Laserfiche WebLink
ELECTRICAL SPECIFICATIONS <br />1.1 SCOPE <br />A. WORK INCLUDED: Include the following Work in addition to Items normally part of this Section: <br />01 VAdng for lighting and power. <br />02 Installation of lighting fixtures with lampL <br />03 Lighting panalboarde and distribution ponelboards. <br />04 Connection of equipment shown. <br />05 Control wiring. <br />06 Disconnection and removal of existing fixtures and wiring not to be rou"d. <br />1.2 MINIMUM COMPLIANCE STANDARDS <br />A. AN work shall be done In accordance with the requirements of the following: <br />01 Florida Building Code Sixth Edition (2017). <br />02 Florida Building Code - Electrical Conservation Sixth Edition (2017). Section C405. <br />03 2014 issue of the National Electrical Code (NFPA 70). <br />04 All Receptacle Control to conform to ASHRAE Standard 90.1. 8.4.2. 2010. <br />05 Vf1ring In Patient Care Areas shall comply with NEC 517. <br />06 Other applicable NFPA Codes. <br />07 Regulation of local authorities having jurisdiction. <br />B. Furnish and Install all loborII material and equipment and services necessary for complete and <br />ode Installation of the electrical system Indicated on the drawings and noted In the <br />specificailone hereinafter. Electrical systems and equipment shall In general Include the following: <br />01 General provisions for electrical work. <br />02 Ming. distribution equipment and devices. <br />03 Lighting fixtures and lamps. <br />04 Grounding syrdern. <br />1.3 GENERAL PROVISIONS FOR ELECTRICAL WORK <br />A. DRAWINGS: Electrical drawings considered diagrammatic and Indicate general arrangement of work <br />and systems. Refer to ather drawings to verfly Wation of equipment. air- Check drawings of <br />allwr trades to vwffy exact space condition or underground line& Drawing Swiss prohibit the <br />Indication of all offeeft. fittings and accessories required. however the" Items will be <br />provided by We subcontractor at no extra cost to the owner. <br />B. OUALITY OF MATERIALS: Now. best of their respective kind. free from defects. and listed by <br />Underwdtses Laboratorlm Inc. or bearing their label. <br />C. SHOP DRAWINGS: Submit four (4) copies of shop drawings for lighting fixtures and ponelboords. <br />Obtain approval before equipment Is ordered. built or Installed. <br />D. EXCAVATION AND BACKFILLING- Excavate. backfill and restare surfaces for all electrical work. <br />E. Visit site and Inspect existing facilities before bid In order to ensure proper evaluation of <br />working conditions and location of existing equipme-t, <br />1.4 WIRING. DISTRIBUTION EQUIPMENT AND DEVICES <br />A. CONDUCTORS: Copper. In accordance with ASTM Standards. size references AND. Conductors No. 10 and <br />smaller size solid. No. 8 and larger stranded. Insulation of conductor thermoplastic. type THHIN <br />(min. she: No. 12) any wire Installed outside, underground. In dabs. or exposed to moisture <br />shall have THINN Insulation. <br />B. RACEWAYS: RIGID STEEL CONDUIT, full weight pipe galvanized. threaded. and minimum 1/2 Inch except <br />as noted or required for wiring. ELECTRICAL METALLIC TUBING (EMT). thin wall pipe, galvanized. threadless. <br />cornresslon fittinge. and minimum 1/2" except as noted or required for wiring. FLEXIBLE STEEL CONDUIT, <br />continuous singlestrIp. galvanized. and minimum 1/2' sin except as noted or required for wiring. PVC <br />CONDUIT, heavy duty type. size as Indicated Separate raceways shall be used for each vofte" system. <br />Type AC or MC Cable where permitted. <br />C. DISCONNECT SWITCHES: General Duty. horsepower rated for motor loads 600 or 250 volt rating, fu@W <br />or non-lused as noted; number of poke as Indicated. cover Interlocked with switch. Enclosure <br />NEMA 1 for Indoor use and NEMA 3R for weatherproof applications. Switch to be Square W or equal. <br />D. CIRCUIT BREAKERS: Molded case. thermal-magnstle quick -make. quick -break. bolt -on type with <br />manually operated insulated Ibip-fror handle. Multi-polle types with Internal common trip bar. <br />Terminals suitable for copper or aluminum conductors. Interrupting capacity minimum 10.000 RMS <br />symmetirical amperes circuit breakers to be Square IV or equal. type as required. <br />E. PANELBOARDS. Voltage. phasing and ampers ratings an Indicated. circuit breaker iyps as Indicated. <br />busbars of hard drawn copper. minimum WX conductivity, galvanized stsel back box. door and trim. <br />All comers lapped and welded. hardware chrome plated with flush lack and catch. Hinges serni- <br />concealed, 5 knuckle steel with nonferrous pins. 180 degree openings. Minimum gutter Waco 5- <br />3/4' sides. top and bottom. Increase @I= where required by code. Directory holder complete <br />with clear plastic transparent a~ Indicating "werItten list of feeder cables, conduit sizes, <br />circult numbers. outlets of equipment supplied. and their location. Circult breaker type <br />ponelboards to be Square 'D" type NOOD or I -Lino. or equal. A plastic MW shall be located on extolor of <br />parvelboard Identifying the system voltage, ptme. and current rating. <br />F. VARING DEVICES:- All devices the product at the earns manufacturer. Wall switches sIngle pass. 20 <br />ampere. 120 volt. Wall switches three-way. 20ampere, 120 volL Receptacles duplex, 2 wire; 3 <br />pole grounded. 20 ampers. 120 volt. <br />G. DEVICE PLATEL- Provide for all outlets whom devices are Installed. Provide engraved marking for <br />special outlets. Provide blank plain for empty or future outlet boxes. DEVICE AND DEVICE PLATES <br />COLORS TO BE VERIFIED WITH INTERIOR DEMER AND OWNER. <br />1.5 LIGHTING FIXTURES AND LAMPS <br />A. Furnish and Install complete system of lighting fixtures, lam^ accessories and supports an <br />specified and Indicated. Submittals of equal quality are allowed. <br />1.6 GROUNDING SYSTEM <br />A. EQUIPMENT- Ground non -current carrying metal parts of ponsiboard. raceways and all lighting <br />fixtures. AN conduits shall have equipment grounding conductors. <br />1.7 INSTALLATION <br />A. Secure all supports to building structure. Support horizontal runs <br />of metallic conduit not more than 10 feet aporL Run expand mc*woyv parallel with or at right <br />angles to walls. <br />B. Pon raceways over water. @tsom or other piping when pWI boxe@ am not required. No raceway <br />within 3 Inches of steam or hat water pipes, or appliances, except craWnge woo raceway shall <br />be at least 2 Inch" from pipe cover. <br />C. Cut conduit ends square, room smooth. Point trials threads of field threaded conduit with graphite <br />base pipe compounrl. Dmw up tight with conduit couplkW. <br />0. Leave wire sufficiently long to permit making final connectlonL In raceways over 50 fed in <br />which wiring Is not Installed, furnish pull wire. <br />E. Verify locations of outlets and switches. <br />F. Support panel, junction and pull boxes Independently to building structure with no weight bearing <br />on conduitL <br />0. Connect conduit to motor conduit terminal boxes with flexible conduit. minimurn 18 inches in <br />length and 50% slock. Do not terminate In or fatten raceways to motor founda". <br />H. Contractor to remove and salvage all abandoned electrical equirnant. <br />1. This contractor shall warrant all labor and materials for one year from date of final written <br />acceptance. <br />J. Owner assumes responsibility to do periodic maintenance on all Aluminum Wire Connections and will <br />provide a signed letter to attest to this agreement. <br />K. Contractor will provide to the Building Owner. within 30 days after the date of the system acceptance. record <br />drowimp of the actual Installation Documents and Manuals per C405.6.4 <br />L Contractor shall provide construction documems that certify lighting contrals mest performance "its& of <br />Section C405 of the Florida Building Code Sixth Edition (2017) Energy Conservation, and provided to the <br />Building Owners within 90 days of receipt of the Cortificate of Occupancy per C408.3.2 of the same code. <br />1.8 LOW VOLTAGE <br />A. Low Voltage wiring drawings to be provided by others. <br />ELECTRICAL SYMBOLS <br />SIM — mmum. MOTOR sTwrER Sam Ais REQUIRED <br />S3D— -3-WAY SINGLE ME DIMMER SWITCH (O-1OV OR LINE VOLT. AS REQUIRED) <br />SD — SINGLE POLE DIMMER SWITCH (O-10V OR LINE VOLTAGE AS REQUIRED) <br />S*_ 3-WAY SINGLE POLE TOGGLE SM704 W/PlLOT LIGHT <br />5 — SINGLE POLE TOGGLE SWITCH <br />S3 — 3-WAY W40LE POLE TOGGLE SWITCH <br />SO — -0/b- INDICATES LIGHTS TO BE SVITICHED <br />(%.b — OCCUPANCY SENSOR W/TWO LEVELS OF LIGHIIING LINE VOLTAGE <br />— TIME CLOCK wmDE Swim (MAX. 2 HR) <br />— LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR <br />— LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR <br />— LINE VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR (LARGE RESTROOMS) <br />— LINE VOLTAGE WALL MOUNTED OCCUPANCY SENSOR (SMALL RESIROOMIS) <br />L�MOUNTM OCCUPANCY SENSOR W/2 LIGHT CONTROL <br />0 — WALL MOUNTED OCCUPANCY SENSOR (CLOSETS) <br />Q) — WALL MOUNTED DIMMABLE OCCUPANCY S84SOR <br />VERIFY LINE VOLTAGE OR O-10V <br />411 — MANUAL "ON" OCCUPANCY SENSOR <br />MANUAL *ON" DIMMABLE OCCUPANCY SENSOR <br />VERIFY LINE VOLTAGE OR O-1OV <br />0 — U14E VOLTAGE CEILING MOUNTED OCCWANCY SO4SOR FOR RECEPTACLES <br />DAYLG*T SENSOR <br />SPLIT DUPLEX MPTACLE HALF ON J&E OR OOCUP <br />IM A6A&T%W.. <br />RECEPTACLES BE MARKED TO I ATME MTHAT THEY <br />& .4'1 P <br />CYM %W&$ <br />A%O %r <br />A%%�RTRRU <br />ART%NWM. <br />F& CU <br />RMAC WB?N KWPONKAW T&A4%MRbONCr%M.`ED <br />SIMPLEX RECEPTACLE <br />DUPLEX RECEPTACLE <br />QUADRAPLEX RECEPTACLE <br />FLOOR BOX W/DUPLEX RECEPTACLE. LOCATIONS TO BE VERIFIED W/OWNERS <br />FLOOR BOX W/QUADRAPLEX RECEPTACLE. VERIFY LOCA71M W/OWNERS <br />MONITOR CABLEAERIFY TERMINA71ON W/OWNERS <br />On — GROUND FAULT INTERRUPTER <br />WP — WATER PROOF 311 NEMA 31t <br />W — NON -FUSED NL NIGHT' LIGHT <br />— DISCONNECT SWITCH <br />— ELECTRICAL PMIELBOARD <br />EMERGENCY LIGHTING/EXIT SIGN W/BATTERY BACKUP <br />EMERGENCY LIGHTING-W/BATTERY BACKUP 3 <br />TC — TIME CLOCK <br />— PHOTO ELEMIC SENSOR <br />— 208V 30 RECEPTACLE <br />I— CONDUIT IN FLOOR <br />RC — RECEPTACLE CONTACTOR <br />— 208V RECEPTACLE - VFRIFY <br />2 VOICE (CAT 5)/2 DATA (CAT 6) OUTLET <br />DATA & COMMUNICATIONS TO BE VERIFIED W/OWNERS <br />RESTROOM EXHAUST FAN <br />NOTE: <br />Occupancy sensors are to be 'OocuponqVVaoancy Sensors unless indicated <br />otherwise. Is: "Manual On* to a Vacancy sensor w/outo off. <br />MARK <br />MFG CATALOG NUMBER <br />LAMPS <br />REMARKS <br />QUANITY <br />A <br />METALUX 24FP4735C <br />40.4W/LED <br />LAY IN <br />5 PER UNIT <br />B <br />METALUX 4BCLED-LD4-32SL-F-UNV-GL-L835-CD1-U <br />32.5W/LED <br />WALL <br />PER UNIT <br />C <br />METALUX 8ST2L8040R <br />78.2W/LED <br />STRIP <br />10 PER UNIT <br />D <br />EATON WP1135LPC (W/DUSK TO DAWN <br />CONTROL) 13W/LED <br />WALL <br />14 <br />E <br />LUMARK WPSLED-30-GL-UNV <br />27W/LED <br />WALL PACK <br />2 <br />X-1 <br />SURE-LITES LPXC50SD <br />LED <br />EXIT/EMERG. LIGHT <br />X-2 <br />SURE-LITES APELH2 <br />LED <br />EMERG. LIGHT <br />NOTES: <br />1. ALL LIGHTING AND SWITCHING TO MEET <br />FLORIDA ENERGY CODE REQUIREMENTS <br />2. ALL LIGHTING TO BE VERIFIED WITH OWNERS BEFORE PURCHASE <br />3. LAMP COLOR INDEX IS TO BE VERIFIED <br />W/OWNERS BEFORE PURCHASE <br />4. ALL EMERGENCY LIGHTING TO BE WIRED <br />AHEAD OF ANY SWITCHING OR <br />TIME CLOCK/LIGHTING <br />CONTRACTORS <br />5, OTHER LIGHT FIXTURES BEING EQUAL AND APPROVED BY OWNER ARE PERMITTED <br />6. CONTRACTOR TO VERIFY STEM MOUNTS <br />7. VERIFY W/CONTRACTOR IF STEM OPTIONS REQUIRED <br />mm mm mm <br />SUITE SUITE B � <br />LIGHTING PLAN <br />I herelay certif y that I have reviewed this plan and f ound it to lo <br />compliance with ASCE 7-10 and the Florida Building Code 2017 6th Ed <br />David W, Smith, P.E. # <br />in <br />!on <br />3608 <br />ENGINEER <br />LICENCE #53608 <br />CHANCEY PARTNERS <br />3761 CORREIA DR <br />ZEPHYRHILLS, FLORIDA <br />D.W.SM1TH,M.S.,P.E.#53608 <br />FLORIDA PROFESSIONAL ENGINEER LICENSE NUMBER 53608 <br />PROJECTS ENGINEERING CONSULTANT <br />9909 WALLASTON DRIVE—DADE CITY,FLORIDA 33525 <br />PHONE:813-469-2289 E-MAIL: duftpeliearthlinknet <br />RICK GOLLHARDT - DRAFTSMAN <br />813-781-3651 <br />rgollhardt@tampabay.rr.com <br />LIGHTING PLAN SHEET OF <br />3 OF 7 <br />SCALE DATE JOB NO. <br />DO NOT SCALE 9 OCT 2020 <br />DESIGN/DRAWN CHECKED 2020-1003 <br />R. GOLLHARDT D. W. S., p. e. <br />T___77TF__1FF i F— --------------------- TI-1— <br />