ENGINEER'S NnTES:
<br />1, DESIGN WIND SPEED: 140 MPHu(t / 110 MPHasol , 3 sec gust
<br />PER ATC HAZARDS BY LOCATION
<br />2. RISK CATEGORY PER FBC 17 GTH EDITION Table 1604,5 : II
<br />3, EXPOSURE CATEGORY = iii
<br />4, INTERNAL PRESSURE COEFFICIENT 0.18 (ENCLOSED BLDG)
<br />5, COMPONENTS 9, CLADDING DESIGN PRESSURES PER ASCE 7-10:
<br />FIGURE 30,5-1
<br />(R 11 F1 F)
<br />ZONE
<br />11o:
<br />+101-21
<br />ps-F
<br />ZONE
<br />2a:
<br />+10/-37
<br />psf
<br />ZONE
<br />3a:
<br />+10/-55
<br />psf
<br />(WALLS)
<br />ZONE
<br />4b:
<br />+21/-23
<br />psf
<br />ZONE
<br />51c:
<br />+211-27
<br />psf
<br />GENERAL NOTES
<br />BUSINESS GROUP B 393 SQ FT/100 4 PEOPLE PER TABLE 1004.1.2 FBC
<br />GROUP S LOW HAZARD 2007 SQ FT/500 4 PEOPLE PER TABLE 1004.1.2 FBC
<br />3 SUITES @ 2400 = 7200 SQ FT
<br />INTERIOR REQUIREMENTS
<br />FLAME SPREAD/SMOKE DEV.-EXIT ACCESS UNSPRK:TYPE ii FLAMESPREAD 26-75 SMOKE DEV. 0-450
<br />FLAME SPREAD/SMOKE DEV,-EXIT ACCESS SPRK: TYPE "C' FLAMESPREAD 76-200 SMOKE DEV. 0-450
<br />FLAME SPREAD/SMOKE DEV,-OTHER SPACES UNSPRKITYPE #C' FLAMESPREAD 76-200 SMOKE DEV. 0-450
<br />FLAME SPREAD/SMOKE DEV.-OTHER SPACES SPIRKITYPE "C' FLAMESPREAD 76-200 SMOKE DEV, 0-450
<br />X
<br />TABLE 803,11
<br />INTERIOR WALL AND CEILING FINISH REQUIREMENTS BY OCCUPANCYk
<br />ZONING CLASSIFICATION1
<br />BUILDING AREA: 7200 SQ.FT.
<br />13UILDING USE: BUSINESS
<br />SPECIAL OCCUPANCY: N/A
<br />GROUP: GROUP B
<br />TYPE OF CONSTRUCTION: 3B
<br />MIXED CONSTRUCTION� NO
<br />BUILDING HEIGHT: <35'
<br />SPRINKLED: NO
<br />APPLICABLE BUILDING CODES
<br />TOTAL
<br />FLORIDA
<br />BUILDING CODE (FBC) 6th
<br />ed. BUILDING (2017)
<br />FLORIDA
<br />BUILDING CODE (FBC) 6th
<br />ed. MECHANICAL (2017)
<br />FLORIDA
<br />BUILDING CODE (FBC) 6th
<br />ed. ENERGY (2017)
<br />FLORIDA
<br />BUILDING CODE (FBC) 6th
<br />ed, PLUMBING (2017)
<br />FLORIDA
<br />FIRE PREVENTION CODE 6th
<br />eol.(2017)
<br />NATIONAL
<br />ELECTRICAL CODE, 2014
<br />E-DITION
<br />FLORIDA
<br />ACCESSIBILITY CODE 6th
<br />ed. (2017)
<br />AMERICANS
<br />W/DISSABILITIES ACT (ADASAD),
<br />ed, (2010)
<br />FIXTURES SHOWN MEET REQUIREMENTS
<br />GROUP
<br />SPRINKLITRED
<br />NONSPRINKLERED
<br />Interior exit stairways and rcmpQsorrIdors
<br />and exit passageways a, b
<br />and
<br />enclosure for exit
<br />access stairways
<br />and ramps
<br />Rooms and
<br />enclosed
<br />spaceg
<br />Interior exit stairways
<br />ramps and exit
<br />passageways a, b
<br />a6drrIdors qnd
<br />enclosure for exit
<br />access stairways
<br />and ramps
<br />Rooms and
<br />enclosed
<br />spaces c
<br />A-1 & A-2
<br />B
<br />B
<br />C
<br />A
<br />Ad
<br />Be
<br />A-3f, A-4, A-5
<br />B
<br />B
<br />C
<br />A
<br />Ad
<br />C
<br />(OB E, M, R-1
<br />B
<br />C
<br />C
<br />A
<br />B
<br />C
<br />R-4
<br />B
<br />C
<br />C
<br />A
<br />B
<br />B
<br />F
<br />C
<br />C
<br />C
<br />B
<br />C
<br />C
<br />H
<br />B
<br />B
<br />C9
<br />A
<br />A
<br />B
<br />B
<br />C
<br />C
<br />A
<br />B
<br />B
<br />1-2
<br />B
<br />B
<br />B h.1
<br />A
<br />A
<br />B
<br />1-3
<br />A
<br />AJ
<br />C
<br />A
<br />A
<br />B
<br />1-4
<br />B
<br />B
<br />B
<br />A
<br />A
<br />B
<br />R-2
<br />C
<br />C
<br />C
<br />B
<br />B
<br />C
<br />R-3
<br />C
<br />C
<br />C
<br />C
<br />C
<br />C
<br />9
<br />1 C
<br />C
<br />C
<br />B
<br />B
<br />C
<br />U
<br />I No restrictions
<br />No restrictions
<br />For SI: 1 Inch = 25,4 mm, 1 square foot = 0,0929 m2.
<br />a,C(ass C interior finish materials shalt be permitted for wainscotting or paneling of not more than 1,000 square feet of baippliIe " surface area in the grade
<br />Lobby where applied directly to a noncombustible base or over furring strips applied to a noncombustible base and fire oc eel as required by Section 803.13.1.
<br />b,In other than Group 1-3 occupancies In buILdIn s Less than three stories above grade ptane, Class B interior finish for nonsprinkLered buiLdings and Class C
<br />Interior finish for sprinkLered buildings shalt b ge permitted In Interior exit stairways and ramps.
<br />c.Requirements for rooms and enclosed spaces shalt be based upon spaces enclosed by partitions, Where a fire -resistance rating is required for structural
<br />elements, the enclosing partitions shalt extend from the floor to the ceiling. Partitions that do not comply with this shalt be considered enclosing spaces
<br />and the rooms or spaces on both sides shalt be considered one, In determining the applicable reTuirements for rooms and enclosed spaces, the specific
<br />occupancy thereof shalt be the governing factor regardLess of the group cLassification of the It ding or structure.
<br />dLobby areas In Group A-1, A-2 and A-3 occupancies shalt not be less than Class B nateriats.
<br />e.Ci C Interior finish materials shalt be permitted In places of assembly with an occupant Load of 300 persons or Less.
<br />fFor places of religious worship, wood used for ornamental purposes, trusses, paneling or chancel furnishing shalt be permitted,
<br />g.C(ass B material is required where the bultding exceeds two stories.
<br />h.Class C Interior finish materials shalt be permitted In administrative spaces,
<br />I.CLass C interior finish materia(s shalt be permitted In rooms with a capacl t of four ersons or Less,
<br />jC[ass B materials shalt be permitted as wainscotting extending not more t�an 48 inci s above the finished floor in corridors and exit access stairways and ramps,
<br />kFinish materials as provided for in other sections of this code.
<br />L,Applies when protected by an automatic sprinkler system InstaLLed In accordance with Section 903.3.1.1 or 903.3.1.2,
<br />INTERIOR FINISH SCHEDULE
<br />INTERIOR FINISHES TO BE DETERMINED BY OWNER
<br />RESTROOM FLOORS TO BE A NON ABORBENT MATERIAL
<br />RESTROOM WALL TO BE A NON ABSORBENT MATERISL
<br />MINIMUM 480 A.F.F.
<br />El IT10) =INg 91,4E09 *=I=
<br />AN EXTERIOR VERTICAL CHEMICAL BARRIER SHALL BE INSTALLED AFTER CONSTRUCTION 13
<br />COMPLETE (INCLUDING LANDSCAPING AND IRRMATION) ANV SOILS DISTURBED AFTER THE
<br />VERTICAL BARRIER 03 APPLIED, SHALL BE RE -TREATED
<br />CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 12 INCHES AWAY FROM THE
<br />BUILDING SIDEWALLS
<br />M I (a) I L
<br />10AT00,111111TO-1 11, 1 �iii I i FAN
<br />WIND
<br />1611111 jj. PEIL. JOIJ F
<br />COW*
<br />WIND DESIGN ASSUMPTIONS:
<br />BUILDING (EXPOSURE - 0
<br />BUILDING RISK CATEGORY - It
<br />MEAN ROOF HEIGHT W OR1ESS
<br />HEIGHT la EXPOSURE ADJUSTMENT
<br />COEFFICIENT a 1.0
<br />ENCLOSED BUILDING
<br />INTERNAL PRESSURE COEFFICIENT = +P 0 IF,'
<br />. . . . . . . . . . 'Rt( —
<br />W(VO-DO)IONZIL
<br />2
<br />ROOF OVERHANG
<br />LOADS
<br />N/A
<br />.A 37.10W 5
<br />-75.5
<br />.0137AWA
<br />A26.9
<br />IMP,
<br />it I E TIES TIF
<br />k7it(0)F-AICO]r.illl[A\LTIMTIH-I PANWAIM]
<br />01
<br />D&TV04A
<br />M. I "At
<br />FU
<br />.............
<br />RM,
<br />1FAWYA150AC6,00 IN.911*141094 _wz
<br />gjN*
<br />TOD
<br />21 A-119WIT(O-TAT11060
<br />IIVDEX S H T #
<br />1, CFIVER
<br />2, FLOOR PLAN
<br />3, LIEHT PLAN
<br />4, POWER PLAN
<br />5, HVAC PLAN
<br />6, FIRE SAFETY
<br />7, UL SHEETS
<br />uv;xw jjkATj:j1 �'7_4
<br />CM (W zowird;uAl
<br />KJR-i 0'FMC1AL--tL')QP
<br />ALL WORK SHALL
<br />WFA CODES COMPLY wl�rH
<br />AND sTANDAI�DS
<br />REVIEW DATE
<br />UITYOFZEp'
<br />FIRE AND LIFE SAFM
<br />IN,
<br />PARCEL: 19-26-22-0010-00000-0130
<br />PLAN
<br />ALL WORK SHALL COMPLY WITH PREVAIUNL,,
<br />CODES FLORIDA BUILDING CODE,
<br />NATIONAL ELECTRIC CODE,
<br />AND THE CITY OF ZEPHYRHILLS
<br />ORDINANCES
<br />I hereloy certify that I have reviewed this plan and found it to lo(
<br />compliance with ASCE 7-10 and the Florida Building Code 2017 Sth Edi
<br />David W, Smith, P,E, #
<br />
|