ELECTRICAL CONSTRUCTION NOTES
<br />1. ALL WORK. SHALL BE 1N ACCORDANCE WITH THE NATIONAL ELECTRICAL
<br />CODE (NEC), LATEST EDITION, AND APPLICABLE STATE AND LOCAL
<br />ORDINANCES, EACH PIECE OF ELECTRICAL EQUIPMENT INSTALLED
<br />SHALL BEAR A U.L. LABEL. ALL WORK SHALL BE PERFORMED IN
<br />COMPLIANCE WITH THE OCCUPATIONAL SAFETY AND HEALTH 'ACT
<br />(OSHA) LATEST EDITION.
<br />2. THE ELECTRICAL CONTRACTOR SHALL ARRANGE AND PAY FOR ALL ,
<br />PERMITS, FEES, INSPECTIONS, ETC., AND CARRY ALL INSURANCE AS
<br />REQUIRED BY LAW PRIOR TO STARTING CONSTRUCTION.
<br />3. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY LABOR.
<br />MATERIALS, TRANSPORTATION, RIGGING, TOOLS, STORAGE, ETC.,
<br />FOR ALL WORK INDICATED AND REQUIRED FOR A COMPLETE
<br />INSTALLATION,
<br />It. THE ELECTRICAL WORK SHALL INCLUDE COMPLETE TESTING OF ALL
<br />EQUIPMENT AND WIRING. WORKMANSHIP SHALL BE OF THE HIGHEST
<br />QUALITY AS ESTABLISHED BY TRADE STANDARDS.
<br />S. ELECTRICAL CONTRACTOR SHALL KEEP A MASTER SET OF BLUE LINES
<br />THAT ARE TO BE MARKED UP TO REFLECT "AS BUILT" CONDITIONS ON
<br />A DAILY BASIS. THESE "AS BUILT" MARK UPS MAY BE REVIEWED BY
<br />TILL•: ARCHITECT, ENGINEER OR OWNER'S REPRESENTATIVE, AT THEIR
<br />REQUEST WITHOUT PRIOR NOTIFICATION. THESE "AS BUILT" MARK
<br />UPS WILL BE REVIEWED BY THE ENGINEER AND TURNED OVER TO THE
<br />OWNER AT THE CONCLUSION OF THE PROJECT.
<br />S. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
<br />C01111UNICAT10N WITH THE LOCAL BUILDING DEPARTMENT AND
<br />INSPECTION PERSONNEL TO REVIEW CONTRACT DOCUMENTS PRIOR TO
<br />INSTALLATION.
<br />7. THE: OWNER WILL NOT BE FIELD LIABLE FOR FIELD CHANGES THAT
<br />ARISE FROM CONTRACTOR ERROR OR OMISSION OF MATERIALS OR
<br />WDIRKHANSH I P 1 N WORK PERFORMANCE.
<br />B. THE ELECTRICAL CONTRACTOR SHALL 11AKE ALL NECESSARY
<br />ARRANGEMENTS WITH THE LOCAL POWER COMPANY FOR SERVICE AND
<br />SHALL BE RESPONSIBLE FOR VERIFICATION OF ALL UTILITIES AND
<br />THE PLACEMENT LOCATION OF TILE ELECTRICAL SERVICE AND
<br />EQUIPMENT. THE ELECTRICAL CONTRACTOR SHALL PAY ALL
<br />NECESSARY CHARGES TO THE POWER COMPANY PRIOR TO
<br />CONSTRUCTION.
<br />S. ALL ELECTRICAL EQUIPMENT, MATERIALS, AND WORKMANSHIP SHALL
<br />BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF
<br />ACCEPTANCE.
<br />10. IN GENERAL, PLANS AND DIAGRAMS ARE SCHEMATIC ONLY, AND
<br />SHOULD NOT BE SCALED. COORDINATE ALL ELECTRICAL WORK WITH
<br />OTIIER TRADES, (PLUMBING, HVAC, ETC.) SO AS NOT TO CONFLICT
<br />IN LOCATION OR PERFORMANCE OF OTHER SYSTEMS.
<br />11. NECESSARY, OBVIOUSLY REQUIRED ELECTRICAL ITEMS THAT ARE NOT
<br />SHOWN ON THE DRAWINGS, DOES NOT RELIEVE THE CONTRACTOR OF
<br />HIS RESPONSIBILITY TO INSTALL A COMPLETE AND SAFE ELECTRICAL
<br />SYSTEM.
<br />12. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH OTHER TRADES
<br />SO THAT INTERFERENCES BETWEEN CONDUITS, RACEWAYS, DUCTS,
<br />PIPING A140 STRUCTURAL MEMBERS WILL BE AVOIDED.
<br />13. THE ELECTRICAL COITRACTOR SHALL FURNISH, INSTALL AND CONNECT
<br />ALL WIRING IN ACCORDANCE WITH TILE WIRING DIAGRAMS FOR POWER AND CONTROL OF ALL AIR CONDITIONING, HEATING AND VENTILATING
<br />i EUU 1 PIIENT AS PROV 10EO BY THE IIVAC CONTRACTOR.
<br />14. WIRE AND CABLE SHALL BE 600 VOLT MINIMUM AWG #12. ALL
<br />WIRING SHALL BE TYPE TW, THN OR THEN AS NECESSARY TO MEET
<br />ALL APPLICABLE CODES.
<br />IS. ALL WIRE AND CABLE SHALL BE IN CONDUIT, MINIMUM SIZE 1/2"
<br />WITH LARGER SIZES AS INDICATE❑ OR REQUIRED BY NEC. ALL
<br />SERVICE AND PANELBOARD FEEDER CONDUITS, CONDUITS IN OR BELOW
<br />FLOOR. IN DAMP AND WET LOCATIONS, IN CONCRETE AND LARGER
<br />THAN Two 114CIIES SHALL BE RIGID GALVANIZED STEEL,
<br />ALL CONDUCTORS, UNLESS -OTHERWISE NOTED, SHALL BE COPPER RUN
<br />IN Ai'PROVEO METAL RACEWAY. METAL RACEWAY PENETRATING FLOORS
<br />AND F'IR.E RATED PARTITIONS SHALL BE SEALED AIR TIGHT WITH
<br />MATERIAL RATED EQUAL TO THE PENETRATED MATERIAL.
<br />FURNISH AND INSTALL ALL BRANCH CIRCUITS. CIRCUITS SHALL BE
<br />#12 WIRE IN 1/2" CONDUIT UNLESS OTHERWISE NOTED. THESE ARE
<br />11 I N I1'IUN WIRE AND CONDUIT SIZES. ALL WIRE SHALL BE COPPER.
<br />NO ALUMINUM CONDUCTORS WILL BE PERMITTED,
<br />16. ALI. NEW RACEWAYS/CONDUITS SHALL BE METALLIC MINIMUM SIZE
<br />1/2"; SUPPORTED AT INTERVALS NOT TO EXCEED EIGHT (B) FEET; ALL FITTINGS SHALL BE COMPRESSION TYPE, NO SET -SCREW TYPE FIrT INGS WILL BE PERMITTED.
<br />17. IN NO CASE 11AY E11T OR FLEXIBLE CONDUIT BE RUN FROM FIXTURE
<br />TO FIXTURE WITHOUT THE USE OF OUTLET BOXES.
<br />1B. FLEXIBLE CONDUIT CAN ONLY BE USED FOR SHORT (MAXIMUM SIX
<br />FEET) FINAL CONNECTIONS TO INTERIOR LIGHTING FIXTURES AND
<br />EQU I PTIENT .
<br />19. TILE ELECTRICAL CONTRACTOR SHALL FbLLOW THE SAME COLOR CODE
<br />IDENTIFICATION FOR EACH PHASE THROUGHOUT THE SYSTEM FROM
<br />SERVICE SWITCH OR* TRANSFORMER THROUGH ALL BRANCH CIRCUITS.
<br />20. ALI. SLAB OR ROOF PENETRATIONS SHALL DE WITH APPROVED FIRE
<br />RATED AND SMOKE BARRIER FITTINGS. PROVIDE ACCESSORIES
<br />(PITCH POCKETS, CONCRETE, ETC.) AS REQUIRED,
<br />21. AL.I. cONDUITfi SHALL DE RUN CONCEALED WHERE POSSIBLE. EXPOSED
<br />CONDUITS SHALL BE RUN PARALLEL AND/OR PERPENDICULAR TO
<br />BUILDING CONSTRUCTION.
<br />22. CONDUIT MAY NOT BE RUN IN DUCTWORK.
<br />23. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL A 3/4"
<br />EMPTY CONDUIT FROM EACH TELEPHONE OUTLET TO THE OWNER'S
<br />TELEPHONE BOARD, WITH PULL.WIRE. PROVIDE ALL REQUIRED
<br />CONDUIT F•ROII OWNER'S TELEPHONE BOARD TO BUILDING'S TELEPHONE
<br />ROOM, PROVIDE PULL BOXES AND PULL WIRE AS REQUIRED. VERIFY
<br />EXACT LOCATION OF EXISTING TELEPHONE SERVICE AND CONDUITS.
<br />COORDINATE ALL WORK WITH OTHER TRADES AND TELEPHONE COMPANY.
<br />21. THE ELECTRICAL CONTRACTOR SHALL PROVIDE AND INSTALL ALL
<br />CONDUIT, BOXES, FITTINGS, PULL WIRE, ETC., REQUIRED FOR ALL
<br />MISCELLANEOUS SYSTEMS PER OWNER'S REQUIREMENTS. COORDINATE
<br />EXACT LOCATIONS AND REQUIRE11ENTS WITH OWNER.
<br />25. ALL COMMUNICATION AND CONTROL WIRING SHALL BE IN CONDUIT.
<br />26. FURNISH AND INSTALL PANEL BOARDS OF AMPACITIES SHOWN ON
<br />PLANS. PANELS SHALL BE CIRCUIT BREAKER TYPE, WITH MAIN LUGS
<br />ANLI BRANCH CIRCUIT BREAKERS AS SCHEDULED. ALL ELECTRICAL
<br />PANELS AND EQU-IPMENT SHALL BE U.L. LISTED AND APPROVED FOR
<br />SUCH USE. PANELS SHALL BE SOLT-ON TYPE AS MANUFACTURED BY
<br />SQUARE 0 OR APPROVED EQUALr
<br />27. ALL EQUIPMENT SHALL BE PROPERLY GROUNDED IN ALL RACEWAYS,
<br />BRANCH CIRCUITS & FEEDERS, PER LOCAL ELECTRICAL CODES AND
<br />THE NEC.
<br />20. THE ELECTRICAL CONTRACTOR SHALL COORDINATE ALL RECEPTACLE
<br />AND OUTLET LOCATIONS WITH ARCHITECTURAL DRAWINGS AND GENERAL
<br />CONTRACTOR BEFORE ROUGH IN.
<br />29. ALL LIGHTING FIXTURE5 SHALL BE SELECTED BY THE OWNER AND
<br />INSTALLED BY THE ELECTRICAL CONTRACTOR2. ' (LIGHTING FIXTURES
<br />INDICATED ON DRAWINGS AND SCHEDULES ARE FOR REFERENCE ONLY.
<br />FIXTURES OF EQUAL QUALITY MAY BE USED AS DIRECTED.)
<br />30. ALL TEMPORARY ELECTRICAL SERVICE REQUIRED FOR CONSTRUCTION
<br />SHALL BE FURNISHED BY THE ELECTRICAL CONTRACTOR. FOLLOWING
<br />CONSTRUCTION, ALL TEMPORARY WIRING AND EQUIPMENT SHALL BE
<br />REHOVED W1lEN DIRECTED BY THE GENERAL CONTRACTOR. ELECTRIC
<br />OUTLETS CORDS, LIGHTS, LIGHTING LEVELS, ETC., SHALL
<br />CONFORM TO 0.5.H.A. AND LOCAL ORDINANCES.
<br />31. ALL ELECTRICAL EQUIPMENT EXPOSED TO WEATHER SHALL BE
<br />WEATIIERPROOF AND ALL CONDUIT EXPOSED TO WEATHER SHALL -BE
<br />HEAVY WALL GALVANIZED STEEL.
<br />32. SUBIIIT SIX COMPLETE COPIES OF SHOP DRAWINGS AND PRODUCT DATA
<br />FOR L•IGF(TING.FIXTURES, ELECTRICAL PANELS, SERVICE EQUIPMENT,
<br />WIRING DEVICES AND DISCONNECT SWITCHES.
<br />I I 11 -L-_ 1
<br />2x 4F 1::.4`(= I R. _ FLUOi2E:vC]Elf�IT �OFF�-F[Xi`(:1:12ES
<br />W ITH ACRYLIC PRISMATIC IDIFFU5F�46 ; NUMeEIZ
<br />LIAleKEb ON FIXTURE: INDICA7E:S QUAh1TiTY 0F: -
<br />LAMI°15 SEE DE'fA I LS - T`(f I CAL)
<br />ELECTRICAL. LEGEND
<br />®
<br />21X41 FLUORESCENT LIGHTING FIXTURE -"A" DENOTES TYPE
<br />®
<br />iX21 FLUORESCENT LIGHTING FIXTURE
<br />a
<br />WALL MOAJNTED LIGHTING FIXTURE -"A" DENOTES 1%PE
<br />e
<br />EXIT LIGHTING SIGN WITN AFt4ROW5 AS PlERUIIZED
<br />JQ
<br />JUNCTION BOX
<br />G'}I
<br />'DISCONNECT SWITCH - 51ZE AND 'TYPE AS NOTED
<br />DUPLEX RECEPTACLE-20A.-125V. WITH GROURD
<br />GFI
<br />DUPLEX RECEPTACLE WEATHERPROOF/GROUND FAULT INTER.
<br />-►F-
<br />CONDUIT -CONCEALED IN WALL OR CEILING
<br />HOMERUN TO PANELBOARD
<br />n/ww
<br />FLEXIBLE CONDUIT
<br />■r
<br />PANELBOARD
<br />SINGLE POLE SWITCH
<br />AHU
<br />AIR HANDLER UNIT
<br />CU
<br />CONDENSING UNIT
<br />T
<br />TELEPHONE OUTLET
<br />$3,
<br />THREE WAY SWITCH
<br />O�
<br />ELECTRIC SERVICE METER
<br />BATTERY PACK EMERGENCY LIGHT
<br />CEILING MOUNTED LIGHTIRC; FIXTURE - "A" MNOTE5
<br />bINciLE KECEpTACL,E - W A.-125 V. WITH GROUND
<br />SPECIAL PURPOSE- RECEPTACLE - VERIFY `T` I-P-
<br />pUPLEX FECEPTAGLE - FLOOR. MOUNTED
<br />QIaADRAPI-EX Rp_CC-rTACLE - 20 A. - 125 V.
<br />v
<br />VAR "LE SPEW FAt CORTWL SW IYCN
<br />D
<br />DIMMER SW ITCH - SIZE AS Xr_iQLXI REo
<br />?CACT 87YLES + TrPr--S OF . M I5C. LIC�HTINC, 21-811 WIDE D12gp� SOFFITS -
<br />�IXT(lRE:9 SHALL �3E AS SEL�GTEd >3Y oWN- bowN To 8 -�, ,g.FF o�/Et2 CouN
<br />TER
<br />SHALL e�. pteov l aEb I NS`r,4L.LEt� SY `1'EIQS IN i2E El°T10N AREA +
<br />000771 C7O R ( FIELD COOIep I MATE - Trr I CAL) MU RS E STATION OF METAL STl.l.a�
<br />@ IG11 O.C. W iT14 1/211 CgYIo l30A8,D
<br />_ - ATTACH Eli 70 STEEL.. EAR J O1 vTS
<br />- (FI EL0 WOR001 HATE - TYr I CAL)
<br />__ LIGHTI N
<br />LOO-k LAN 4M.
<br />' I
<br />LINE 12WAC,601-lz
<br />WATTSTOPPE I DW-100 DUAL
<br />TECHNOLOGY WALLSENSOR
<br />WALL rouwrsD occurMaY sENsae wMna oIII oMA"
<br />MINIMUMG01�17UGTOR SIZES
<br />i XNT RATING
<br />CURRENT CARRYINS
<br />AW t�UTRAL CONDUCTOR
<br />bROUND CONDUCTOR
<br />NIK" CONDUIT
<br />W+6
<br />3W+6
<br />2"
<br />MPS
<br />012
<br />*12
<br />0.15P
<br />DSO"OSO8
<br />MPS
<br />010
<br />010
<br />0.15"
<br />050"
<br />050"
<br />"wj
<br />*b
<br />*10
<br />i"
<br />0.'155
<br />MPS
<br />46
<br />*10
<br />10,
<br />0.-15"
<br />51 - 60 AMPS
<br />*6
<br />*10
<br />1.25"
<br />IN
<br />61 - 10 AMPS
<br />04
<br />*8
<br />1..W
<br />IN
<br />11 - 60 AMPS
<br />*4
<br />*9
<br />1.25"
<br />IN
<br />81. - 40 AMP5
<br />*3
<br />#6
<br />1,25Y
<br />1,25"
<br />41 - 100 AMPS
<br />*3
<br />*9
<br />1.23"
<br />1.254
<br />1��T IcoppER, ,MANGE WI -E STMIOTH RIN S %TED�OMIAGL�NOTE5� FOR
<br />ADDITIONAL. CONDUIT AND WIRE INSULATION REGKIIREMENTSE .
<br />i
<br />trots.
<br />8UP rORT ORE6 SMALL DE
<br />INSTALLED NOT To EXcEED
<br />45, N OPPOSNG. DIRECTIONS.
<br />!1F'rORT PROM FIXTURE 90DY
<br />4tTAX
<br />4t -' •
<br />(NOT R' OAR SYSTEM! TO
<br />\/
<br />STFILMRE POUR TIE ONES
<br />\
<br />/
<br />PER FIXtIIRE.
<br />\
<br />/
<br />\
<br />/
<br />T-OAR5
<br />C40NCFWM ROM AD R O.
<br />MANS FIXTUFWI6 WITH
<br />POUR TIE ORE& TO
<br />EYE DOLTS N SLAM -
<br />NDEPENDENTLY OmP
<br />FIXUSaE.
<br />LAY-1 12ILN6 .
<br />WA
<br />OPEN WEO STEEL JOIST
<br />�- - MANG FIXTWE6 WITN
<br />POUR TO WIRE6 TO
<br />JOIST.
<br />7X4 LAY -IN FIXTURE
<br />1.14Y-IN FIXTURE
<br />R-EVISIONS my
<br />k
<br />
|