- _1 L__. _. -. <br />GENERAL INSTALLATION NOTES <br />1. Provide full mortar head and bed joints. <br />2. Shore filled lintels as required. <br />3. Installation of lintel must comply with the architectural and/or structural drawings. <br />4. U-Lintels are manufactured with 5-1/2" long notches at the ends to accommodate <br />vertical cell reinforcing and grouting. <br />5. All lintels meet or exceed L/360 vertical deflection, except lintels 17'-4" and <br />longer with a nominal height of 8" meet or exceed L/180. <br />6, Bottom field added rebar to be located at the bottom of the lintel cavity. <br />7. 7/32" diameter wire stirrups are welded to the bottom steel for mechanical anchorage. <br />8. Cast -in -place concrete may be provided In composite lintel in lieu of concrete <br />masonry units. <br />9. Safe load ratings based on rational design analysis per ACI 318 and ACI 530 <br />10. Product Approvals: Miami Dade County, Florida Nos.20-0630.16 and 20-0630.15. <br />11. The exterior surface of lintels installed in exterior concrete masonry walls shall have <br />a coating of stucco applied in accordance with ASTM C-926 or other approved <br />coating. <br />12. Lintels loaded simultaneously with veritcal (gravity and uplift) and horizontal (lateral) <br />loads shoud be checked for combine loading with the following equation: <br />Applied vertical load + Applied horizontal load . O <br />Safe vertical load Safe horizontal load - <br />GENERAL CONCRETE LINTEL SCHEDULE <br />APPROVED LINTEL MANUFACTURERS: CASTE-CRETE, QUALITY, LOTTS <br />ZJIHIJIH�Jlml <br />LIVA LIRA Iml <br />8RF14-1B/1T8RF14-0B/1T 8F16-0B/1T 81716-113/11T Ulu <br />8F441B/1T8F401B/1T 8RF400B/1T 8F321B/1T <br />FORM dt GROUT SOLID <br />o �w <br />O #5 BAR CONT. <br />8F12-1 B/1 T <br />O <br />"V" LINTEL DETAIL <br />SCALE = N.T.S. <br />F = FILLED WITH <br />GROUT / U <br />= UNFILLED <br />R = RECESSED <br />QTY. OF #5 <br />REBAR @ BOTTOM <br />OF LINTEL CAVITY <br />8 F 16- <br />B/ 1 T <br />U <br />a <br />00 <br />tNOMINAL. <br />QUANTITYOF <br />WIDTH <br />#5 REBAR AT <br />TOP <br />NOMINAL - <br />HEIGHT <br />MATERIALS <br />cTf precas irntels = 3500 psi. <br />2. fc prestressed lintels = 6000 psi. <br />3. grouted per ASTM C476 fg = 3000 psi w/ <br />4. maximum 318" aggregate and 8" to 11" slump. <br />5. Concrete masonry units (CMU) per ASTM C90 w/ <br />minimum net area compressive strength = 1900 psi. <br />6. Reber per ASTM A615 Grade 60. <br />Prestressing strand per ASTM A416 grade <br />7. 270 low relaxation. <br />7132 wire per ASTM A510. <br />8. Mortar per ASTM C270 type M or S. <br />#5 REBAR <br />MIN..(1)REQ'D <br />(1) <br />CLEAR <br />ALTERNATE POWERS <br />STEEL LINTEL <br />° <br />G ° ° <br />.M.U. <br />#5 REBAR AT TOP <br />w <br />° ° <br />MIN. (1) REO'D <br />1-1/2" CLEAR <br />2 <br />° <br />° <br />° ° <br />-i <br />Z <br />° <br />G ° <br />GROUT <br />O <br />^ J <br />° <br />5 REBAR AT <br />= N U)) w <br />° <br />BOTTOM OF <br />co Z L <br />W L O <br />o <br />LINTEL CAVITY <br />U)) <br />pUF <br />OTTOM <br />o it p Z <br />REINFORCING <br />< ¢ C7 <br />LL <br />- <br />7-5/8"ACTUAL <br />i.PROVIDED IN <br />LINTEL <br />z 0 n <br />¢ •' O 3 <br />#5 REBAR AT BOTTC <br />8" NOMINAL WIDTH <br />(VARIES) <br />in u��i cr a <br />AS INDICATED <br />LINTEL MINIMUM DEPTHS ARE CALLED OUT ON LINTEL PLAN. IF CONTRACTOR INSTALLS A DEEPER <br />LINTEL THAN INDICATED ON THE PLAN, DOING THIS INCREASES THE STRENGTH OF THE LINTEL AND IS <br />APPROVED WITHOUT ENGINEERING LETTER. IF A SMALLER LINTEL IS INSTALLED CONTACT E.O.R. FOR <br />APPROVAL. (SEE LINTEL PLAN FOR SCHEDULE) <br />16 GAUGE POWERS <br />STEEL BOXED LINTEL <br />POWERS STEEL BOXED LINTEL NOTES (ALT.) <br />ONLY IF NOTED ON LINTEL PLAN <br />1. Refer to manufacturers specifications for installation. <br />2. Contractor to provide proper protection of lintel to prevent rusting <br />Refer to manufacturers specifications. <br />3. If lintel is scratched or damaged refer to Powers Steel for repair. <br />4. Lintel depth to match precast depth. One #5 Bar required at top <br />see lintel plan/details for bottom steel required. <br />5. A bonding agent must be applied to the Steel Box lintels prior to <br />applying the cementitiuos coating. See contractor specifications <br />LINTEL PLAN NOTES: <br />1. THIS PLAN IS TO BE USED FOR STRUCTURAL <br />INFORMATION ONLY. <br />2. UNLESS NOTED OTHERWISE ALL LINTEL DEPTHS ARE <br />TO BE ASSUMED TO BE 16" MINIMUM DEPTH. <br />3. THE NUMBER OF COURSES OF MASONRY REQUIRED <br />BETWEEN THE LINTEL & THE BOND BEAM SHOULD BE <br />COORDINATED WITH THE ELEVATION DRAWINGS <br />4. THE CONTRACTOR IS RESPONSIBLE FOR <br />COORDINATING THE PROPER LINTEL HEIGHT. <br />5. LINTELS AT GARAGE DOOR OPENING ARE MINIMUM <br />DEPTH REQUIRED FOR THE DESIGN LOADS. THE <br />DEPTH MAY BE INCREASED IF REQUIRED FOR <br />PROPER LINTEL HEIGHT,G.C. COORDINATE. <br />POWER STEEL LINTEL IS AN ADEQUATE <br />SUBSTITUTION @ ALL LOCATIONS UNLESS <br />NOTED OTHERWISE AT OPENING LOCATION <br />2x8 #2 SYP STUDS @ 8" O.C. W/ (2) USP OR <br />SIMPSON MSTAM36 STRAPS EACH STUD ((1) <br />STRAPS EACH SIDE) CENTERED W/ (13) 10d <br />NAILS & (8) Y4"x1 J" TAPCONS OR TITENS <br />*CENTER OF STRAP @ T/WALL TYP. U.N.O. <br />2x8 #2 SYP P.T. BASE PLATE <br />W/ Y2" EPDXY ANCHOR OR Yz" <br />J BOLT W/ MIN. 7" EMBEDMENT @ <br />32" O.C. & 6" FROM EACH END <br />STRUCTURAL SHEATHING <br />ATTACHED PER NAILING <br />SCHEDULE <br />OIL SEE PLAN <br />T/VVALL <br />II.1 <br />8" KNOCKOUT COURSE <br />SEE PLAN FOR FILLED CELL <br />SPACING <br />WALL SPLICE DETAIL <br />REVISED: 11/04/19 SCALE: 1" = 1'-0" <br />(D O <br />5'-10" LL 13'-0" LL <br />O <br />8'-0" LL <br />O <br />4'-6" LL <br />O <br />4'-6" LL <br />MIN.B <br />5'-8" LL <br />MIN. E <br />17'-4" LL <br />LINTEL PLAN - ELEV B <br />SCALE: Y4'=1'-O" <br />CV <br />C <br />>N <br />QO <br />a <br />u L :a <br />c M r_.) <br />4) <br />Z2. <br />�C2 W.� <br />E <br />c E <br />o <br />O- U <br />a <br />CM <br />N <br />0 <br />N <br />o_ <br />M <br />.. �� • x., <br />.. <br />ist4V*_•kjia. <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 <br />Florida Building Code - <br />Residential <br />7th Edition. Engineers signature and seal is only for <br />the structural engineering portions of the drawing pages bearing <br />Engineers <br />signature and seal. <br />w o ow <br />'�t o <br />0 <br />? LL LL <br />N `` a w <br />0 <br />a <br />r) - <br />u- LL a U <br />air <br />Zmc <br />z <br />O <br />L Y O o <br />W <br />C c m L ¢ <br />�m <br />„ <br />W <br />M <br />v) � pj Q) r- <br />0 O L <br />N rN,) Z W ~ <br />OIL U ❑❑❑ <br />Z <br />�� ��_)Aa W <br />U mm <br />Z N N) <br />O <br />z m <br />QQ <br />Z o <br />Q <br />:a <br />J <br />7 <br />- N <br />CDl o <br />LL <br />+ <br />(6 <br />Cn <br />w <br />° <br />U <br />O <br />W o <br />U <br />W <br />'g, <br />J <br />_ <br />z� <br />yy <br />ts, <br />� <br />U) <br />N <br />.4 <br />w <br />M <br />¢ <br />z <br />Q <br />U <br />zo <br />o' <br />>� <br />�o <br />o <br />z® <br />ro <br />00 <br />CID <br />°Z <br />Z <br />roC <br /><o <br />wz <br />N <br />M C <br />40 <br />SU <br />m0 <br />Z, <br />Z <br />m� <br />�mQw <br />� <br />of <br />Z Z <br />go <br />W <br />c <br />T } <br />p } <br />aLL <br />a <br /><o <br />az <br />NF <br />S <br />m <br />o� <br />�3 <br />�0 <br />J <br />JW <br />Q <br />0 <br />M <br />W <br />a <br />V <br />zl¢ <br />NO <br />= <br />M <br />J <br />O <br />C <br />m <br />0 <br />N <br />L <br />� <br />co <br />N <br />o <br />LO <br />Cr <br />J <br />N <br />U) m <br />N <br />4- <br />o <br />L0 <br />L <br />M <br />m CN <br />Lo <br />N <br />Q <br />� � <br />CV)O <br />T <br />CD <br />cM <br />o <br />z <br />m <br />Z <br />E N <br />N <br />ID <br />M <br />E <br />0 <br />� ca <br />4) <br />a <br />U � <br />Q p <br />JOB <br />NO: <br />23-02469 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />7 <br />