<br />General Air Conditioning Notes
<br />1. This installation to comply with the Florida Model Energy Code, Southern Mechanical Code and any local
<br />code requirements, the mechanical contractor shall secure a mechanical permit from the governing authority
<br />and be responsible for timely inspections of the mechanical work.
<br />2. Ductwork to be fabricated from rigid fiberglass, with the clear dimensions stated
<br />on the mechanical drawings. All supply air takeoffs shall have dampers to balance the airflow to the A/D
<br />scheduled quantities. Identify the damper handles with 12" of "survey flag" to facilitate locating after ceiling is
<br />installed. Ductwork to be R=6.0 or greater where in unconditioned space, R=4.3 in conditioned space;
<br />outdoor air and exhaust air to be un-insulated metal duct. All duct to conform to UA181 standard. Rigid fiberglass
<br />(R=6.0, 1 1/2" thickness) to be reinforced per the SMACNA schedule were the dimension exceeds 26", note
<br />requirements differ between supply and return air, positive vs. negative pressure. Support rigid fiberglass
<br />duct from 1" metal strap, flex support may be in nylon mesh.
<br />3. Duct seam closure and wrap vapor barrier may be in either fiberglass fabric and mastic or duct tape. If duct
<br />tape, the it MUST BE FASSON #0810 - ABSOLUTELY NO SUBSTITUTION!
<br />4. Condensate drains to be in Schedule 40 PVC with a clean out located at the air handler and
<br />a minimum 2 "
<br />deep trap. CD line size to be 3/4" for all
<br />systems. Provide "Armaflex"
<br />type insulation (3/16"
<br />thickness) on any
<br />drain run overhead or where drain sweating
<br />would damage the
<br />structure. Condensate drains to
<br />terminate at
<br />a I$ green space". Provide a secondary drain
<br />system, with aux.
<br />drain pans on the horizontal air
<br />handlers, run
<br />outside and identified with red paint OR a
<br />float switch system
<br />is acceptable.
<br />5. Horizontal air handlers to hang from top cord of roof trusses. Hung above rest rooms drop ceiling in meachanical room.
<br />6. No smoke detector is required as AHU supply air is not greater than 2000 CFM.
<br />7. Condensing units to rest on rubber vibration isolation pads, with a minimum height of 1/2", on concrete slabs.
<br />The concrete slabs by the GC with the mechanical contractor responsible to coordinate the size allowing a
<br />minimum 6" beyond the dimension of the condensing unit.
<br />8. Refrigerant copper lines to be per schedule shown with condensing units, These size lines to have oxygen
<br />purged with dry nitrogen before brazing to minimize scale. All systems to have 1/2" "Armaflex"' type insulation
<br />applied to the suction line. ABSOLUTELY NO DUCT TAPE ON THE INSULATION, use "Preflex" glue on all
<br />joints. Install liquid line filter drier on systems that do not have them factory installed.
<br />9. Thermostat to be TRANE model TCONT602A, 2 heating / 1 cooling / off with fan switch type. Thermostat to be
<br />located as shown at 54" AFF.
<br />10. Thermostat wire to be minimum gauge 18 wire, with a minimum of one spare conductor in each jacket.
<br />LESSOR GAUGE "THERMOSTAT" WIRE IS UNACCEPTABLE!
<br />11. Set outdoor air dampers to quantities indicated on the air handler schedule to meet the requirements of
<br />ASHRAE 62.1-2004. Air quantities are located on the air handler schedule.
<br />12. Air conditioning equipment to have a one-year parts and labor warranty, with an additional warranty of four
<br />years on the compressor by the unit manufacturer. Provide the owner with warranty papers at close out.
<br />13. HVAC contractor to provide a test & balance report to the owner as part of the close out package. This report
<br />to contain model / serial numbers of all mechanical equipment as well as the final balance report showing
<br />airflow by diffuser. A calibrated "flow hood" with an experience technician is required to perform this work.
<br />Contractor may employ a NEBB certified company to perform this work and provide the necessary report. Air
<br />quantities to be balanced to within 10% of listed values. A report of vital system pressures, refrigerant and
<br />duct static, temperatures and amperage readings to be included in this report.
<br />EXHAUST
<br />FANS
<br />MARK
<br />CFM
<br />ESP
<br />DUCT SIZE
<br />REMARKS
<br />EF-1
<br />110
<br />0.25
<br />4-Rd,
<br />NUTONE 672
<br />NOTES,
<br />1) SWITCH WITH LIGHT
<br />2) 115/1/60, LESS THAN 2.5 AMPS.
<br />3) 4' T-FIN UP TO ROOF CAP.
<br />C/U HURRICANE TIE DOWN
<br />NOT M SCAIX
<br />Note: Condensing unit tie down to be as follows, use RM
<br />CUTD Clip securd to a concrete slab with 1 eash J 14 x 1
<br />1/2" screw and washer and 2-3/16* x 3/8" length to the
<br />condensing unit. 4 Clips per condensing unit up to size 4'
<br />x 4' x 4'.
<br />The design meets the reqirements of the Florida Building
<br />Code 2001, Chapter 301.13 Vind Resistance, ASCE 7-98
<br />153 MPH and SBCC1.
<br />This is for Ground Mounted unit or concrete roof deck Only.
<br />00
<br />00
<br />4.11 5 00
<br />)L
<br />Flex
<br />Duct
<br />Closer
<br />Detail
<br />NOT
<br />TO SCALE
<br />*NOTE: T
<br />BAR CEILING
<br />NO SCREWS OR
<br />SILICONE*
<br />Outer core Flex
<br />Nylon Strap, Masti & Glass Fab Outer Core to Box
<br />I &
<br />Nylon Strap Mastic Inter Core Flex to Collar
<br />Collar
<br />Tape Collar to Box _7zz::::�,,�Inter core Flex
<br />WA
<br />Pre. -Fab. Fiberglass Box R- 7,- -Nylon Strap
<br />Grill crews
<br />Drywall Grill
<br />Seal Edge of Grill with Silicone
<br />EQUIPMENT SCHEDULE
<br />MARK
<br />MARK
<br />AHU#1 / GU#1
<br />AHU#2 / CU#2
<br />AHU#3 / CU#3
<br />NOMINAL SIZE
<br />TONS
<br />3
<br />2
<br />3
<br />SUPPLY AIR QUANTITY
<br />CFM
<br />1348
<br />851
<br />1216
<br />OUTSIDE AIR QUANTITY
<br />CFM
<br />215
<br />152
<br />232
<br />EXTERNAL STATIC PRESSURE
<br />IN. H20
<br />.5
<br />.5
<br />.5
<br />CONDENSING MODEL NO.
<br />-----
<br />4TWR3036A
<br />4TWR3024A
<br />4TWR3036A
<br />-UNIT
<br />COND. UNIT OPERATING WEIGHT
<br />LBS.
<br />245
<br />197
<br />245
<br />COND. UNIT DIMESIONS
<br />HxWxD
<br />370704
<br />290200
<br />370704
<br />QTY. OF COMPRESSORS
<br />1 1
<br />1
<br />1
<br />COMPRESSOR POWER
<br />V/O/HZ
<br />240/1/60
<br />240/1/60
<br />240/1/60
<br />COPRESSOR AMPACITY
<br />RLA LRA
<br />1 5.4 /83
<br />9.4 /63
<br />15.4/83
<br />QTY. OF CONDENSER FANS
<br />1
<br />1
<br />1
<br />CONDENSER FAN H.P.
<br />HP (EA.)
<br />1/4
<br />1/8
<br />1/4
<br />UNIT MIN. CIRCUIT AMPACITY
<br />MCA
<br />21
<br />12
<br />21
<br />0
<br />0
<br />UNIT MAX. OVER CURRENT PROTEC11ON
<br />MOC P
<br />35
<br />20
<br />35
<br />0
<br />AIR HANDLER UNIT MODEL NO.
<br />----
<br />4TEC3F42C
<br />4TEC3F3OB
<br />4TEC3F42C
<br />A.H.U. OPERATING WEIGHT
<br />LBS.
<br />150
<br />125
<br />150
<br />A.H.U. DIMESIONS
<br />HxWxD
<br />52x23.5x2l
<br />45x2l.5x2l
<br />52x23.5x2l
<br />TOTAL CAPACITY
<br />MBH
<br />36,200
<br />23,400
<br />36,200
<br />SENSIBLE CAPACITY
<br />MBH
<br />25,340
<br />16,380
<br />25,340
<br />ENTERING AIR
<br />DB / WB
<br />77 / 65
<br />77 / 65
<br />77 / 65
<br />MIN. UNIT EFFICIENCY
<br />----
<br />13.00 SEER
<br />13.00 SEER
<br />13.00 SEER
<br />FAN H.P.
<br />BHP
<br />1/2
<br />1/3
<br />1/2
<br />TOTAL HEATING CAPACITY
<br />MBH
<br />33,200
<br />22,400
<br />33,200
<br />Z
<br />ENTERING AIR
<br />DB
<br />1 70
<br />70
<br />70
<br />F-
<br /><
<br />Ld
<br />POWER
<br />V/O/HZ
<br />240/1/60
<br />1 240/1/60
<br />240/1/60
<br />1
<br />X:
<br />I HEATER SIZE
<br />KW
<br />4.80
<br />1 4.80
<br />1 4.80
<br />1
<br />NOTES:
<br />1. BREAKERS TO BE HACR.
<br />2. FURNISH FIVE YEAR COMPRESSOR WARRANTY.
<br />3. PROVIDE 2 1/2- DEEP 24GA. GALV. SHEET METAL AUX. DRAIN PAN / EXTEND 3- BEYOND UNIT ON ALL SIDES.
<br />4. PROVIDE FLOAT SWITCH TO SHUT DOWN SYSTEM UPON DETECTION OF WATER.
<br />5. PROVIDE FILTERS AT AIR HANDLERS.
<br />6. PROVIDE FIRE STATS IN ALL UNITS.
<br />7. PROVIDE INSULTED SCH.40 PVC CONDENSTAE DRAIN LINES FROM AIR HANDLERS. RUN TO BLDG. EXTERIOR AND
<br />DISCHARGE TO AN APPROVED PLANTING AREA, STORM DRAIN OR DRYWELL.
<br />8. REFRIGERANT PIPING TO BE TYPE "L" COPPER WITH WROUGHT COPPER SOLDER FITTINGS. SILBRAZE JOINTS.
<br />9. PROVIDE BAROMETRIC OUT DOOR DAMPERS.
<br />10. GENERAL CONTRACTOR TO SUPPLY CONCRETE PADS.
<br />10. TRANE IS BASE OF DESIGN.
<br />Ashrae 62.1 - 2004 CaLcul,ation
<br />Restrooms
<br />3 x 50
<br />150
<br />Offices
<br />(Area AHU#l)
<br />1000 X 0.06
<br />60
<br />Offices
<br />(People AHU#l)
<br />7 x 15
<br />105
<br />Offices
<br />(Area AHU#2)
<br />700 x 0,06
<br />42
<br />Flf f ices
<br />(People AHU#2)
<br />4 x 15
<br />60
<br />nf f ices
<br />(Area AHU#3)
<br />950 x 0,06
<br />57
<br />Off ices
<br />(Peop(e AHU#3)
<br />5 x 15
<br />75
<br />Total
<br />549
<br />CFM
<br />AIR DISTRIBUTION SCHEDULE
<br />MARK
<br />CFM
<br />NECK SIZE
<br />REMARKS
<br />237
<br />8"rd.
<br />PRICE SPD-AS
<br />120
<br />6"rd.
<br />PRICE SPD-AS
<br />220
<br />8 rd.
<br />PRICE SPD-AS
<br />192
<br />8 rd.
<br />PRICE SPD-AS
<br />70
<br />1 Ox6 (5"rd.)
<br />AIRMATE CIELING GRILLE
<br />147
<br />6 tp rd.
<br />PRICE SPD-AS
<br />192
<br />8 13, rd.
<br />PRICE SPD-AS
<br />205
<br />8 $p rd.
<br />PRICE SPD-AS
<br />121
<br />270
<br />8"rd.
<br />PRICE SPD-AS
<br />0
<br />250
<br />8 $1 rd.
<br />PRICE SPD-AS
<br />0
<br />166
<br />6"rd.
<br />PRICE SPD-AS
<br />0
<br />24xl 2
<br />PRICE 80
<br />19
<br />- - -
<br />24x24
<br />PRICE 80
<br />15
<br />8x4 (4"rd.)
<br />AIRMATE CIELING GRILLE IN MECH. ROOM
<br />0
<br />E
<br />U�
<br />0
<br />U
<br />-C
<br />Q-
<br />Q)
<br />N
<br />4-)
<br />M
<br />0 U ( 0
<br />4--J
<br />k4- U
<br />0 4-1
<br />U)
<br />0 4-1
<br />Q) U C
<br />Q)
<br />0
<br />DRAVIN BY. MMMc
<br />oo
<br />UJ
<br />C-) (U
<br />00
<br />cu
<br />C) ON
<br />co
<br />LL1
<br />0 00
<br />LL_
<br />Finn Mom wW Ad&aw
<br />Gulf Coast Air
<br />Systems, Inc.
<br />5411 Comfort Dr.
<br />Tampa, FIL 33610
<br />813) 689-2082
<br />A/C Duct '
<br />Layout �M 2
<br />Dde
<br />2/02/2009
<br />sccde
<br />11� /4" = 1v -10
<br />zt2l, 9