<br />ELECTRICAL SPECIFICATIONS
<br />GENERAL ELECTRICAL SPECIFICATIONS
<br />1 . THE ELECTRICAL CONTRACTOR REFERRED TO HEREAFTER, AS THE
<br />"CONTRACTOR" SHALL PROVIDE COMPLETE ELECTRICAL SYSTEMS AS
<br />INDICATED ON THE DRAWINGS AND SPECIFIED HEREIN.
<br />2. CONTRACTOR SHALL PROVIDE PROTECTIVE DEVICES, CONDUCTORS,
<br />SUPPORTS, RACEWAYS, AND MISCELLANEOUS MATERIALS TO SERVE
<br />ALL DEVICES REQUIRING ELECTRICAL POWER.
<br />3. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, FEES, AND
<br />INSPECTIONS REQUIRED TO COMMENCE AND COMPLETE ELECTRICAL
<br />WORK.
<br />4. CONTRACTOR SHALL CONDUCT A THOROUGH SITE INSPECTION TO
<br />FAMILIARIZE HIMSELF WITH EXISTING CONDITIONS AND ALL ASPECTS OF
<br />HIS SCOPE OF WORK. SUCH AN INSPECTION SHALL BE CONDUCTED
<br />PRIOR TO SUBMITTING A BID.
<br />5. CONTRACTOR SHALL REFER TO INTERIOR ARCHITECTURAL CASE WORK
<br />ELEVATIONS FOR EXACT MOUNTING HEIGHTS AND/OR LOCATIONS OF
<br />SWITCHES, OUTLETS, AND WIRING DEVICES.
<br />6. CONTRACTOR SHALL MAINTAIN A COMPLETE TEMPORARY POWER AND
<br />LIGHTING SYSTEM DURING CONSTRUCTION.
<br />7. THE CONTRACTOR SHALL PROVIDE, DROP CLOTH, RUBBER MATS AND,
<br />PLYWOOD COVERS FOR OWNERS EQUIPMENT SUSCEPTIBLE TO DAMAGE
<br />DURING CONSTRUCTION. VERIFY SPECIFIC LOCATIONS WITH OWNER'S
<br />REPRESENTATIVE.
<br />8. ALL WORK SHALL BE PERFORMED DURING PERIODS ACCEPTABLE TO
<br />THE OWNER. SCHEDULE ALL WORK WITH THE OWNER'S
<br />REPRESENTATIVE BEFORE PROCEEDING.
<br />9. THE CONTRACTOR SHALL PERFORM TEMPORARY WORK NECESSARY TO
<br />MAINTAIN CONTINUITY OF ELECTRICAL SERVICE WHEN CONNECTION IS
<br />MADE TO EXISTING SYSTEMS AND FACILITIES. EXISTING SERVICE SHALL
<br />NOT BE INTERRUPTED WITHOUT PRIOR CONSENT OF THE OWNER'S
<br />REPRESENTATIVE.
<br />10. AT PROJECT COMPLETION, THE CONTRACTOR SHALL INSURE THAT ALL
<br />ELECTRICAL SYSTEMS OPERATE PROPERLY. CONTRACTOR SHALL
<br />DEMONSTRATE OPERATION OF EACH SYSTEM WITH THE OWNER'S
<br />REPRESENTATIVE.
<br />11. CONTRACTOR IS TO PROVIDE THE OWNER WITH AS -BUILT DRAWINGS OF
<br />THE SINGLE LINE DIAGRAM OF THE ELECTRICAL DISTRIBUTION SYSTEM
<br />AND FLOOR PLANS INDICATING LOCATIONS OF EQUIPMENT SERVED.
<br />PROVIDE OPERATIONS AND MAINTENANCE MANUALS FOR EQUIPMENT
<br />REQUIRING MAINTENANCE AND THE CONTACT INFORMATION FOR A
<br />QUALIFIED SERVICE AGENCY.
<br />12. CONTRACTOR SHALL COORDINATE AND VERIFY WITH LOCAL POWER
<br />COMPANY THE FOLLOWING:
<br />- EXACT LOCATION OF SERVICE CONNECTION
<br />- ELECTRICAL CHARACTERISTICS (VOLTAGE AND PHASING)
<br />- AVAILABLE FAULT CURRENT
<br />- METERING REQUIREMENTS
<br />12. "PROVIDE" SHALL MEAN "FURNISH AND INSTALL".
<br />CODES AND STANDARDS
<br />1 . ELECTRICAL WORK HAS BEEN DESIGNED TO AND SHALL COMPLY WITH:
<br />- NFPA 70 2017 (NATIONAL ELECTRICAL CODE)
<br />- NFPA 72 2016 (NATIONAL FIRE ALARM & SIGNALING CODE)
<br />- FBC 2020 7TH EDITION
<br />- NFPA 101 (LIFE SAFETY CODE)
<br />- FLORIDA FIRE PREVENTION CODE.
<br />- CODES SPECIFIC TO OTHER SECTIONS HEREIN
<br />2. ELECTRICAL WORK SHALL COMPLY WITH ALL LOCAL AND STATE
<br />ELECTRICAL CODES AND IN ACCORDANCE WITH REQUIREMENTS OF THE
<br />AUTHORITY HAVING JURISDICTION (AHJ).
<br />QUALITY
<br />1 . WORKMANSHIP SHALL BE HIGH QUALITY AND FOLLOW INDUSTRY
<br />STANDARDS. SUBSTANDARD WORK WILL BE REJECTED. THE
<br />CONTRACTOR IS RESPONSIBLE FOR REPAIR AND REWORK TO RECTIFY
<br />SUBSTANDARD WORK. QUALITY OF WORK SHALL BE DETERMINED BY
<br />THE OWNER'S REPRESENTATIVE AND/OR ENGINEER OF RECORD.
<br />INTERFERENCES
<br />1 . PLANS ARE GENERALLY DIAGRAMMATIC. THE CONTRACTOR SHALL
<br />COORDINATE WITH THE OTHER TRADES SO THAT INTERFERENCES
<br />BETWEEN CONDUITS, PIPING, EQUIPMENT, DUCTS, AND STRUCTURAL
<br />WORK WILL BE AVOIDED. IN SUCH CASE, IF THE CONTRACTOR FAILS TO
<br />COORDINATE WITH OTHER TRADES AND INTERFERENCES ARE ALLOWED
<br />TO DEVELOP, THE OWNER'S AUTHORIZED REPRESENTATIVE WILL DECIDE
<br />WHICH EQUIPMENT, DUCT, CONDUIT, ETC., MUST BE RELOCATED,
<br />REGARDLESS OF WHICH WAS INSTALLED FIRST. ELECTRICAL REWORK
<br />REQUIRED TO CORRECT INTERFERENCES WILL BE AT THE
<br />CONTRACTORS EXPENSE.
<br />MATERIALS,
<br />1 . ALL ELECTRICAL EQUIPMENT AND MATERIALS SHALL BE NEW AND
<br />APPROVED BY UNDERWRITERS LABORATORY FOR THE APPLICATION
<br />AND SHALL BEAR A UL LABEL.
<br />2. ELECTRICAL ENCLOSURES SHALL BE NEMA RATED. UNLESS OTHERWISE
<br />NOTED, ENCLOSURE RATINGS SHALL ADHERE TO THE FOLLOWING:
<br />- NEMAl INDOOR
<br />- NEMA 3R OUTDOOR
<br />- NEMA4 CORROSIVE ENVIRONMENT
<br />GUARANTEE
<br />1. CONTRACTOR SHALL GUARANTEE ALL WORK FOR A PERIOD OF ONE
<br />YEAR FROM DATE OF OWNER'S ACCEPTANCE. THE CONTRACTOR SHALL
<br />RECTIFY ANY DEFECTS DUE TO FAULTY MATERIALS OR WORKMANSHIP
<br />AND PAY FOR DAMAGE CAUSED BY FAILURE AND REWORK. THE OWNER
<br />WILL GIVE NOTICE OF DEFECTS WITH REASONABLE PROMPTNESS AFTER
<br />DISCOVERY. THE CONTRACTOR SHALL START REWORK WITHIN TEN (10)
<br />WORKING DAYS OF NOTIFICATION AND COMPLETE REPAIRS IN A TIMELY
<br />MANNER.
<br />IDENTIFICATION OF EQUIPMENT
<br />1 . LABEL ALL ELECTRICAL EQUIPMENT WITH ENGRAVED LAMINATED
<br />PLASTIC NAMEPLATE THAT CLEARLY DESCRIBES THE EQUIPMENT NAME,
<br />VOLTAGE, AMPERAGE RATING, AND FUNCTION. NAMEPLATES SHALL BE
<br />BLACK BACKGROUND WITH WHITE STENCILED UPPER CASE LETTERING A
<br />MINIMUM OF 3/16" IN HEIGHT. USE RED BACKGROUND FOR EMERGENCY
<br />SYSTEMS.
<br />2. INSTALL VINYL CLOTH SELF-ADHESIVE CIRCUIT LABELS ON ALL WIRE
<br />AND CABLE IN JUNCTION BOXES, WIRE TROUGHS, AND PANELBOARD
<br />WIRING GUTTERS.
<br />3. IDENTIFY JUNCTION BOXES WITH PERMANENT MARKER INDICATING
<br />PANELBOARD AND CIRCUIT NUMBERS OF WIRING CONTAINED WITHIN.
<br />4. PROVIDE TYPEWRITTEN PANELBOARD DIRECTORIES WITH ACCURATE AS
<br />BUILT INFORMATION. DIRECTORIES SHALL REFLECT TYPE OF LOAD AND
<br />AREA SERVED FOR EACH BREAKER.
<br />RACEWAYS AND FITTINGS
<br />1 . CONDUIT SHALL BE PROPERLY ALIGNED, GROUPED AND SUPPORTED.
<br />EXPOSED CONDUIT SHALL BE INSTALLED AT RIGHT ANGLES TO OR
<br />PARALLEL TO THE PRINCIPAL STRUCTURAL MEMBERS. CONDUIT SHALL
<br />BE SUPPORTED AT INTERVALS NOT EXCEEDING 8 FEET. CONDUIT SHALL
<br />BE SUPPORTED FROM STRUCTURE AND NOT FROM CEILING SUPPORT
<br />SYSTEM.
<br />2. CONDUITS SHALL BE INSTALLED CONCEALED WHERE POSSIBLE EXCEPT
<br />IN ELECTRICAL AND MECHANICAL ROOMS UNLESS NOTED OTHERWISE
<br />ON THESE PLANS.
<br />3. ELECTRICAL METAL TUBING (EMT) SHALL BE GALVANIZED STEEL FOR ALL
<br />INSTALLATIONS. COUPLINGS AND CONNECTORS SHALL BE
<br />COMPRESSION TYPE.
<br />4. FLEXIBLE METALLIC CONDUIT IN DRY LOCATIONS SHALL BE
<br />UNDERWRITERS'APPROVED, STEEL, ZINC COATED, SINGLE STRIP TYPE.
<br />FITTINGS SHALL BE AS MANUFACTURED BY THOMAS AND BETTS
<br />"TITE-BITE", OR APPROVED EQUAL.
<br />5. CONDUIT AND WIRING PENETRATING RATED FLOORS AND WALLS SHALL
<br />BE SEALED WITH A UL RATED ASSEMBLY TO MAINTAIN FIRE RATING AND
<br />INTEGRITY OF SEPARATION IN ACCORDANCE WITH FBC 713. REFER TO
<br />ARCHITECTURAL DOCUMENTS FOR ALL FLOOR AND WALL RATINGS AS
<br />WELL AS DETAILS IDENTIFYING THRU-WALL, FLOOR AND CEILING
<br />PENETRATIONS.
<br />BOXES
<br />1. BOXES SHALL BE RIGIDLY MOUNTED AND COVERED WITH MATCHING
<br />PLATE. OPEN KNOCK -OUTS OR HOLES IN BOXES SHALL BE PLUGGED
<br />WITH A SUITABLE BLANKING DEVICE.
<br />CONDUCTORS
<br />1 . ALL LIGHTING BRANCH CIRCUIT CONDUCTORS AND BRANCH CIRCUIT
<br />CONDUCTORS OVER 75'IN LENGTH SHALL BE SOLID NO. 10 AWG COPPER
<br />UNLESS NOTED OTHERWISE. ALL BRANCH CIRCUIT CONDUCTORS UNDER
<br />761N LENGTH SHALL BE SOLID NO. 12 AWG COPPER UNLESS NOTED
<br />OTHERWISE.
<br />2. ALLOW SUFFICIENT CABLE SLACK IN BOXES, OUTLETS AND CABINETS TO
<br />MAKE CONNECTION AND INSURE THERE IS NO BINDING AT THE
<br />SPLICE/TAP.
<br />3. THE USE OF METAL CLAD CABLE (MC -CABLE), AS DEFINED BY NEC 330.2,
<br />SHALL BE PERMISSABLE FOR THIS APPLICATION. INSTALLATION MUST
<br />COMPLY WITH ALL REQUIREMENTS SET FORTH IN NEC ARTICLE 330.
<br />4. CONDUCTORS SHALL BE COPPER. UNLESS OTHERWISE NOTED,
<br />INSULATION SHALL BE DUAL TYPE THHNrrHWN 75'C. CONDUCTORS
<br />SHALL BE COLOR CODED IN ACCORDANCE WITH NFC 70. COLOR CODING
<br />SHALL BE BY MEANS OF COLORED INSULATING MATERIAL, COLORED
<br />BRAID OR JACKET OVER THE INSULATION OR BY MEANS OF SUITABLE
<br />COLORED, PERMANENT, NON -AGING, INSULATING TAPE APPLIED TO
<br />CONDUCTORS AT EACH CABINET OR JUNCTION POINT. THE FOLLOWING
<br />SYSTEM OF COLOR CODING SHALL BE ADHERED TO:
<br />- GROUND LEADS: GREEN
<br />- 120/208 NEUTRAL CONDUCTOR: WHITE
<br />- 120/208 VOLT, PHASE CONDUCTORS: BLACK, RED, BLUE
<br />6. EXISTING FACILITIES: WHERE EXISTING COLOR CODING SCHEME
<br />DIFFERS FROM THAT SPECIFIED HEREIN, CONTRACTOR SHALL ADHERE
<br />TO ESTABLISHED BUILDING STANDARD. ADVISE PROJECT
<br />ADMINISTRATOR IN WRITING OF COLOR CODING SCHEME BEING USED.
<br />7. THE COLOR CODE ASSIGNED TO EACH PHASE WIRE SHALL BE
<br />CONSISTENTLY FOLLOWED THROUGHOUT.
<br />GROUNDING
<br />1 . ALL INTERIOR ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND
<br />EFFECTIVELY GROUNDED AS REQUIRED BY NFPA 70 AND AS SPECIFIED
<br />HEREIN.
<br />2. METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY
<br />SECURE AT ALL JOINTS AND AT ALL BOXES, CABINETS, FITTINGS, AND
<br />EQUIPMENT. METALLIC RACEWAYS SHALL BE CONNECTED TO A DIRECT
<br />GROUND AT POINT OF ELECTRICAL SERVICE ENTRANCE AND SHALL BE
<br />ELECTRICALLY CONTINUOUS THROUGHOUT THE ENTIRE SYSTEM.
<br />3. ALL GROUND CONDUCTORS SHALL BE INSULATED COPPER UNLESS
<br />OTHERWISE NOTED.
<br />4. RACEWAYS WITH NO. 10 OR 12 AWG PHASE CONDUCTORS FOR
<br />RECEPTACLES, LIGHT FIXTURES AND SIMILAR CIRCUITS (NEW BRANCH
<br />CIRCUITS) SHALL BE PROVIDED WITH A PARITY SIZED GREEN EQUIPMENT
<br />GROUND CONDUCTOR. GROUND CONDUCTOR SHALL BE INSTALLED IN
<br />ENTIRE RACEWAY SYSTEM INCLUDING WALL SWITCHES AND FLEXIBLE
<br />CONDUIT TO LIGHT FIXTURES. EQUIPMENT GROUND CONDUCTOR SIZES
<br />FOR CIRCUITS WITH PHASE CONDUCTORS LARGER THAN NO. 12 AWG
<br />ARE INDICATED ON DRAWINGS.
<br />LIGHTING
<br />1 . CONTRACTOR SHALL PROVIDE ALL MOUNTING HARDWARE AND LIGHTING
<br />OPTIONS TO PROVIDE A PROPER LIGHTING INSTALLATION.
<br />2. FIXTURES SHALL BE PROPERLY SUPPORTED AND ALIGNED. LIGHTING
<br />FIXTURES SHALL BE CLEANED AND LAMPED IMMEDIATELY PRIOR TO
<br />FINAL INSPECTION.
<br />WIRING DEVICES
<br />1. LIGHTING TOGGLE SWITCHES SHALL BE 20 AMP, SPECIFICATION GRADE
<br />TOGGLE TYPE SWITCHES. ALL SWITCHES AND COVERPLATES SHALL BE
<br />GRAY. ALL COVER PLATES SHALL BE STAINLESS STEEL. ALL ADJACENT
<br />SWITCHES SHALL BE GANGED IN ONE COMMON COVERPLATE/BOX.
<br />LOCATIONS AND HEIGHTS SHALL BE COORDINATED WITH DOOR SWINGS
<br />AND COUNTER HEIGHTS.
<br />2. DUPLEX AND DOUBLE DUPLEX RECEPTACLES SHALL BE 20 AMP, 125
<br />VOLT RATED, SPECIFICATION GRADE. RECEPTACLES SHALL HAVE A
<br />GREEN GROUNDING SCREW TERMINAL AND A SELF GROUNDING CLIP.
<br />ALL RECEPTACLES SHALL BE GRAY WITH STAINLESS STEEL COVER
<br />PLATES. EXACT LOCATIONS AND MOUNTING HEIGHTS SHALL BE
<br />COORDINATED WITH THE COUNTER HEIGHTS AND ALL LOCATIONS SHALL
<br />BE VERIFIED WITH THE OWNER PRIOR TO ROUGH -IN. GFCI TYPE
<br />RECEPTACLES SHALL BE 20 AMP 125V, NON FEED-THRU TYPE.
<br />GENERAL NOTES
<br />I . THE CONTRACTOR SHALL REFER TO THE ELECTRICAL SPECIFICATIONS
<br />FOR ADDITIONAL DESIGN STANDARDS. THE ELECTRICAL SPECIFICATIONS
<br />ARE A BINDING PART OF THE CONSTRUCTION DOCUMENTS.
<br />2. ALL MATERIALS USED FOR CONSTRUCTION SHALL BE INSTALLED IN A
<br />NEAT AND WORKMANLIKE MANNER. RACEWAY AND CABLES SHALL RUN
<br />PARALLEL OR PERPENDICULAR TO WALL AND CEILING STRUCTURES FOR
<br />A NEAT APPEARANCE. ALL MATERIAL AND INSTALLATION WILL BE
<br />SUBJECT TO OWNER'S APPROVAL. COORDINATE AND SCHEDULE
<br />INSPECTIONS WITH THE AHJ AND THE OWNER ACCORDINGLY.
<br />3. PRIOR TO ROUGH -IN FOR LIGHTING SWITCHES, VERIFY ALL DOOR
<br />SWINGS WITH ARCHITECTURAL PLANS.
<br />4. ARRANGE LIGHTING FIXTURES IN ACCORDANCE WITH THE
<br />ARCHITECTURAL REFLECTED CEILING PLANS.
<br />5. COORDINATE LIGHTING FIXTURES INSTALLATION WITH GRILLES,
<br />DIFFUSERS, SPRINKLER HEADS, AND ACCESS PANELS, PROVIDE FIXTURE
<br />MOUNTING BRACKETS, ACCESSORIES, PLASTER FRAMES, ETC. SUITABLE
<br />FOR THE CEILING TYPES INDICATED ON THE ARCHITECTURAL PLANS.
<br />6. SYMBOLS NOT LISTED IN THE LEGEND ARE IDENTIFIED WHERE THEY
<br />OCCUR ON THE DRAWINGS.
<br />7. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING FIRE STOPPING
<br />AT WALL, FLOOR AND CEILING PENETRATIONS WHERE CONDUIT
<br />PENETRATIONS OCCUR IN FIRE RATED CONSTRUCTION. FIRE STOPPING
<br />AT CONDUIT PENETRATIONS SHALL BE Ul. LISTED.
<br />8. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. FURNISH ALL
<br />REQUIRED JUNCTION BOXES, PULL BOXES, FITTINGS, CONDUIT BODIES,
<br />SUPPORT, ACCESS DOORS, HARDWARE, ACCESSORIES, ETC. REQUIRED
<br />FOR A COMPLETE AND WORKING ELECTRICAL SYSTEM, WHETHER OR
<br />NOT SUCH EQUIPMENT IS INDICATED ON THE DRAWINGS.
<br />9. THE CONTRACTOR SHALL COORDINATE WITH ALL CONTRACT
<br />DOCUMENTS AND EQUIPMENT SHOP DRAWINGS.
<br />10. THE CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL OTHER
<br />TRADES BEFORE INSTALLATION OF HIS WORK IN CHASES, CEILING
<br />SPACES AND OTHER AREAS WHERE CONFLICT MAY OCCUR.
<br />11. REFER TO MECHANICAL, PLUMBING AND FIRE PROTECTION DRAWINGS
<br />FOR EXACT LOCATION AND REQUIREMENTS OF MECHANICAL, PLUMBING
<br />AND FIRE PROTECTION EQUIPMENT.
<br />12. ALL ELECTRICAL EQUIPMENT AND MATERIAL SHALL BE NEW AND FREE
<br />FROM DEFECT EXCEPT WHERE SPECIFICALLY SHOWN TO REUSE
<br />EXISTING MATERIAL. ALL EQUIPMENT AND MATERIAL USED SHALL BE
<br />LISTED AND LABELED UNDERWRITER'S LABORATORY (U.L.).
<br />13. ALL WORK SHALL BE SUITABLE FOR THE ENVIRONMENT THAT IT IS
<br />INSTALLED.
<br />14. COORDINATE THE INSTALLATION OF THE UTILITY TRANSFORMER WITH
<br />THE APPROPRIATE POWER COMPANY. CONFIRM WITHIN 10 DAYS OF THE
<br />AWARD OF CONTRACT THAT THE AVAILABLE FAULT CURRENT AT THE
<br />TRANSFORMER SECONDARY BUSHINGS DOES NOT EXCEED THE
<br />DESIGNED FAULT CURRENT AT THE SERVICE ENTRANCE EQUIPMENT.
<br />NOTIFY THE ENGINEER IMMEDIATELY IF THE DESIGNED FAULT CURRENT
<br />IS EXCEEDED.
<br />15. VISIT THE SITE OF THE PROPOSED PROJECT TO BECOME FAMILIAR WITH
<br />CONDITIONS AND NATURE OF THE WORK PRIOR TO SUBMITTING BIDS.
<br />NOTIFY THE ENGINEER OF DISCREPANCIES OR OMISSIONS FOR
<br />INTERPRETATION OR DECISION PRIOR TO SUBMITTING BIDS. SUBMISSION
<br />OF A PROPOSAL WILL BE EVIDENCE THAT SUCH FAMILIARIZATION HAS
<br />BEEN ATTAINED.
<br />16. WHERE CONTRACTOR PROPOSES ALTERNATE SOLUTIONS, DIFFERENT
<br />ROUTINGS OF CONDUIT, DIFFERENT LOCATIONS OF EQUIPMENT, ETC.
<br />THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OF THE
<br />RAMIFICATIONS OF THE PROPOSED CHANGE THAT ARE NOT INCLUDED IN
<br />HIS PROPOSAL, BUT BECOME APPARENT AT A LATER DATE, AND SHALL
<br />BE RESPONSIBLE FOR ALL COST AND CONSEQUENCES OF CORRECTING
<br />ANY AND ALL CONFLICTS, DEFICIENCIES OR PROBLEMS THAT INCREASE
<br />COST, INCREASE CONSTRUCTION TIME OR CREATE CODE VIOLATIONS.
<br />17. INFORMATION SHOWN ON THE DRAWINGS AS TO THE LOCATION OF
<br />EXISTING UTILITIES HAS BEEN PREPARED FROM THE MOST RELIABLE
<br />DATA AVAILABLE TO THE ENGINEER. IT IS TO BE UNDERSTOOD THAT
<br />UNFORESEEN CONDITIONS PROBABLY EXIST AND NEW WORK MAY NOT
<br />BE LOCATED EXACTLY AS SHOWN ON THE DRAWINGS. COORDINATION
<br />WITH OTHER TRADES FOR LOCATION AND BURIAL DEPTHS WILL BE
<br />REQUIRED AND ANY SUCH REQUIRED DEVIATIONS SHALL BE
<br />CONSIDERED PART OF THIS SCOPE OF WORK. SITE UTILITY
<br />INFORMATION IS NOT GUARANTEED, THEREFORE THE CONTRACTOR
<br />SHALL FIELD VERIFY THE EXACT LOCATIONS AND DEPTHS OF EXISTING
<br />UTILITIES PRIOR TO BEGINNING WORK. PROTECT ANY EXISTING UTILITIES
<br />TO REMAIN FROM DAMAGE DURING THE COURSE OF CONSTRUCTION
<br />18. PROVIDE DEDICATED NEUTRAL WIRES FOR ALL BRANCH CIRCUITS U.N.O.
<br />19. WHERE THE WORD -PROVIDE" IS USED, THIS SHALL MEAN -FURNISH AND
<br />INSTALL".
<br />20. COMPLY WITH SAFETY REGULATIONS INCLUDING BUT NOT LIMITED TO
<br />OSHA, NFPA-70E AND ALL ELECTRICAL SAFETY REGULATIONS.
<br />21. PROVIDE GROUNDING AND BONDING OF ALL METALLIC RACEWAY,
<br />BOXES, WIREWAY, DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE
<br />NEC. PROVIDE GROUNDING CONDUCTOR IN ALL POWER CONDUITS.
<br />22. INSTALL ALL DEVICES AND EQUIPMENT IN ACCORDANCE TO THE
<br />MANUFACTURER'S RECOMMENDATIONS AND U.L. REQUIREMENTS.
<br />23. WHERE THE SIZE OF A JUNCTION BOX. PULL BOX OR WIREWAY IS NOT
<br />INDICATED ON THE DRAWINGS, THE SIZE SHALL BE SELECTED IN
<br />ACCORDANCE WITH THE NEC. WHERE THE ENCLOSURE TYPE OF THE
<br />JUNCTION BOX, PULL BOX OR WIREWAY IS NOT INDICATED ON THE
<br />DRAWINGS, THE ENCLOSURE TYPE SHALL BE SUITABLE FOR THE
<br />ENVIRONMENT WHERE IT IS BEING INSTALLED IN ACCORDANCE THE NEC.
<br />24. VOLTAGE DROP FOR FEEDERS AND BRANCH CIRCUITS HAVE BEEN
<br />INCLUDED IN THE DESIGN OF THE ELECTRICAL SYSTEM TO MEET A
<br />MAXIMUM OF 5% VOLTAGE DROP PERMITTED BY 2020 FBC ENERGY
<br />CONSERVATION CODE C405.5.3.
<br />25. PROVIDE LABELS FOR ALL PANELBOARDS, CABINETS, SAFETY SWITCHES
<br />AND MOTOR CONTROLLERS, LABELS SHALL BE MACHINE ENGRAVED,
<br />LAMINATED PLASTIC, PERMANENTLY ATTACHED WITH SELF -TAPPING
<br />SCREWS OR RIVETS.
<br />26. PROVIDE TYPE WRITTEN PANELBOARD DIRECTORY CARD IN EACH
<br />PANELBOARD WITH CIRCUIT LOAD INFORMATION AND ROOM
<br />NUMBER -LOAD DESCRIPTION CLEARLY IDENTIFIED. USE ACTUAL ROOM
<br />NUMBERS IN THE BUILDING WHEN DIFFER FROM ROOM NUMBERS
<br />SHOWN ON THE CONTRACT DOCUMENTS. HAND WRITTEN DIRECTORIES
<br />ARE NOT ACCEPTABLE.
<br />27. LABEL ALL JUNCTION BOXES WITH PERMANENT MARKER IDENTIFYING
<br />PANEL'S NAME AND CIRCUIT NUMBERS WITHIN.
<br />28. ALL MOTORS SHALL HAVE DISCONNECTING MEANS.
<br />29. WHERE FUSE PROTECTION IS SPECIFICALLY REQUIRED BY THE
<br />EQUIPMENT MANUFACTURER, PROVIDE FUSED SWITCHES IN LIEU OF
<br />NON -FUSED SWITCHES OR ENCLOSED CIRCUIT BREAKERS, OR OTHER
<br />DEVICES INDICATED.
<br />30. SECURE APPROVED SHOP DRAWINGS SHOWING WIRING DIAGRAMS,
<br />ROUGH -IN AND ELECTRICAL INSTALLATION DETAILS FROM OTHER
<br />INVOLVED CONTRACTORS FOR EQUIPMENT WHICH MUST BE
<br />CONNECTED ELECTRICALLY.
<br />31. MECHANICAL EQUIPMENT WILL BE PROVIDED BY MECHANICAL
<br />CONTRACTOR. THE LOCATIONS SHOWN ON THE ELECTRICAL DRAWINGS
<br />ARE APPROXIMATE. COORDINATE WITH MECHANICAL CONTRACTOR TO
<br />DETERMINE THE EXACT LOCATION OF EACH PIECE OF EQUIPMENT AND
<br />DETERMINE THE EXACT ROUGH -IN AND CONNECTION REQUIREMENTS.
<br />32. HVAC DAMPERS AND CONTROLS. CONTRACTORS SHALL COORDINATE
<br />WITH THE EQUIPMENT AND SYSTEM BEING PROVIDED AND PROVIDE
<br />POWER CONNECTIONS ACCORDINGLY. THESE CONNECTIONS SHALL BE
<br />FOR FIRE/SMOKE DAMPERS, DDC CONTROL DEVICES, ETC. CONTRACTOR
<br />SHALL COORDINATE THE VOLTAGE REQUIREMENTS AND PROVIDE ALL
<br />NECESSARY CONNECTIONS, COMPONENTS, ETC. INCLUDING
<br />TRANSFORMERS, BOXES, ETC.
<br />33. COORDINATE FINAL LOCATIONS OF ELECTRICAL EQUIPMENT WITH
<br />MECHANICAL DUCTWORK, PIPING, ETC. AND ASSURE WORKING
<br />CLEARANCE REQUIRED BY NEC WILL BE MET. SUFFICIENT ACCESS AND
<br />WORKING SPACE SHALL BE PROVIDED AND MAINTAINED AROUND
<br />ELECTRICAL EQUIPMENT AS REQUIRED BY NEC.
<br />34. THOROUGHLY REVIEW AND COORDINATE ALL CASEWORK AND CABINETS
<br />DRAWINGS AND ARCHITECTURAL ELEVATIONS WITH DEVICE LOCATIONS
<br />PRIOR TO ROUGH -IN OF OUTLET BOXES.
<br />35. ALL SYSTEMS SHALL BE TESTED FOR PERFORMANCE VERIFICATION IN
<br />THE PRESENCE OF THE INSPECTOR, AT THE COMPLETION OF THE
<br />PROJECT. ALLOW 6 HOURS FOR TRAINING OWNER'S PERSONNEL ON ALL
<br />SYSTEMS.
<br />36. WHERE CONDUIT CROSS BUILDING EXPANSION JOINTS, USE SUITABLE
<br />SLIDING EXPANSION FITTINGS.
<br />LIGHTS LEGEND
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />WALL MOUNT FIXTURE ON FLUSH 4" SQUARE J-BOX, LETTER INDICATES TYPE
<br />SURFACE
<br />B
<br />WALLBRACKET FIXTURE ON 4"SQUARE FLUSH J-BOX, LENGTH: 2%
<br />SURFACE
<br />T, OR 4'- AS SHOWN ON PLANS, LETTER INDICATES TYPE
<br />TROFFER FIXTURE, LETTER INDICATES TYPE
<br />RECESSED
<br />RECESSED DOWNLIGHT WITH TRIM AND REQUIRED CEILING ADAPTERS. LETTER
<br />A
<br />INDICATES TYPE.
<br />A
<br />E-0
<br />SURFACE MOUNT DOWNLIGHT, ROUND HOUSING, WITH TRIM AND MOUNTING
<br />SEE FIXTURE SCHEDULE
<br />HARDWARE. LETTER INDICATES TYPE.
<br />LIGHTING CONTROLS LEGEND.
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />$
<br />SWITCH, SINGLE POLE, 20 A, 120/277 VAC. REFER TO SPECIFICATIONS FOR DEVICE
<br />COLOR, WALL PLATE COLOR AND MATERIAL, AND DEVICE MODEL NUMBER.
<br />48" AFF TO TOP UNLESS
<br />NOTED OTHERWISE
<br />$3
<br />SWITCH, THREE-WAY, 20 A, 120/277 VAC. REFER TO SPECIFICATIONS FOR DEVICE
<br />COLOR, WALL PLATE COLOR AND MATERIAL, AND DEVICE MODEL NUMBER.
<br />48" AFF TO TOP
<br />UNLESS NOTED OTHERWISE
<br />POWER LEGEND.
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />Im
<br />NON -FUSED DISCONNECT SWITCH,
<br />60" AFF TO TOP
<br />CURRENT RATING/FUSING/NUMBER OF POLES/ENCLOSURE
<br />UNLESS NOTED OTHERWISE
<br />LM
<br />FUSED DISCONNECT SWITCH,
<br />60" AFF TO TOP
<br />CURRENT RATING/FUSING/NUMBER OF POLES/ENCLOSURE
<br />UNLESS NOTED OTHERWISE
<br />72" AFF TO TOP
<br />BRANCH CIRCUIT PANELBOARD, 120/208 V OR 120/240 V, FLUSH MOUNT
<br />UNLESS NOTED OTHERWISE
<br />ELECTRIC METER
<br />60" AFF TO TOP
<br />UNLESS NOTED OTHERWISE
<br />RECEPTACLE LEGEND.
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />(P
<br />DUPLEX RECEPTACLE, 20 A, 120 VAC. REFER TO SPECIFICATIONS FOR DEVICE
<br />REQUIREMENTS, AND DEVICE MODEL NUMBER.
<br />18" AFF TO CENTERLINE
<br />COLOR, WALL PLATE
<br />UNLESS NOTED OTHERWISE
<br />DUPLEX RECEPTACLE, 20 A, 120 VAC. REFER TO SPECIFICATIONS FOR DEVICE
<br />DEVICE
<br />ABOVE COUNTER
<br />UNLESS NOTED OTHERWISE
<br />COLOR, WALL PLATE REQUIREMENTS, AND MODEL NUMBER.
<br />DUPLEX RECEPTACLE, 20 A, 120 VAC. REFER TO SPECIFICATIONS FOR DEVICE
<br />COLOR, AND DEVICE MODEL NUMBER.
<br />BELOW COUNTER
<br />UNLESS NOTED OTHERWISE
<br />WALL PLATE REQUIREMENTS,
<br />SIMPLEX RECEPTACLE, RANGE OUTLET, 50 A, 125/250 VAC, 3P, 4W, NEMA 14-50,
<br />AS NOTED
<br />WITH MATCHING COVER PLATE. LEVITON: 279
<br />SIMPLEX RECEPTACLE, DRYER OUTLET, 30 A, 125/250 VAC, 3P, 4W, NEMA 14-30,
<br />AS NOTED
<br />WITH MATCHING COVER PLATE. LEVITON: 278
<br />HOME RUN TO PANEL. LABEL INDICATES PANEL NAME AND CIRCUIT NUMBER(S).
<br />SEE SPECIFICATIONS
<br />rLlA-1,3
<br />ALL CONDUCTORS ARE #12 AWG Cu UNLESS NOTED OTHERWISE.
<br />RACEWAY CONCEALED IN WALL OR ABOVE CEILINGS
<br />SEE SPECIFICATIONS
<br />RACEWAY CONCEALED UNDER FLOOR OR BELOW GRADE
<br />SEE SPECIFICATIONS
<br />RACEWAY EXPOSED ON WALL OR CEILING
<br />SEE SPECIFICATIONS
<br />SYSTEMS LEGEND.
<br />SYMBOL
<br />DESCRIPTION
<br />MOUNTING
<br />v
<br />COMMUNICATIONS OUTLET
<br />18" AFF TO CENTERLINE
<br />UNLESS NOTED OTHERWISE
<br />9
<br />TELEVISION OUTLET
<br />18" AFF TO CENTERLINE
<br />UNLESS NOTED OTHERWISE
<br />AC ABOVE COUNTER
<br />AFF ABOVE FINISHED FLOOR
<br />AFG ABOVE FINISHED GRADE
<br />AHJ AUTHORITY HAVING JURISDICTION
<br />BFG BELOW FINISHED GRADE
<br />CLG CEILING MOUNTED
<br />ABBREVIATIONS
<br />CTE CONNECT TO EXISTING
<br />EX EXISTING
<br />GFI GROUND FAULT CURRENT INTERRUPTER
<br />IAW IN ACCORDANCE WITH
<br />IG ISOLATED GROUND
<br />N NEW
<br />RL RELOCATED
<br />UG UNDERGROUND
<br />UNO UNLESS NOTED OTHERWISE
<br />WP WEATHER PROOF
<br />U-)
<br />00
<br />c:1
<br />cl)
<br />Lo
<br />cl) U-)
<br />Ln
<br />-i C?
<br />C?
<br />u- r-
<br />:r
<br />cli c�
<br />co
<br />c�
<br />CL m
<br />c) M 0
<br />z
<br />E -
<br />cc cc)
<br />>, Lo U)
<br />M .t co
<br />�: 64
<br />E
<br />0
<br />x
<br />0) Cc
<br />r M X
<br />CD m
<br />0
<br />LL.
<br />1 _j LL.
<br />u_
<br />c�
<br />co
<br />Ln
<br />r,_
<br />2, u
<br />.2)
<br />C-4
<br />9
<br />L) C�l
<br />o cc c�
<br />42
<br />'a
<br />>,,n
<br />co
<br />"t
<br />0)
<br />() co c)
<br />4)
<br />000
<br />LIU
<br />C�
<br />m cl)
<br />0 CD C�
<br />> > 'n
<br />c)
<br />T
<br />Lu ,
<br />CL 00
<br />0 Lu o US
<br />1- Lo - co
<br />0) cm
<br />CD
<br />U
<br />00
<br />E CN -5
<br />m C%4
<br />to w M
<br />0 cf) 0 75
<br />U) Lo U)
<br />INFO
<br />wIt I I I
<br />ce-,
<br />0% STXrE OF
<br />.p
<br />0
<br />Abb'I PE
<br />FL 73853
<br />SEAL
<br />EMERALD
<br />ENGINEERING INM
<br />9942 CURRIE DAVIS DR. STE H., TAMPA, FL 33619
<br />TEL (813) 995-0300 FLORIDA EB*27845
<br />WWW.EMERALDMEP.COM EEI PROJECr* 210807
<br />CLIENT
<br />c\l
<br />It
<br />Lo
<br />cv)
<br />cf)
<br />_j
<br />LL
<br />cl)
<br />z
<br />cl a-
<br />D Lu
<br />N
<br />z
<br /><
<br />0
<br />Lo
<br />cf)
<br />Lf)
<br />It
<br />00
<br />cy)
<br />17
<br />PROJECT
<br />@ CHANCEY DESIGN PARTNERSHIP
<br />THIS DRAWING AND ALL GRAPHIC AND WRITTEN MATERIAL CONTAINED HEREIN CONSTITUTES ORIGINAL
<br />AND UNPU13LISHED WORK AND IS NOT TO BE COPIED. DtSTROUTED. OR USED IN WHOLE OR IN PART.
<br />WITHOUT EXPRESSED WRITTEN PERMISSION OF CHANCEY DESIGN PARTNERSW. THIS DRAWING IS
<br />PROTECTED UNDER THE 'ARCHITECTURAL WORKS COF�RIGHT PROTECTION ACT OF 19W�'
<br />PROJECT# 21-250
<br />PROJASSUED 8-24-2021
<br />SHEET ISSUED
<br />DIESCRIP-wok
<br />ELECTRICAL
<br />LEGEND AND
<br />SHEET TITLEGENERAL NOTES
<br />E-001
<br />
|