©n <br />GENERAL NOTES: <br />THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ALL OTHER CONSTRUCTIONS DOCUMENTS. THIS <br />INCLUDES, BUT IS NOT LIMITED TO, SPECIFICATIONS, ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND <br />SITE DRAWINGS. <br />ALL CONDITIONS, ELEVATIONS, AND DIMENSIONS SHALL BE VERIFIED IN THE FIELD AND WITH THE OTHER <br />CONSTRUCTION DOCUMENTS BY THE CONTRACTOR. ANY DISCREPANCIES RELATED TO THESE DRAWINGS SHALL BE <br />BROUGHT TO THE ATTENTION OF AUSTIN STRUCTURAL GROUP, INC. BEFORE PROCEEDING WITH THE AFFECTED <br />PORTION OF WORK. <br />THE STRUCTURE IS DESIGNED TO BE SELF SUPPORTING AND STABLE AFTER CONSTRUCTION IS COMPLETED. THE <br />CONTRACTOR IS RESPONSIBLE TO DETERMINE PROPER PROCEDURE AND SEQUENCE OF CONSTRUCTION TO INSURE <br />THE SAFETY OF THE BUILDING, ITS COMPONENTS AND PERSONNEL ON SITE. THIS INCLUDES TEMPORARY SUPPORT <br />OF STRUCTURE DURING CONSTRUCTION WHICH MAY INCLUDE, BUT IS NOT LIMITED TO, TEMPORARY SHORING, <br />BRACING AND TIE -DOWNS. <br />CODES AND STANDARDS EDITION: <br />1. FLORIDA BUILDING CODE - 2017 <br />2. ACI 318-08 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE WITH COMMENTARY. <br />3. AISC, "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES". <br />4. AISC, "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS". <br />5. AISC, "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS <br />6. SJI, "STANDARD SPECIFICATIONS FOR OPEN WEB JOISTS, K SERIES, LH SERIES, DLH SERIES, SLH SERIES AND <br />JOIST GIRDERS". <br />7. SDI, "DESIGN MANUAL FOR FLOOR DECKS AND ROOF DECKS". <br />8. ACI, 'BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (ACI 530-05)". <br />9. ACI, "SPECIFICATIONS FOR MASONRY STRUCTURES (ACI 530.1-05)". <br />10. AISI, "SPECIFICATIONS FOR THE DESIGN OF COLD -FORMED STEEL STRUCTURAL MEMBERS". <br />11. NFPA, "NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION, 2005 EDITION". <br />12. AITC, "TIMBER CONSTRUCTION MANUAL, 5TH EDITION, 2004". <br />GENERAL: <br />1. THE CONTRACTOR SHALL VERIFY THE LOCATION OF UTILITIES IN THE AREA OF THE CONSTRUCTION. THE <br />CONTRACTOR SHALL REPAIR OR REPLACE ANY UTILITIES DAMAGED DURING CONSTRUCTION TO THE <br />SATISFACTION OF THE OWNER OF THE UTILITY. <br />2. THE CONTRACTOR SHALL REPAIR OR REPLACE EXISTING BUILDINGS AND STRUCTURES ADJACENT TO THE <br />CONSTRUCTION IF DAMAGED BY THE CONTRACTOR DURING CONSTRUCTION. <br />3. SHOP DRAWINGS AS REQUIRED BY THE CONTRACT DOCUMENTS SHALL BE SUBMITTED BY THE <br />CONTRACTOR PRIOR TO THE CONSTRUCTION OF ANY ELEMENTS INCLUDED IN THE SHOP DRAWINGS. <br />THE ARCHITECT/ENGINEER WILL NOT CERTIFY CONSTRUCTION FOR ELEMENTS REQUIRING SHOP <br />DRAWINGS UNLESS AND UNTIL THE SHOP DRAWINGS ARE REVIEWED AND APPROVED BY THE <br />ARCHITECT/ENGINEER. <br />4. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO CONSTRUCTION AND NOTIFY THE <br />ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR CONFLICTS. <br />5. LOCATIONS AND SIZES OF OPENINGS, SLEEVES AND ANCHORAGE FOR ELECTRICAL AND MECHANICAL <br />EQUIPMENT SHOWN ON THE STRUCTURAL PLANS ARE APPROXIMATE. THE CONTRACTOR SHALL VERIFY THE <br />SIZE AND LOCATION OF ALL OPENINGS, SLEEVES AND ANCHORAGE WITH THE TRADES FURNISHING AND <br />INSTALLING THE EQUIPMENT. <br />6. ALL ELEVATIONS ARE BASED ON THE FINISHED FLOOR ELEVATION OF THE GROUND FLOOR TO BE Y-0". <br />7. THE CONTRACTOR SHALL VERIFY THE LOCATION AND DEPTH OF ALL DEPRESSIONS IN CONCRETE SLABS. <br />CONTRACTOR PROPOSED CHANGES AND SUBSTITUTIONS: <br />1. PROPOSED CHANGES OR SUBSTITUTIONS TO STRUCTURAL DETAILS OR PLANS SHALL BE SUBMITTED TO THE <br />ENGINEER OF RECORD (EOR) FOR REVIEW AND APPROVAL. SUBMITTALS SHALL CONTAIN FULL <br />DOCUMENTATION OF CHANGES OR SUBSTITUTIONS WITH SUPPORTING, SEALED CALCULATIONS (WHERE <br />APPLICABLE). THE REVIEW OF CHANGES AND SUBSTITUTIONS, RE -ANALYSIS AND/OR RE -DRAFTING TO <br />INCORPORATE CHANGES OR SUBSTITUTIONS INTO CONTRACT DOCUMENTS ARE ADDITIONAL SERVICES FOR <br />EOR. CONSTRUCTION COST REVISIONS ARE BETWEEN THE CONTRACTOR AND OWNER AND ARE NOT <br />REVIEWED BY THE FOR <br />FOUNDATIONS: <br />1. FOUNDATIONS ARE DESIGNED FOR A MAXIMUM NET SOIL BEARING PRESSURE OF 1500 PSF BASED ON SECTION <br />1806.2 OF THE FLORIDA BUILDING CODE 2017. <br />2. ALL SOIL BELOW THE BUILDING FOOTPRINT SHALL BE TREATED FOR TERMITE CONTROL PRIOR TO PLACEMENT <br />OF SLABS ON GRADE. <br />3. ALL SLABS ON GRADE SHALL BE PLACED ON A 6 MIL VAPOR RETARDER. <br />4. ALL FILL BENEATH FOUNDATIONS OR GROUND SLABS SHALL BE COMPACTED TO 95% OF THE MAXIMUM DRY <br />DENSITY AS DETERMINED BY ASTM D1557 (MODIFIED PROCTOR TEST). <br />REINFORCED CONCRETE: <br />1. REQUIRED CONCRETE COMPRESSIVE STRENGTHS AT 28 DAYS, UNLESS OTHERWISE NOTED: <br />SIDEWALKS, SLABS ON GROUND, & FOUNDATIONS ................... fc = 3000 PSI <br />COLUMNS, BEAMS, SHEAR WALLS & ELEVATED SLABS, TIE BEAMS ......... fc = 4000 PSI <br />2. MINIMUN CONCRETE COVER <br />CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH ........... 3" <br />CONCRETE EXPOSED TO EARTH OR WEATHER: <br />NO.6 THROUGH NO.18 BAR ............................................... 2" <br />NO.5 BAR, W31 OR D31 WIRE AND SMALLER ... . .............................1 1/2" <br />CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND: <br />SLABS, WALLS & JOISTS: <br />NO. 14 & NO. 18 BARS .....................................................1 1/2" <br />NO. 11 BARS AND SMALLER ................. . ............................. 3/4" <br />BEAMS & COLUMNS: <br />PRIMARY REINFORCEMENT, TIES, STIRRUPS & SPIRALS .......................1 1/2" <br />SHELLS & FOLDED PLATE MEMBERS: <br />NO.6 BARS AND LARGER..................................................3/4" <br />NO.5 BAR, W31 OR D31 WIRE AND SMALLER..................................1/2" <br />3. REINFORCING STEEL IN CONCRETE SHALL HAVE A MINIMUM LAP AS SCHEDULED, UNLESS OTHERWISE NOTED <br />AND SHALL CONFORM TO ASTM A615, GRADE 60. <br />4. ALL EXPOSED SURFACES OF CONCRETE SLABS, BEAMS AND COLUMNS EXPOSED TO THE EXTERIOR SHALL <br />RECEIVE A SEALER IN CONFORMANCE TO THE SPECIFICATIONS. <br />5. SLABS ON GROUND FOR INTERIOR CONDITIONED SPACES SHALL BE 4" THICK WITH 6x6 - W2.1xW2.1 WWF (GC <br />OPTION TO SUBSTITUTE WITH 1.0 LB OF FIBERMESH PER CUBIC YARD) PLACED 1 112" FROM TOP SURFACE, <br />PLACED OVER 6 MIL VAPOR RETARDER AND TERMITE TREATED COMPACTED SOIL, UNLESS OTH <br />ERWISE NOTED. <br />6. CONTRACTOR SHALL SAW CUT (1" DEEP X 1/8" WIDE) CONTROL JOINTS IN SLABS ON GROUND WITHIN 24 HOURS <br />AFTER PLACING CONCRETE, CONTROL JOINTS SHALL BE LOCATED AT CENTERS OF COLUMNS, UNDER <br />NON -LOAD BEARING WALLS AND AT SPACING NOT GREATER THAN 16-0" IN BOTH DIRECTIONS. <br />7. PROVIDE DOWELS FOR LAP OF ALL HORIZONTAL REINFORCING BARS AT CORNERS AND TEES FOR WALL <br />FOOTINGS, BEAMS, WALLS AND TIE BEAMS TO MAINTAIN CONTINUOUS REINFORCING THROUGH INTERSECTION. <br />8. TIE BEAMS ( NOTED "TB)XX" SHALL BE FORMED AND PLACE AFTER CONSTRUCTION OF SUPPORTING MASONRY <br />WALLS. <br />9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND CONSTRUCTION OF FORM WORK, BRACING <br />AND SHORING IN CONFORMANCE WITH ACI 347-04 AND ACI 347R-05 <br />REINFORCING STEEL: <br />1. REINFORCING STEEL FOR REINFORCED CONCRETE AND REINFORCED MASONRY SHALL CONFORM TO ASTM <br />A615, GRADE 60, DEFORMED REINFORCEMENT, UNLESS OTHERWISE NOTED. <br />2. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A185 <br />3. SPLICES SHALL BE IN CONFORMANCE WITH ACI 318-05 UNLESS OTHERWISE NOTED <br />4. ELEVATED SLABS AND SLABS ON GROUND, EXCEPT SIDEWALKS, SHALL USE SHEET STOCK WELDED WIRE <br />FABRIC. ROLL STOCK SHALL NOT BE USED FOR THESE MEMBERS. <br />5. MECHANICAL SPLICING DEVICES FOR REINFORCING STEEL MAY BE SUBMITTED TO THE ARCHITECT/ENGINEER <br />FOR APPROVAL. <br />FORMWORK AND SHORING: <br />1. NO STRUCTURAL CONCRETE SHALL BE STRIPPED UNTIL IT HAS REACHED AT LEAST TWO THIRDS OF THE 28 <br />DAY DESIGN STRENGTH. DESIGN, ERECTION AND REMOVAL OF ALL FORMWORK, SHORES AND RESHORES <br />SHALL MEET THE REQUIREMENTS SET FORTH IN ACI STANDARDS 347 AND 301. <br />CONSTRUCTION JOINTS: <br />1. ANY DEVIATION OR ADDITION OF CONSTRUCTION JOINT FROM THAT SHOWN ON THE PLANS MUST BE <br />REVIEWED BY THE ENGINEER. ALTERNATE OR ADDED CONSTRUCTION JOINT LOCATIONS ARE ACCEPTABLE <br />ONLY AS A CHANGE ORDER, WHICH WILL INCLUDE ENGINEERING CHARGES BY THE ENGINEER OF RECORD FOR <br />REDESIGN OF THE STRUCTURE, SHORING, ETC. <br />PENETRATIONS: <br />1. NO PENETRATIONS SHALL BE MADE IN ANY STRUCTURAL MEMBERS OTHER THAN THOSE LOCATED ON <br />THESE DRAWINGS WITHOUT PREVIOUS APPROVAL OF THE ENGINEER. <br />STRUCTURAL CONCRETE MASONRY: <br />1. CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90, TYPE II, GRADE N, SQUARE END WITH A MINIMUM <br />AVERAGE COMPRESSION STRENGTH OF 1900 PSI ON NET SECTION, COMPRESSIVE STRENGTH OF MASONRY <br />fm =1,500 PSI U.N.O. <br />2. MORTAR SHALL CONFORM TO ASTM C270, TYPE S, PORTLAND CEMENT LIME MORTAR CEMENT OR MORTAR <br />CEMENT. MASONRY CEMENT SHALL NOT BE USED FOR STRUCTURAL MASONRY. <br />3. MASONRY GROUT SHALL CONFORM TO ASTM C476 AND HAVE AN AVERAGE COMPRESSION STRENGTH OF 3000 <br />PSI AT 28 DAYS. MASONRY GROUT SHALL HAVE A SLUMP OF B-10 INCHES. <br />4. REINFORCING STEEL IN STRUCTURAL MASONRY SHALL BE LAPPED 48 BAR DIAMETERS, <br />5. VERTICAL REINFORCING IN MASONRY WALLS IS NOTED ON THE FLOOR PLANS OF THE FLOOR BELOW THE <br />WALLS. <br />6. ALL CONCRETE MASONRY BELOW GRADE SHALL BE FULLY GROUTED. <br />7. ALL VERTICALREINFORCINGIN CONCRETE MASONRY CELLS SHALL BE HELD IN PLACE WITH RE <br />BAR <br />POSITIONERS LOCATED NEAR THE TOP AND BOTTOM OF EACH GROUT POUR. <br />8. ALL MASONRY GROUTING SHALL UTILIZE THE HIGH LIFT GROUTING METHOD AS SET FORTH IN NCMA TEK 23A. <br />GROUT POURS SHALL BE LIMITED TO 12 FT IN HEIGHT PLACED IN TWO 6 FT LIFTS. CLEAN -OUT OPENINGS SHALL <br />BE CUT IN THE FACE SHELL AT THE BOTTOM COURSE OF CELLS TO BE GROUTED TO ALLOW REMOVAL OF <br />DEBRIS AND INSPECTION OF CELL PRIOR TO GROUTING. <br />9. HORIZONTAL JOINT REINFORCING SHALL BE 9 GAUGE LADDER TYPE REINFORCING WITH ONE LONGITUDINAL <br />WIRE FOR EACH FACE SHELL IN THE WALL CONSTRUCTION. JOINT REINFORCING SHALL BE LOCATED IN <br />ALTERNATE COURSES, AT 16" VERTICAL SPACING. LAP JOINT REINFORCING 6" MINIMUM. USE PREFORMED "L" <br />AND "T" SECTIONS TO MAINTAIN JOINT REINFORCING CONTINUOUS THROUGH CORNERS AND TEES. <br />10, THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN AND CONSTRUCTION OF FORM WORK, AND <br />SHORING IN THE CONFORMANCE WITH ACI 347-04 AND ACI 347R-05. <br />11, MECHANICAL REBAR SPLICES ARE ACCEPTABLE. MECHANICAL SPLICER SHALL DEVELOP AT LEAST 1.25 (125°%) <br />fy OF THE SPLICED BAR. <br />12. WELDED REBAR SPLICES ARE ACCEPTABLE. WELDED SPLICER SHALL DEVELOP AT LEAST 1,25 (125%) fy OF THE <br />SPLICED REBAR. <br />13. ALL MASONRY OPENINGS SHALL HAVE A PRECAST LINTEL INSTALLED. REFERENCE LINTEL SCHEDULE FOR SIZE <br />AND REINFORCING. PRECAST LINTELS SHALL BEAR A MINIMUM OF 8" AT EACH END, U.N.O. <br />14. PROVIDE CONTINUOUS BOND BEAM AT THE TOP OF ALL MASONRY WALLS, TYP. HOOK ALL VERTICAL WALL <br />REINFORCING 900 INTO BOND BEAM AT THE TOP OF ALL WALLS, TYP. <br />POST -INSTALLED ANCHORS: <br />1. POST INSTALLED ANCHORS SHALL ONLY BE USED WHERE SPECIFIED ON THE DRAWINGS. <br />2. CONTRACTOR SHALL OBTAIN APPROVAL FROM ENGINEER OF RECORD PRIOR TO USING POST -INSTALLED <br />ANCHORS FOR MISSING OR MISPLACED CAST -IN ANCHORS. <br />3. CARE SHALL BE GIVEN TO AVOID DAMAGING EXISTING REBAR WHEN DRILLING HOLES. HOLES SHALL BE <br />DRILLED AND CLEANED PER MANUFACTURER'S INSTRUCTIONS. <br />4. UNLESS SPECIFIED OTHERWISE, ANCHORS SHALL BE EMBEDDED IN THE APPROPRIATE SUBSTRATE WITH A <br />MINIMUM EMBEDMENT OF 8 TIMES THE NOMINAL ANCHOR DIAMETER OR THE EMBEDMENT REQUIRED TO <br />SUPPORT THE INTENDED LOAD. ANCHORS SHALL BE INSTALLED PER THE MANUFACTURER'S INSTALLATION <br />INSTRUCTIONS AT NOT LESS THAN MINIMUM EDGE DISTANCE AND/OR SPACING INDICATED IN THE <br />MANUFACTURER'S LITERATURE. <br />5. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE LISTED BELOW SHALL BE SUBMITTED TO THE <br />ENGINEER OF RECORD FOR REVIEW AND APPROVAL WITH CALCULATIONS PREPARED, SIGNED AND SEALED BY <br />AN ENGINEER REGISTERED IN THE LOCALITY OF THE PROJECT SHOWING THAT THE SUBSTITUTED PRODUCT <br />WILL ACHIEVE AN EQUIVALENT CAPACITY USING THE APPROPRIATE DESIGN PROCEDURE. <br />6. ACCEPTABLE PRODUCTS ARE: <br />A) EXPANSION ANCHORS FOR NON -CRACKED CONCRETE ONLY: <br />-WEDGE-ALL (WA) BY SIMPSON STRONG -TIE <br />-KWIK BOLT 3 BY HILTI <br />B) CRACKED CONCRETE MECHANICAL ANCHORS: <br />-STRONG-BOLT (STB) BY SIMPSON STRONG -TIE <br />-KWIK BOLT (TZ) BY HILT[ <br />C) SCREW ANCHORS: <br />-TITEN HD (THD) BY SIMPSON STRONG -TIE <br />-HUS-H BY HILTI <br />D) ADHESIVE ANCHORS: <br />1) FOR ANCHORING INTO SOLID BASE MATERIAL: <br />-ACRYLIC -TIE (AT) BY SIMPSON STRONG -TIE <br />-SET EPDXY -TIE (SET) WITH RETROFIT BOLTS (RFB) BY SIMPSON STRONG -TIE <br />-HIT RE 500 BY HILTI <br />2) FOR ANCHORING INTO HOLLOW BASE MATERIAL: <br />-CONTACT ENGINEER OF RECORD <br />ANCHOR RODS: <br />ANCHOR RODS SHALL CONFORM TO ASTM F1554 GRADE 55 HAVE A MINIMUM DIAMETER EQUAL TO Y", (U.N.O. ON <br />STRUCTURAL PLANS) AND SHALL BE THREADED WITH TACK WELDED NUT AT BOTTOM WITH A MINIMUM OF 8" EMBED <br />ASTM 6 WA <br />SHERS SHALL <br />U.N.O.N STRUCTURAL PLANS. NUTS SHALL CONF <br />ORM TO S A 5 3 GRADE A. W S <br />INTO CONCRETE,U , <br />T HALL BE HOT DIPPED GALVAN <br />IZED. <br />T F4 TYPE LLP SS 0 CONFORM TO ASTM 36, PE 1. A AR <br />1. STRUCTURAL WOOD COMPONENTS (BEAMS, JOISTS, RAFTERS, ETC.) SHALL HAVE THE FOLLOWING MINIMUM <br />ALLOWABLE FIBER STRESSES OF NO, 2 SOUTHERN PINE CONFORMING TO THE LATEST EDITION OF NDS, AS <br />FOLLOWS: <br />SHEAR Fv = 175 psi. <br />BENDING 2x6 Fb =1,250 psi. <br />BENDING 2x8 Fb =1,200 psi. <br />BENDING 2x10 Fb =1,050 psi. <br />BENDING 2x12 Fb = 975 psi. <br />2. WOOD IN CONTACT WITH CONCRETE OR MASONRY, AND AT OTHER LOCATIONS AS SHOWN ON STRUCTURAL <br />DRAWINGS, SHALL BE PROTECTED OR PRESSURE TREATED IN ACCORDANCE WITH AMERICAN WOOD - <br />PRESERVERS' ASSOCIATION STANDARDS, MEMBER SIZES SHOWN ARE NOMINAL UNLESS NOTED OTHERWISE. <br />3. ENGINEERED WOOD TRUSS SYSTEM SHALL BE DESIGNED BY THE SUPPLIER'S SPECIALTY ENGINEER TO <br />CONFIGURATION AND LOAD -CARRYING CAPACITY SHOWN ON DRAWINGS. TRUSS DESIGNS SHALL COMPLY WITH <br />ANSI/TPI 1 "NATIONAL DESIGN STANDARD FOR METAL -PLATE -CONNECTED WOOD TRUSS CONSTRUCTION." TPI HIB <br />"COMMENTARY AND RECOMMENDATIONS FOR HANDLING INSTALLING & BRACING METAL PLATE CONNECTED <br />WOOD TRUSSES"AND TPI DSB "RECOMMENDED DESIGN SPECIFICATION FOR TEMPORARY BRACING OF METAL <br />PLATE CONNECTED WOOD TRUSSES." ALTERNATE TRUSS LAYOUTS ARE NOT ACCEPTABLE. SHOP DRAWINGS <br />SHALL BE SUBMITTED AND SHALL SHOW AND SPECIFY CONNECTOR TYPES UTILIZED WITHIN TRUSSES, AS WELL <br />AS CONNECTORS UTILIZED IN OTHER CONNECTIONS AND ATTACHMENTS BETWEEN TRUSSES OR COMPONENTS <br />SUPPLIED AS PART OF THE ENGINEERED TRUSS SYSTEM. AN ERECTION DRAWING SHALL IDENTIFY TRUSS <br />SYSTEM COMPONENTS AND ANY PERMANENT BRACING REQUIRED FOR TRUSS DESIGN, <br />4. ENGINEERED SHOP DRAWINGS SHALL BEAR THE SIGNATURE AND IMPRESSED SEAL OF A FLORIDA <br />REGISTERED ENGINEER AS THE SPECIALTY ENGINEER AND SHALL BE SUBMITTED FOR REVIEW BY THE ENGINEER <br />OF RECORD. <br />5. THE FOLLOWING LOAD DURATION FACTORS SHALL BE USED: <br />DEAD LOAD .90 <br />DEAD LOAD + FLOOR LIVE LOAD 1.00 <br />DEAD LOAD + ROOF LIVE LOAD 1.25 <br />6. ROOF SHEATHING IS DESIGNED AS A DIAPHRAGM AND SHALL COMPLY WITH CHAPTER 23 OF THE FLORIDA <br />BUILDING CODE. UNLESS SHOWN OTHERWISE, SPAN RATED PANELS SHALL BE FASTENED TO NOMINAL 2X <br />FRAMING SPACED AT 24" O.C. MAX. AS FOLLOWS: <br />7. PANELS UP TO 1/2" THICK: 8d NAILS AT 6" O.C. EDGE, 12" O.C. ELSEWHERE <br />8. PANELS UP TO 5/8" THICK:10d NAILS AT 6" O.C. EDGE, 12"O.C. ELSEWHERE <br />9. PANELS UP TO 3/4" THICK:12d NAILS AT 6" O.C. EDGE, 12" O.C. ELSEWHERE <br />10. SEE ROOF SHEATHING NAILING PLAN FOR OTHER NAILING PATTERNS. <br />11. SPAN DIRECTION OF PLYWOOD SHEETS IS CONTRACTOR'S OPTION UNLESS SPECIFICALLY NOTED <br />OTHERWISE. <br />METAL PLATE CONNECTED WOOD TRUSSES: <br />1. THE APPORTIONMENT OF THE RESPONSABILITIES BETWEEN THE STRUCTURAL ENGINEER OF RECORD AND THE <br />DELEGATED ENGINEER FOR WOOD TRUSSES SHALL BE AS SET FORTH IN CHAPTER2 OF ANSI/PRI1-1995, <br />"NATIONAL DESIGN STANDARD FOR METAL PLATE CONNECTED WOOD CONSTRUCTION" WITH THE AMENDED <br />DEFINITIONS SUBSTITUTED AS FOLLOWS: <br />A, ANSI/TPI "TRUSS DESIGNER" REFERS TO THE DELEGATED ENGINEER FOR WOOD TRUSSES. <br />B. ANSI/TPI "BUILDING DESIGNER" REFERS TO THE STRUCTURAL ENGINEER OF RECORD FOR THE PROJECT. <br />2. METAL PLATE CONNECTED WOOD TRUSSES AND THEIR CONNECTIONS SHALL BE DESIGNED BY A DELEGATED <br />ENGINEER FOR THE LOADS AND DESIGN CRITERIA PROVIDED HEREIN IN ACCORDANCE WITH THE EDITION OF THE <br />LOCAL BUILDING CODE AND NDS REFERENCED UNDER GENERAL NOTES ON THIS SHEET AND SECTION <br />61G15-31.003 OF THE F.A.C. AS WELL AS 61 G1 5-31.003. SUBMIT DELEGATED ENGINEERING DOCUMENTS FOR <br />APPROVAL AND DO NOT FABRICATE WITHOUT RECEIVING APPROVAL. <br />3. THE DELEGATED ENGINEER SHALL BE DEEMED A "TRUSS SYSTEM ENGINEER" AS DEFINED IN 61 G1 5-31.003(4) OF <br />F.A.C. AND SHALL DESIGN A TRUSS SYSTEM, MEANING THE ASSEMBLAGE OF TRUSSES AND TRUSS GIRDERS <br />TOGETHER WITH ALL BRACING, CONNECTIONS AND OTHER STRUCTURAL ELEMENTS AND ALL SPACING AND <br />LOCATIONAL CRITERIA THAT, IN COMBINATION, FUNCTION TO SUPPOPRT THE DEAD LOAD, LIVE LOAD, LIVE ROOF <br />LOAD, AND WIND LOADS APPLICABLE TO THE TRUSS SYSTEM. SUPPORTING WALLS, FOUNDATIONS AND <br />HEADERS ARE BEYOND THE SCOPE OF THE TRUSS SYSTEM ENGINEER'S SERVICES. <br />4. THE TRUSSES SHALL BE DESIGNED TO ACCOMODATE THE SUPERIMPOSED LOADS AS TABULATED OR SPECIFIED <br />HEREIN IN ADDITION TO THE TRUSS SELF -WEIGHT. <br />5. THE TRUSS SHALL BE DESIGNED TO MEET THE SERVICEABILITY LIMITS AS FOLLOWS: <br />TRUSS CASE LONG TERM CREEP SHORT TERM CREEP DEFLECTION <br />LOCATION WITH A 1.5 FACTOR WITH NO FACTOR LIMIT <br />ROOF <br />Lr - <br />100% LIVE LOAD <br />U360 <br />ROOF <br />D + Lr 100% DEAD + 25% LIVE <br />75% LIVE LOAD <br />U240 <br />6. TRUSS DESIGN DRAWINGS AND TRUSS BEARING REACTION VALUES & LOCATIONS, PREPARED BY A <br />PROFESSIONAL ENGINEER LICENSED IN THE STATE IN WHICH THE PROJECT IS LOCATED, SHALL BE PROVIDED <br />AND APPROVED BY THE STRUCTURAL ENGINEER OF RECORD FOR THE PROJECT PRIOR TO FABRICATION. TRUSS <br />DESIGN DRAWINGS SHALL BE PROVIDED WITH THE SHIPMENT OF TRUSSES DELIVERED TO THE PROJECT SITE, <br />AND SHALL INCLUDE, AT A MINIMUM, THE FOLLOWING: <br />A. BASIC DESIGN WIND SPEED AND RISK CATEGORY, <br />B, SLOPE AND/OR DEPTH, SPAN AND SPACING <br />C. LOCATION OF ALL JOINTS. <br />D, REQUIRED BEARING WIDTHS. <br />E, DESIGN LOADS AS PER LOAD TABLE <br />F. ADJUSTMENTS TO LUMBER AND JOINT CONNECTOR DESIGN VALUES FOR CONDITIONS OF USE. <br />G. EACH REACTION FORCE, DIRECTION AND LOCATION <br />H. LUMBER SIZES, SPECIES AND GRADE FOR EACH MEMBER. <br />1. JOINT CONNECTOR TYPE AND DESCRIPTION, E.G., SIZE THICKNESS OR GAUGE, AND THE <br />DIMENSIONED LOCATION OF EACH JOINT CONNECTOR EXCEPT WHERE SYMMETRICALLY LOCATED RELATIVE <br />TO THE JOINT INTERFACE. <br />J. CONNECTIONS REQUIREMENTS FOR: <br />(1) TRUSS -TO -TRUSS GIRDER, <br />2 TRUSS PLY -TO -PLY AND <br />(3) FIELD SPLICES. <br />K. CALCULATED DEFLECTION RATIO AND/OR MAXIMUM DESCRIPTION FOR LIVE AND TOTAL LOAD. <br />L. THE SIZE, CONNECTION AND LOCATION OF ALL TEMPORARY AND PERMANENT BRACING. <br />7. THE DELEGATED ENGINEER SHALL VERIFY THE APPLICABILITY OF THE SPECIFIED TRUSS CONNECTORS <br />REGARDING THE ABILITY TO WITHSTAND UPLIFT, BEARING AND LATERAL LOADS AS MAY BE APPLICABLE AND <br />MAKE RECOMMENDATIONS FOR SUBSTITUTE CONNECTORS AS REQUIRED. <br />WOOD FRAMING CONNECTORS: <br />1. CONNECTORS SHALL BE GALVANIZED (Z-MAX COATED). CONNECTOR MODEL NUMBERS SHOWN ARE Strong tie <br />CONNECTORS AS MANUFACTURED BY SIMPSON Strong Tie Co.,1450 DOOLITTLE DR., P.O. BOX 1568, SAN LEANDRO, <br />CA 94577, SUBSTITUTIONS ARE ACCEPTABLE WITH THE APPROVAL OF THE STRUCTURAL ENGINEER, UNLESS <br />SHOWN OTHERWISE, INSTALL SIZE AND NUMBER OF FASTENERS SHOWN IN LATEST SIMPSON CATALOG, <br />SHOP DRAWINGS FOR SPECIALTY ENGINEERED PRODUCTS: <br />1. THE FOLLOWING SYSTEMS AND COMPONENTS AS A MINIMUM REQUIRE FABRICATION AND ERECTION DRAWINGS <br />PREPARED BY A DELEGATED ENGINEER: <br />2. ROOF TRUSS SYSTEMS, LIGHT GAGE STEEL EXTERIOR WALL SYSTEMS, ALUMINUM SYSTEMS, GLAZED CURTAIN <br />WALLS, PREFABRICATED STEEL STAIRS & RAILINGS, STRUCTURAL STEEL CONNECTIONS REQUIRING <br />ENGINEERING. <br />3, SUBMITTALS SHALL CLEARLY IDENTIFY THE SPECIFIC PROJECT AND APPLICABLE CODES, LIST THE DESIGN <br />CRITERIA, AND SHOW ALL DETAILS AND PLANS NECESSARY FOR PROPER FABRICATION AND INSTALLATION. <br />CALCULATIONS AND SHOP DRAWINGS SHALL IDENTIFY SPECIFIC PRODUCT UTILIZED. GENERIC PRODUCTS WILL <br />NOT BE ACCEPTED. <br />4. SHOP DRAWINGS AND CALCULATIONS SHALL BE PREPARED UNDER THE DIRECT SUPERVISION AND CONTROL OF <br />THE DELEGATED ENGINEER. <br />5. SHOP DRAWINGS AND CALCULATIONS REQUIRE THE IMPRESSED SEAL, DATE AND SIGNATURE OF THE <br />DELEGATED ENGINEER. COMPUTER PRINTOUTS ARE AN ACCEPTABLE SUBSTITUTE FOR MANUAL <br />COMPUTATIONS PROVIDED THEY ARE ACCOMPANIED BY SUFFICIENT DESCRIPTIVE INFORMATION TO PERMIT <br />THEIR PROPER EVALUATION. SUCH DESCRIPTIVE INFORMATION SHALL BEAR THE IMPRESSED SEAL AND <br />SIGNATURE OF THE DELEGATED ENGINEER AS AN INDICATION THAT HE/SHE HAS ACCEPTED RESPONSIBILITY <br />FOR THE RESULTS. SEPIAS DO NOT REQUIRE SIGNATURE AND SEAL. THE STRUCTURAL ENGINEER WILL RETAIN <br />ONE SIGNED AND SEALED BLUELINE PRINT FOR RECORD. <br />6. DRAWINGS PREPARED SOLELY TO SERVE AS A GUIDE FOR FABRICATION AND INSTALLATION (SUCH AS <br />REINFORCING STEEL SHOP DRAWINGS OR STRUCTURAL STEEL ERECTION DRAWINGS) AND REQUIRING NO <br />ENGINEERING DO NOT REQUIRE THE SEAL OF A DELEGATED ENGINEER, <br />7. CATALOG INFORMATION ON STANDARD PRODUCTS DOES NOT REQUIRE THE SEAL OF A DELEGATED ENGINEER. <br />8. REVIEW BY THE STRUCTURAL ENGINEER OF RECORD OF SUBMITTALS IS LIMITED TO VERIFYING THE FOLLOWING: <br />A. THAT THE SPECIFIED STRUCTURAL SUBMITTALS HAVE BEEN FURNISHED. <br />B. THAT THE STRUCTURAL SUBMITTALS HAVE BEEN SIGNED AND SEALED BY THE DELEGATED ENGINEER. <br />C. THAT THE DELEGATED ENGINEER HAS UNDERSTOOD THE DESIGN INTENT AND HAS USED THE SPECIFIED <br />STRUCTURAL CRITERIA. (NO DETAILED CHECK OF CALCULATIONS WILL BE MADE). <br />D. THAT THE CONFIGURATION SET FORTH IN THE STRUCTURAL SUBMITTALS IS CONSISTENT WITH THE <br />CONTRACT DOCUMENTS. (NO DETAILED CHECK OF DIMENSIONS OR QUANTITIES WILL BE MADE). <br />SUBMITTALS NOT MEETING THE ABOVE CRITERIA WILL NOT BE REVIEWED. <br />ABBREVIATIONS <br />@ = AT <br />E.S.= EACH SIDE <br />OPNG. = OPENING <br />A.B. = ANCHOR BOLT <br />E.W = EACH WAY <br />P.A.F. = POWDER ACTUATED FASTENER <br />ALT. = ALTERNATE <br />EXIST.= EXISTING <br />PART. = PARTITION <br />APPROX. = APPROXIMATELY <br />EXP.= EXPANSION <br />PAR7L. = PARTIAL <br />ARCH. = ARCHITECT <br />EXT.= EXTERIOR <br />PL = PLATE <br />ARCH7L. = ARCHITECTURAL <br />FIN.= FINISH <br />plf = POUNDS PER LINEAR FOOT <br />BAL. = BALANCE <br />FLR.= FLOOR <br />psf = POUNDS PER SQUARE FOOT <br />B.C. = BOTTOM CHORD <br />FDN.= FOUNDATION <br />psi = POUNDS PER SQUARE INCH <br />BLDG. = BUILDING <br />F.S. = FAR SIDE <br />P.T. = POST TENSION OR <br />BM. = BEAM <br />FT. = FOOT <br />PRESSURE TREATED <br />BOTT = BOTTOM <br />FTG. = FOOTING <br />REINF. = REINFORCING <br />BRG. = BEARING <br />GA. = GAGE <br />REQ'D. = REQUIRED <br />CH. = CHANNEL <br />GALV. = GALVANIZED <br />REV. = REVISED/ REVISION <br />C.I.P. = CAST IN PLACE <br />G.C. = GENERAL CONTRACTOR <br />R.O. = ROUGH OPENING <br />C.J. = CONSTRUCTION JOINT <br />HC = HOLLOW CORE <br />SCHED. = SCHEDULE <br />CL = CENTERLINE <br />H,D.G. = HOT DIPPED GALVANIZED <br />SECT. = SECTION <br />CLR. = CLEAR <br />HG = HIP GIRDER <br />SIM. = SIMILAR <br />CMU = CONCRETE MASONRY UNIT <br />HORIZ. = HORIZONTAL <br />SQ. = SQUARE <br />COL. = COLUMN <br />H.P. = HIGH POINT <br />S.J. = CONTRACTION JOINT <br />CONC. = CONCRETE <br />HSS = TUBE STEEL <br />S.M.S. = SHEET METAL SCREW <br />CONFIG. = CONFIGURATION <br />I.J. = ISOLATION JOINT <br />STD. = STANDARD <br />CONT. = CONTINUOUS <br />INFO. = INFORMATION <br />SW = SHEARWALL <br />CONTR. = CONTRACTOR <br />INT. = INTERIOR <br />S.W. = SHORT WAY <br />CONSTR, = CONSTRUCTION <br />JT. = JOINT <br />STL. = STEEL <br />CTR. = CENTER <br />L = ANGLE <br />STRUCT. = STRUCTURAL <br />CVR. = COVER <br />LG. = LONG <br />T.C. = TOP CHORD <br />DBL. = DOUBLE <br />L.W. = LONG WAY <br />T/O = THRU OUT <br />DTL. = DETAIL <br />MFR. = MANUFACTURER <br />T.O. = TOP OF ... <br />DIA. = DIAMETER <br />MAT'L. = MATERIAL <br />T = TOP <br />DIM. = DIMENSION <br />MAX. = MAXIMUM <br />TEMP. = TEMPERATURE <br />DN. = DOWN <br />M.D. = MID -DEPTH <br />TYP. = TYPICAL <br />DWG. = DRAWING <br />M.C.J. = MASONRY CONTROL JOINT <br />U.N.O. = UNLESS NOTED OTHERWISE <br />EA. = EACH <br />MIN. = MINIMUM <br />VERT. = VERTICAL <br />E.E. = EACH END <br />MISC. = MISCELLANEOUS <br />V.S. = VALLEY SET <br />E.F. = EACH FACE <br />N.S. = NEAR SIDE <br />W = WIDE FLANGE <br />E.J. = EXPANSION JOINT <br />N.I.C. = NOT IN CONTRACT <br />w/ = WITH <br />ELEV. / EL. = ELEVATION <br />N.T.S. = NOT TO SCALE <br />WD. = WOOD <br />E.O.R. = ENGINEER ON RECORD <br />O.C. = ON CENTER <br />WP = WORK POINT <br />EQ. = EQUAL <br />O.H, = OPPOSITE HAND <br />W.W.F. = WELDED WIRE FABRIC <br />ASCE 7-10 WIND DESIGN CRITERIA <br />DESIGN PARAMETER <br />SYMBOL <br />VALUE <br />ASCE/SE17-10 <br />REFERENCE <br />RISK CATEGORY <br />- <br />I <br />TABLE 1.5-1 <br />ULTIMATE BASIC WIND SPEED <br />VOLT <br />135 MPH <br />SECTION 26.5 <br />NOMINAL BASIC WIND SPEED <br />VASD <br />104 MPH <br />SECTION 26.5 <br />WIND DIRECTIONALITY FACTOR <br />Kd <br />0.85 <br />TABLE 26.6-1 <br />EXPOSURE CATEGORY <br />- <br />C <br />SECTION 26.7.3 <br />TOPOGRAPHIC FACTOR <br />Kt <br />1.00 <br />SECTION 26.8 <br />_ I v1 a <br />rt KWNI-d "I'.: <br />'"' ., +",'' �„rJr o�, a,5J1 <br />•,„ ,,:i, ,� 3�a ,¢''� <br />r wt p� Y s <br />11 <br />FREE STANDING WALLS & SIGNS <br />- <br />OPEN SECTION 29.4 <br />n�n, <br />FREE STANDING WALLS & SIGNS Cf <br />1.45 <br />FIGURE 29.4-1 <br />r ,_y <br />- ., d. s, n 9PSF <br />FREE STANDING WALLS & SIGNS <br />qh <br />45 <br />CHAPTER <br />ARNOLD AUSTIN <br />rL 66375 <br />AUG 3 0 2019 <br />Al <br />0 <br />o' <br />N p <br />00 <br />0 b <br />bp <br />N <br />o � <br />z �A y N <br />0. t tl <br />.� � <br />W � N p <br />bo m �' <br />U � <br />y U <br />o y <br />W � <br />w <br />W� <br />5904-A Hampton Oaks Pkwy. J <br />Tampa, Florida 33610 1 i <br />Office:813-253-5311 <br />Fax:813-464-7629 ti <br />www.HeidtDesign.com <br />v) <br />Q <br />Z <br />Z <br />F� <br />w <br />Z <br />� <br />0 <br />0 <br />0 <br />w <br />U <br />W <br />Q <br />� <br />I-� <br />Z <br />U <br />M� <br />W <br />w <br />� <br />0-4 <br />0 <br />w <br />n <br />wd <br />CL LLo <br />6810 EBB TIDE AVENUE I APOLLO BEACH, FL 33572 I <br />813.500.7595 I www.austrucgroup.com 1 FL CA#300% <br />This drawing is signed and sealed by the <br />structural engineer for structural <br />requirements only. Architectural, <br />Electrical and Mechanical requirements <br />and design which are incidental to the <br />structural design in these drawings are <br />not included under the Engineer's Seal. <br />Printed copies of this document are not <br />considered signed and sealed unless <br />bearing the engineer's original signature. <br />Lu <br />z <br />W <br />W <br />0 <br />w <br />Z <br />0 <br />w <br />4_ <br />_o <br />U) <br />rn <br />W <br />0 <br />W <br />0 <br />m <br />N <br />N <br />N <br />I.- <br />M <br />0 <br />0 <br />0 <br />0 <br />M <br />N <br />� <br />PROJECT NO: PHC OP 1004 <br />FILE: <br />L-370 <br />DESIGN BY: <br />AFC <br />DRAWN BY: <br />AFC <br />ARNOLD AUSTIN, P.E. <br />DATE: <br />LICENSE NO. 66375 <br />L-374 <br />WZ <br />�� <br />oCi <br />m U H <br />$�a <br />K¢U <br />0Zu; <br />LL <br />Z J r <br />J 3 <br />z <br />,O-/3 U <br />MZ <br />OFEL <br />=o <br />J M2 Z <br />8 O - <br />z�0 <br />mWF- <br />z <br />z�W <br />m� <br />0 <br />S <br />U <br />UW <br />Z in <br />=W <br />F¢Z� <br />W'o <br />pa0 <br />OZO <br />Z W <br />? LU <br />wUC7 <br />W LL Q <br />W WI <br />u�ILZ <br />W <br />E2 J W <br />Z. <br />o� <br />FW. O <br />2 m J <br />�/7 m U <br />oow <br />3 wW <br />U0 <br />�5� <br />x0 <br />a <br />0wW -0 L" <br />0L5D <br />