BUSINESS GROUP B
<br />1,776 GSF
<br />RESIDENTIAL
<br />LOW -HAZARD STORAGE GROUP S-2
<br />2,619 GSF (EXISTING)
<br />BUILDING CODE ANALYSIS: RENOVATION OF EXISTING FIRE STATION
<br />JURISDICTIONAL CODES:
<br />Florida Building Code (FBC) 2010 - Existing Building
<br />Florida Building Code 2010 - Building
<br />Florida Building Code 2010 - Accessibility
<br />2010 Florida Fire Prevention Code (includes NFPA I - Uniform Fire Code and
<br />NFPA 101 - Life Safety Code, 2010 Editions)
<br />ALTERATIONS - LEVEL 2
<br />404.1 Scope. Level 2 Alterations include the r000nfiguration of space, the addition or elimination ofany door or window, the
<br />reconfiguarion or extension of any system, or the Installation of any additional equipment
<br />701.3 Complisance. All now construction elements, components, systems, and spaces shall comply with the requirements of the
<br />Florida Building Code, Building.
<br />703.1 Scope. The requirements of this section are limited to work areas In which Level 2 alterations are being perliormed, and
<br />shall apply beyond the work area wherespecifled.
<br />PROJECT SCOPE OF WORK: Reconfigure 1,529 GSF (20%) of building area into office space, replace exterior doors and
<br />windows with Impact -resistant doom and windows, and re -roof flat roof areas.
<br />EXISTING FIRE STATION:
<br />The original building was constructed In 1960. There was a first addition. The second addition was completed In 1983.
<br />Mixed Occupancy: Business Group B
<br />Residential Group R-2
<br />Low -Hazard Storage Group S-2
<br />CONSTRUCTION TYPES (FBC Construction Classification -Table 601, pg 6.1):
<br />Conversion to current
<br />FBC, 2010 Edition: TYPE II-B, Unprotected, Sprinklered
<br />Structural Frame: 0
<br />Exterior Bearing Walls 0
<br />Interior Bearing Walls 0
<br />Nonbearing Walls and Partitions 0
<br />Floor Construction 0
<br />Roof Construction 0
<br />Sprinkler System: Fully sprInklered
<br />Fire Alarm: Existing
<br />Existing Bldg. Area: 7,671 GSF
<br />Existing Bldg. Height +/- I W-0" (Building), +/- 37-00 (Tower)
<br />FBC 603.1 (4): Roof coverings shall have an A, B or C classification.
<br />Check Allowable Area for Existing Fire Station: Type II-B, Sprinklered (Table 503, pg 5.2)
<br />Group B
<br />3 Stories Allowable: Complies
<br />551 High Building Allowable: Compiles
<br />23,000 SF Allowable Area (w/o sprinkler system): Compiles
<br />Check Allowable Area with Automatic Sprinkler System Increase (FBC; 506.3, pg 5.4) = 300% for buildings with no more than one
<br />story above grade plans.
<br />Allowable Area (sprinkler system) = 23,000 GSF x 300% m 69,000 GSF
<br />Actual Area = 7,671 GSF (Compiles)
<br />Arrangement and Number of Exits:
<br />705.4.1.1 Occupant load and travel distance: In any work area, all rooms and spaces having an occupant load greater than 50 or
<br />In which the travel distance to an exit exceed 75 feet shall have a minimum of two egress doorways.
<br />Required Number of Exits for Occupant Load (Persons per Story) per FBC 1019. 1:
<br />1-50 Persons: 1 ExIt
<br />50-500 Persons: 2 Exits
<br />501 - 1,000 Persons: 3 Exits
<br />More than 1,000 Persons: 4 Exits
<br />Exit Access Travel Distance
<br />Work Area: 300'fbr Business, Sprinklered per FBC Table 1016.1
<br />Common Path of Travel: 100,
<br />(NFPA, Table A7.6 & 7.12.1)
<br />FIRE SEPARATIONS
<br />FBC SECTION 508 MIXED USE AND OCCUPANCY
<br />Business Group B
<br />508.4 Separated occupancies. Buildings or portions of buildings that comply with the provisions of this section shall be
<br />considered as separated occupancies.
<br />Business Group B
<br />Residential Group R-2
<br />Low -Hazard Storage, Group S-2 (Apparatus Bays)
<br />FBC Table 508.4 - REQUIRED SEPARATION OF OCCUPANCIES thours
<br />Residential Group R-2 / Business Group B: 1 hour fire separation required.
<br />Low -Hazard Storage Group S-2 / Business Group B: I hour fire separation required.
<br />Residential Group R-2 / Low -Hazard Storage Group S-2: 1 hour fire separation required.
<br />FBC Table 508 . 2.5 - INCIDENTAL ACCESSORY OCCUPANCIES
<br />Provide a one -hour fire separation or an automatic fire-extingulshing system for storage rooms over 100 SF, furnace rooms
<br />(where any piece of equipment Is over 400,000 BTU per hour Input), rooms with boilers (where the largest piece of equipment Is
<br />over 15 psi and 10 horsepower) and refrigerant machinery rooms.
<br />Calculate FBC Occupant Load of the Building
<br />Minimum Occupant Load - Table 1004.1.1
<br />Per FBC Section 1002: Gross Floor Area = Floor area within the Inside perimeter of the exterior wells of the building,
<br />exclusive of vent shaft and courts, without deduction for corridors, stairways, closets, to thickness of interior wells,
<br />columns or other features. The floor area of a building, or portion thereof, not provided with surrounding exterior walls
<br />shall be the usable area under the horizontal projection of the roof or floor above. The gross floor area shall not
<br />include shaft with no openings or Interior courts. Not Floor Area = the actual occupied area not Including unocupled
<br />accessory areas such as corridors, stairways, toilet rooms, mechanical rooms and closets.
<br />W.W=01001do
<br />plens
<br />Review
<br />122 SIF
<br />Tower
<br />69 SF
<br />I L — — — — — — L
<br />F- — — — — — — — — — — — — — — — — —
<br />I
<br />office
<br />96 SF
<br />103 :1
<br />169sp-
<br />Reception
<br />Ej-007] FE
<br />229 SF
<br />1117�0'
<br />Bath 3,276 GSF (EXISTING)
<br />LIL2A h
<br />— — — — — 50 S—F —1 — — — — — — — — — — — — — — —
<br />Future officees
<br />office office Bunk
<br />112
<br />Lobby
<br />91 SF 93SF 106 SF
<br />�j [ 110
<br />3:F� 1 97 SF
<br />74 FT TRAVEL DISTANCE
<br />i4mor
<br />C
<br />EMME 0M ME . . ME
<br />mEN'mSR `70
<br />ME ME ME ME E
<br />(F; rO MmM M)
<br />FEC
<br />ES
<br />1,01me
<br />Conference
<br />Z
<br />0
<br />21
<br />\\,44
<br />300 SF
<br />21
<br />0
<br />SF�
<br />0
<br />tZ
<br />01
<br />ce)
<br />looticlor'
<br />F
<br />F_
<br />E3
<br />_j
<br />,SF
<br />*Jftn
<br />- 49 SF"
<br />L
<br />Reports
<br />0111108
<br />108 SF
<br />115
<br />32 SF Room
<br />lie
<br />110SF
<br />corrid"
<br />71
<br />117
<br />FireMarshal's
<br />75 SF
<br />011fice
<br />253 SF
<br />0
<br />OFE Corrklor
<br />JL ME ME ME
<br />#*(-_—
<br />Kitchen Ell M
<br />F-12-17 ......... / ...........
<br />256 SF Decontarril
<br />85 SIF
<br />Dayroorn
<br />417 8F
<br />108 SIF
<br />_�o
<br />If a07
<br />E)08T. TO
<br />REMAIN
<br />,/0 0
<br />r1K
<br />154 FT Bunk
<br />Room
<br />Broakroorn (FROM MEN'S ROOM) F 122
<br />313 SF
<br />610 SF
<br />SOLAR PUMP STATION
<br />�POLAR WATER HEATER
<br />1 HR
<br />L
<br />1 HR
<br />IE
<br />I
<br />Equipment ..... .... Generator
<br />Storep Wall Room
<br />IL 164 SF 268 SF 189 SF
<br />LIFE SAFETY FLOOR PLAN
<br />/A VI/I
<br />��i 1/8' = V-0,
<br />storage
<br />L 125
<br />L
<br />21 SF
<br />FBC TABLE 1004.1.1 - MAX. FLOOR AREA ALLOWANCES PER OCCUPANT
<br />Business
<br />1 Person/ 100 GSF
<br />Assembly (UnconoenftW)
<br />1 Person/ 15 NSF
<br />Dormitories
<br />1 Person/ 50 GSF
<br />Parking Garages
<br />I Person / 200 GSF
<br />Storage
<br />1 Person / 300 GSF
<br />Calculate FBC Occupant Load of the Building:
<br />Room No. & Room Name
<br />Area
<br />Factor
<br />Occupants
<br />(for
<br />Exiting & Fixture Count)
<br />Now Construction:
<br />Reception
<br />229 NSF
<br />1 Person/ 100 GSF
<br />2
<br />Tower
<br />64 NSF
<br />I Person/ 100 GSF
<br />1
<br />Plans Review
<br />122 NSF
<br />I Person / 100 GSF
<br />2
<br />Office
<br />96 NSF
<br />I Person / 100 GSF
<br />I
<br />Office
<br />91 NSF
<br />I Person/ 100 GSF
<br />I
<br />Future Office
<br />93 NSF
<br />I Person/ 100 GSF
<br />I
<br />Women
<br />47 NSF
<br />1 Person /100 GSF
<br />1
<br />Men
<br />53 NSF
<br />1 Person/ 100 GSF
<br />1
<br />Conference Room 300 NSF I Person/ 15 NSF 20
<br />30 Persons
<br />Existina Construction:
<br />Lobby
<br />97 NSF
<br />1 Person/ 100 GSF
<br />1
<br />Reports Office
<br />108 NSF
<br />I Person/ 100 GSF
<br />I
<br />Fire Marshal's Office
<br />253 NSF
<br />1 Person/ 100 GSF
<br />1
<br />Gear Room
<br />110 NSF
<br />I Person /100 GSF
<br />1
<br />Decontamination
<br />85 NSF
<br />1 Person/ 100 GSF
<br />1
<br />Restroom
<br />106 NSF
<br />1 Person/ 100 GSF
<br />I
<br />Dayroom
<br />417 NSF
<br />I Person/ 100 GSF
<br />4
<br />Kitchen
<br />286 NSF
<br />1 Person/ 100 GSF
<br />3
<br />Breakroom
<br />615 NSF
<br />1 Person/ 100 GSF
<br />6
<br />Bunk Room
<br />313 NSF
<br />I Person/ 50 GSF
<br />6
<br />Officer's Bunk
<br />106 NSF
<br />I Person/ 50 GSF
<br />2
<br />Bath
<br />50 NSF
<br />I Person/ 50 GSF
<br />I
<br />Apparatus Bay
<br />480 NSF
<br />1 Person / 200 GSF
<br />2
<br />Apparatus Bay
<br />476 NSF
<br />1 Person / 200 GSF
<br />2
<br />Apparatus Bay
<br />478 NSF
<br />I Person / 200 GSF
<br />2
<br />Apparatus Bay
<br />478 NSF
<br />1 Person / 200 GSF
<br />2
<br />Equipment Storage
<br />164 NSF
<br />1 Person / 300 GSF
<br />1
<br />Well
<br />272 NSF
<br />I Person 1300 GSF
<br />I
<br />Generator Room
<br />192 NSF
<br />1 Person / 300 GSF
<br />1
<br />Storaos
<br />75 NSF
<br />I Person / 300 GSF
<br />I
<br />43 Persons
<br />TOTAL OCCUPANCY 73Persons
<br />Required Egress width for Doors:
<br />Factor 020 per occupant for Door Opening a (FBC Table 1005, Pg 10.5)
<br />73 Persons (Xfilerson) - 14.6- Door WIM
<br />Exist Capacity: Sr Wide Door Opening + .2"/Person 170 Persons
<br />W Wide Door Opening + 2"lPerson 340 Poisons
<br />Portable Fire Extinguishers:
<br />Re* to NFPA 10 - Standard for ftrtohlb Rm Wnyukhers, 2010 EdWon lbr portable fire extingul" requiremerits.
<br />Class A Hazards (Typical):
<br />Maxlrnurn Travel Distance to Ex*VuWw - 717
<br />Apparatus Apparatus
<br />Bay Bay
<br />128 129
<br />480 SF 478 SF
<br />170
<br />131 FT
<br />ME M5 ME M0 ME ME ME SEE ME ME
<br />(FROM MEN'S ROOM)
<br />Apparatus ApparAn
<br />Bay B"
<br />130 131
<br />478 SF 478 SF
<br />4
<br />4
<br />4
<br />Plumbing Fixture Calculations:
<br />Plumbing fixtures shall be provided .... as per FBC-P Table 403.1. The number of Occupants
<br />shall be determined by the Florida Building Code - Building.
<br />The occupant load content shall be composed of 50 percent of each sex (FBC-P 403.1.1 Pg 4.4)
<br />FBC-P 403.1.1 Fixture Calculations - Exception: the total occupant load shall not be required to be divided In half where
<br />approved statistical data indicates a distribution of ft sexes of other than 50 percent of each sex.
<br />73 PERSONS: 70% MALES + 30% FEMALES = 51 MALES + 22 FEMALES
<br />PLUMBING FIXTURE REQUIREMENTS
<br />WATER CLOSETS
<br />LAVATORIES
<br />DRINKING
<br />FOUNTAIN
<br />MALE
<br />I FEMALE
<br />MALE __]_
<br />FEMALE
<br />I PER 25 FOR THE FIRST 50 AND I PER 50
<br />FOR THE REMAINDER EXCEEDING 50
<br />1 PER 40 FOR THE FIRST 80 AND I PER 80
<br />FOR THE REMAINDER EXCEEDING 80
<br />1 PER 100
<br />2 REQUIRED
<br />I REQUIRED
<br />I REQUIRED
<br />I REQUIRED
<br />I REQUIRED
<br />3 EXISTING
<br />3 EXISTING
<br />I EXISTING
<br />NEW CONSTRUCTION:
<br />3 PROVIDED
<br />1 PROVIDED
<br />3 PROVIDED
<br />I PROVIDED
<br />2 PROVIDED
<br />FBC PLUMBING
<br />SECTION 419 URINALS: URINALS SHALL NOT BE SUBSTITUTED FOR MORE THAN 50
<br />PERCENT OF THE REQUIRED WATER CLOSETS IN BUSINESS OCCUPANCIES.
<br />URINALS PROVIDED: 0 REQUIRED / 0 PROVIDED
<br />SERVICE SINKS: 0 REQUIRED / I PROVIDED
<br />M-0
<br />ILIFE &AFEW LEGEND (SEE ELECTRICAL SYMBOL LEGENID)
<br />PRIMARY EXrr
<br />IM1116INCY UWff FDCrURE
<br />Eu
<br />ampummusiffrKME
<br />SECONDARY E)ff
<br />EMERGENCY FLUORESCENT FDCrURE
<br />MOT S*N
<br />E)ffCAPACrrY
<br />MA�OFPWWONM
<br />FIRE ALARM MANUAL PULL STATION
<br />FE
<br />FIRM EXT94OUNHOM
<br />14AM ALARM HORNN%ASHINQ 8 IRONS LXW
<br />WAXETWITID.
<br />FEC
<br />FRE EXTV49UNIM CANDMIT
<br />AND FIRE EXTHRODMIL
<br />FIRE ALARM HORN
<br />FIRE RATED PARTMONS
<br />FIRE ALARM Wini RAMON 87MM LOU
<br />AS PER PLANS
<br />EXISTING CONSTRUCTION
<br />FACP
<br />FIRE EXTINGUISHERS
<br />PROVIDE MULTI -PURPOSE, DRY CHEMICAL TYPE FIRE EXTINGUISHERS FOR
<br />CLASS A. B AND C FIRES. MINIMUM RATING IS 2A 10 BC.
<br />LEANDRO A. ARROYO
<br />FL. REG. NO. 12326
<br />CITY OF ZEPHYRHILLS
<br />RENOVATION
<br />OF
<br />FIRE RESCUE
<br />STATION NO. 2
<br />CONSTRUCTION
<br />DOCUMENTS
<br />12-07-2012 N
<br />CB+A #1202
<br />CANERDAY
<br />BELFSKY
<br />ARROYO
<br />ARCHITECTS
<br />800 SECOND AVENUE SOUTH
<br />ST. PETERSBURG, Fl. 33701
<br />(727)823-0675
<br />AA2WM7
<br />0 N
<br />LIFE SAFETY FLOOR PLAN Al A
<br />SCALE: 1/8"= V-0" m 0