT RENEWAL SHALL BE PROVIDED. THE SIGN SHALL BE POSTED NEAR THE WATER <br />HEATER OR ELECTRIC PANEL. <br />2. CONDENSATE AND ROOF DOWN SPOUTS SHALL DISCHARGE V-0" AWAY FROM BUILDING SIDE WALLS. <br />3. IRRIGATION/SPRINKLER SYSTEM INCLUDING ALL RISERS AND SPRAY HEADS SHALL NOT BE INSTALLED WITHIN <br />V-0" OF THE BUILDING SIDE WALLS. <br />4. TO PROVIDE FOR INSPECTION FOR TERMITE INFESTATION THE DISTANCE BETWEEN WALL COVERING AND FINAL <br />EARTH GRADE SHALL NOT BE LESS THAN 6". EXCEPTION: PAINT OR DECORATIVE CEMENTITIOUS FINISH LESS <br />THAN 518" THICK ADHERED DIRECTLY TO THE FOUNDATION WALL. <br />5. INITIAL TREATMENT SHALL BE DONE AFTER ALL EXCAVATION AND BACKFILL IS COMPLETE. IN ACCORDANCE <br />WITH FLORIDA BUILDING CODE 7TH EDITION 2020 SECTION 1816.1.1 <br />6. SOIL DISTRIBUTED AFTER THE INITIAL TREATMENT SHALL BE RE -TREATED INCLUDING SPACES BOXED AND <br />FORMED. IN ACCORDANCE WITH FLORIDA BUILDING CODE 7TH EDITION 2020 SECTION 1816.1.2 <br />7. BOXED AREAS IN CONCRETE FLOORS FOR SUBSEQUENT INSTALLATIONS OF TRAPS, ETC., SHALL BE MADE WITH <br />PERMANENT METAL OR PLASTIC FORMS. PERMANENT FORMS MUST BE THE SIZE AND DEPTH THAT WILL <br />ELIMINATE THE DISTURBANCE OF SOIL AFTER THE INITIAL TREATMENT. IN ACCORDANCE WITH FLORIDA <br />BUILDING CODE 7TH EDITION 2020 SECTION 2304.11 <br />8. INIMUM 6 MIL RETARDER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS <br />BEFORE VAPOR RETARDER PLACEMENT, RETREATMENT IS REQUIRED. IN ACCORDANCE WITH FLORIDA BUILDING <br />CODE 7TH EDITION 2020 SECTION 2304.11, <br />9. CONCRETE OVER POUR AND MORTAR ALONG THE FOUNDATION PERIMETER MUST BE REMOVED BEFORE <br />EXTERIOR SOIL TREATMENT. IN ACCORDANCE WITH FLORIDA BUILDING CODE 7TH EDITION 2020 SECTION <br />2304.11. <br />10. SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE WITHIN V-0" OF THE <br />STRUCTURE SIDEWALLS. IN ACCORDANCE WITH FLORIDA BUILDING CODE 7TH EDITION 2020 SECTION 2304.11. <br />11. AN EXTERIOR VERTICAL CHEMICAL BARRIER MUST BE INSTALLED AFTER CONSTRUCTION IS COMPLETE <br />INCLUDING LANDSCAPING AND IRRIGATION ANY SOIL DISTRIBUTED AFTER THE VERTICAL BARRIER IS APPLIED, <br />SHALL BE RETREATED. IN ACCORDANCE WITH FLORIDA BUILDING CODE 7TH EDITION 2020 SECTION 2304.11. <br />12. ALL BUILDING ARE REQUIRED TO HAVE PRE -CONSTRUCTION TREATMENT. IN ACCORDANCE WITH FLORIDA <br />BUILDING CODE 7TH EDITION 2020 SECTION 2304.11. <br />13. A CERTIFICATE OF COMPLIANCE MUST BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED PEST <br />CONTROL COMPANY BEFORE A CERTIFICATE OF OCCUPANCY WILL BE ISSUED. THE CERTIFICATE OF <br />COMPLIANCE SHALL STATE: 'THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF <br />SUBTERRANEAN TERMITES THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE FLORIDA <br />DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES." IN ACCORDANCE WITH FLORIDA BUILDING CODE <br />7TH EDITION 2020 SECTION 2304.11. <br />14. AFTER ALL WORK IS COMPLETED, LOOSE WOOD AND FILL MUST BE REMOVED FROM BELOW AND WITHIN V-0" OF <br />THE BUILDING. THIS INCLUDES ALL GRADE STAKES, TUB TRAP BOXES, FORMS, SHORING OR OTHER CELLULOSE <br />CONTAINING MATERIAL. <br />15. NO WOOD, VEGETATION, STUMPS, CARDBOARD, TRASH, ETC., SHALL BE BURIED WITHIN 15'-0" OF ANY BUILDING <br />OR PROPOSED BUILDING. <br />STRUCTURALSTEEL: <br />1. ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING ASTM SPECIFICATIONS, UNLESS NOTES <br />OTHERWISE ON PLAN: <br />ROLLED W SHAPES ASTM A992, GRADE 50 <br />ROLLED C & MC SHAPES ASTM A36 <br />ANGLES ASTM A36 <br />ROUND HSS ASTM A500, GR B (Fy=42 KSI) <br />RECTANGULAR HSS ASTM A500, GR B (Fy=46 KSI) <br />2. ALL SHOP AND FIELD WELDING SHALL CONFORM TO AWS STRUCTURAL WELDING CODE, ANSI/AWS D1.1, AND ALL <br />WELDS SHALL BE PERFORMED USING E70XX U.N.O. <br />3. DESIGN CONNECTIONS FOR ALL BEAMS TO SUPPORT HALF OF THE UNIFORM CAPACITY SHOWN IN AISC "TABLES <br />FOR ALLOWABLE LOADS ON BEAMS" FOR THE GIVEN SECTION AND SPAN UNLESS OTHERWISE SHOWN ON <br />PLANS. <br />4. GROUT BELOW BASE PLATES SHALL BE NON -SHRINK, NON-METALLIC GROUT WITH A MINIMUM COMPRESSIVE <br />STRENGTH OF 6000 PSI. <br />5. HOT -DIP GALVANIZE ALL STRUCTURAL STEEL ITEMS AND THEIR CONNECTIONS PERMANENTLY EXPOSED TO <br />WEATHER AFTER FABRICATION. ALL FIELD AND ERECTION MARKS SHALL BE COVERED DURING FIELD TOUCH-UP <br />PAINTING. <br />6. CUTS, HOLES, COPING, AND ALL OTHER MODIFICATIONS REQUIRED TO BE MADE FOR THE WORK OF OTHER <br />TRADES SHALL BE SHOWN IN THE STRUCTURAL STEEL SHOP DRAWINGS, AND SHALL BE PERFORMED ONLY BY <br />THE SHOP ISSUING SAID DRAWINGS, OR OTHER FACILITY APPROVED BY THE ENGINEER TO PERFORM SAID <br />WORK. HOLES IN STRUCTURAL ELEMENTS SHALL BE REINFORCED AS REQUIRED BY THE ENGINEER. <br />7. CUTS, HOLES, COPING, AND ALL OTHER MODIFICATIONS TO STEEL MEMBERS IN THE FIELD IS NOT PERMITTED <br />WITHOUT THE EXPLICIT APPROVAL OF THE ENGINEER. <br />SUBMITTALS: <br />1. THE GENERAL CONTRACTOR SHALL SUBMIT FOR ENGINEER REVIEW SHOP DRAWINGS FOR THE FOLLOWING <br />ITEMS: <br />1.1. REINFORCING STEEL <br />1.2. CONCRETE MIX DESIGN <br />1.3. STRUCTURAL STEEL ERECTION DRAWINGS <br />1.4. METAL DECKS <br />1.5. OPEN WEB STEEL JOISTS (*) <br />1.6. STAIRS (*) <br />1.7. GUARD/HANDRAILS (*) <br />1.8. MASONRY PRODUCTS INCLUDING VERIFICATION OF fm AND CERTIFICATES FOR ALL OTHER MATERIALS <br />USED IN MASONRY CONSTRUCTION INDICATING THE COMPLIANCE WITH THE CONTRACT DOCUMENTS. <br />1.9. EMBEDDED ITEMS (PLATES, ANGLES, BOLTS, ETC.) <br />1.10. ELEVATORS <br />1.11. PRE-ENGINEERED ALUMINUM CANOPY (*) <br />1.12. PRE-ENGINEERED FLOOR TRUSSES (*) <br />1.13. PRE-ENGINEERED ROOF TRUSSES (*) <br />1.14. TIE DOWN SYSTEM (*) <br />1.15. PROJECT SIGNAGE {*) <br />1.16. COLD FORMED STEEL (LIGHT GAUGE STEEL) <br />1.17. CONCRETE CONSTRUCTION JOINT LOCATION FOR ALL CONCRETE ELEMENTS <br />1.18. CONTROL JOINT LOCATIONS (CMU CONSTRUCTION) <br />ALL ITEMS MARKED (*) SHALL HAVE SHOP DRAWINGS SIGNED, SEALED, AND DATED BY A REGISTERED ENGINEER IN <br />THE STATE OF FLORIDA. <br />2. ALL SHOP DRAWINGS MUST BE REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR PRIOR TO SUBMITTAL <br />TO THE ARCHITECT/ENGINEERING. DRAWINGS SUBMITTED WITHOUT REVIEW WILL BE RETURNED UNCHECKED. <br />3. ALL SHOP DRAWINGS SHALL BE SUBMITTED AND APPROVED PRIOR TO CONSTRUCTION. THE CONTRACTOR <br />SHALL PLAN AND ALLOW (10) WORKING DAYS FOR APPROVAL FROM BELT ENGINEERING'S OFFICE. THIS SHALL <br />BE FIGURED INTO THE CONTRACTOR'S SCHEDULE BEFORE CONSTRUCTION BEGINS. <br />4. THE CONTRACT DOCUMENTS WILL GOVERN OVER THE SHOP DRAWINGS UNLESS OTHERWISE SPECIFIED IN <br />WRITING BY THE ENGINEER. <br />5. CHANGES AND ADDITIONS MADE ON THE RE -SUBMITTALS SHALL BE CLEARLY FLAGGED AND NOTED. THE <br />PURPOSE OF RE -SUBMITTALS SHALL BE CLEARLY NOTED ON THE LETTER OF TRANSMITTAL. <br />ARCHITECT/ENGINEER REVIEW WILL BE LIMITED TO THOSE ITEMS CAUSING RE -SUBMITTAL. <br />10. ALL WOOD TRUSSES SHALL BE FASTENED TO THEIR SUPPORTS WITH APPROVED HURRICANE CLIPS OR STRAPS. <br />ALL CONNECTION HARDWARE SHALL BE SUPPLIED BY SIMPSON STRONG -TIE CO OR APPROVED EQUIVALENT 6. SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT OF THE CONTRACT <br />MANUFACTURER. ALL CONNECTION HARDWARE IS TO BE FULLY FASTENED PER MANUFACTURER DOCUMENTS ONLY. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY COMPLIANCE WITH THE <br />REQUIREMENTS WITH THE MAXIMUM NUMBER AND SIZE OF NAILS, BOLTS AND SCREWS, U.N.O. CONTRACT DOCUMENTS AS TO QUANTITY, LENGTH, ELEVATIONS, DIMENSIONS, ETC. <br />FOR REVIEW AND PERMIT. NOT FOR CONSTRUCTION UNTIL APPROVED BY THE OWNER AND THE BUILDING OFFICIAL. THEN MUST BE MARKED "APPROVED FOR CONSTRUCTION" BY THE ENGINEER. <br />COMPONENTS AND CLADDING PRESSURE ZONES <br />GABLE ROOFS <br />7'<0 <271 <br />WALLZONES <br />W/ 7' < e 5 30* HIP OR GABLE ROOF SLOPE <br />COMPONENTS AND CLADDING WIND PRESSURE CHART <br />COMPONENTS AND CLADDING COMPONENTS AND CLADDING <br />ULTIMATE PRESSURE SCHEDULE ULTIMATE PRESSURE SCHEDULE <br />WALLS, DOORS AND WINDOWS ROOFS <br />ENCLOSED BUILDING ENCLOSED BUILDING <br />GCP,= +/- 0.18 GCP1=+/- 0.18 <br />(+) INDICATES INWARD; (-) INDICATES OUTWARD (+) INDICATES INWARD; (-) INDICATES OUTWARD <br />EFFECTIVE AREA OF <br />COMPONENT <br />ZONE 5: WITHIN a' OF <br />CORNER <br />ZONE 4: NOT WITHIN a' <br />OF CORNER <br />EFFECTIVE AREA OF <br />COMPONENT <br />ZONE 3r <br />ZONE 3e, 2r & 2n <br />ZONE 2e & 1 <br />0 S.F. < "AREA" < 20 S.F. <br />+34.2 <br />-45.8 <br />+34.2 <br />-37.1 <br />0 S.F. < "AREA" < 20 S.F. <br />+25.5 -110 <br />+25.5 <br />-77.8 <br />+25.5 <br />-48.7 <br />20S.F. < "AREA" < 50 S.F. <br />+32.7 <br />-42.7 <br />+32.7 <br />-35.6 <br />20S.F. < "AREA" < 50 S.F. <br />+18.8 -76.2 <br />+18.8 <br />-67.9 <br />+18.8 <br />-48.7 <br />50 S.F. < "AREA" < 100 S.F. <br />+30.6 <br />-38.6 <br />+30.6 <br />-33.5 <br />50 S.F. < "AREA' < 100 S.F. <br />+16.0 -57.5 <br />+16.0 <br />-55.2 <br />+16.0 <br />-41.8 <br />100 S.F. < "AREA" < 200 S.F. <br />+29.1 -35.6 <br />+29.1 -32.0 <br />200 S.F. < "AREA" < 500 S.F. <br />1 +27.6 <br />-32.5 <br />+27.6 <br />-30.5 <br />> 100 S.F. <br />+13.9 -57.5 <br />+13.9 <br />-45.7 <br />+13.9 <br />-36.7 <br />> 500 S.F. <br />+25.5 -28.4 <br />+25.5 -28.4 <br />NU I tJ: ALL bUILUINU tLtMtN 1 J tAt'U6LU I U VVINU SHALL tit IN51 ALLtU t'tK MANUt AU I UKtK'S IN51 KUG I IUNS 10 KE515 I I HE WIND PRESSURES <br />INDICATED AND TO MEET OTHER CODE REQUIREMENTS FOR AIR AND WATER INTRUSION. WIND LOADS ABOVE ARE ULTIMATE LOADS. USE <br />ULTIMATE WIND PRESSURE W/ ASCE7-16 LOAD COMBINATIONS, MULTIPLY LOADS BY 0.6 TO OBTAIN NOMINAL LOADS. <br />1n r- <br />o a <br />M -, <br />2 <br />O <br />� U <br />> O <br />� Z <br />m <br />U W <br />rn N Z <br />O - C� <br />W M J <br />�ww <br />m <br />a CL <br />C:, <br />Jf <br />;77 <br />LL <br />s= = L w <br />0; <br />o <br />q• •°`� o� <br />1211111 l4t' Lu <br />O <br />LL J W W o Q� <br />OaZ ZO�Q p <br />fnLL W r)z<z ) J <br />mWw�_WCL Lu <br />w=m <br />W -1 CO Z- Z) F_ F- <br />Wm WWLLIOmNoww <br />�Z�OQUQZ�QI <br />OQ9�=Z-O(6coLL <br />~wM) wwo�F-w0 <br />QCOU��LL m�WZ-jF- <br />F- Q it w U Q 2~ w w m <br />L}i>�Q=LUF-"_jrnU3 <br />F - <br />Zm<F_ 0 w < 0 <br />wYHU)OF-O W rL <br />W U5;� U 2 W <br />-20 o O w <br />U) <br />Z <br />O <br />W <br />w <br />w <br />1111111111 <br />p <br />It �L JpI <br />U <br />Cl <br />ry <br />F_ <br />V) <br />Ld <br />Q <br />LL <br />(r% <br />> <br />O <br />L.L <br />Q <br />u- <br />W <br />-� <br />�®�_ <br />W <br />0 <br />> <br />'Lo <br />o- <br />c <br />N <br />JOB NO. <br />E19-751 <br />DATE <br />12/03/2019 <br />DRAWN <br />VMC <br />DESIGN <br />JWB <br />DESIGN <br />CRITERIA <br />