PLUMBING FIXTURE SCHEDULE
<br />MARK
<br />QTY
<br />FIXTURE
<br />SOIU
<br />VENT
<br />COLD
<br />HOT
<br />ELEC
<br />MANUFACTURER
<br />DESCRIPTION
<br />WASTE
<br />WATER
<br />WATER
<br />CONN.
<br />MS-1
<br />1
<br />MOP SINK
<br />2"
<br />2"
<br />1/2"
<br />1/2"
<br />-
<br />MUSTEE
<br />MOLDED MOP BASIN WITH 3" OUTLET.
<br />MODEL 63M
<br />• PROVIDE FAUCET WITH WALL BRACE, PAIL HOOK AND APPROVED VACUUM BREAKER.
<br />• PROVIDE HOSE & HOSE BRACKET, MOP HANGER, BUMPER GUARDS AND STAINLESS STEEL
<br />WALL GUARD
<br />S-1
<br />2
<br />HAND SINK
<br />1-1/2"
<br />1-1/2"
<br />1/2"
<br />1/2"
<br />-
<br />REGENCY TABLES AN
<br />• 20-GAUGE TYPE 304 STAINLESS STEEL, SINGLE BOWL WITH 1-1/2" IPS DRAIN BASKET, EASY TO
<br />SINKS #600HS12SP
<br />INSTALL 8" GOOSNECK FAUCET INCLUDED, HOLES PUNCHED FOR 4" CENTERS.
<br />S-2
<br />1
<br />3 COMP SINK
<br />1-112"
<br />1-1/2"
<br />1/2"
<br />1/2"
<br />-
<br />REGENCY TABLES AND
<br />' MADE OF HIGH QUALITY 16-GAUGE, TYPE 304 STAINLESS STEEL, GALVANIZED 1-5/8" STEEL
<br />SINKS #60OS318242X
<br />LEGS WITH SOCKETS, FAUCET HOLES PRE -PUNCHED ON 8" CENTERS (FAUCET SOLD
<br />SEPARATELY).
<br />S-3
<br />1
<br />1 COMP PREP SINK
<br />1-1/2"
<br />1-1/2"
<br />1/2"
<br />1/2"
<br />-
<br />REGENCY TABLES AND
<br />MADE OF HIGH QUALITY 16-GAUGE, TYPE 304 STAINLESS STEEL, GALVANIZED 1-5/8" STEEL
<br />SINKS #60OS12323G
<br />LEGS WITH SOCKETS, FAUCET HOLES PRE -PUNCHED ON 8" CENTERS (FAUCET SOLD
<br />SEPARATELY).
<br />FD-1
<br />-
<br />FLOOR DRAIN
<br />3"
<br />-
<br />-
<br />-
<br />-
<br />ZURN MODEL Z400H
<br />ZURN FLOOR DRAIN "TYPE H" ROUND STRAINER WITH CLAMP DEVICE.
<br />• ALL FLOOR DRAINS SHALL BE INSTALLED WITH TRAP PRIMERS. COORDINATE EXACT
<br />LOCATIONS AND QUANTITY OF FLOOR DRAINS WITH ARCHITECTURAL DRAWINGS PRIOR TO
<br />ROUGH -IN.
<br />• PROVIDE TRAP PRIMER CONNECTION TO FLOOR DRAINS IN TOILET ROOMS EQUAL TO J.R.
<br />SMITH MODEL 2698, SEE DETAIL ON SHEET 9.1 ALL OTHER FLOOR DRAINS TO BE PROVIDED
<br />WITH TRAP PRIMERS EQUAL TO PRECISION PRODUCTS INC., SEE DETAIL ON SHEET P9.1
<br />HD-1
<br />-
<br />HUB DRAIN
<br />3"
<br />-
<br />-
<br />-
<br />-
<br />ZURN MODEL Z1870
<br />• ZURN FLOOR DRAIN "TYPE 304 STAINLESS STEEL" ROUND STRAINER WITH CLAMP DEVICE.
<br />TYPE 304
<br />• ALL FLOOR DRAINS/HUB DRAIN SHALL BE INSTALLED WITH TRAP PRIMERS. COORDINATE
<br />EXACT LOCATIONS AND QUANTITY OF FLOOR DRAINS WITH ARCHITECTURAL DRAWINGS PRIOR
<br />TO ROUGH -IN.
<br />• PROVIDE TRAP PRIMER WITH AUTOMATIC TRAP PRIMER VALVE ZURN Z1022-XL. COORDINATE
<br />FINAL LOCATION WITH G.C.
<br />PLUMBING LEGEND
<br />DESCRIPTION
<br />SYMBOL
<br />NEW SANITARY WASTE BELOW SLAB
<br />— —
<br />NEW SANITARY WASTE ABOVE SLAB
<br />EXISTING SANITARY WASTE ABOVE SLAB TO REMAIN
<br />EXISTING SANITARY WASTE TO BE REMOVED
<br />X_ X—X—X—X—X _E
<br />EXISTING SANITARY WASTE TO BE REMOVED
<br />X-X-)(-X-X-X-X
<br />GAS, PROPANE LINE
<br />GAS
<br />EXISTING GAS, PROPANE LINE
<br />— — — — — — —
<br />NEWVENT
<br />-------
<br />EXISTING VENT TO REMAIN
<br />— — — — — — —
<br />EXISTING VENT TO BE REMOVED
<br />X _E -X X iF X- X
<br />NEW COLD WATER PIPING
<br />—
<br />EXISTING COLD WATER PIPING TO REMAIN
<br />—
<br />EXISTING COLD WATER PIPING TO BE REMOVED
<br />x x x X x x
<br />NEW HOT WATER PIPING
<br />— —
<br />EXISTING HOT WATER PIPING TO REMAIN
<br />— —
<br />EXISTING HOT WATER PIPING TO BE REMOVED
<br />Xx—X—X—X X—iE
<br />NEW HOT WATER RECIRCULATION PIPING
<br />— —
<br />EXISTING HOT WATER RECIRCULATION PIPING TO REMAIN
<br />— — —
<br />EXISTING HOT RECIRCULATION WATER PIPING TO BE REMOVED
<br />x X-1X_ X x x
<br />STORM WATER DRAIN PIPING
<br />ST
<br />EXISTING STORM WATER DRAIN PIPING
<br />— — — —
<br />NEW GREASE/WASTE PIPING
<br />GW
<br />EXISTING GREASE/WASTE PIPING
<br />GW
<br />EXISTING GREASE/WASTE PIPING TO BE REMOVED
<br />*x_X GWX X
<br />TRAP PRIMER PIPING
<br />TP
<br />TRAP PRIMER
<br />TP
<br />BACK WATER VALVE
<br />SHUT-OFF VALVE
<br />SHUT-OFF VALVE WITH VALVE BOX
<br />FLOOR DRAIN
<br />FLOOR SINK
<br />SMOKE DECK
<br />POINT OF CONNECTION TO EXISTING SYSTEM
<br />PIPE PENETRATION THROUGH FINISHED FLOOR
<br />ABBREVIATIONS
<br />BALL VALVE
<br />BV
<br />AIR ADMITTANCE VALVE
<br />AAV
<br />DOUBLE CHECK BACKFLOW
<br />DCBF
<br />COLD WATER SYSTEM
<br />CW
<br />EXISTING
<br />EX.
<br />FLOOR DRAIN, FLOOR SINK, FLOOR HUB
<br />FS, FD, FH
<br />GENERAL CONTRACTOR
<br />G.C.
<br />GRADE/FLOORANALL CLEAN OUT
<br />GCO/FCO/WCO
<br />HOSE-BIBB
<br />HB
<br />HOT WATER SYSTEM (110°F)
<br />HW
<br />HOT WATER RETURN SYSTEM (110°F)
<br />HWR
<br />INDIRECT DRAIN PIPING
<br />ID
<br />INVERT ELEVATION BELOW FINISHED FLOOR OR GRADE. I
<br />IE
<br />PLUMBING CONTRACTOR
<br />P.C.
<br />TEMPERATURE & PRESSURE RELIEF VALVE
<br />T&P
<br />UNLESS OTHERWISE NOTED
<br />U.O.N.
<br />BASIC PLUMBING MATERIAL
<br />REQUIREMENTS
<br />SOIL WASTE, VENT, ROOF DRAIN PIPING ABOVE GRADE:
<br />CAST IRON, NO HUB, WITH STAINLESS STEEL CLAMPS
<br />X❑ PVC-DWV, SCHEDULE 40
<br />SOIL WASTE, VENT, ROOF DRAIN PIPING BELOW GRADE:
<br />CAST IRON, NO HUB, WITH STAINLESS STEEL CLAMPS
<br />XD PVC-DWV, SCHEDULE 40
<br />WATER PIPING ABOVE GRADE:
<br />COPPER, TYPE L
<br />X CPVC, SCHEDULE 40, RETURN AIR PLENUM RATED
<br />WATER PIPING BELOW GRADE:
<br />X❑ COPPER, TYPE K, NO JOINTS BELOW GRADE
<br />CPVC
<br />FUEL GAS PIPING:
<br />X❑ SEAMLESS BLACK STEEL PIPE
<br />PVC
<br />NOTES:
<br />X❑ UTILIZE MATERIALS ABOVE UNLESS NOTED OTHERWISE ON PLANS
<br />PLUMBING SHEET INDEX
<br />P0.1
<br />— PLUMBING GENERAL
<br />P4.1
<br />— PLUMBING PROPOSED SANITARY PLAN
<br />P5•1
<br />— PLUMBING PROPOSED WATER PLAN
<br />P8• i
<br />— PLUMBING RISER DIAGRAMS
<br />P&I
<br />— PLUMBING DETAILS
<br />PLUMBING SPECIFICATIONS
<br />PART 1 -GENERAL
<br />0.01 GENERAL SCOPE
<br />A. THIS PROJECT WILL REQUIRE INSTALLATION OF PLUMBING SYSTEMS AS
<br />INDICATED.
<br />B. GENERAL CONTRACTOR SHALL FURNISH OWNER WITH COPIES OF
<br />AS-BUILTS, WARRANTIES AND OWNER'S MANUALS PRIOR TO REQUESTING
<br />FINAL PAYMENT.
<br />1.01 GENERAL DOCUMENTS
<br />A. INSTALLATION SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING
<br />CODE 7TH EDITION 2020 (EFFECTIVE 12/31/2020), WHICH INCLUDES THE
<br />FLORIDA BUILDING CODE, PLUMBING AND FUEL GAS CODES. ALL
<br />EQUIPMENT SHALL BE UL LISTED.
<br />B. THE PLUMBING WORK SHALL INCLUDE FURNISHING ALL LABOR,
<br />EQUIPMENT, MATERIALS AND SERVICE NECESSARY FOR THE PROPER
<br />COMPLETION OF ALL PLUMBING WORK SHOWN ON THE DRAWINGS AND
<br />AS SPECIFIED. ALL MATERIAL SHALL BE NEW.
<br />C. THIS ENGINEER IS NOT RESPONSIBLE FOR MATERIALS, METHODS,
<br />INSTALLATION, AND CONSTRUCTION WHICH DEVIATE FROM THESE
<br />CONSTRUCTION DOCUMENTS AND SPECIFICATIONS.
<br />1.02 SUBMITTALS
<br />A. MATERIALS OR PRODUCTS SPECIFIED HEREIN AND/OR INDICATED ON
<br />DRAWINGS BY TRADE NAME, MANUFACTURER'S NAME OR CATALOG
<br />NUMBERS SHALL BE INTERPRETED AS ESTABLISHING A STANDARD OF
<br />QUALITY AND DESIGN. SUBSTITUTIONS MAY BE ALLOWED IF THEY MEET
<br />THE QUALITY STANDARDS AND DESIGN INTENT, UNLESS OTHERWISE
<br />NOTED.
<br />B. PRIOR TO STARTING THE PROJECT, THE PLUMBING CONTRACTOR SHALL
<br />STUDY THE COMPLETE SET OF CONSTRUCTION DOCUMENTS AND
<br />COORDINATE WITH THE MANUFACTURER(S) AS REQUIRED TO PROVIDE
<br />EQUIPMENT SUBMITTALS TO SUBMIT TO PLUMBING ENGINEER OF
<br />RECORD FOR REVIEW AND APPROVAL. THE EQUIPMENT SUBMITTALS
<br />SHALL INCLUDE DIMENSIONS, WEIGHTS, SPECIFIED ACCESSORIES AND
<br />REQUIRED CLEARANCES, AS WELL AS FAN CURVES, SOUND LEVELS,
<br />CONSTRUCTION DETAILS, WARRANTY INFORMATION, AND ALL OTHER
<br />RELEVANT DATA.
<br />C. IF SUBSTITUTIONS TO THE BASIS OF DESIGN ARE SUBMITTED, THE
<br />PLUMBING CONTRACTOR SHALL PROVIDE A CLEAR, DETAILED SUMMARY
<br />IN THE SUBMITTALS OF THE DIFFERENCES BETWEEN THE SUBMITTED
<br />EQUIPMENT AND THE BASIS OF DESIGN. ADDITIONALLY, PLUMBING
<br />CONTRACTOR SHALL PROVIDE AN AFFIDAVIT STATING THAT PROPOSED
<br />SUBSTITUTION IS AN EQUAL TO THAT WHICH IS SPECIFIED. PLUMBING
<br />ENGINEER OF RECORD MAY ACCEPT OR REJECT THE SUBSTITUTIONS.
<br />1.03 SHOP DRAWINGS
<br />A. FURNISH SIX (6) COPIES OF SHOP DRAWINGS OF EQUIPMENT, FIXTURES
<br />AND SYSTEM LAYOUT TO GENERAL CONTRACTOR PRIOR TO PURCHASING
<br />ANY EQUIPMENT AND BEGINNING WORK.
<br />1.04 RECORD DRAWINGS
<br />A. AFTER COMPLETION OF ALL WORK, THE PLUMBING CONTRACTOR SHALL
<br />PROVIDE THE GENERAL CONTRACTOR WITH AS BUILT RECORD
<br />DRAWINGS. PLUMBING CONTRACTOR SHALL KEEP A RECORD OF THE
<br />LOCATIONS OF ALL CONCEALED WORK AND UPON COMPLETION OF THE
<br />JOB, SHALL SUPPLY AS -BUILT DRAWINGS SHOWING ANY DEVIATION FROM
<br />THE ORIGINAL DRAWINGS. THESE DRAWINGS SHALL INDICATE DIMENSION
<br />OF BURIED UTILITY LINES FROM BUILDING WALLS.
<br />PART 2 - INSTALLATION
<br />2.01 MATERIAL
<br />A. SOIL, WASTE, VENT, & ROOF DRAIN PIPING DRAINAGE PIPING:
<br />A.A. CAST IRON - SERVICE WEIGHT CAST IRON, NO HUB, WITH STAINLESS
<br />STEEL CLAMPS AND SHIELDS WITH NEOPRENE SEALING SLEEVES
<br />A.B. PVC - PVC-DWV SCHEDULE 40 PIPE AND BELOW SLAB SHALL BE
<br />PVC-DWV SCHEDULE 40 PIPE AND FITTINGS WITH SOLVENT WELD
<br />JOINTS AND DRAINAGE PATTERN FITTINGS.
<br />A.C. REFER TO BASIC PLUMBING MATERIAL REQUIREMENTS CHART ON
<br />THIS SHEET FOR MATERIAL SELECTION.
<br />A.D. SAW CUT FLOOR AS NECESSARY FOR INSTALLATION OF NEW
<br />SANITARY DRAINAGE PIPING. REPAIR/PATCH FLOOR TO MATCH
<br />ADJACENT AREAS.
<br />B. DOMESTIC WATER PIPING:
<br />B.A. TYPE L COPPER - TUBING WITH LEAD FREE SOLDER JOINTS.
<br />B.B. TYPE K COPPER - TUBING WITH LEAD FREE SOLDER JOINTS.
<br />B.C. COPPER FITTINGS - PIPE FITTING SHALL BE WROUGHT COPPER,
<br />B.D. SCHEDULE 40 CPVC WITH SOLVENT WELD JOINTS ASTM 02846, F441 &
<br />F442 INSTALLED AS PER MANUFACTURERS RECOMMENDATIONS.
<br />B.E. REFER TO BASIC PLUMBING MATERIAL REQUIREMENTS CHART ON
<br />THIS SHEET FOR MATERIAL SELECTION.
<br />C. PIPE INSULATION: HOT WATER SUPPLY AND RETURN PIPING SHALL BE
<br />INSULATED WITH 1" THICK R-6 MINIMUM FIBERGLASS OR EQUAL, IN
<br />COMPLIANCE WITH APPLICABLE ENERGY CODES, STORM WATER PIPING
<br />INCLUDING ROOF DRAIN SUMPS, ALL HORIZONTAL RAINWATER LEADERS &
<br />ANY PIPING ABOVE SLAB RECEIVING COLD WATER DISCHARGE FROM A/C
<br />UNITS, ICE MACHINES ETC. SHALL BE INSULATED WITH 1" THICK R-6
<br />MINIMUM FIBERGLASS (OR EQUAL) INSULATION WITH VAPOR JACKET.
<br />2.02 VALVES
<br />A. EQUAL TO NIBCO, CRANE, OR WALWORTH. ALL BRONZE 150 LB. BALL
<br />VALVES WITH RISING STEMS.
<br />2.03 SPECIALTIES
<br />H. PROVIDE UL LISTED FIRE STOPPING PIPE PENETRATION ASSEMBLIES AT
<br />ALL PIPING THROUGH RATED WALLS AND ASSEMBLIES.
<br />I. TRAP PRIMERS: RESEAL ALL FLOOR DRAIN TRAPS WITH 2' WATER LINE
<br />CONNECTED TO A TRAP PRIMER FITTING IN THE COLD WATER SUPPLY
<br />LINE SERVING A FREQUENTLY USED PLUMBING FIXTURE.
<br />J. ADA WRAP: HANDICAPPED LAVATORIES SHALL HAVE ADA APPROVED
<br />UNDER COUNTER WRAP FOR WASTE AND WATER PIPING.
<br />PART 3 - EXECUTION
<br />3.01 INSTALLATION
<br />A. INSTALL PIPE ABOVE GROUND PLUMB AND SQUARE WITH BUILDING LINES,
<br />ADEQUATELY SUPPORTED WITHOUT SAGS OR HIGH POINTS, CONCEAL
<br />PIPING IN OCCUPIED AREAS AND MAINTAIN HEAD ROOM AND ACCESS
<br />SPACE IN UNFINISHED AREAS. SLEEVE PIPING THROUGH ALL WALLS,
<br />SLABS, OR PARTITIONS WITH ESCUTCHEONS AT ALL FINISHED SURFACE.
<br />PROVIDE UNIONS AT ALL FINAL CONNECTIONS AND STOPS ON ALL
<br />SUPPLIES. ALL PIPE OPENINGS SHALL BE PLUGGED DURING
<br />INSTALLATION.
<br />B. SANITARY DRAINAGE PIPING 3" & LARGER SHALL BE INSTALLED WITH A
<br />MINIMUM 1/8" PER FOOT SLOPE UNLESS NOTED OTHERWISE. ALL
<br />DRAINAGE PIPING 2-1/2" AND SMALLER SHALL BE INSTALLED WITH A
<br />MINIMUM OF 1/4" PITCH PER FOOT.
<br />C. ALL FIXTURES AND TRIM FOR HANDICAPPED SHALL BE INSTALLED IN
<br />COMPLIANCE WITH ADA CODE,
<br />D. INSTALL ALL PIPING TO ALLOW FOR EXPANSION.
<br />E. SEE RISER DIAGRAMS FOR ALL DRAINAGE &VENT PIPE SIZING FOR THE
<br />PLUMBING SYSTEMS. REFER TO PLUMBING FLOOR PLAN (WATER SYSTEM)
<br />& SCHEDULES FOR ALL WATER PIPING SYSTEM SIZING.
<br />F. ALL WORK ASSOCIATED WITH HANDICAPPED TOILETS SHALL COMPLY
<br />WITH ADA REQUIREMENTS AND FLORIDA BUILDING CODE - CHAPTER 11
<br />FLORIDA ACCESSIBILITY CODE FOR BUILDING CONSTRUCTION.
<br />G. FINAL CONNECTIONS TO DRAINAGE AND WATER SERVICE LINES TO
<br />EXISTING OR NEW AS SHOWN ON THESE DOCUMENTS SHALL BE BY THE
<br />PLUMBING CONTRACTOR.
<br />3.02 DISINFECTING OF POTABLE WATER SYSTEM
<br />A. THE SYSTEM SHALL BE FILLED WITH A SOLUTION CONTAINING 50 PARTS
<br />PER MILLION OF AVAILABLE CHLORINE AND ALL ALLOWED TO STAND 24
<br />HOURS BEFORE FLUSHING AND RETURNING TO SERVICE. DISINFECTION
<br />PROCEDURE AND RESULT SHALL BE SUBJECT TO THE APPROVAL OF THE
<br />LOCAL PLUMBING INSPECTOR.
<br />3.03 TEST
<br />A. ALL PLUMBING SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH THE
<br />FLORIDA BUILDING CODE PLUMBING. ALL TESTS SHALL BE APPROVED BY
<br />THE LOCAL PLUMBING INSPECTOR AND SHALL BE OBSERVED BY A
<br />REPRESENTATIVE OF THE OWNER.
<br />3.04 SYSTEM IDENTIFICATION
<br />A. THE PLUMBING CONTRACTOR SHALL PROVIDE IDENTIFICATION TAGS FOR
<br />ALL NEW PIPING AND VALVES IN THE BUILDING AS PER OWNER ACCEPTED
<br />STANDARDS, THE PIPE MARKS SHALL INCLUDE PIPING SYSTEM
<br />IDENTIFICATION AND DIRECTIONS OF FLOW. EVERY 10 FEET AND
<br />CHANGES OF DIRECTION.
<br />3.05 SPECIFICATIONS AND DRAWINGS
<br />A. PLUMBING CONTRACTOR SHALL FURNISH AND INSTALL COMPLETE
<br />SANITARY, STORM, AND DOMESTIC WATER PIPING SYSTEMS: INCLUDING
<br />ALL ASSOCIATED DEVICES, EQUIPMENT, CONTROLS, AND CONNECTIONS
<br />TO NEW SERVICES, SUPPORTS, AND HARDWARE REQUIRED FOR THE
<br />SATISFACTORY OPERATIONS OF THE SYSTEMS, WHETHER SPECIFICALLY
<br />SHOWN OR NOT ON THE DRAWINGS.
<br />B. THE PLANS SHOW THE LOCATION OF ALL FIXTURES AND EQUIPMENT AND
<br />ARE INTENDED TO DEPICT THE GENERAL INTENT OF THE WORK IN SCOPE,
<br />LAYOUT, AND QUALITY OF WORKMANSHIP. THEY ARE NOT INTENDED TO
<br />SHOW IN MINUTE DETAIL EVERY AND ALL ACCESSORIES INTENDED FOR
<br />THE PURPOSE OF EXECUTION OF THE WORK, BUT IT SHALL BE
<br />UNDERSTOOD THAT SUCH DETAILS SHALL BE PART OF THIS WORK.
<br />C. THE DRAWINGS AND SPECIFICATIONS ARE MEANT TO BE
<br />SUPPLEMENTARY, HOWEVER, WHERE DRAWINGS AND SPECIFICATIONS
<br />CONFLICT, IT SHALL BE THE RESPONSIBILITY OF THIS CONTRACTOR TO
<br />BRING SUCH CONFLICT TO THE ATTENTION OF PLUMBING ENGINEER OF
<br />RECORD FOR CLARIFICATION.
<br />D. REFER TO ARCHITECTURAL DRAWINGS AND VERIFY FIELD CONDITIONS
<br />FOR EXACT LOCATION OF ALL PLUMBING FIXTURES.
<br />E. ALL DOCUMENTS, TEST REPORTS, & AS -BUILT DRAWINGS SHALL BE
<br />ATTACHED TO THE CLOSING DOCUMENTS OF THE PROJECT.
<br />3.06 WARRANTY
<br />A. THE PLUMBING CONTRACTOR SHALL WARRANT ITS WORK TO BE FREE
<br />FROM DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE
<br />YEAR FROM FINAL ACCEPTANCE OF ALL WORK.
<br />B. THE PLUMBING CONTRACTOR SHALL PROVIDE FIVE (5) BOUND COPIES OF
<br />ALL PLUMBING CONTRACTOR WARRANTIES, MANUFACTURER'S
<br />WARRANTIES, PARTS LISTS, AND INSTALLATION AND MAINTENANCE
<br />MANUALS FOR ALL PLUMBING EQUIPMENT, AS WELL AS INSTRUCTIONS
<br />FOR OPERATING AND MAINTAINING ALL PLUMBING EQUIPMENT TO THE
<br />OWNER UPON FINAL COMPLETION,
<br />3.07 COORDINATION
<br />A. PIPE PROTECTIVE COATING: FOR STEEL OR COPPER PIPE, PERMACEL OR
<br />SCOTCHWRAP VINYL TAPE APPLIED OVER PIPE TO A TOTAL MINIMUM
<br />THICKNESS OF 20 MLS. APPLY TO ALL WATER PIPE IN CONTACT WITH
<br />MASONRY OR CONCRETE.
<br />B. PIPE HANGERS: HANGERS FOR BARE COPPER PIPE THROUGH 4 INCH (4")
<br />DIAMETER OR SMALLER SHALL BE ADJUSTABLE RING TYPE, PLASTIC
<br />COATED EQUAL TO MICHIGAN 102a, FOR STEEL PIPE MICHIGAN 100.
<br />C. DRAINS AND CLEANOUTS: SEE SCHEDULE ON DRAWINGS.
<br />D. DIELECTRIC UNIONS: PROVIDE EBCO OR CAPITOL DIELECTRIC UNIONS AT
<br />ALL POINTS OF CONNECTION BETWEEN DISSIMILAR PIPE METALS.
<br />E. FLASHING AND VENT STACKS: ALL VENTS EXTENDING THROUGH THE
<br />ROOF SHALL BE PROVIDED WITH FOUR POUND SHEET LEAD FLASHING
<br />EXTENDING UPWARD AROUND THE PIPE AND TURNED DOWN INSIDE THE
<br />PIPE OR AS OTHERWISE SHOWN ON THE DRAWINGS. THE ROOF FLASHING
<br />SHALL BE INSTALLED BY LICENSED ROOFING CONTRACTOR.
<br />F. ESCUTCHEONS AND SLEEVES. WHERE PIPES PIERCE EXPOSED
<br />PARTITIONS, FLOORS, WALL, OR CEILINGS, PROVIDE CHROME PLATED
<br />ESCUTCHEONS TO THE COVER THE RAW EDGE.
<br />G. SLEEVES SHALL BE PROVIDED A ALL PIPE PENETRATIONS OF MASONRY
<br />AND CONCRETE WALLS AND FLOORS.
<br />A. COORDINATE WORK WITH OTHER TRADES AND EXISTING CONDITIONS
<br />PRIOR TO BEGINNING WORK. PLUMBING CONTRACTOR SHALL PROVIDE
<br />ROUTING AND OFFSETS NECESSARY TO AVOID CONFLICT WITH
<br />STRUCTURE, FINISHES, AND WORK OF OTHER TRADES.
<br />B. VERIFY LOCATIONS, SIZES, AND INVERT ELEVATIONS OF SANITARY DRAIN,
<br />AND DOMESTIC WATER PIPING CONNECTIONS WITH FIELD CONDITIONS
<br />AND CIVIL ENGINEERING DRAWINGS (AS APPLICABLE) PRIOR TO
<br />PROCEEDING WITH THE WORK. SHOULD ANY DISCREPANCIES BE
<br />DISCOVERED, PLUMBING CONTRACTOR SHALL SUBMIT A REQUEST FOR
<br />INFORMATION TO PLUMBING ENGINEER OF RECORD.
<br />C. COORDINATE WITH ARCHITECTURAL DRAWINGS FOR WALL AND
<br />PARTITION CONSTRUCTION AND THICKNESS WHERE PLUMBING PIPING,
<br />FIXTURES CARRIERS OR EQUIPMENT IS INDICATED. BEFORE STARTING
<br />CONSTRUCTION, IDENTIFY ANY CONFLICT PRIOR TO STARTING
<br />CONSTRUCTION.
<br />D. COORDINATE EXACT LOCATION, ELEVATIONS, AND SIZES OF ALL SLEEVES
<br />IN NEW STRUCTURE WITH STRUCTURAL AND ARCHITECTURAL DRAWINGS
<br />AND FIELD CONDITIONS.
<br />GS JOB #: S831 .21 .00
<br />GLOBAL
<br />5,,�Cn�ZINC.
<br />MEPF ENGINEERING
<br />INFO@GLOBAL-SANCHEZ.COM
<br />CA#: 6237
<br />B 1 6 MANATEE AVE. E, SUITE 18
<br />BRADENTON, FL 3420B
<br />PHONE: 941-75B-2SS1
<br />3825 HENDERSON BLVD.,
<br />SUITE 103
<br />TAMPA, FL 33629
<br />PHONE: B 1 3-28 1 -❑❑❑ 1
<br />C&K ARCHITECTS I INTERIORS
<br />architecture• interior design -client services
<br />AAC0.01629
<br />4221 WEST BOY SCOUT BLVD., SUITE 150
<br />TAMPA, FL 33607-5743
<br />813.884.2000
<br />280 WEST CENTRAL AVE.
<br />WINTER HAVEN, FL 33880-2957
<br />863.577.2054
<br />c
<br />A SF�
<br />N 1 4'
<br />u
<br />5/1 /2021: W
<br />STATE OF
<br />I '• FtOR��Pr°G�
<br />SS/ONAL1��
<br />-
<br />z
<br />c
<br />_
<br />t
<br />2
<br />z
<br />0
<br />-
<br />'
<br />s
<br />i
<br />mQ
<br />0
<br />O
<br />z
<br />J
<br />LL
<br />�
<br />J
<br />x
<br />0-
<br />w
<br />N
<br />v r
<br />i
<br />O
<br />I..L
<br />Z
<br />W
<br />(
<br />Z Lu
<br />NO
<br />m
<br />I
<br />J
<br />J
<br />Q
<br />0
<br />M
<br />LO
<br />01
<br />ISSUED FOR:
<br />PERMIT
<br />PROJECT NUMBER
<br />21020
<br />DATE
<br />5.5.21
<br />DRAWING NUMBER
<br />PO I I