ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />FTF <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />94 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUSTFAN <br />IWO <br />EXHAUST FAN/LIGHT COMBINATION <br />®D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />i9 <br />PUSH BUTTON SWITCH (OPTIONAL) <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />f USB <br />TELEPHONE/USB (OPTIONAL) <br />® <br />TELEVISION (OPTIONAL) <br />® 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />_a <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />J <br />OPT. CEILING FAN <br />W <br />(1) PHONE LINE, (1) DATA PORT <br />150A/200A INDOOR <br />PANEL CENTER <br />10 #14 to lights & outlets <br />NEMA 1 01 #12 to appliances and GFI <br />150 AMP/ <br />200 AMP 10 #10 to WH <br />10 #6 to Range <br />10 #6 to HVAC <br />w-,T <br />MAIN <br />0 <br />200 amp <br />150 amp <br />150=2/0 <br />200=4/0 in 2" Conduit <br />UNDERGROUND Disconnect \iT <br />SERVICE BY POWER CO. �It, L <br />INTERSYSTEM 4 Bare Cu Ground '`1 A � <br />BONDING #4 GROUNDING WIRE l <br />TERMINATION PER WITH CODE APPROVED <br />NEC 17, 250.94 CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />! <br />C.M <br />AV _vTA <br />PLUMBING RISER <br />NOTE: PLUMBING RISER IS SCHEMATIC TO SCALE: NTS <br />BE VERIFIED WITH PLUMBER <br />GFI <br />OWNER'S S Y ITE O. BATH <br />/ ROUGH -IN FOR / <br />/ OPT. CLG. FAN/ <br />LIGHT PRE -WIRE / <br />/ dVP <br />— u4 <br />I� CAFE <br />1 <br />1 <br />FAMILY RM <br />ROUGH -IN FOR <br />OPT. CLG. FAN/ <br />LIGHT PRE -WIRE <br />j U.C. OUTLET <br />FOR DW <br />I <br />U.C. OUTLET <br />I <br />I <br />I / � <br />I <br />GFI <br />- - - - - --_-_AD=- -- <br />GFI C—---------- GFI <br />�- -1 <br />07 <br />I D.W. I <br />SINK w/ DISP <br />\ KITCHEN U.C. SWITCH <br />PENDANT AS <br />FOR DISPOSAL <br />� � <br />PER SPECS <br />RANGE <br />M <br />GFI JVM AM <br />MOPE <br />OPT. <br />REF. I <br />DEDICATED RECEPTACLE <br />H.B. FOR MICROWAVE RANGE <br />HOOD PER SPECS <br />15'-0" <br />RECEPT. VERIFY METER <br />FOR ALARM LOCATION WITH <br />SYSTEM BUILDER WP H.B. <br />Izz A GFI I <br />I <br />I <br />I <br />I <br />W.I.C. <br />I <br />� I <br />\ I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />I <br />-----------J <br />I <br />A <br />GFI <br />BEDROOM 2 /Z, <br />ROUGH -IN FOR '\'�/ <br />OPT. CLG. FAN/ <br />LIGHT PRE -WIRE y <br />W IRRIGATION <br />VERIFY LOCATION <br />W H <br />DELECTRICAL PANEL <br />O I <br />I <br />I <br />I <br />2 CAR GARAGE <br />I <br />I <br />GFI FOR <br />GAR. DOOM <br />GFI <br />_-GFI @ 44" <br />A.F.F. <br />I <br />I I <br />I <br />I <br />I <br />I <br />\ — / L - - - - - - - - - - - - <br />GFI @ 44" <br />Ak A.F.F. <br />FOYER,' <br />)IIIIIIII-1-TENTRY <br />I I <br />I I <br />WP I I <br />r_ct I I <br />ELECTRICAL PLAN — ELEV—B1 <br />SCALE: %4"=1'-0" <br />%W3 <br />N <br />Alt <br />•� <br />o <br />3i <br />p LJJ <br />Q_ <br />o <br />C lO f� N <br />N O <br />kn O N t <br />Vf O CV <br />Q eV X <br />W <br />c' <br />d c <br />tr <br />3 cc <br />y CD tr <br />c.� W <br />c o <br />_ d <br />N G� <br />c E <br />� o <br />a � <br />0 <br />CV <br />C'4 <br />0 <br />CV <br />00 <br />_o <br />C`M <br />14 <br />//'<<rtsrsso�s'e <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential 7th Edition. Engineers signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal. <br />W <br />Q <br />";r E N <br />N <br />CD O CN W0 <br />N ���� <br />Ci <br />ID <br />M <br />rnLZ ° LL ur <br />to <br />.4 <br />rrNia W a a <br />JoLL tL a N <br />0 t9 <br />3 0 <br />_� o . <br />0 <br />Z <br />r 03 o <br />o <br />W <br />= O <br />�� d J <br />0 <br />LL <br />M Z U H <br />Z <br />N U <br />o <br />Z <br />❑DD <br />W <br />0 <br />Z N c) <br />z co <br />La <br />Z n <br />r <br />N <br />Ni <br />z W <br />1 l <br />U <br />O <br />W g <br />C <br />w m <br />= E <br />I <br />z <br />U S <br />o <br />c to d <br />o <br />rr <br />cn <br />J <br />- <br />o 3 <br />z <br />z <br />� <br />ri <br />E <br />z o <br />o0 <br />QR <br />Q <br />r6 <br />z® <br />2` <br /><= <br />w0 <br />� E <br />CID <br />as <br />o� <br />a <br />wz <br />Z <br />rQ <br />t <br />wz <br />�w <br />= n3 <br />C <br />ao <br />z <br />a <br />w0 <br />mO <br />oLL <br />N <br />OY <br />ma <br />Zr <br />'aZ <br />ZN <br />m J <br />¢ ° <br />2 Z <br />S< <br />5� <br />W <br />co <br />T <br />wLL <br />2Z <br />N Z <br />m <br />a ¢ <br />tY <br />3 <br />o <br />J <br /><< <br />;a = <br />v <br />=la <br />o <br />3 <br />.0 O <br />= <br />110 <br />rn <br />m <br />ca <br />c <br />O <br />Y <br />C.?O <br />r <br />v J <br />`� <br />m <br />L.n <br />V) <br />ate-+ <br />O <br />`- N <br />c) <br />I <br />M o <br />O <br />r <br />L- N <br />� <br />T <br />Q <br />M <br />� <br />T <br />M <br />L <br />CV <br />M <br />0 <br />z <br />Z <br />E O <br />i <br />0 <br />E <br />U <br />c <br />a <br />_j <br />Q p <br />JOB <br />NO: <br />23-02469 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />4 <br />