PART 1 -GENERAL <br />0.01 GENERAL SCOPE <br />A. THIS PROJECT WILL REQUIRE INSTALLATION OF NEW HVAC SYSTEMS AS <br />INDICATED. <br />1.01 GENERAL DOCUMENTS <br />A. INSTALLATION SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING <br />CODE 7TH EDITION 2020 (EFFECTIVE 12131/2020), WHICH INCLUDES THE <br />FLORIDA BUILDING CODE, MECHANICAL, FLORIDA BUILDING CODE, <br />ENERGY CONSERVATION, AS WELL AS FLORIDA FIRE PREVENTION CODE, <br />7TH EDITION 2020 (EFFECTIVE 12/31/2020). ALL EQUIPMENT SHALL BE UL <br />LISTED. <br />B. THE MECHANICAL WORK SHALL INCLUDE FURNISHING ALL LABOR, <br />EQUIPMENT, MATERIALS AND SERVICE NECESSARY FOR AND <br />REASONABLY INCIDENTAL TO THE PROPER COMPLETION OF ALL <br />MECHANICAL WORK SHOWN ON THE DRAWINGS AND AS SPECIFIED. ALL <br />MATERIAL SHALL BE NEW. <br />C. EACH PROSPECTIVE MECHANICAL CONTRACTOR SHALL EVALUATE THE <br />SCOPE OF WORK THOROUGHLY PRIOR TO SUBMITTING A BID. <br />D. SOME CONDUIT, PIPING, AND OTHER OBSTACLES MAY NEED TO BE <br />RELOCATED AND SUCH RELOCATION SHOULD BE INCLUDED IN EACH <br />PROSPECTIVE MECHANICAL CONTRACTOR'S BID. <br />E. THIS ENGINEER IS NOT RESPONSIBLE FOR MATERIALS, METHODS, <br />INSTALLATION, AND CONSTRUCTION WHICH DEVIATE FROM THESE <br />CONSTRUCTION DOCUMENTS AND SPECIFICATIONS. <br />1.02 SUBMITTALS <br />A. MATERIALS OR PRODUCTS SPECIFIED HEREIN AND/OR INDICATED ON <br />DRAWINGS BY TRADE NAME, MANUFACTURER'S NAME OR CATALOG <br />NUMBERS SHALL BE INTERPRETED AS ESTABLISHING A STANDARD OF <br />QUALITY AND DESIGN. SUBSTITUTIONS MAY BE ALLOWED IF THEY MEE <br />THE QUALITY STANDARDS AND DESIGN INTENT, UNLESS OTHERWISE <br />NOTED. <br />B. PRIOR TO STARTING THE PROJECT, THE MECHANICAL CONTRACTOR <br />SHALL STUDY THE COMPLETE SET OF CONSTRUCTION DOCUMENTS AND <br />COORDINATE WITH THE MANUFACTURER(S) AS REQUIRED TO PROVIDE <br />EQUIPMENT SUBMITTALS TO SUBMIT TO THIS ENGINEER FOR REVIEW <br />AND APPROVAL. THE EQUIPMENT SUBMITTALS SHALL INCLUDE <br />DIMENSIONS, WEIGHTS, SPECIFIED ACCESSORIES AND REQUIRED <br />CLEARANCES, AS WELL AS FAN CURVES, SOUND LEVELS, CONSTRUCTION <br />DETAILS, WARRANTY INFORMATION, AND ALL OTHER RELEVANT DATA. <br />C. IF ALTERNATES TO THE BASIS OF DESIGN ARE SUBMITTED, THE <br />MECHANICAL CONTRACTOR SHALL PROVIDE A CLEAR, DETAILED <br />SUMMARY IN THE SUBMITTALS OF THE DIFFERENCES BETWEEN THE <br />SUBMITTED EQUIPMENT AND THE BASIS OF DESIGN. MECHANICAL <br />ENGINEER OF RECORD MAY ACCEPT OR REJECT THE ALTERNATES. <br />1.03 SHOP DRAWINGS <br />A. PRIOR TO STARTING THE PROJECT, THE MECHANICAL CONTRACTOR SHALL <br />STUDY THE COMPLETE SET OF CONSTRUCTION DOCUMENTS AND <br />COORDINATE WITH THE OTHER TRADES AS REQUIRED TO PROVIDE SHOP <br />DRAWINGS TO SUBMIT TO MECHANICAL ENGINEER OF RECORD FOR <br />APPROVAL. THE SHOP DRAWINGS MAY BE SUBMITTED AS HAND -DRAWN <br />NOTES UPON A COPY OF THE CONSTRUCTION DOCUMENTS. THE <br />CONSTRUCTION DOCUMENTS ARE DIAGRAMMATIC IN NATURE AND <br />INTENDED SOLELY TO CLARIFY THE SCOPE OF WORK AND INDICATE THE <br />GENERAL ARRANGEMENT OF SYSTEMS. THE CONSTRUCTION DOCUMENTS <br />ARE NOT INTENDED TO ALERT THE MECHANICAL CONTRACTOR OF ALL <br />OBSTACLES. THE SHOP DRAWINGS SHALL SHOW THE COORDINATION OF <br />DUCTWORK AND MECHANICAL EQUIPMENT INSTALLATION WITH EXISTING <br />AND NEW OBSTACLES INCLUDING; BUT NOT LIMITED TO, ELECTRICAL <br />CONDUITS, FIRE PROTECTION PIPING, RAIN LEADERS, SANITARY DRAINS, <br />STRUCTURAL MEMBERS, AND WATER PIPING, AS WELL AS THE MECHANICAL <br />EQUIPMENT MANUFACTURERS' RECOMMENDED CLEARANCES. THE <br />MECHANICAL CONTRACTOR SHALL ALSO SHOW THE EXISTING CONDITIONS <br />ON THE SHOP DRAWINGS WHERE THE EXISTING CONDITIONS ARE <br />DIFFERENT FROM THOSE SHOWN ON THE CONSTRUCTION DOCUMENTS. <br />B. FURNISH SIX (6) COPIES OF SHOP DRAWINGS OF EQUIPMENT, MATERIALS <br />AND SYSTEM LAYOUT TO GENERAL CONTRACTOR AND MECHANICAL <br />ENGINEER OF RECORD PRIOR TO PURCHASING ANY EQUIPMENT AND <br />BEGINNING WORK. <br />1.04 RECORD DRAWINGS <br />A. AFTER COMPLETION OF ALL WORK, THE MECHANICAL CONTRACTOR SHALL <br />PROVIDE THE GENERAL CONTRACTOR WITH AS BUILT RECORD DRAWINGS. <br />MECHANICAL CONTRACTOR SHALL KEEP A RECORD CIF THE LOCATIONS OF <br />ALL CONCEALED WORK AND UPON COMPLETION OF THE JOB, SHALL <br />SUPPLY AS -BUILT DRAWINGS SHOWING ANY DEVIATION FROM THE <br />ORIGINAL DRAWINGS. THESE DRAWINGS SHALL INDICATE DIMENSION OF <br />BURIED UTILITY LINES FROM BUILDING WALLS. <br />PART 2 - INSTALLATION <br />2.01 EQUIPMENT <br />A. ALL MECHANICAL EQUIPMENT SHALL BE INSTALLED AS REQUIRED BY THE <br />MANUFACTURER'S' INSTALLATION AND MAINTENANCE MANUALS. THOSE <br />MANUALS WILL TYPICALLY PROVIDE MORE DETAIL THAN THE <br />CONSTRUCTION DOCUMENTS. IF THERE IS A CONFLICT BETWEEN THE <br />INSTALLATION AND MAINTENANCE MANUALS AND THE CONSTRUCTION <br />DOCUMENTS, THEN THE MECHANICAL CONTRACTOR SHALL SUBMIT A <br />REQUEST -FOR -INFORMATION TO MECHANICAL ENGINEER OF RECORD. <br />B. VIBRATION ISOLATION: THE MECHANICAL CONTRACTOR SHALL PROVIDE <br />VIBRATION ISOLATION AS RECOMMENDED BY THE MANUFACTURER(S) <br />AND/OR REQUIRED BY MECHANICAL ENGINEER OF RECORD TO ENSURE <br />QUIET OPERATION OF THE MECHANICAL EQUIPMENT. NO UNDUE VIBRATION <br />OR SOUND SHALL BE TRANSMITTED TO THE STRUCTURE OR ANY OCCUPIED <br />SPACES WITHIN THE STRUCTURE, <br />C. FILTERS: THE MECHANICAL CONTRACTOR SHALL PROVIDE FILTER RACKS <br />FOR THE MECHANICAL EQUIPMENT AS REQUIRED. THE FILTER RACKS <br />SHALL BE INSTALLED SUCH THAT SUFFICIENT CLEARANCES ARE PROVIDED <br />FOR MAINTENANCE AND SHALL BE SEALED AIRTIGHT. THE MECHANICAL <br />CONTRACTOR SHALL PROVIDE A TOTAL OF THREE (3) COMPLETE SETS OF <br />FILTERS FOR ALL MECHANICAL EQUIPMENT IN THE SIZE AND ARRANGEMENT <br />RECOMMENDED BY THE MANUFACTURER. THE FILTERS SHALL PROVIDE <br />ASHRAE FILTRATION EFFICIENCY AS SHOWN ON THE CONSTRUCTION <br />DOCUMENTS OR 30% ASHRAE FILTRATION EFFICIENCY (MERV 6) IF NO <br />HIGHER VALUE IS SPECIFIED. <br />D. THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL STARTERS, <br />CONTACTORS, RELAYS, CONTROLS, AND ACCESSORIES NECESSARY TO <br />PROVIDE A COMPLETE AND WORKING POWER AND CONTROL SYSTEM FOR <br />THE MECHANICAL EQUIPMENT WITHIN THE SCOPE OF WORK. THE <br />ELECTRICAL CONTRACTOR WILL PROVIDE ALL DISCONNECT SWITCHES, <br />CONDUIT, AND WIRING FOR THE MECHANICAL EQUIPMENT WITHIN THE <br />SCOPE OF WORK. ALL ELECTRICAL WORK SHALL COMPLY WITH THE <br />REQUIREMENTS OF THE NATIONAL ELECTRIC CODE. THE MECHANICAL <br />CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROPER OPERATION OF <br />THE COMPLETE SYSTEM AND SHALL ENSURE THAT WRING DIAGRAMS ARE <br />PROVIDED TO THE GENERAL CONTRACTOR. NO WIRING OF ANY KIND SHALL <br />BE EXPOSED IN FINISHED AREAS. <br />E. HOUSEKEEPING PADS: THE GENERAL AND MECHANICAL CONTRACTORS <br />SHALL PROVIDE A 4" HIGH CONCRETE HOUSEKEEPING PAD UNDER ALL <br />MECHANICAL EQUIPMENT, UNLESS OTHERWISE NOTED ON THE <br />CONSTRUCTION DOCUMENTS. THE HOUSEKEEPING PAD SHALL EXTEND 8" <br />BEYOND THE MECHANICAL EQUIPMENT ON ALL SIDES. <br />F. ELECTRIC DUCT HEATERS: ELECTRIC DUCT HEATERS SHALL BE <br />UNDERWRITERS' LABORATORIES LISTED, BEAR THE SEAL OR MARK OF AN <br />APPROVED TESTING AGENCY, AND BE EQUIPPED WITH AN APPROVED, <br />AUTOMATICALLY RESETTING OUTLET AIR TEMPERATURE LIMIT CONTROL <br />THAT WILL LIMIT THE OUTLET AIR TEMPERATURE TO NOT MORE THAN 200°F. <br />THE MECHANICAL CONTRACTOR AND MANUFACTURER SHALL EQUIP THE <br />ELECTRIC ELEMENTS OF THE HEATER WITH FUSIBLE LINKS OR A MANUAL <br />RESET TEMPERATURE CONTROL THAT WILL PREVENT THE OUTLET AIR <br />TEMPERATURE FROM EXCEEDING 250°F. EACH ELECTRIC DUCT HEATER <br />SHALL BE INTERLOCKED WITH THE ASSOCIATED AIR HANDLER TO ENSURE <br />ELECTRIC DUCT HEATER SHUTDOWN IN THE EVENT OF AN AIR HANDLER FAP <br />FAILURE. <br />LL <br />02 ACCESS PANELS, FIRE DAMPERS, AND FIRE/SMOKE DAMPERS <br />A. THE GENERAL AND MECHANICAL CONTRACTORS SHALL PROVIDE <br />ACCESS PANELS TO ALLOW ACCESS TO VOLUME DAMPERS ABOVE <br />TURNING VANES. FIRE DAMPERS <br />PLASTER OR GYPSUM CEILINGS, U <br />FIRE/SMOKE DAMPERS, DUCT -MOUNTED SMOKE DETECTORS, AND <br />WHERE REQUIRED FOR THE MAINTENANCE OF ALL MECHANICAL <br />EQUIPMENT. ACCESS PANELS SHALL HAVE A FIRE RATING EQUAL TO <br />THE PENETRATED ASSEMBLY, WITH A MINIMUM FIRE RATING OF ONE (1) <br />HOUR. <br />B. THE MECHANICAL CONTRACTOR SHALL ATTACH A BRIGHTLY -COLORED <br />STRIP OF PLASTIC TAPE TO EVERY DUCT -MOUNTED ACCESS PANEL. THE <br />STRIP SHALL BE OF SUFFICIENT LENGTH TO HANG A MINIMUM OF 12" <br />BELOW THE BOTTOM OF THE ASSOCIATED DUCT. <br />C. THE MECHANICAL CONTRACTOR SHALL PROVIDE A FIRE DAMPER AT <br />EVERY DUCT PENETRATION OF A FIRE -RATED ASSEMBLY AND A <br />FIRE/SMOKE DAMPER WITH A MINIMUM FIRE/SMOKE RATING OF TWO (2) <br />HOURS AT EVERY DUCT PENETRATION OF A SMOKE ASSEMBLY OR <br />CHASE. EACH FIREISMOKE DAMPER SHALL CLOSE AND THE <br />ASSOCIATED AIR HANDLER SHALL SHUT DOWN IF EITHER OF THE AIR <br />HANDLER'S OR THE SPACE'S SMOKE DETECTORS ARE ACTIVATED. <br />D. THE MECHANICAL CONTRACTOR SHALL PROVIDE ADDITIONAL <br />DUCTWORK AND PIPING SUPPORTS WITHIN EIGHTEEN (18) INCHES OF <br />BOTH SIDES OF ALL FIRE -RATED ASSEMBLIES. DUCTWORK AND PIPING <br />SHALL NOT BE SUPPORTED BY FIRE -RATED WALLS, BUT INSTEAD SHALL <br />BE SUPPORTED BY THE BUILDING STRUCTURE. <br />Q SMO E DETECTORS <br />I <br />A. DIVIDUAL AIR HANDLING SYSTEMS WITH A DESIGN CAPACITY OF MORE <br />THAN 2000 CFM SHALL AUTOMATICALLY SHUT DOWN BY MEANS OF AN <br />APPROVED SMOKE DETECTOR PLACED IN THE SUPPLY AIRFLOW AFTER <br />ANY AIR FILTERS AND BEFORE ANY BRANCH CONNECTIONS IN THE <br />SUPPLY DUCTWORK. <br />B. MULTIPLE AIR HANDLING SYSTEMS SERVING THE SAME SPACE WITH A <br />COMBINED DESIGN CAPACITY OF MORE THAN 2000 CFM SHALL <br />AUTOMATICALLY SHUT DOWN BY MEANS OF AN APPROVED SMOKE <br />DETECTOR PLACED IN THE SUPPLY AIRFLOW AFTER ANY AIR FILTERS <br />AND BEFORE ANY BRANCH CONNECTIONS IN THE SUPPLY DUCTWORK, <br />AS WELL AS AN APPROVED SMOKE DETECTOR PLACED IN THE RETURN <br />AIRFLOW AFTER ANY BRANCH CONNECTIONS IN THE RETURN <br />DUCTWORK AND BEFORE ANY EXHAUST OR OUTSIDE AIR <br />CONNECTIONS. MORE INFORMATION IS AVAILABLE IN CHAPTER 4 OF <br />NFPA 90A. <br />C. THE MECHANICAL CONTRACTOR SHALL INCLUDE IN HIS/HER BID ALL <br />COSTS ASSOCIATED WITH FURNISHING, INSTALLING, AND WIRING ALL <br />SMOKE DETECTORS. THIS WILL INCLUDE, BUT NOT NECESSARILY BE <br />LIMITED TO, MAKING DUCTWORK MODIFICATIONS AS REQUIRED BY THE <br />MANUFACTURER'S INSTRUCTIONS. THE GENERAL OR MECHANICAL <br />CONTRACTOR SHALL SUB -CONTRACT THE PURCHASE AND WIRING OF <br />ALL SMOKE DETECTORS TO THE ELECTRICAL CONTRACTOR TO ENSURE <br />THE SMOKE DETECTORS' COMPATIBILITY WITH THE FIRE ALARM <br />SYSTEM. <br />D. THE CONTRACTOR -PROVIDED INSTRUCTIONS TO THE OWNER FOR <br />OPERATING AND MAINTAINING ALL MECHANICAL EQUIPMENT SHALL <br />INCLUDE TESTING ALL AUTOMATIC SHUTDOWN DEVICES AT LEAST ONCE <br />PER YEAR. SPECIAL INSTRUCTIONS SHALL BE GIVEN WITH REGARD TO <br />ENSURING THAT SMOKE SENSING DEVICES ARE PROPERLY CLEANED <br />AND CALIBRATED IN ACCORDANCE WITH THE MANUFACTURER'S <br />REQUIREMENTS. MORE INFORMATION IS AVAILABLE IN CHAPTER 4 OF <br />NFPA 90A. <br />E. THE MECHANICAL AND ELECTRICAL CONTRACTORS SHALL PROVIDE <br />EACH AIR HANDLING SYSTEM WITH A MINIMUM OF ONE (1) <br />MANUALLY -OPERABLE MEANS TO SHUT DOWN ALL SUPPLY, RETURN, <br />EXHAUST, AND OUTSIDE AIR FANS IN AN EMERGENCY. MORE <br />INFORMATION IS AVAILABLE IN CHAPTER 6 OF NFPA 90A. <br />2.05 CONDENSATE DRAIN LINES <br />A. REFER TO BASIC MATERIAL REQUIREMENTS ON THIS SHEET <br />FOR G.D. MATERIAL SELECTIONS. <br />B. THE MECHANICAL CONTRACTOR SHALL PROVIDE A P-TRAP AT <br />EACH AIR HANDLER'S CONDENSATE DRAIN LINE CONNECTION. <br />EACH CONDENSATE DRAIN LINE SHALL BE SLOPED DOWN A <br />MINIMUM OF ONE -EIGHTH (118) INCH PER LINEAR FOOT <br />TOWARD THE ASSOCIATED POINT OF DISCHARGE. <br />C. THE DIAMETER OF THE CONDENSATE DRAIN LINE SHALL BE <br />EQUAL TO OR GREATER THAN THE CONDENSATE DRAIN LINE <br />CONNECTION. TO AVOID EXCESSIVE DIPS IN AND TO PREVENT <br />ANY SHIFTING OF THE CONDENSATE DRAIN LINES, THE <br />MECHANICAL CONTRACTOR SHALL PROVIDE SUPPORTS AT <br />THE FOLLOWING INTERVALS: THREE (3) FEET FOR <br />CONDENSATE DRAIN LINES CONSTRUCTED OF PVC, SIX (6) <br />FEET FOR CONDENSATE DRAIN LINES CONSTRUCTED OF <br />COPPER, AND TEN (10) FEET FOR CONDENSATE LINES <br />CONSTRUCTED OF STEEL. CONDENSATE DRAIN LINE <br />SUPPORTS SHALL BE FIXED SOLIDLY IN PLACE. <br />D. CONDENSATE DRAIN LINES SHALL NOT BE ROUTED TO THE <br />SANITARY SEWER SYSTEM OR TO SCUPPERS. <br />E. THE MECHANICAL CONTRACTOR SHALL INSULATE EACH <br />CONDENSATE DRAIN LINE WITH ONE-HALF (1/2) INCH <br />ARMAFLEX WHEREVER THAT CONDENSATE DRAIN LINE IS <br />ROUTED WITHIN THE STRUCTURE OR THE CONDENSATE MAY <br />OTHERWISE CAUSE DAMAGE. <br />F. THE MECHANICAL CONTRACTOR SHALL CLEARLY LABEL ALL <br />CONDENSATE DRAIN LINES TO INDICATE CONTENT AND <br />DIRECTION OF FLOW. <br />07 ROOF MOUNTED -EQUIPMENT <br />THE MECHANICAL CONTRACTOR SHALL SET EACH ITEM OF <br />ROOF -MOUNTED MECHANICAL EQUIPMENT ON A FACTORY <br />CURB, CURB ADAPTER, OR ON A MINIMUM OF FOUR (4) PHP <br />SYSTEMS/DESIGN MODEL RTU-20 EQUIPMENT SUPPORTS AT <br />THE HEIGHT REQUIRED BY TABLE 1509.7 OF THE FLORIDA <br />BUILDING CODE, UNLESS OTHERWISE NOTED ON THE <br />CONSTRUCTION DOCUMENTS. <br />> Pr <br />hV <br />�N�� <br />s <br />2.08 DUCTWORK CONSTRUCTION <br />A. THE SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL <br />ASSOCIATION'S "FIBROUS GLASS DUCT CONSTRUCTION STANDARDS" <br />AND "HVAC DUCT CONSTRUCTION STANDARDS" SHALL BE <br />CONSIDERED PART OF THE SPECIFICATIONS FOR THIS PROJECT, ANY <br />WORK THAT DOES NOT COMPLY WITH THESE STANDARDS MAY BE <br />REJECTED AT ANY TIME DURING THE PROJECT. <br />B. REFER TO BASIC MATERIAL REQUIREMENTS ON THIS SHEET FOR <br />DUCTWORK AND DUCT INSULATION MATERIAL SELECTIONS. <br />C. ALL DUCT DIMENSIONS SHOWN ON THE CONSTRUCTION DOCUMENTS <br />ARE INSIDE CLEAR DIMENSIONS. THE MECHANICAL CONTRACTOR <br />SHALL PROVIDE FLEXIBLE CONNECTIONS BETWEEN EACH ITEM OF <br />MECHANICAL EQUIPMENT AND ITS ASSOCIATED DUCT(S). ALL ITEMS <br />OF THE HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM <br />INCLUDING, BUT NOT LIMITED TO, AIR HANDLERS, FANS, DUCTWORK, <br />DIFFUSERS, AND GRILLES SHALL NOT BE SUPPORTED BY THE CEILING <br />OR CEILING SUSPENSION SYSTEM, BUT INSTEAD SHALL BE <br />SUPPORTED BY THE BUILDING STRUCTURE. <br />D. ALL ELBOWS SHALL HAVE A ONE AND ONE-HALF (1.5) CENTERLINE <br />RADIUS -TO -WIDTH OR RADIUS -TO -DEPTH RATIO OR SHALL BE <br />CONSTRUCTED WITH SINGLE BLADE TURNING VANES. ANGULAR <br />TAPERS SHALL BE LIMITED TO THIRTY (30) DEGREES FOR <br />CONTRACTING TAPERS AND TWENTY (20) DEGREES FOR EXPANDING <br />TAPERS. <br />E. THE MAXIMUM LENGTH OF NEW FLEXIBLE DUCT SHALL BE 10'-0". <br />FLEXIBLE DUCT SHALL BE INSTALLED AND SUPPORTED SO AS TO <br />PREVENT THE USE OF EXCESS DUCT MATERIAL, PREVENT <br />DISLOCATION OR DAMAGE, AND PREVENT CONSTRICTION OF THE <br />DUCT BELOW THE RATED DUCT DIAMETER. FLEXIBLE DUCT BENDS <br />SHALL MAINTAIN A CENTERLINE RADIUS OF NOT LESS THAN ONE AND <br />ONE-HALF (1.5) DUCT DIAMETERS. SAGS SHALL NOT EXCEED <br />ONE-HALF (0.5) INCH PER LINEAR FOOT OF FLEXIBLE DUCT. HANGERS, <br />SADDLES, AND OTHER SUPPORTS SHALL HAVE A MINIMUM WIDTH OF <br />ONE AND ONE-HALF (1.5) INCHES. THE MECHANICAL CONTRACTOR <br />SHALL PROVIDE SUPPORT FOR NEW AND MODIFIED EXISTING FLEXIBLE <br />DUCTWORK IN THE SCOPE OF WORK WITH A MAXIMUM SPACING OF <br />6-0", UNLESS OTHERWISE NOTED ON THE CONSTRUCTION <br />DOCUMENTS OR AUTHORIZED BY MECHANICAL ENGINEER OF RECORD. <br />F. SURFACES UPON WHICH CLOSURE OR SEALING PRODUCTS ARE TO BE <br />APPLIED SHALL BE CLEAN AND DRY IN ACCORDANCE WITH THE <br />MANUFACTURER'S INSTALLATION INSTRUCTIONS. ALL DUCTWORK <br />SHALL BE SEALED WITH A NON -HARDENING, NON -MIGRATING MASTIC <br />OR LIQUID ELASTIC SEALANT AS REQUIRED TO MEET THE FLORIDA <br />ENERGY CONSERVATION CODE. THE MECHANICAL CONTRACTOR <br />SHALL PROVIDE HOT -DIPPED GALVANIZED STEEL FASTENERS, <br />ANCHORS, RODS, STRAPS. TRIM, AND ANGLES FOR INTERIOR <br />DUCTWORK SUPPORTS. INTERIOR DUCTWORK SUPPORT SPACING <br />SHALL NOT EXCEED 6-0". <br />G. ALL DUCTWORK INSULATION. FITTINGS, COVERS, AND FINISHES SHALL <br />HAVE A MAXIMUM FLAME SPREAD RATING OF 25, A MAXIMUM SMOKE <br />DEVELOPMENT RATING OF 50, AND SHALL BE IN COMPLIANCE WITH <br />NFPA 90A. PROVIDE MINIMUM OF 1/2" FIBERGLASS WITH FOIL/SCRIM <br />VAPOR BARRIER ON THE BACK PAN OF ALL NEW AIR DEVICES. <br />H. ALL OUTSIDE AIR INTAKES SHALL BE A MINIMUM OF 1U-0" FROM ANY <br />EXHAUST OUTLET OR VENT PIPE (UNLESS THE VENT PIPE IS AT LEAST <br />TWO (2) FEET ABOVE THE OUTSIDE AIR INTAKE). THE MECHANICAL <br />CONTRACTOR SHALL PROVIDE SCREENS ON ALL OUTSIDE AIR INTAKES <br />AND EXHAUST OUTLETS AT NO LESS THAN 1/4° BY 1/4 AND NO <br />GREATER THAN 1/2" BY 1/2". THE MECHANICAL CONTRACTOR SHALL <br />PROVIDE MOTORIZED DAMPERS IN ALL OUTSIDE AIR DUCTS. EACH <br />MOTORIZED DAMPER SHALL BE CONTROLLED TO OPEN IN OCCUPIED <br />MODE. <br />I. THE MECHANICAL CONTRACTOR SHALL PROVIDE AN OPPOSED -BLADE <br />VOLUME DAMPER FOR EVERY RECTANGULAR BRANCH AND OUTLET <br />AND AT EVERY RECTANGULAR TAKE -OFF FOR A DIFFUSER OR GRILLE. <br />(ROUND OR OVAL BRANCHES, OUTLETS, AND TAKE -OFFS FOR <br />DIFFUSERS AND GRILLES SHALL BE PROVIDED WITH STANDARD <br />VOLUME DAMPERS.) NOT ALL DAMPERS ARE SHOWN ON THE <br />CONSTRUCTION DOCUMENTS. HOWEVER, DAMPERS ARE REQUIRED <br />FOR EVERY BRANCH, OUTLET, AND TAKE -OFF. SOME DAMPERS MAY BE <br />REQUIRED AFTER TRANSITIONS. <br />J. THE MECHANICAL CONTRACTOR SHALL ATTACH A BRIGHTLY -COLORED <br />STRIP OF PLASTIC TAPE TO EVERY VOLUME DAMPER, EXCEPT THOSE <br />AT THE HEAD OF A DIFFUSER OR GRILLE. THE STRIP SHALL BE OF <br />SUFFICIENT LENGTH TO HANG A MINIMUM OF 12" BELOW THE BOTTOM <br />OF THE ASSOCIATED DUCT. <br />K. THE MECHANICAL CONTRACTOR SHALL CLEARLY AND PERMANENTLY <br />MARK EACH VOLUME DAMPER'S OPEN AND CLOSED POSITIONS. THE <br />MECHANICAL CONTRACTOR SHALL PROVIDE A VOLUME DAMPER WITH <br />A 2" STANDOFF WITH A LOCKING QUADRANT THAT IS 24 GAUGES OR 2 <br />GAUGES HEAVIER. <br />L. PROVIDE AND INSTALL "RUSKIN PRD-18" POSITIVE PRESSURE RELIEF <br />DOORS IN SUPPLY DUCTWORK FOR ALL AIR HANDLER SYSTEMS WITH <br />VAV BOXES, SMOKE DAMPERS OR FIRE DAMPERS, PROVIDE AND <br />INSTALL "RUSKIN NRD-18 NEGATIVE PRESSURE RELIEF DOOR IN <br />RETURN DUCTWORK FOR ALL AIR HANDLER SYSTEMS THAT HAVE <br />MOTORIZED RETURN AIR DAMPERS, SMOKE DAMPERS OR FIRE <br />DAMPERS. <br />M. ALL DUCT SHALL MEET THE FOLLOWING CONSTRUCTION <br />REQUIREMENTS: <br />• SUPPLY DUCTWORK (UPSTREAM OF ANY VAV): 2.0 IWG POSITIVE STATIC <br />PRESSURE AND VELOCITIES LESS THAN 2500 FPM. <br />• SUPPLY DUCTWORK (DOWNSTREAM OF ANY VAV): 1.0 IWG POSITIVE <br />STATIC PRESSURE AND VELOCITIES LESS THAN 1600 FPM. <br />• ALL OTHER RETURN DUCTWORK: 1.0 IWG NEGATIVE STATIC PRESSURE <br />AND VELOCITIES LESS THAN 1600 FPM. <br />• ALL EXHAUST AND OUTSIDE AIR DUCTWORK: 1.0 IWG POSITIVE OR <br />NEGATIVE STATIC PRESSURE AND VELOCITIES LESS THAN 1600 FPM. <br />• ALL TRANSFER DUCTWORK: 0.5 IWG POSITIVE OR NEGATIVE STATIC <br />PRESSURE AND VELOCITIES LESS THAN 500 FPM. <br />• ANY OTHER DUCTWORK: REFER TO SMACNA`HVAC DUCT CONSTRUCTION <br />STANDARDS". <br />ALL RECTANGULAR METALLIC DUCTWORK SHALL BE SHOP <br />FABRICATED OF GALVANIZED STEEL SHEETS, FOLLOWING ARE THE <br />SMACNA RECOMMENDATIONS FOR GAUGES AND SEAMS. CONFORM <br />TO THE RECOMMENDATIONS OF SMACNA AS TO SEAMS: JOINTS, <br />CROSS BREAKS AND TRANSITIONS, ETC. <br />RECTANGULAR STEEL DUCT GAGE <br />DUCT WITH FLAT "S" SLIP WITH STANDING "S" SLIP <br />DIAMETER IN INCHES ON 5' SPACING (GA) ON 5' SPACING (GA) <br />0-12 <br />26 <br />26 B <br />13 - 14 <br />24 <br />26 B <br />15 - 18 <br />22 <br />26 B <br />19 - 20 <br />20 <br />26 C <br />21 -26 <br />18 <br />26 C <br />27 - 28 <br />16 <br />26 C <br />29 - 30 <br />16 <br />26 D <br />31 - 36 <br />- <br />24 D <br />37 - 42 <br />- <br />24 E <br />43 - 60 <br />22 G <br />STANDING "S" SLIP <br />SIZE <br />B 1" x 26 GA <br />C 1 "x 22 GA <br />D 1-1/8" x 22 GA <br />E 1-1/8" x 18 GA <br />G 1-5/8" x 18 GA <br />REFER TO SMACNA TABLES FOR REINFORCEMENT FOR DUCT LENGTHS <br />OTHER THAN FIVE (5) FEET. <br />ALL ROUND RIGID METAL DUCTWORK CAN BE PREFABRICATED OR SHOP <br />FABRICATED, FOLLOWING ARE THE SMACNA RECOMMENDATIONS FOR <br />GAUGES AND SEAMS. ELBOWS SHALL HAVE CENTERLINE RADIUS OF 1-112 <br />TIMES DUCT DIAMETER. THE CONTRACTOR MAY PROVIDE EQUIVALENT <br />ROUND OR RECTANGULAR DUCT AS CONDITIONS AND SPACE PERMIT. <br />ROUND STEEL DUCT GAGE <br />DUCT LONGITUDINAL <br />SEAM DIAMETER SPIRAL S SEAM <br />IN INCHES IN INCHES IN INCHES <br />3-8 28 28 <br />9-14 28 26 <br />15 - 26 26 24 <br />27 - 36 24 22 <br />37 - 50 22 20 <br />51 - 60 20 18 <br />61 - 84 18 16 <br />ROUND ALUMINUM DUCT GAGE <br />DUCT LONGITUDINAL <br />DIAMETER SPIRAL SEAM SEAM <br />IN INCHES IN INCHES IN INCHES <br />3 - 14 .025 .032 <br />15 - 26 .032 .040 <br />27 - 36 .040 .050 <br />37 - 50 .050 .063 <br />2.09 DUCT LEAKAGE PERFORMANCE <br />A. FOR AIR CONDITIONING SYSTEMS OF FIFTEEN (15) TONS OR <br />GREATER CAPACITY, AN INDEPENDENT TEST AND BALANCE <br />CONTRACTOR SHALL PERFORM A DUCT LEAKAGE TEST IN <br />COMPLIANCE WITH SMACNA'S "HVAC AIR DUCT LEAKAGE TEST <br />MANUAL" TO VERIFY THE FUNCTION OF THE DESIGN AND THE <br />WORKMANSHIP OF THE MECHANICAL CONTRACTOR. A DUCT <br />LEAKAGE TEST USED TO CONFIRM DUCT LEAKAGE CLASS <br />SHALL BE CONDUCTED AT THE PRESSURE FOR WHICH THE <br />DUCT WAS DESIGNED AND CONSTRUCTED. <br />B. DUCT CONSTRUCTION AND SEALING SYSTEMS SHALL MEET THE <br />REQUIREMENTS OF THE FLORIDA ENERGY CONSERVATION <br />CODE AND SMACNA'S "FIBROUS GLASS DUCT CONSTRUCTION <br />STANDARDS" AND "HVAC DUCT CONSTRUCTION STANDARDS". <br />IF THERE IS A CONFLICT AMONG THE STANDARDS, THEN THE <br />MORE STRINGENT STANDARD SHALL BE ENFORCED. <br />C. THE MECHANICAL CONTRACTOR SHALL SEAL ALL TRANSVERSE <br />JOINTS, LONGITUDINAL SEAMS, AND DUCT WALL <br />PENETRATIONS TO A MAXIMUM ALLOWABLE DUCT LEAKAGE <br />CLASS OF THREE (3) CFM PER 100 SQUARE FEET OF DUCT AREA <br />(1.5%) FOR ROUND DUCT AND SIX (6) CFM PER 100 SQUARE <br />FEET OF DUCT AREA (3%) FOR ALL OTHER DUCT TYPES, <br />UNLESS OTHERWISE NOTED ON THE CONSTRUCTION <br />DOCUMENTS OR AUTHORIZED BY MECHANICAL ENGINEER OF <br />RECORD. TRANSVERSE JOINTS ARE CONNECTIONS OF TWO <br />DUCT OR FITTING ELEMENTS ORIENTED PERPENDICULAR TO <br />THE DIRECTION OF THE AIRFLOW. LONGITUDINAL SEAMS ARE <br />JOINTS ORIENTED IN THE DIRECTION OF THE AIRFLOW. DUCT <br />WALL PENETRATIONS ARE OPENINGS MADE BY SCREWS, <br />NOWSELF-SEALING FASTENERS, PIPES, TUBING, RODS, AND <br />WIRE. ROUND AND FLAT -OVAL SPIRAL LOCK SEAMS NEED NOT <br />BE SEALED PRIOR TO ASSEMBLY BUT SHALL BE COATED AFTER <br />ASSEMBLY TO REDUCE LEAKAGE. ALL OTHER CONNECTIONS <br />ARE CONSIDERED TRANSVERSE JOINTS INCLUDING, BUT NOT <br />LIMITED TO, SPIN -INS, TAPS OR OTHER BRANCH CONNECTIONS, <br />ACCESS DOOR FRAMES, AND DUCT CONNECTIONS TO <br />EQUIPMENT. MORE INFORMATION IS AVAILABLE IN CHAPTER 35 <br />OF ASHRAE'S "FUNDAMENTALS HANDBOOK <br />D. ALL DUCTWORK SHALL BE INSPECTED BY MECHANICAL <br />ENGINEER OF RECORD PRIOR TO BEING COVERED OR <br />INSULATED. THE OWNER AND MECHANICAL ENGINEER OF <br />RECORD SHALL. BE PRESENT DURING ALL DUCT LEAKAGE <br />TESTING AND THE DUCTWORK SHALL BE TESTED AS <br />INSTRUCTED BY MECHANICAL ENGINEER OF RECORD AND <br />RETESTED IF REQUIRED BY MECHANICAL ENGINEER OF <br />RECORD. IF ANY DISCREPANCIES ARE IDENTIFIED, THE <br />DUCTWORK SHALL BE UNCOVERED AND REPAIRS SHALL BE <br />MADE AT THE MECHANICAL CONTRACTOR'S EXPENSE. THE <br />(MECHANICAL CONTRACTOR SHALL GIVE MECHANICAL <br />ENGINEER OF RECORD TWO (2) WEEKS NOTICE BEFORE <br />TESTING THE DUCTWORK. <br />2.10 AIR DEVICES <br />A. THE MECHANICAL CONTRACTOR SHALL VERIFY THE LOCATIONS <br />OF THE DIFFUSERS AND GRILLES AND SUBMIT A <br />REQUEST -FOR -INFORMATION IF THERE IS A CONFLICT <br />BETWEEN THE ARCHITECTURAL AND MECHANICAL PORTIONS <br />OF THE CONSTRUCTION DOCUMENTS, THE MECHANICAL <br />CONTRACTOR SHALL ALSO VERIFY THE TYPES OF CEILINGS IN <br />THE SCOPE OF WORK PRIOR TO ORDERING DIFFUSERS AND <br />GRILLES, FOR DIFFUSERS AND GRILLES LOCATED IN PLASTER <br />OR GYPSUM CEILINGS, THE MECHANICAL CONTRACTOR SHALL <br />PROVIDE METALAIRE MODEL TBPF / TITUS MODEL TRM PLASTER <br />FRAMES, THE FRAMES MAY BE ALUMINUM IN NON -FIRE -RATED <br />CEILINGS BUT MUST BE STEEL IN FIRE -RATED CEILINGS. THE <br />MECHANICAL CONTRACTOR SHALL COORDINATE THE FINISH OF <br />ALL DIFFUSERS AND GRILLES, EXPOSED DUCTWORK, GRAVITY <br />VENTILATORS, LOUVERS, AND WALL CAPS WITH THE <br />(ARCHITECT/OWNER). ALL VISIBLE EXTERIOR COMPONENTS <br />(SUCH AS EXPOSED DUCTWORK AND LOUVERS) SHALL BE <br />PROVIDED WITH A PAINT -GRIP FINISH. <br />2.11 CONTROLS <br />A. THE MECHANICAL CONTRACTOR SHALL PROVIDE ALL <br />CONTROLS AND SUB -CONTRACT TO THE ELECTRICAL <br />CONTRACTOR ALL CONTROLS POWER AND TRANSFORMERS <br />NOT IDENTIFIED IN THE ELECTRICAL PORTION OF THE <br />CONSTRUCTION DOCUMENTS. <br />B. THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR <br />DETERMINING WHAT IS REQUIRED TO INCORPORATE NEW <br />MECHANICAL EQUIPMENT AND CONTROLS INTO THE EXISTING <br />CONTROL SYSTEM(S) AND INCLUDING ALL COSTS ASSOCIATED <br />WITH INCORPORATING NEW MECHANICAL EQUIPMENT AND <br />CONTROLS INTO THE EXISTING CONTROL SYSTEM(S) IN HISIHER <br />BID. THE CONTROLS CONTRACTOR SHALL PROVIDE A <br />COMPLETE DESCRIPTION OF THE ENTIRE CONTROL SYSTEM, <br />INCLUDING SCHEMATIC DRAWINGS. <br />C. THE MECHANICAL CONTRACTOR SHALL PROVIDE A HONEYWELL <br />MODEL 7350 PROGRAMMABLE THERMOSTAT WITH A REMOTE <br />SENSOR AND A LOCKABLE COVER FOR EACH NEW AND <br />EXISTING AIR CONDITIONING SYSTEM. THE MECHANICAL <br />CONTRACTOR SHALL ALSO PROVIDE ONE (1) PERSONAL <br />DIGITAL ASSISTANT (PDA) AND HONEYWELL'S THERMOSTAT <br />INTERFACE MODULE AND PROGRAMMING SOFTWARE. THE <br />MECHANICAL CONTRACTOR SHALL COORDINATE THE INITIAL <br />OCCUPANCY SCHEDULE(S) AND PROGRAMMING WITH THE <br />OWNER AND PROVIDE TRAINING AS REQUIRED, ALL <br />PROGRAMMING SHALL BE COMPLETED USING HONEYWELL'S <br />THERMOSTAT PROGRAMMING SOFTWARE. <br />D. EACH SENSOR SHALL BE INSTALLED AT 4'-6" ABOVE THE <br />FINISHED FLOOR UNLESS OTHERWISE NOTED ON THE <br />CONSTRUCTION DOCUMENTS. THE MECHANICAL CONTRACTOR <br />SHALL COORDINATE THE EXACT LOCATION OF EACH SENSOR <br />WITH THE OWNER AND SUBMIT THE PROPOSED LOCATION TO <br />MECHANICAL ENGINEER OF RECORD FOR APPROVAL. THE <br />MECHANICAL CONTRACTOR SHALL PROVIDE COORDINATION OF <br />ALL SENSOR FINISHES WITH ROOM FINISHES AT NO ADDITIONAL <br />COST TO THE OWNER. <br />E. ALL EXHAUST AND OUTSIDE AIR FANS SHALL BE INTERLOCKED <br />WITH THE AIR HANDLER SERVING THE ASSOCIATED SPACE. <br />F. ALL 120-VOLT RESTROOM EXHAUST FANS WITH ELECTRICAL <br />REQUIREMENTS OF UP TO 800 WATTS SHALL BE CONTROLLED <br />BY AN OCCUPANCY SENSOR WITH A TIME DELAY. THE INITIAL <br />TIME DELAY SHALL BE SET AT TWENTY (20) MINUTES. <br />G. THE MECHANICAL CONTRACTOR SHALL PROVIDE A TIME CLOCK <br />FOR ALL OUTDOOR AIR FANS. THE MECHANICAL CONTRACTOR <br />SHALL COORDINATE THE INITIAL OCCUPANCY SCHEDULE(S) <br />AND SETTINGS WITH THE OWNER AND PROVIDE TRAINING AS <br />REQUIRED. <br />PART 3 - EXECUTION <br />3.01 INSTALLATION <br />A. OCOORDINATE WORK WITH OTHER TRADES AND EXISTING CONDITIONS <br />PRIOR TO BEGINNING WORK, MECHANICAL CONTRACTOR SHALL PROVIDE <br />ROUTING AND OFFSETS NECESSARY TO AVOID CONFLICT WITH <br />STRUCTURE, FINISHES, AND WORK OF OTHER TRADES. <br />3.02 DISINFECTING OF POTABLE WATER SYSTEM <br />A. THE SYSTEM SHALL BE FILLED WITH A SOLUTION CONTAINING 50 PARTS <br />PER MILLION OF AVAILABLE CHLORINE AND ALL ALLOWED TO STAND 24 <br />HOURS BEFORE FLUSHING AND RETURNING TO SERVICE. DISINFECTION <br />PROCEDURE AND RESULT SHALL BE SUBJECT TO THE APPROVAL OF THE <br />LOCAL MECHANICAL INSPECTOR. <br />3.03 TEST <br />A. ALL MECHANICAL SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH THE <br />FLORIDA BUILDING CODE MECHANICAL. ALL TESTS SHALL BE APPROVED BY <br />THE LOCAL MECHANICAL INSPECTOR AND SHALL BE OBSERVED BY A <br />REPRESENTATIVE OF THE ARCHITECT. <br />3.04 SYSTEM IDENTIFICATION <br />A. THE MECHANICAL CONTRACTOR SHALL PROVIDE IDENTIFICATION TAGS <br />FOR ALL NEW EQUIPMENT, PIPING AND VALVES IN THE BUILDING. TAGS <br />SHALL BE METAL WITH ENGRAVED UNIT/TAG NUMBER. <br />3.05 TESTING, ADJUSTING, BALANCING AND COMMISSIONING <br />B. THE MECHANICAL CONTRACTOR SHALL ENSURE THAT THE MECHANICAL <br />SYSTEMS ARE TESTED AND BALANCED. <br />C. THE MECHANICAL CONTRACTOR SHALL PERFORM ALL TESTING, <br />ADJUSTING, BALANCING, AND DATA RECORDING NECESSARY TO <br />ESTABLISH THE CAPACITY AND QUALITY OF THE SYSTEMS AND CONFIRM <br />THE SATISFACTORY COMPLETION OF ALL ASPECTS OF THE SCOPE OF <br />WORK. THIS WILL INCLUDE ALL SYSTEMS WITHIN THE SCOPE OF WORK. <br />ANYTIME FLOWS OR CALCULATIONS ARE SHOWN ON PLANS, DETAILS OR <br />SCHEDULES, TEST & BALANCE IS REQUIRED. <br />D. THE MECHANICAL CONTRACTOR SHALL ENSURE THAT THE BUILDING IS <br />UNDER POSITIVE PRESSURE AT THE CONCLUSION OF THE TEST AND <br />BALANCE PROCESS. IF THE BUILDING IS NOT UNDER POSITIVE PRESSURE <br />AT THE CONCLUSION OF THE TEST AND BALANCE PROCESS, THEN THE <br />TEST AND BALANCE AND MECHANICAL CONTRACTORS SHALL IMMEDIATELY <br />AND WITHOUT DELAY NOTIFY THE ARCHITECT AND MECHANICAL ENGINEER <br />OF RECORD. <br />E. THE MECHANICAL CONTRACTOR SHALL, UPON COMPLETION OF ALL <br />NECESSARY TESTING AND BALANCING AND AT LEAST ONE (1) WEEK PRIOR <br />TO SUBSTANTIAL COMPLETION, SUBMIT THREE (3) BOUND COPIES OF THE <br />TEST AND BALANCE AND COMMISSIONING REPORTS TO THE GENERAL <br />CONTRACTOR AND MECHANICAL ENGINEER OF RECORD. <br />F. THE MECHANICAL CONTRACTOR SHALL INCLUDE IN HIS/HER BID THE COST <br />OF ANY SHEAVE CHANGES REQUIRED FOR REBALANCING THE SYSTEM. <br />3.06 SUBSTANTIAL AND FINAL COMPLETION <br />A. THE MECHANICAL CONTRACTOR SHALL MAINTAIN A SET OF <br />CONTINUOUSLY UPDATED, REPRODUCIBLE AS -BUILT DRAWINGS DURING <br />CONSTRUCTION AND PROVIDE A COMPLETE SET OF THOSE DRAWINGS IN <br />BOTH ELECTRONIC AND HARDCOPY FORMATS TO THE GENERAL <br />CONTRACTOR AND MECHANICAL ENGINEER OF RECORD UPON FINAL <br />COMPLETION. <br />B. THE MECHANICAL CONTRACTOR SHALL CLEAN ALL COOLING AND HEATING <br />COILS, CONDENSATE PANS, AND CONDENSATE DRAIN LINES PRIOR TO <br />SUBSTANTIAL COMPLETION. THE MECHANICAL CONTRACTOR SHALL ALSO <br />REPLACE ALL FILTERS AND BELTS PRIOR TO SUBSTANTIAL COMPLETION <br />AND PROVIDE TWO (.3) COMPLETE REPLACEMENT SETS OF FILTERS AND (2) <br />SETS OF BELTS FOR ALL MECHANICAL EQUIPMENT TO THE OWNER UPON <br />FINAL COMPLETION. <br />3.07 WARRANTY <br />A. THE MECHANICAL CONTRACTOR SHALL WARRANT ITS WORK TO BE FREE <br />FROM DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE <br />YEAR FROM FINAL ACCEPTANCE OF ALL WORK. <br />B. THE MECHANICAL CONTRACTOR SHALL PROVIDE FIVE (5) BOUND COPIES <br />OF ALL MECHANICAL. CONTRACTOR WARRANTIES, MANUFACTURER'S' <br />WARRANTIES, PARTS LISTS, AND INSTALLATION AND MAINTENANCE <br />MANUALS FOR ALL MECHANICAL EQUIPMENT, AS WELL AS INSTRUCTIONS <br />FOR OPERATING AND MAINTAINING ALL MECHANICAL EQUIPMENT TO THE <br />OWNER UPON FINAL COMPLETION. <br />RIGID DUCT - DOUBLE LINE <br />RIGID DUCT - SINGLE LINE <br />i <br />I FLEXIBLE DUCT INSULATED, SINGLE LINE <br />FLEXIBLE DUCT - INSULATED <br />SUPPLY AIR DUCT -SECTION <br />RETURN AIR DUCT - SECTION <br />DUCT TRANSITION - SINGLE LINE <br />DUCT TRANSITION <br />ELBOW WITH "AIRFOIL" TURNING VANES <br />VD <br />MANUAL VOLUME DAMPER (VD) <br />SUPPLY AIR DIFFUSER <br />RETURN AIR OR VENTILATION EXH. GRILLE <br />EXHAUST AIR GRILLE OR CEILING <br />MOUNTED EXHAUST FAN <br />THERMOSTAT OR HUMIDISTAT - WALL MOUNTED <br />$D <br />DUCT SMOKE DETECTOR <br />- --U - <br />I 3/4"UNDERCUT <br />-G -- 16X16 DOOR GRILLE <br />SPIN -IN FITTING WITH VOLUME DAMPER <br />BDD BACKDRAFT DAMPER <br />j MOTORIZED DAMPEP <br />XX FD=FIRE DAMPER, SD=SMOKE DAMPER <br />FSD = FIRE/SMOKE DAMPER <br />TO MATCH ASSEMBLY <br />PENETRATION RATING (1 HR, 2-HR, ETC.), <br />PROVIDE ACCESS PANEL FOR ACCESS <br />CONNECTION - NEW TO EXISTING WORK. <br />NEW LINE TYPE <br />- - - - EXISTING LINE TYPE <br />+r�a�r.Ran� <br />M,:0.1 <br />M2.1 <br />MECHANICAL ra <br />t • LAN <br />MECHANICAL DEMO <br />:. <br />MECHANICAL PROPOSED D PLAN <br />MECHANICAL Is <br />i <br />MECHANICAL D <br />M9.1 <br />MECHANICALDETAILS <br />BASIC 1w%jU%0%;TWuAftwm%2r'%0 MATERIAL REQUIREMENTS, <br />SUPPLY/RETURN: <br />SHEET METAL <br />X DUCTBOARD <br />EXHAUST/OUTSIDE AIR: <br />X SHEET METAL <br />DUCTBOARD <br />NOTES: <br />X UTILIZE MATERIALS ABOVE UNLESS NOTED OTHERWISE ON PLANS <br />X CONTRACTOR TO PROVIDE DEDUCTIVE COST ALTERNATE FOR USE OF <br />DUCTBOARD <br />BASHC . . <br />MATERIAL REQUIREME1242TE11%jo <br />CONDENSATE DRAIN: <br />X SCHEDULE 40, PVC <br />COPPER, TYPE L, W/ARMAFLEX INSULATION <br />NOTES: <br />X UTILIZE MATERIALS ABOVE UNLESS NOTED OTHERWISE ON PLANS <br />BASIC INSWLATIOM MATERIAL e <br />ON CONCEALED DUCTWORK: <br />X FLEXIBLE FIBERGLASS <br />FIBROUS DUCTBOARD <br />ON EXPOSED DUCTWORK: <br />FLEXIBLE FIBERGLASS <br />X FIBROUS DUCTBOARD <br />R-VALUE: <br />X IN UNCONDITIONED SPACE, R-8 <br />ALL OTHER DUCTWORK, R-4.2 <br />NOTES: <br />X UTILIZE MATERIALS ABOVE UNLESS NOTED OTHERWISE ON PLANS <br />l' <br />y: <br />.'"em s s <br />CK ARCHITECTS INTERIORS <br />architecture. interior design• client services <br />AAC001629 <br />4221 WEST BOY SCOUT BLVD., SUITE 150 <br />TAMPA, FL 33607-5743 <br />813.884.2000 <br />280 WEST CENTRAL AVE. <br />WINTER HAVEN, FL 33880-2957 <br />863.577.2054 <br />21. <br />O <br />1k <br />5/ 2021 ° Or <br />TATE OF + 4/ <br />ANAL _ <br />T.. <br />0 <br />LLj <br />LLj <br />Ca <br />Cn <br />z <br />0 <br />z <br />p <br />I Z <br />m _ <br />ca <br />/ Z <br />ci <br />z <br />J z <br />S T <br />z <br />c} <br />2 <br />_ z <br />CL <br />w <br />ra <br />LLj <br />LAJ <br />z <br />0 <br />J <br />m <br />z <br />ew3 � <br />LID <br />ua <br />ISSUED FOR: T <br />t Z <br />a <br />PROJECT NUMBER - <br />Q <br />DATE <br />z <br />DRAWING NUMBER <br />m u <br />z <br />a <br />a <br />■ <br />0 <br />cs <br />