6i <br />0 <br />C> <br />00 <br />GENERAL NOTES: <br />1.0 GENERAL <br />1.1 ALL WORK IS TO BE PERFORMED IN A GOOD, <br />WORKMANLIKE AND PROFESSIONAL MANNER. <br />1.2 ALL CONSTRUCTION SHALL BE IN STRICT COMPLIANCE <br />WITH THE REQUIREMENTS OF THE FLORIDA STATE BUILDING <br />CODE, LATEST EDITION, OR LOCAL BUILDING CODE <br />REQUIREMENTS IF MORE STRINGENT. <br />1.3 THESE DRAWINGS DO NOT SHOW PROVISIONS FOR SAFETY <br />DURING CONSTRUCTION. IT IS THE RESPONSIBILITY OF THE <br />GENERAL CONTRACTOR TO PROVIDE THE REQUIRED BRACING, <br />SHORING, AND SAFETY DEVICES THROUGHOUT THE <br />CONSTRUCTION OF THIS PROJECT. <br />2.0 COORDINATION <br />2.1 STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION <br />WITH AND COORDINATED WITH GENERAL, ARCHITECTURAL, <br />CIVIL, ELECTRICAL AND MECHANICAL DRAWINGS AND OTHER <br />CONTRACT DOCUMENTS. <br />2.2 COORDINATE THE EXACT SIZE AND LOCATION OF ALL <br />SLEEVES AND OPENINGS THROUGH SLABS AND WALLS w/ <br />GENERAL, ARCHITECTURAL, CIVIL, ELECTRICAL AND <br />MECHANICAL DRAWINGS AND OTHER CONTRACT DOCUMENTS. <br />2.3 ANY DISCREPANCIES BETWEEN ACTUAL CONDITIONS AND <br />THOSE SHOWN ON THESE DRAWINGS ARE TO BE BROUGHT TO <br />THE ATTENTION OF THE STRUCTURAL ENGINEER BEFORE <br />CONSTRUCTION WORK PROCEEDS, INCLUDING ORDERING AND <br />FABRICATING MATERIALS. <br />2.4 INDEPENDENT TESTING OF MATERIALS SHALL BE <br />PROVIDED AS DEFINED IN PROJECT SPECIFICATIONS. IN <br />GENERAL THIS PROJECT INVOLVES THE FOLLOWING: <br />A. CONCRETE. <br />2.5 IF COORDINATION OF INFORMATION PRESENTED ON <br />DRAWINGS CONFLICTS wl THE PROJECT SPECIFICATIONS, THE <br />DRAWINGS WILL TAKE PRECEDENCE. <br />2.6 IN GENERAL CALL -OUTS ARE FOR NEW CONSTRUCTION <br />U.N.O.. EXISTING CONSTRUCTION CALL -OUTS, ELEVATIONS <br />AND DIMENSIONS OF EXISTING STRUCTURES ARE BASED ON <br />EXISTING RECORD DRAWINGS PROVIDED TO McKim & Creed. <br />THE (*) SYMBOL ON INDIVIDUAL FACILITY "STRUCTURAL" <br />DRAWINGS INDICATES EXISTING CONSTRUCTION CALL -OUTS, <br />CONDITIONS, ELEVATIONS AND DIMENSIONS TO BE FIELD <br />VERIFIED BY THE GENERAL CONTRACTOR U.N.O. PRIOR TO <br />CONSTRUCTION, INCLUDING ORDERING & FABRICATING <br />MATERIALS. RECORD DRAWINGS PROVIDED BY THE CITY OF <br />ZEPHYR HILLS UTILIZED INCLUDES: <br />A. NONE UTILIZED. <br />3.0 FOUNDATIONS <br />3.1 DESIGN ALLOWABLE SOIL BEARING PRESSURE - 2,500 <br />PSF IN ACCORDANCE WITH THE PROJECT GEOTECHNICAL <br />REPORT AS PREPARED BY MC SQUARED, INC. (PROJECT No. <br />T051005.078 DATED JANUARY, 2011). THE CONTRACTOR IS <br />RESPONSIBLE FOR VERIFYING THIS VALUE PRIOR TO <br />FOUNDATION CONSTRUCTION. IN AREAS WHERE THE SOIL <br />DOES NOT YIELD THIS BEARING STRESS VALUE, ADJUSTMENT <br />IN THE SLAB DEPTHS AND FOUNDATION DIMENSION MAY BE <br />MADE BY THE ENGINEER BEFORE WORK PROCEEDS. <br />CONTRACTOR IS RESPONSIBLE FOR PERFORMING ANY SUCH <br />ADJUSTMENTS. <br />3.2 PREPARE THE EXISTING SUBGRADE IN ACCORDANCE w/ <br />THE PROJECT GEOTECHNICAL REPORT AS PREPARED BY MC <br />SQUARED, INC. (PROJECT No. T051005.078, DATED JANUARY, <br />2011). IN THE EVENT UNUSUAL SOIL CONDITIONS ARE <br />UNCOVERED, INCLUDING CONDITIONS THAT DEVIATE FROM <br />THOSE DESCRIBED IN THE PROJECT GEOTECHNICAL REPORT, <br />NOTIFY THE OWNER AND ENGINEER PRIOR TO FOUNDATION <br />CONSTRUCTION FOR INSTRUCTIONS HOW TO PROCEED. <br />ADJUSTMENT IN THE SLAB DEPTHS AND GENERAL <br />FOUNDATION CONSTRUCTION MAY BE MADE BY THE ENGINEER <br />BEFORE WORK PROCEEDS. CONTRACTOR IS RESPONSIBLE <br />FOR PERFORMING ANY SUCH ADJUSTMENTS. <br />3.3 ALL FILL BELOW FOUNDATIONS SHALL BE SELECT <br />MATERIAL FREE FROM ROOTS, TRASH WOOD SCRAPS, AND <br />OTHER EXTRANEOUS MATERIALS. PLACE FILL IN LIFTS NOT <br />EXCEEDING THE RECOMMENDATIONS OF THE PROJECT <br />GEOTECHNICAL REPORT AS PREPARED BY MC SQUARED, INC. <br />(PROJECT No. T051005.078, DATED JANUARY, 2011). <br />3.4 SLAB ELEVATIONS SHALL NOT BE RAISED OR LOWERED <br />WITHOUT APPROVAL OF THE STRUCTURAL ENGINEER. <br />3.5 ALL EXCAVATIONS SHALL BE ADEQUATELY DEWATERED <br />BEFORE PLACEMENT OF CONCRETE. NO CONCRETE OR <br />CONCRETE FILL SHALL BE PLACED IN STANDING WATER. <br />WATER ACCUMULATION EXCEEDING 1 INCH SHALL BE PUMPED <br />OUT. <br />3.6 SLAB AND FOOTING EXCAVATIONS AND FORMS SHALL BE <br />REVIEWED BY AN OWNER'S CONSTRUCTION REPRESENTATIVE <br />PRIOR TO PLACEMENT OF CONCRETE. <br />3.7 ALL SLABS AND FOOTINGS SHALL BE CENTERED UNDER <br />THE SUPPORTING MEMBER UNLESS NOTED OTHERWISE. <br />3.8 CONSTRUCTION JOINTS IN SLABS, WALLS AND FOOTINGS <br />SHALL BE MADE AT LOCATIONS SHOWN ON DRAWINGS. <br />3.9 ANCHOR BOLTS SHALL BE SET BY MEANS OF TEMPLATE. <br />"FLOATING" ANCHOR BOLTS INTO PLACE IS PROHIBITED. <br />3.10 CONTRACTOR IS TO VERIFY THE ELEVATION AND <br />LOCATION OF ALL EXISTING AND PROPOSED UTILITIES PRIOR <br />TO CONSTRUCTION. ANY "KNOWN" UTILITY LINES DAMAGED <br />WILL BE REPLACED AT THE CONTRACTOR'S EXPENSE. IF <br />ANY "UNKNOWN" UTILITY LINES ARE ENCOUNTERED WHEN <br />EXCAVATING THE CONTRACTOR IS TO CEASE ALL EXCAVATION <br />ACTIVITY UNTIL THE ENGINEER AND OWNER ARE NOTIFIED <br />AND INSTRUCTIONS ARE PROVIDED ABOUT HOW TO PROCEED. <br />3.11 THE CONTRACTOR SHALL OBTAIN THE OWNER'S <br />PERMISSION BEFORE ENCASING OR BACK FILLING AROUND <br />ANY EXISTING UNDERGROUND STRUCTURE, PIPING, <br />ELECTRICAL, OR OTHER UNDERGROUND WORK. <br />4.0 REINFORCING STEEL <br />4.1 BARS SHALL BE ROLLED FROM NEW BILLET -STEEL OF <br />DOMESTIC MANUFACTURE CONFORMING TO "STANDARD <br />SPECIFICATION FOR DEFORMED AND PLAIN BILLET STEEL <br />BARS FOR CONCRETE REINFORCEMENT," ASTM A 615, GRADE <br />60 AND SUPPLEMENTARY REQUIREMENT S-1. <br />4.2 DETAIL AND FABRICATE REINFORCING STEEL IN <br />ACCORDANCE WITH THE AMERICAN CONCRETE INSTITUTE "ACI <br />DETAILING MANUAL," LATEST PUBLICATION. <br />4.3 REINFORCING STEEL IN PLACE SHALL BE REVIEWED BY <br />THE OWNER'S CONSTRUCTION REPRESENTATIVE PRIOR TO <br />PLACEMENT OF CONCRETE. IN GENERAL "CLR" DISTANCES <br />FOR CONCRETE COVER ARE PROVIDED ON THE DRAWINGS IN <br />THE SECTIONS & DETAILS. FOR SECTIONS & DETAILS w/OUT <br />CONCRETE COVER FOR REINFORCING BARS REFERENCE THE <br />PROJECTS SPECIFICATIONS. <br />4.4 WELDED WIRE FABRIC SHALL CONFORM TO "STANDARD <br />SPECIFICATION FOR WELDED STEEL WIRE FABRIC FOR <br />CONCRETE REINFORCEMENT," ASTM A-185. <br />4.5 WHERE WELDED WIRE FABRIC IS REQUIRED IN <br />SLABS -ON -GRADE PLACE AT CENTER OF SLABS -ON -GRADE <br />UNLESS NOTED OTHERWISE. <br />4.6 PROVIDE BARS AT CORNERS AND INTERSECTIONS OF <br />SLAB THWID T/D EDGES, AT CORNERS AND INTERSECTIONS <br />OF FOOTINGS. CORNER BARS SHALL BE OF THE SAME <br />NUMBER AND SIZE AS LONGITUDINAL BARS, U.N.O. ON THE <br />DRAWINGS. <br />4.7 FABRICATE CONTINUOUS BARS IN SLABS, WALLS AND <br />FOOTINGS TO THE LONGEST PRACTICABLE LENGTHS. <br />4.8 REINFORCING STEEL SHALL NOT BE BENT AFTER BEING <br />PARTIALLY EMBEDDED IN HARDENED CONCRETE. <br />4.9 BARS SHALL BE COLD BENT AND SHALL NOT BE HEATED <br />FOR ANY REASON. <br />4.10 REINFORCING BARS SHALL NOT BE WELDED UNLESS <br />NOTED OTHERWISE ON THE DRAWINGS. <br />4.11 REFERENCE DRAWINGS FOR REQUIREMENTS FOR LAP <br />REINFORCING STEEL IN CONCRETE. IT IS ACCEPTABLE TO LAP <br />REINFORCING A MINIMUM 50 BAR DIAMETERS, UNLESS NOTED <br />OTHERWISE. <br />4.12 LAP SPLICED BARS IN CONCRETE ARE TO BE WIRE TIED. <br />5.0 CONCRETE <br />5.1 IN GENERAL CONCRETE SHALL DEVELOP 3,000 TO 4,000 <br />psi MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS. <br />REFERENCE "DESIGN CRITERIA" THIS DWG. & PROJECT <br />SPECIFICATIONS, FOR APPLICATION & SPECIFIC CONCRETE MIX <br />DESIGN REQUIREMENTS. <br />5.2 CONCRETE WORK SHALL CONFORM TO "BUILDING CODE <br />REQUIREMENTS FOR REINFORCED CONCRETE", ACI 318 & TO <br />"CODE REQUIREMENTS FOR ENVIRONMENTAL ENGINEERING <br />CONCRETE STRUCTURES", ACI 350 (LATEST EDITIONS). <br />5.3 PLACE 1/2 INCH EXPANSION JOINT MATERIAL BETWEEN <br />EDGES OF SLABS AND VERTICAL SURFACES UNLESS NOTED <br />OTHERWISE. <br />5.4 PROVIDE CONSTRUCTION OR CONTROL JOINTS IN SLABS, <br />FOOTINGS AND WALLS AT LOCATIONS SHOWN ON THE <br />DRAWINGS, AT OFFSETS AND CHANGES IN DIRECTION AND AT <br />(30) FEET MAXIMUM U.N.O.. GENERAL CONTRACTOR IS TO <br />PROVIDE CONSTRUCTION JOINT LAYOUT PLAN PER THE <br />PROJECT SPECIFICATIONS PRIOR TO CONSTRUCTION, <br />INCLUDING ORDERING & FABRICATING MATERIALS. <br />5.5 CHAMFER EXPOSED EDGES OF CONCRETE 3/4 INCH, <br />UNLESS NOTED OTHERWISE. <br />5.6 CONTRACTOR SHALL BE RESPONSIBLE FOR PROPER <br />CURING OF ALL CONCRETE. CURING METHODS SHALL <br />CONFORM TO "BUILDING CODE REQUIREMENTS FOR <br />REINFORCED CONCRETE", ACI 318, "CODE REQUIREMENTS FOR <br />ENVIRONMENTAL ENGINEERING CONCRETE STRUCTURES" ACI <br />350 AND "STANDARD PRACTICE FOR CURING CONCRETE," ACI <br />308, LATEST EDITIONS. <br />5.7 UNLESS NOTED OTHERWISE DOWELS SHALL BE THE SAME <br />NUMBER AND SIZE AS THE LARGEST VERTICAL/HORIZONTAL <br />BAR TO WHICH THEY ARE SPLICED. <br />5.8 REFERENCE PROJECT SPECIFICATIONS FOR REQUIRED <br />FINISHES. <br />5.9 CONTRACTOR SHALL SUBMIT REBAR SHOP DRAWINGS FOR <br />APPROVAL TO OWNER PRIOR TO FABRICATION. DO NOT <br />FABRICATE REINFORCING PRIOR TO RECEIPT OF APPROVED <br />SHOP DRAWINGS. <br />5.10 CONCRETE MIXES TO BE REVIEWED BY THE OWNER'S <br />CONSTRUCTION REPRESENTATIVE PRIOR TO PLACEMENT OF <br />CONCRETE. COMPRESSIVE STRENGTH TEST CYLINDERS TO BE <br />REVIEWED BY THE OWNER'S CONSTRUCTION REPRESENTATIVE <br />THROUGHOUT CONCRETE CONSTRUCTION OF THE PROJECT. <br />5.11 CONCRETE ACCESSORIES AS FOLLOWS: <br />PREFORMED WATERSTOPS SHALL BE PVC IN <br />ACCORDANCE w/ THE PROJECT SPECIFICATIONS. <br />b.) EXPANSIVE WATERSTOPS MAY BE ADEKA ULTRA <br />SEAL TYPE MC-2010M OR AN APPROVED EQUAL. <br />THE WATERSTOP CAN BE ADHERED TO THE <br />CONCRETE w/ 3M-2141 BONDING ADHESIVE OR <br />NAILED IN PLACE USING 1.5 INCH CONCRETE NAILS <br />SPACED (3) TO (6) INCHES APART. <br />c.) CAULK/SEALANT - SONOLASTIC (2) PART <br />POLYSULFIDE. <br />d.) BONDING AGENT - SHALL BE STRUCTURAL EPDXY <br />ADHESIVE CONFORMING TO ASTM C-881 TYPE I <br />AND 11, GRADE 2, CLASS 8 AND C WITH A MINIMUM <br />BOND STRENGTH OF 1900 PSI. <br />1.) SIKA ARMATEC 110 EpoCem OR AN APPROVED <br />EQUAL. <br />REV. NO. DESCRIPTIONS DATE <br />V, REVISIONS i <br />___ I I qA_�Ik' <br />WILLIAM F BAND, P.E. <br />No, 67838 <br />6.0 GROUT <br />6.1 PROVIDE NON -SHRINK GROUT UNDER ALL COLUMN BASE <br />PLATES AND BEAM BEARING PLATES AND ELSEWHERE AS <br />INDICATED ON DRAWINGS. NON -SHRINK GROUT SHALL <br />CONFORM TO ASTM C 1107. <br />6.2 GROUT SHALL BE NON-METALLIC AND NON -STAINING <br />AND HAVE A MINIMUM COMPRESSIVE STRENGTH OF 7000 psi. <br />7.0 MASONRY <br />7.1 CONCRETE MASONRY UNITS SHALL CONFORM TO THE <br />REQUIREMENTS OF ASTM C 90. UNITS ARE TO BE NORMAL <br />WEIGHT UNLESS NOTED OTHERWISE. <br />7.2 REQUIRED COMPRESSIVE STRENGTH OF MASONRY <br />ASSEMBLAGE, f'm, IS 1900 psi (MINIMUM), UNLESS NOTED <br />OTHERWISE ON THE DRAWINGS. <br />7.3 MORTAR SHALL CONFORM TO THE REQUIREMENTS OF <br />ASTM C 270 AND SHALL BE TYPE S WITH PORTLAND <br />CEMENT (ASTM C 150), MASONRY SAND (ASTM C 144) AND <br />HYDRATED LIME (ASTM C 207). CALCIUM CHLORIDE IS <br />PROHIBITED. <br />7.4 GROUT FILL FOR HOLLOW MASONRY UNITS SHALL HAVE A <br />28 DAY COMPRESSIVE STRENGTH OF 3000 psi AND SHALL <br />BE NORMAL WEIGHT PEA -GRAVEL CONCRETE. <br />7.5 JOINT REINFORCING: "TRUSS" TYPE OR "LADDER" TYPE <br />REFERENCE PROJECT SPECIFICATIONS AND DRAWINGS. <br />7.6 JOINT ANCHORS: REFERENCE PROJECT SPECIFICATIONS. <br />7.7 WALL TO COLUMN TIES: REFERENCE PROJECT <br />SPECIFICATIONS. <br />7.8 MASONRY CONSTRUCTION INCLUDING GROUT FILL, <br />MORTAR AND HORIZONTAL & VERTICAL REINFORCING TO BE <br />REVIEWED BY THE THE OWNER'S CONSTRUCTION <br />REPRESENTATIVE THROUGHOUT MASONRY & CONCRETE <br />CONSTRUCTION OF THE PROJECT. <br />8.0 STRUCTURAL STEEL <br />8.1 STEEL SHALL CONFORM TO "STANDARD SPECIFICATION <br />FOR STRUCTURAL STEEL," ASTM A-36 (Fy--36 ksi) FOR <br />ANGLES, PLATES AND CHANNEL SECTIONS. WIDE FLANGE <br />SECTIONS SHALL CONFORM TO ASTM A-572 (Fy=50ksi). <br />HOLLOW STEEL SECTIONS (HSS) SHALL CONFORM TO ASTM <br />A500, GRADE B (Fy--46 ksi). STEEL PIPE SHALL CONFORM <br />TO ASTM A-53, GRADE B, (Fy--35 ksi). <br />8_2 STEEL WORK SHALL CONFORM TO "SPECIFICATION FOR <br />THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL <br />STEEL BUILDINGS", OF THE AMERICAN INSTITUTE OF STEEL <br />CONSTRUCTION, INC., (LATEST EDITION), INCLUDING ALL <br />SUPPLEMENTS AND THE "CODE OF STANDARD PRACTICE FOR <br />STEEL BUILDINGS AND BRIDGES", (LATEST EDITION). <br />8.3 CONNECTION BOLTS SHALL BE 3/4 INCH DIAMETER <br />CONFORMING TO "STANDARD SPECIFICATION FOR <br />HIGH -STRENGTH BOLTS FOR STRUCTURAL STEEL JOINTS", <br />ASTM A-325, UNLESS NOTED OTHERWISE CONNECTIONS ARE <br />BEARING TYPE WITH THREADS EXCLUDED FROM SHEAR <br />PLAN ES- (A- 325x). <br />8.4 WELDING SHALL BE IN ACCORDANCE WITH THE LATEST <br />EDITION OF THE AMERICAN WELDING SOCIETY AWS D1.1 <br />"STRUCTURAL WELDING CODE". WELDING SHALL BE <br />PERFORMED BY CERTIFIED PERSONNEL WHO HAVE BEEN <br />PREVIOUSLY QUALIFIED BY TEST PRESCRIBED IN THE AWS <br />"STRUCTURAL WELDING CODE". ELECTRODES SHALL CONFORM <br />TO AWS 5.5, E70XX. <br />8.5 STEEL LINTELS FOR MASONRY CONSTRUCTION SHALL <br />BEAR (8) INCHES MINIMUM ON THE MASONRY U.N.O.. <br />8.6 THE GENERAL CONTRACTOR SHALL PROVIDE ADEQUATE <br />TEMPORARY BRACING, SHORING, AND GUYING OF STEEL <br />FRAMING AGAINST WIND, CONSTRUCTION LOADS, AND OTHER <br />TEMPORARY FORCES UNTIL SUCH PROTECTION IS NO LONGER <br />REQUIRED FOR THE SAFE SUPPORT OF THE FRAMING. <br />8.7 ALL COPES, BLOCKS, CUTS, CUT-OFFS AND OTHER <br />CUTTING OF STRUCTURAL STEEL MEMBERS SHALL HAVE ALL <br />RE-ENTRANT CORNERS SHAPED, AND NOTCH FREE TO A <br />RADIUS OF 1/2 INCH MINIMUM. THE FILLET AND ITS <br />CONTIGUOUS CUTS SHALL MEET WITHOUT OFFSET OR CUTTING <br />PAST THE POINT OF TANGENCY. <br />8.8. ANCHOR BOLTS SHALL BE ASTM F-1554 OR A-36 <br />HEADED OR NON -HEADED AS INDICATED ON THE DRAWINGS. <br />NON -HEADED SHALL HAVE HOOKS AS REQUIRED BY THE <br />DRAWINGS. PROVIDE TWO (2) NUTS AND WASHERS WITH <br />EACH ANCHOR BOLT AT COLUMNS UNLESS NOTED <br />OTHERWISE. <br />8.9 OVERSIZED AND SLOTTED HOLES SHALL NOT BE USED <br />FOR BOLTED CONNECTIONS EXCEPT AT LOCATIONS NOTED ON <br />THE DRAWINGS. <br />8.10 SPLICING OF STRUCTURAL STEEL MEMBERS IS <br />PROHIBITED WITHOUT THE APPROVAL OF THE STRUCTURAL <br />ENGINEER AS TO LOCATION & TYPE OF SPLICE. ANY <br />MEMBER �AVING A SPLICE NOT SHOWN AND DETAILED ON <br />THE APPROVED SHOP DRAWINGS SHALL BE REPLACED. <br />8.11 PRE -GROUTING BASE PLATES IS PROHIBITED. <br />8.12 ALL HOLES IN STRUCTURAL STEEL ARE TO BE PUNCHED <br />OR DRILLED. FLAME CUTTING OF STEEL IS STRICTLY <br />PROHIBITED. <br />8.13 ALL DESIGN, DETAILING, FABRICATION, COATING AND <br />ERECTION SHALL BE IN ACCORDANCE w/ THE LATEST <br />EDITION OF THE AMERICAN INSTITUTE OF STEEL <br />CONSTRUCTION (AISC) MANUAL OF STEEL CONSTRUCTION. <br />8.14 STRUCTURAL STEEL ERECTION SHALL BE REVIEWED BY <br />THE OWNER'S CONSTRUCTION REPRESENTATIVE. <br />8.15 IN GENERAL SHOP CONNECTIONS SHALL BE EITHER <br />WELDED AND BOLTED AND FIELD CONNECTIONS SHALL BE <br />BOLTED UNLESS NOTED OTHERWISE. <br />SEAL <br />8.16 FABRI CATOR/CON TRACTOR SHALL SUBMIT SHOP <br />DRAWINGS FOR OWNER/ENGINEER APPROVAL PRIOR TO <br />FABRICATION. ALL SHOP DRAWINGS MAY BE EXPEDITED IF <br />THE FABRICATOR ADHERES CLOSELY TO THE DETAILS, NOTES, <br />AND INSTRUCTIONS, SHOWN ON THE DRAWINGS. <br />8.17 ALL GALVANIZED MATERIALS THAT ARE FIELD CUT, <br />FIELD WELDED OR DAMAGED IN SURFACE FINISH SHALL BE <br />CLEANED AND RE -COATED AS CALLED OUT IN THE PROJECT <br />SPECIFICATIONS. <br />9.0 AWMINUM <br />9.1 ALUMINUM FABRICATION SHALL BE IN CONFORMANCE <br />WITH THE ALUMINUM ASSOCIATION, INC. "SPECIFICATIONS <br />FOR ALUMINUM STRUCTURES". <br />9.2 UNLESS NOTED OTHERWISE, MATERIALS SHALL BE: <br />a. PLATE & SHEET - ASTM B209; 6061-T6, 6061-T651 <br />ALLOY. <br />b. EXTRUDED SHAPES - ASTM B221; 6061-T6, 6061-T651 <br />ALLOY. PIPE SECTIONS ARE SCHEDULE 40 U.N.O.. <br />c. CASTINGS - ASTM B108; 214 ALLOY. <br />d. BOLTS - ASTM A193; GRADE B8 OR, ASTM 276; TYPE <br />316 STAINLESS STEEL. <br />e. NUTS - ASTM A194; GRADE M, OR ASTM 276; TYPE 316 <br />STAINLESS STEEL. <br />9.3 ALUMINUM SHALL BE SEPARATED FROM DIRECT CONTACT <br />WITH OTHER MATERIALS (STEEL, CONCRETE, ETC.) BY <br />PRESSURE SENSITIVE TAPE, BITUMASTIC COATING, OR OTHER <br />PROTECTIVE METHOD SUBMITTED BY THE CONTRACTOR AND <br />APPROVED BY THE OWNER'S CONSTRUCTION REPRESENTATIVE. <br />9.4 CONNECTIONS SHALL HAVE A MINIMUM OF TWO 3/4" <br />DIAMETER STAINLESS STEEL BOLTS. <br />9.5 WELDING ALUMINUM SHALL CONFORM TO AWS A5.10 & <br />THE REQUIREMENTS OF THE ALUMINUM ASSOCIATIONS <br />"ALUMINUM DESIGN MANUAL" (LATEST EDITION) <br />TABLE 7.1-1 FOR WELD FILLERS FOR WROUGHT ALLOYS. <br />9.6 PRE -GROUTING BASE PLATES IS NOT PERMITTED. <br />9.7 ALL HOLES IN ALUMINUM ARE TO BE PUNCHED OR <br />DRILLED. FLAME CUTTING OF STEEL IS STRICTLY PROHIBITED. <br />9.8 FAB RI CATOR/CON TRACTOR SHALL SUBMIT SHOP <br />DRAWINGS FOR OWNER/ENGINEER APPROVAL PRIOR TO <br />FABRICATION. ALL SHOP DRAWINGS MAY BE EXPEDITED IF <br />THE FABRICATOR ADHERES CLOSELY TO THE DETAILS, NOTES, <br />AND INSTRUCTIONS, SHOWN ON THE DRAWINGS. <br />9.9 REFERENCE PROJECT SPECIFICATIONS AND DRAWINGS FOR <br />HANDRAIL/GUARDRAIL REQUIREMENTS. <br />10.0 PRE-ENGINEERED TIMBER TRUSSES <br />10.1 TRUSS FABRICATOR SHALL FURNISH TRUSS LAYOUT, <br />SHOP DRAWINGS, ENGINEERING DESIGN COMPUTATIONS, <br />CONNECTION DETAILS, TOP & BOTTOM CHORD BRIDGING & <br />BRACING REQUIREMENTS FOR TRUSSES ON THE TRUSS <br />LAYOUT PLAN, ALL INCLUDING THE SEAL OF AN ENGINEER <br />REGISTERED IN THE STATE OF FLORIDA. NOTE THE <br />ENGINEER's SEAL, ACCOMPANIED BY THE ENGINEER's <br />SIGNATURE & DATE CERTIFIES THE TRUSS DESIGN WORK <br />ADHERES TO THESE SPECIFIED REQUIREMENTS IN ADDITION <br />TO THE LATEST REVISION OF THE FLORIDA BUILDING CODE <br />(FBC). <br />10.2 SHOP DRAWINGS ARE TO BE SUPPLIED TO OWNERS <br />REPRESENTATIVE AND SHALL BE SUBMITTED TO THE ENGINEER <br />FOR REVIEW PRIOR TO FABRICATION (INCLUDING ORDERING <br />OF MATERIALS) & ERECTION. THE SHOP DRAWINGS SHALL <br />INCLUDE TRUSS DESIGN IN ADDITION TO: <br />a.) CHORD & WEB MEMBER LAYOUTS AND SIZES. <br />b.) TRUSS HORZ. & VERT. TOP & BOTTOM CHORD <br />BRIDGING AND BRACING MEMBER LAYOUTS AND <br />SIZES. <br />C.) CALL OUT OF ALL INDIVIDUAL TRUSS CONNECTORS. <br />CONNECTORS TO MANUFACTURED BY SIMPSON <br />STRONG -TIE OR AN APPROVED EQUAL. <br />d.) CALL OUT ALL OF THE TRUSS METAL PLATE <br />CHORD/WEB CONNECTORS USED TO FABRICATE THE <br />TRUSSES. <br />e.) CALL OUT REQUIRED HORIZONTAL AND VERTICAL <br />LOADING COMPONENTS & REACTIONS DUE TO <br />APPLICABLE GRAVITY DEAD, COLLATERAL AND LIVE <br />LOADS, WIND, SNOW AND SEISMIC LOADING. <br />10.3 REFERENCE DRAWINGS FOR REQUIREMENTS TO ANCHOR <br />THE TRUSSES TO THE STRUCTURE. <br />10.4 PRE -MANUFACTURED ROOF TRUSSES ARE TO BE <br />CONSTRUCTED OF 2x TIMBER FRAMING & SHALL ADHERE TO <br />THE FOLLOWING: <br />a. ROOF TRUSS DESIGN LOADS ARE THE FOLLOWING: <br />TOP CHORD DEAD LOAD = 15 psf <br />TOP CHORD LIVE LOAD = 20 psf <br />BOTTOM CHORD DEAD LOAD = 15 psf <br />BOTTOM CHORD LIVE LOAD = 20 psf <br />WIND LOADS: FLORIDA BUILDING CODE CHAPTER 16 & <br />ASCE 7. <br />LOAD DURATION FACTOR 1.15 <br />10.5 ALL WOOD MEMBERS SHALL BEAR THE IDENTIFICATION <br />GRADE AS CALLED FOR IN THE FABRICATOR's SEALED <br />ENGINEERED DESIGN CALCULATIONS & SHOP DRAWINGS. <br />10.6 PROVIDE THE REVID CAMBER IN EACH ROOF TRUSS SO <br />THAT THE DEAD LOAD & LIVE LOAD DEFLECTION SHALL BE <br />THE SAME IN ALL PLANES. <br />10.7 THE ERECTOR SHALL BE RESPONSIBLE FOR PROVIDING <br />ADEQUATE BRACING TO RESIST ALL FBC LOAD CASES <br />POSSIBLY ENCOUNTERED DURING ERECTION. <br />10.8 THE ERECTOR SHALL INSTALL ALL TOP & BOTTOM <br />CHORD BRIDGING AND TRUSS BRACING AS CALLED OUT IN <br />THE FABRICATOR's SEALED ENGINEERED DESIGN CALCULATIONS <br />& SHOP DRAWINGS. COORDINATE w/ THE GC RESPONSIBILITY <br />OF INSTALLING THE TOP & BOTTOM CHORD <br />BRACING/BLOCKING. <br />41k <br />4 MC I <br />1# <br />'M <br />&CREED <br />3802 Ehrlich Road, Suite 306 <br />Tampa, Florida 33624 <br />Phone: (813)549-3740, Fax: (813)549-3744 <br />EB0006691 <br />www. m ckim creed. com <br />M <br />DESIGN LOADS: <br />LIVE LOAD: <br />ROOF: <br />10.9. TRUSS CONNECTORS AND TRUSS ANCHOR TIES SHALL SNO* <br />BE GALVANIZED & MANUFACTURED BY "SIMPSON STRONG SEISMIC: <br />TIE". TRUSS CONNECTORS AND ANCHORS AS CALLED OUT ON WIND: ZONE: <br />BOTH THE <br />SHOP AND STRUCTURAL DRAWINGS MAY BE <br />REVISED BY THE ENGINEER OF RECORD <br />(E.O.R.) <br />THIS <br />DRAWING DURING <br />THE SHOP DRAWING REVIEW PHASE. <br />CONNECTORS AND ANCHOR TIES SHOWN <br />ARE BASED UPON <br />ESTIMATED <br />UPLIFT REACTIONS THAT WILL <br />BE VERIFIED BY THE <br />E.O.R. IT IS RECOMMENDED THE GC DO <br />NOT ORDER TRUSS <br />CONNECTORS UNTIL THE "FINAL" ROOF <br />FRAMING <br />SHOP <br />DRAWINGS <br />HAVE BEEN APPROVED. REVISED TRUSS <br />CONNECTORS WILL BE AT NO ADDITIONAL <br />COST <br />TO THE <br />OWNER OR <br />THE ENGINEER OF RECORD <br />(THIS DRAWING). <br />10.10. MAXIMUM TRUSS SPACING AS INDICATED <br />ON THE <br />APPROVED <br />SHOP DRAWINGS. <br />11.0 ABBREVIATIONS <br />11.1 THE FOLLOWING <br />LIST OF ABBREVIATIONS IS <br />NOT <br />INTENDED TO REPRESENT ALL THOSE USED ON <br />THE <br />DRAWINGS, <br />BUT TO SUPPLEMENT THE MORE <br />COMMON <br />ABBREVIATIONS <br />USED. <br />ADD'L <br />ADDITIONAL <br />JT. <br />JOINT <br />AL <br />ALUMINUM <br />L.P. <br />LOW POINT <br />ARCH. <br />ARCHITECTURAL <br />MAS. <br />= MASONRY <br />BD. <br />BOARD <br />MAT'L. <br />= MATERIAL <br />BLDG. <br />BUILDING <br />MFG. <br />MANUFACTURER <br />BILK. <br />BLOCK <br />MIN. <br />MINIMUM <br />BM. <br />BEAM <br />M.O. <br />MAS. OPNG. <br />B.O. <br />BOTTOM OF <br />MTL. <br />METAL <br />BRG. <br />BEARING <br />NOM. <br />NOMINAL <br />BTM. <br />BOTTOM <br />N.S. <br />NEAR SIDE <br />C.I.P. <br />CAST -IN -PLACE <br />N.T.S. <br />NOT TO SCALE <br />CLR. <br />CLEAR <br />O.C. <br />ON CENTER <br />CMU <br />CONIC. MASONRY UNIT <br />O/F <br />OUTSIDE FACE <br />CONC. <br />CONCRETE <br />O/H <br />OVERHANG <br />CONN. <br />CONNECTION <br />0/0 <br />OUT TO OUT <br />CONST.= <br />CONSTRUCTION <br />OPNG. <br />OPENING <br />CONT. = <br />CONTINUOUS <br />OPNG's= <br />OPENINGS <br />COORD.= <br />COORDINATE <br />ORIENT.= <br />ORIENTATION <br />CTR. <br />CENTER <br />PLCS. <br />PLACES <br />CTR'D. <br />CENTERED <br />P.T. <br />PRESSURE TREATED <br />DIR. <br />DIRECTION <br />REF. <br />REFERENCE <br />DWG. <br />DRAWING <br />REINF. <br />REINFORCING <br />DWGS. <br />DRAWINGS <br />REQ'D. <br />REQUIRED <br />DWG's <br />DRAWINGS <br />SIM. <br />SIMILAR <br />DWL. <br />DOWEL <br />SL. <br />SLOPED <br />DWL's <br />DOWELS <br />SPA. <br />SPACED <br />EA. <br />EACH <br />SPECS.= SPECIFICATIONS <br />EL <br />ELEVATION <br />STD. <br />STANDARD <br />E.O. <br />EDGE OF <br />STL. <br />STEEL <br />EQ. <br />EQUAL <br />T&B <br />TOP & BOTTOM <br />EQUIP. = <br />EQUIPMENT <br />T/D <br />TURN DOWN <br />EXIST. = <br />EXISTING <br />THIK. <br />THICK <br />EXP. <br />EXPANSION <br />THIK'D <br />THICKENED <br />EXTR. <br />EXTERIOR <br />T.O. <br />TOP OF <br />FDN. <br />FOUNDATION <br />TYP. <br />TYPICAL <br />FRMG. <br />FRAMING <br />U. N. 0. <br />UNLESS NOTED OTHERWISE <br />F. S. <br />FAR SIDE <br />VERT. <br />VERTICAL <br />FT. <br />FEET <br />W.P. <br />WORK POINT <br />FTG. <br />FOOTING <br />W.W.F. <br />WELDED WIRE FABRIC <br />H.P. <br />HIGH POINT <br />I/F <br />INSIDE FACE <br />INFO. <br />INFORMATION <br />INTR. <br />INTERIOR <br />CITY OF ZEPHYRHILLS <br />300 PSF <br />20 PSF <br />NA, IMPORTANCE FACTOR (Is): NA <br />NA, IMPORTANCE FACTOR (le): NA <br />120 mi/hr, EXPOSURE C, CATEGORY 111, IMPORTANCE FACTOR (1w): 1.15 <br />FLORIDA BUILDING CODE (FBC) 2007 & ASCE 7-05 WIND DESIGN: <br />CALCULATED <br />WIND BASE <br />SHEARS: <br />Vx = 8 <br />k Vy = 8 k <br />COMPONENTS <br />& CLADDING <br />WIND <br />PRESSURES: <br />ROOF: <br />ZONE <br />1 = <br />18.03 <br />PSF <br />& <br />-28.68 <br />PSF <br />ZONE <br />2 <br />= 18.03 <br />PSF <br />& <br />-49.97 <br />PSF <br />ZONE3 <br />= 18.03 <br />PSF <br />& <br />-73.81 <br />PSF <br />WALLS: <br />ZONE <br />4 <br />= 31.34 <br />PSF <br />& <br />-34.00 <br />PSF <br />ZONE <br />5 <br />= 31.34 <br />PSF <br />& <br />-41.99 <br />PSF <br />DESIGN CRITERIA: <br />CONCRETE 28 DAY COMPRESSIVE STRENGTH: <br />SLAB -ON -GRADE: <br />EQUIPMENT PADS: <br />WALLS OF LIQUID CONTAINMENT STUICTURES (LCS): <br />SLABS OF LCS: <br />FOOTINGS: <br />BELOW GRADE & RETAINING WALLS: <br />SIDEWALK: <br />REINFORCING STEEL: <br />WELDED WIRE FABRIC: <br />STRUCTURAL STEEL: <br />ALUMINUM: <br />BOLTS SHALL BE 3/4"0 ASTM A325 OR <br />TYPE 316 S.S.: <br />ANCHOR BOLTS SHALL BE 3/4"0 ASTM F-1554 OR <br />ASTM A-36 (STEEL); TYPE 316 S.S. (ALUMINUM): <br />STEEL ELECTRODES SHALL CONFORM TO: <br />ALUMINUM WELD FILLERS ALLOYS SHALL <br />CONFORM TO: <br />SOIL BEARING CAPACITY: <br />LEGEND: <br />ENLARGED PLAN AREA, <br />DETAIL <br />CONC. MASONRY BLOCK <br />BRICK VENEER <br />CONC. WALL, PAD, ETC. <br />GROUT <br />GRATING <br />DETAIL OR SECTION <br />NUMBER/SHOWN ON SHEET <br />PROJECT NORTH <br />ELEVATION DATUM <br />STEP IN FOOTING ELEVATION = <br />ELEVATION NUMBER/SHOWN <br />ON SHEET <br />'006 Nbl, <br />NORTH <br />f'c = <br />4,000 psi <br />f'c = <br />3,000 psi <br />f'c = <br />NA psi <br />f'c = <br />NA psi <br />f'c = <br />4,000 psi <br />f'c = <br />NA psi <br />f'c = <br />3,000 psi <br />ASTIM <br />A615, GRADE <br />60 <br />ASTM <br />A185 <br />REF. <br />STRUCTURAL <br />NOTE 8.1 <br />REF. <br />STRUCTURAL <br />NOTE 9.2 <br />REF. <br />STRUCTURAL <br />NOTES <br />8.3 & 9.2. d <br />REF. <br />STRUCTURAL <br />NOTE 8.8 <br />AWS <br />5.5 E70XX <br />AWS <br />A5.10 (REF. <br />STRUCTURAL NOTE 9.5) <br />REF. <br />STRUCTURAL <br />NOTE 3.1 <br />ELEVATIONS X'-X" (Y.YY') X'-X" DISTANCE TO/FROM FACILITY REFERENCE EL 0'-0" <br />Y.YY' EQUIVALENT SITE EL VERTICAL DATUM <br />PRODUCTION WELLS <br />No. 11 AND No. 12 <br />WELL SITE IMPROVEMENTS <br />STRUCTURAL GENERAL NOTES, DESIGN <br />LOADS, DESIGN CRITERIA AND LEGEND <br />F, <br />DATE: <br />-1*14 <br />JANUARY 2012 <br />MCE PROJ. # <br />4584-0003 <br />DRAWN <br />WF8 <br />ESIGNED <br />WFB <br />CHECKED <br />JSL <br />PROJ. MGR. <br />MSL <br />SCALE <br />HORIZONTAL: <br />NA <br />VERTICAL: <br />NA <br />S1 <br />3TATUS: REMSION <br />ISSUE FOR BID <br />01 1 <br />