Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />150A/200A INDOOR <br />PANEL CENTER <br />#14 to lights & outlets <br />#12 to appliances and GFI <br />#10 to WH <br />#8 to Range <br />#6 to HVAC <br />MAIN <br />150=2/0 <br />in 2" Conduit <br />200 amp <br />Y200=410 <br />150 amp <br />UNDERGROUND <br />Disconnect <br />SERVICE BY POWER CO. <br />INTERSYSTEM:;;�� <br />BONDING <br />TERMINATION PER <br />WITH CODE APPROVED <br />NEC 17, 250.94 <br />CLAMP PER 250.50 AND <br />250.52 OF THE 2017 NEC. <br />GENERAL ELECTRICAL NOTES . Typical 150-200 Amp Electrical Riser Diagram REV. 03.09.22 <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE <br />Notes: unless otherwise noted, PROVISIONS OF THE NFPA 70-2017, NATIONAL ELECTRICAL CODES (NEC 2017) LOCAL <br />1 EI CODES AND THE LOCAL POWER/UTILITY COMPANY. <br />ectncal outlet heights as measured from finished floor to center line of the box to be. 16 AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory, <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />I� <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />CL13 <br />THREE-WAY SWITCH <br />4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />I _o <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />FLUORESCENT LIGHT FIXTURE <br />EXHAUST FAN <br />11Q1 <br />EXHAUST FAN/LIGHT COMBINATION <br />�D <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />PB <br />PUSH BUTTON SWITCH (OPTIONAL) <br />De <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />0 <br />TELEVISION (OPTIONAL) <br />�2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />�]M <br />ELECTRIC METER <br />ELECTRIC PANEL <br />DISCONNECT SWITCH <br />l� J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />r <br />OPT. CEILING FAN <br />(1) PHONE LINE, (1) DATA PORT <br />DEDICATED . <br />RECEPTACLE FOR <br />MICROWAVE RANC <br />HOOD PER SPECS <br />1.5" VTR III 3" VTR <br />I� <br />��I I <br />I� I <br />I I <br />I ^ I <br />1 �� 1113" VTR <br />a <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC TO <br />BE VERIFIED WITH PLUMBER <br />ITCHEN <br />ITCH FOR <br />POSAL <br />SPEC 3 & 4 KITCHEN <br />SCALE: Y4'=V-0" <br />A/C PAD <br />DISC. WID <br />GuuFI <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE RANGE <br />HOOD PER SPECS <br />FI y--DB & GFI TO <br />------- ' BE ALIGNED <br />VERTICALLY <br />II <br />1 <br />COACH LIGHTS ", COACH LIGHTS <br />OR PREWIRE AS OR PREWIRE AS <br />PER SPECS , / PER SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />I I I <br />I I I <br />I I I <br />I I I <br />I I I <br />I I <br />I ( <br />I I <br />1 I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />t I <br />I I <br />I I <br />I I <br />1 I <br />I I <br />I I <br />I I <br />I I <br />I I <br />I I <br />L----------------------------------------I <br />SECOND FLOOR ELECTRICAL PLAN <br />FIRST FLOOR ELECTRICAL PLAN - ELEV-B <br />ELEV-B <br />NV <br />O <br />' w <br />-- <br />� aka e✓ <br />d, <br />zt; <br />M <br />NO <br />N <br />0 <br />L <br />,90°'+•!'�,�` \.' \ G s <br />eGj <br />SThTE <br />OF �Cr <br />s e"Il J� <br />� � 2 41%0% <br />To the best of the Engineer's knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential 7th Edition. Engineer's signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineer's signature and seal. <br />N <br />F. <br />Q <br />o M Eo 'Cj <br />'" <br />O N U N <br />co <br />0 <br />Loco (o U� <br />N <br />tp�r V LL w <br />M <br />�rNivCL w g a- <br />J LLB Oj <br />Z <br />Z <br />0 <br />3: <br />@ O O <br />O: <br />W <br />W <br />a N Cp m Q <br />ogle ¢ m <br />W <br />co a'' K w <br />Zto <br />IL <br />N Z Q _ <br />M <br />3 <br />N U U) H <br />O v ❑0❑ <br />Z <br />W <br />z N M <br />0 0 <br />Z O aN <br />N <br />N <br />M <br />(3,)l <br />� <br />0 <br />LL <br />T <br />CL <br />LLJ a <br />U <br />OLL1 <br />—� <br />� <br />0 <br />c <br />V)S:§ <br />U <br />W� <br />Ric <br />I <br />z� <br />2 <br />U <br />c U) <br />m <br />�® <br />o <br />JZ <br />w <br />CJ <br />Cl>a <br />J <br />y ¢ <br />O <br />z <br />Z <br />li <br />zo <br />>m <br />zQ <br />E <br />w� <br />oa <br />F— f0 CU <br />�0 <br />OZ <br />OE <br />CID <br />0¢ <br />a,6 <br />0, <br />Z00 <br />ro <br /><° <br />Qo <br />wZ <br />C <br />a <br />mo <br />o, <br />Z <br />m J <br />U <br />o m <br /><� <br />4 W <br />�Z <br />D <br />o� <br />z o <br />g <br />(J7 <br />� LL <br />rL z <br />o <br />c> <br />� <br />wY <br />;o <br />z <br />zld <br />� 3 <br />`' <br />> CY) <br />J <br />rn <br />m <br />m <br />0 <br />00 <br />co <br />N <br />CN <br />LO <br />10-1-1 <br />Q <br />0 Y <br />o <br />J <br />CV <br />°- <br />m <br />4-1 <br />c6 N <br />m <br />0) <br />N <br />Q <br />LO <br />r <br />oo <br />.. <br />ai <br />�(� <br />� MC0 <br />dN <br />Z <br />CVZE <br />" d <br />C <br />C <br />a <br />0 _j <br />a o <br />JOB <br />NO: <br />23-02469 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />3 <br />