SWIMMING POOL
<br />EQUIPMENT AREA
<br />(SEE DETAILS)
<br />DECK NOTES:
<br />1. DECK SHALL HAVE A SMOOTH, SLIP RESISTANT FINISH.
<br />2. DECK SHALL HAVE NO PITTING OR CREVICES MORE
<br />THAN 3/16" DEEP.
<br />3. IF SETTLING OR WEATHERING OF THE DECK OCCURS
<br />THAT WOULD CAUSE STANDING WATER, THE ORIGINAL
<br />SLOPES SHALL BE RESTORED OR CORRECTIVE DRAINS
<br />INSTALLED.
<br />4. DECK AREAS SHALL UNIFORMLY SLOPE 2% AWAY FROM
<br />POOL TOWARD DRAINS OR PERVIOUS AREA (EXCEPT AS
<br />NOTED IN ZERO ENTRY AREAS, IF APPLICABLE).
<br />5. IF A CURB IS PROVIDED, DECK MUST BE LESS THAN
<br />10" FROM TOP OF CURB.
<br />6. POOL DECK SHALL HAVE MINIMUM 4 FEET OF
<br />UNOBSTRUCTED WIDTH AROUND PERIMETER OF POOL,
<br />HANDRAIL AND LADDER ANCHORS, AND SLIDES.
<br />7. TRAFFIC BARRIERS ARE REQUIRED TO PREVENT
<br />OBSTRUCTION OF DECK BY VEHICLES (WHERE
<br />APPLICABLE).
<br />8. HOSE BIBB WITH VACUUM BREAKER SHALL BE PROVIDED
<br />TO WASH DECK WITH POTABLE WATER.
<br />9. THE VERTICAL CLEARANCE ABOVE THE POOL DECK
<br />SHALL BE AT LEAST 7 FEET.
<br />THIS PLAN REMAINS THE PROPERTY OF AQUATIC
<br />CONSULTING ENGINEERS, INC. (ACE), AND IS NOT
<br />TRANSFERABLE FROM ONE CONTRACTOR TO
<br />ANOTHER WITHOUT WRITTEN PERMISSION OF ACE.
<br />THE ENGINEER STRONGLY REQUIRES CONTRACTOR
<br />BUILD FROM PLANS AS APPROVED BY "HE LOCAL
<br />BUILDING DEPARTMENT AND THE FLORIDA
<br />DEPARTMENT OF HEALTH. ACE IS NOT
<br />RESPONSIBLE FOR CONSTRUCTION ERRORS OR
<br />OMISSIONS RESULTING FROM FAILURE TO COMPLY
<br />WITH THIS REQUIREMENT.
<br />POOL WET DECKS SHALL BE
<br />UNIFORMLY SLOPED 2% AWAY FROM
<br />THE POOL(S) OR TO DECK DRAINS
<br />TO PREVENT STANDING WATER.
<br />(DECK DRAINS BY OTHERS)
<br />TO POOL
<br />ELECTRIC PANEL
<br />W/ TIMER FORS
<br />LIGHTS
<br />(BY OTHERS)
<br />J-BOX &
<br />LOW VOLTAGE
<br />TRANSFORMER
<br />FOR LOW
<br />VOLTAGE
<br />POOL LIGHTS
<br />SHOWER AND HOSE BIBB WITH
<br />APPROVED BACKFLOW PREVENTER
<br />INSTALL WITHIN
<br />THE CONFINES OF APPROVED
<br />POOL BARRIER
<br />1" RIG!D PVC
<br />CONDUIT W/
<br />PRE-WIREC POOL
<br />LIGHT CORD
<br />(BY OTHERS)
<br />POOL SAFETY SWIMMING POOL RULES
<br />EQUIPMENT
<br />_ (MOUNT IN A SIGN W/SUNSHELF RULES
<br />CONSPICUOUS AND (SEE REQUIREMENTS -
<br />READILY BY OTHERS)
<br />ACCESSIBLE
<br />LOCATION ALONG
<br />LONGER SIDES OF
<br />PLANTER EACH POOL) 11'
<br />(BY OTHERS) (TYPICAL OF 2)
<br />7.
<br />�e
<br />..
<br />4'-2" j O
<br />i
<br />/
<br />4 •
<br />I,
<br />38'-7" I. PROPOSE
<br />�. .� COMMERCI
<br />SWIMMING F
<br />DECK LEVEL
<br />PLANTER (FLUSH) 4'-5" J
<br />(TYP., BY OTHERS)
<br />1" RIGID PVC CONDUIT
<br />W/ PRE -WIRED POOL
<br />LIGHT CORD (BY
<br />OTHERS)
<br />Tiff
<br />PLANTER
<br />(BY OTHERS)
<br />13'-3"
<br />OBSTRUCTED
<br />POOL PERIMETER
<br />PERMANENT
<br />"NO ENTRY"
<br />SIGNS OR
<br />MARKERS
<br />SHALL BE
<br />INSTALLED
<br />TO
<br />DISCOURAGE
<br />PATRON
<br />? ACCESS
<br />SWIMMING POOL RULES
<br />SIGN W/SUNSHELF RULES
<br />(SEE REQUIREMENTS -
<br />BY OTHERS)
<br />(VERIFY LOCATION IN FIELD)
<br />NOTE:
<br />EQUIPMENT AREA SHALL BE
<br />ILLUMINATED WITH 30 FC MIN.
<br />ILLUMINATION AT FLOOR LEVEL.
<br />--_ --- m
<br />i
<br />ii
<br />I
<br />I
<br />I
<br />i
<br />PLANTER m
<br />(BY OTHERS)
<br />i
<br />I
<br />l � �
<br />I r 4'- 3
<br />m
<br />© � m
<br />I-T-
<br />13'- 3"
<br />OBSTRUCTED
<br />POOL PERIMETER
<br />F-4 ,
<br />DECK LEVEL
<br />---PLANTER (FLUSH)
<br />(TYP., BY OTHERS) ,
<br />ALL DOORS,
<br />WINDOWS, AND GATES
<br />AREA PLAN LEADING TO POOL
<br />NORTH DECK SHALL MEET
<br />SCALE: 3/32'p = 1 -0" FBC POOL BARRIER
<br />REQUIREMENTS
<br />LANDSCAPE IRRIGATION WATER REQUIREMENTS: NOTE:
<br />FOOD OR DRINK SERVICE
<br />LANDSCAPE IRRIGATION WATER THAT WETS THE WET DECK AREA OF THE POOL, THE POOL ITSELF, ENTERS FACILITIES SHALL NOT BE
<br />THE COLLECTOR TANK, OR WETS AN INTERACTIVE WATER FEATURE MUST BE POTABLE WATER FROM A LOCATED WITHIN 12 FEET
<br />PUBLIC WATER SYSTEM OR SHALL MEET THE BACTERIOLOGICAL QUALITY OF POTABLE WATER AS EVIDENCED (3,658 MM) OF THE
<br />BY ANNUAL LABORATORY ANALYSIS SUBMITTED TO THE DEPARTMENT OF HEALTH. RECLAIMED WATER MAY WATER'S EDGE.
<br />NOT BE USED IN THESE AREAS. IF RECLAIMED WATER IS USED IN THE VICINITY OF THE POOL (INSIDE OF
<br />THE POOL FENCE WITHIN 100 FEET OF THE POOL WATER'S EDGE) IT MUST EMPLOY DRIP IRRIGATION OR
<br />SOAKER HOSES. SIGNS SHALL BE POSTED NOTIFYING POOL PATRONS THAT RECLAIMED WATER IS IN USE,
<br />AND IS NOT TO BE CONSUMED.
<br />NOTE: NOTE:
<br />PROVIDE CONTINUOUS 4 FEET WIDE EXCESS FILL SHALL
<br />CLEAR WET DECK AROUND ENTIRE BE HAULED
<br />SWIMMING POOL PERIMETER. OFFSITE.
<br />NOTE:
<br />(2) WP 125V, 15A OR 20A GFCI RECEPTACLE
<br />ON A GENERAL PURPOSE CIRCUIT SHALL BE
<br />LOCATED AT OPPOSITE ENDS OF EACH POOL,
<br />BETWEEN 6' MIN. TO 20' MAX. FROM WATER
<br />AND MOUNTED NOT LESS THAN 8" ABOVE
<br />MAX. WATER LEVEL OR 4" ABOVE POOL DECK
<br />(WHICHEVER IS GREATER) AND NOT MORE
<br />THAN 6'-6" ABOVE POOL DECK TO
<br />FACILITATE POOL MAINTENANCE (BY OTHERS)
<br />THESE PLANS ARE RELEVANT TO THE
<br />POOL & POOL EQUIPMENT ONLY.
<br />RESTROOM INFORMATION IS SHOWN FOR
<br />REFERENCE PURPOSES ONLY.
<br />RESTROOM CONSTRUCTION IS BY
<br />OTHERS UNDER SEPARATE PERMIT.
<br />POOL DECK, FENCING, GATES &
<br />LANDSCAPING IS BY OTHERS UNDER
<br />SEPARATE PERMIT.
<br />NOTE:
<br />NO HIGH VOLTAGE ELECTRIC (>12V)
<br />PERMITTED WITHIN 5' OF POOL WATER -
<br />ELECTRIC OVER 12V AND LESS THAN 10'
<br />FROM POOL (WHILE STILL AT LEAST 5'
<br />FROM POOL WATER) MUST BE GFCI
<br />PROTECTED
<br />BARRIER NOTES:
<br />1. FENCE AND GATES UNDER SEPARATE PERMIT BY OTHERS- ONLY SHOWN ON
<br />PLANS FOR REFERENCE PURPOSES.
<br />2. ACCESS THROUGH THE FENCE FROM DWELLING UNITS SHALL BE VIA MINIMUM
<br />48" HIGH SELF -CLOSING, SELF -LATCHING LOCKABLE GATES. OPERABLE PARTS
<br />USED FOR OPENING DOORS AT THESE ACCESS POINTS SHALL BE 45 INCHES
<br />(1143 MM) MINIMUM TO 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH
<br />FLOOR OR GROUND.
<br />3. DOORED ACCESS FROM PUBLIC ROOMS NEED NOT BE THROUGH GATE, IF THE
<br />DOORS MEET THE SAME SELF -CLOSING, SELF -LATCHING REQUIREMENTS AS A
<br />GATE.
<br />4. PERMANENT NATURAL OR MANMADE FEATURES SUCH AS BULKHEADS, CANALS,
<br />LAKES, NAVIGABLE WATERWAYS, ETC. ADJACENT TO A POOL MAY BE PERMITTED
<br />AS A BARRIER WHEN APPROVED.
<br />5. A LATCHED, LOCKABLE GATE SHALL BE PLACED IN THE FENCE WITHIN 10 FEET
<br />OF THE CLOSEST POINT BETWEEN THE POOL AND THE EQUIPMENT AREA FOR
<br />SERVICE ACCESS.
<br />NIGHT SWIMMING REQUIREMENTS:
<br />THESE POOLS ARE NOT DESIGNED OR INTENDED FOR NIGHT SWIMMING.
<br />IN ORDER FOR NIGHT SWIMMING TO BE AUTHORIZED, THE FOLLOWING MUST BE DONE:
<br />1. OVERHEAD LIGHTING IN ACCORDANCE WITH FBC 454.1.4.2.1 MUST BE INSTALLED.
<br />2. THE LIGHTING MUST BE CERTIFIED BY A FLORIDA REGISTERED ENGINEER.
<br />3. HEALTH DEPARTMENT APPROVAL MUST BE OBTAINED.
<br />NOTE:
<br />ALL FINISHES SHOWN ON THESE DRAWINGS ARE GENERIC. ALL FINISH
<br />MATERIALS (INCLUDING, BUT NOT LIMITED TO, ADHESIVES, GROUTS,
<br />AND BONDING AGENTS) SHALL BE MANUFACTURER SPECIFIED AS
<br />SUITABLE FOR USE IN POOL/SPA APPLICATIONS.
<br />ALL MATERIAL INSTALLATIONS SHALL COMPLY WITH FBC, ALL
<br />RELEVANT INDUSTRY STANDARDS, AND ALL MANUFACTURER
<br />INSTRUCTIONS AND SPECIFICATIONS.
<br />ALL MATERIALS AND FINISHES USED ON HORIZONTAL SURFACES
<br />SHALL BE SLIP RESISTANT WHEN WET.
<br />TE:
<br />ESE PLANS DO NOT INCLUDE ALL TECHNICAL
<br />ECIFICATIONS REQUIRED FOR CONSTRUCTION. LICENSED
<br />NTRACTOR SHALL REFERENCE ALL MANUFACTURER
<br />;TRUCTIONS AND SPECIFICATIONS.
<br />m
<br />0 0
<br />0
<br />TO POOL
<br />ELECTRIC PANEL
<br />W/ TIMER FOR
<br />LIGHTS
<br />(BY OTHERS)
<br />J-BOX &
<br />LOW VOLTAGE
<br />TRANSFORMER
<br />FOR LOW
<br />VOLTAGE
<br />POOL LIGHTS
<br />. o ❑ ❑
<br />POOL SHALL BE ENCLOSED BY A
<br />MIN. 48" HIGH FENCE AND THE
<br />BUILDING WITH SELF -CLOSING,
<br />SELF -LATCHING LOCKABLE GATES
<br />OPENING AWAY FROM POOL.
<br />GATE LATCHES SHALL BE 54"
<br />ABOVE BOTTOM OF GATE OR
<br />MINIMUM 3" BELOW THE TOP OF
<br />GATE ON POOL SIDE. BARRIER
<br />SHALL NOT ALLOW PASSAGE OF
<br />4" DIAMETER SPHERE. LOCKS, IF
<br />SELF-LOCKING, MAY BE 34"
<br />MINIMUM AND 48" MAXIMUM
<br />ABOVE THE FINISHED FLOOR OR
<br />GROUND.
<br />!FDoH POOL NOTES INDEX:
<br />1. POOL LAYOUT NOTES - SEE SHEET 3
<br />2. RESTROOM NOTES - SEE SHEET 2
<br />3. EQUIPMENT ROOM/ENCLOSURE NOTES - SEE SHEET 6
<br />4. FOUNDATION NOTE - SEE SHEET 9
<br />5. CONCRETE & REINFORCEMENT NOTE - SEE SHEET 9
<br />6. MISCELLANEOUS NOTES - SEE SHEET 2
<br />7. DECK NOTES - SEE SHEET 1
<br />8. BARRIER NOTES - SEE SHEET 1
<br />9. LANDSCAPE IRRIGATION WATER NOTES - SEE SHEET 1
<br />10. NIGHT SWIMMING REQUIREMENTS - SEE SHEET 1
<br />10.1. NOTE: POOL NOT DESIGNED FOR NIGHT SWIMMING
<br />11. POOL EQUIPMENT NOTES - SEE SHEETS 10
<br />12. AMERICANS W/ DISABILITIES ACT NOTE - SEE SHEET 2
<br />454.1.4.2 LIGHTING.
<br />ARTIFICIAL LIGHTING SHALL BE PROVIDED AT ALL SWIMMING POOLS WHICH ARE TO BE USED AT NIGHT OR WHICH DO
<br />NOT HAVE ADEQUATE NATURAL LIGHTING SO THAT ALL PORTIONS OF THE POOL, INCLUDING THE BOTTOM, MAY BE
<br />READILY SEEN WITHOUT GLARE.
<br />454.1.4.2.1 OUTDOOR POOL LIGHTING.
<br />LIGHTING SHALL PROVIDE A MINIMUM OF 3 FOOTCANDLES (30 LUX) OF ILLUMINATION AT THE POOL WATER SURFACE
<br />AND THE POOL WET DECK SURFACE. UNDERWATER LIGHTING SHALL BE A MINIMUM OF 1 /2 WATT INCANDESCENT
<br />EQUIVALENT, OR 10 LUMENS, PER SQUARE FOOT OF POOL WATER SURFACE AREA.
<br />454.1.4.2.3 UNDERWATER LIGHTING.
<br />UNDERWATER LUMINAIRES SHALL COMPLY WITH CHAPTER 27 OF THE FLORIDA BUILDING CODE, BUILDING. THE LOCATION
<br />OF THE UNDERWATER LUMINAIRES SHALL BE SUCH THAT THE UNDERWATER ILLUMINATION IS AS UNIFORM AS POSSIBLE.
<br />UNDERWATER LIGHTING REQUIREMENTS CAN BE WAIVED WHEN THE OVERHEAD LIGHTING PROVIDES AT LEAST 15
<br />FOOTCANDLES (150 LUX) OF ILLUMINATION AT THE POOL WATER SURFACE AND POOL WET DECK SURFACE.
<br />454.1.4.2.5VOLTAGE LIMITATION.
<br />UNDERWATER LIGHTING, OR LIGHTING THAT MAY BE EXPOSED TO NOZZLEDIRECTED POOL WATER, SHALL NOT EXCEED 30
<br />VOLTS DC OR 15 VOLTS AC. SUCH LIGHTS SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION
<br />INSTRUCTIONS AND BE LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY.
<br />David
<br />Faerman
<br />PoE
<br />Digitally signed -q
<br />by
<br />David �
<br />Faerman, RE
<br />Date: 2023.01.13
<br />16:23:44-05'00'
<br />ALL WORK SHALL COMPLY WITH PREVAIL
<br />CODES FLORIDA BUILDING CODE,
<br />NATIONAL ELECTRIC CODE,
<br />AND THE CITY OF ZEPHYRHILLS
<br />ORDINANCES
<br />IN -GROUND
<br />AYB 2
<br />COMMERCIAL SWIMMING
<br />POOL'ITYOF®ATE
<br />�� ZEPN��WI
<br />DESIGN DATA
<br />FINER
<br />NUMBER OF LIVING UNITS
<br />252
<br />LODGING STATUS
<br />NON -TRANSIENT
<br />NOMINAL DIMENSIONS
<br />go,-O" X 61'-9"
<br />PERIMETER
<br />260 L.F.
<br />MINIMUM REQUIRED POOL AREA*
<br />728 S.F.
<br />DESIGN SURF/\CE AREA (SWIMMING POOL)
<br />2,495 S.F.
<br />DEPTH
<br />0'-0" TO 5'-0" TO 3'-6-
<br />VOLUME
<br />56,685 GALLONS
<br />DESIGN RECIRC. FLOW RATE
<br />260 GPM
<br />DESIGN TURNOVER TIME
<br />3.6 HOURS
<br />MINIMUM TOTAL FACILITY BATHING LOAD*
<br />36 BATHERS
<br />DESIGN DATH NG LOAD (SWIMMING POOL)
<br />52 BATHERS
<br />*MINIMUM WATER SURFACE AREA AND BATHING LOAD CAPACITY SUFFICIENT TO SUPPORT 252 NON -TRANSIENT LIVING
<br />UNITS
<br />NOTE:
<br />TOTAL OBSTRUCTED PERIMETER = 26.5 L.F. (10.2%)
<br />MAXIMUM INDIVIDUAL OBSTRUCTION LENGTH = 13.2 L.F. (5.1%)
<br />UP TO TWENTY PERCENT CF THE DECK ALONG THE POOL PERIMETER MAY BE OBSTRUCTED AS LONG AS ANY ONE
<br />OBSTRUCTION DOES NOT EXCEED 10 PERCENT OF THE POOL PERIMETER OR
<br />20 FEET (6096 MM), WHICHEVER IS LESS,
<br />IN ANY ONE AREA MERE WATER DEPTH IS 5 FEET (1524 MM) OR LESS.
<br />OBSTRUCTIONS SHALL HAVI: A MIN. 4'-0" WIDE WET DECK AREA BEHIND OR THROUGH THEM, WITH THE NEAR EDGE
<br />OF THE WALK WITHIN 15 F1=ET (4572 MM) OF THE WATER.
<br />NOTE:
<br />THE POOL, POOL DESK. AND POOL EQUIPMENT, AS ILLUSTRATED ON THESE
<br />ENGINEERED PLANS, MEET THE
<br />REQUIREMENTS OF FBC-B 454.1 (2020) AND NEC (2017).
<br />U)
<br />z
<br />I
<br />w�
<br />0
<br />Q
<br />z�op�
<br />z
<br />0
<br />c, 0
<br />� Ln U
<br />w��z�=o
<br />0
<br />V)
<br />Q
<br />ILL
<br />uj
<br />G
<br />J uj
<br />LLJ
<br />Cn
<br />N
<br />{C3
<br />7
<br />N
<br />N
<br />N
<br />OLL_
<br />l
<br />Q1
<br />o
<br />�
<br />Q
<br />c
<br />o0
<br />Ld
<br />w
<br />crJ
<br />a-
<br />O
<br />3:
<br />y C
<br />z
<br />to
<br />w
<br />(DO J
<br />LLJ
<br />O w N
<br />Q
<br />Q'C
<br />Ld Z �. Q
<br />Ld
<br />00
<br />cl-
<br />< 00 w
<br />W
<br />c1f _w
<br />Li.l a
<br />LL
<br />Uc
<br />N w
<br />00 _J
<br />l
<br />I
<br />w
<br />PROJECT NO.
<br />22CO93
<br />Qo
<br />0
<br />z0 Z U
<br />Zw
<br />=
<br />�~
<br />(nU
<br />�LLL
<br />W Q
<br />Q p
<br />2 x< F
<br />z Q Q
<br />V) CL
<br />W p Z
<br />�.wJO
<br />JQ0
<br />_j z
<br />0Wuj
<br />F-�00
<br />0��
<br />Caw "
<br />(n0ll�w
<br />w -o<
<br />LL0w
<br />wQwZ
<br />m5�-
<br />Owmw
<br />cnLDccnC)
<br />cnQZo�
<br />wV)1�
<br />_ U Q O
<br />.
<br />cc U
<br />W w
<br />m w
<br />U -
<br />w
<br />F-� WwN
<br />J Z 0
<br />H0�of
<br />Fn Q~
<br />�Q C�w�
<br />ZZZU
<br />�cww�to
<br />n
<br />0
<br />-Ucnw
<br />`���,•�`��� �� L F AE�'f
<br />* ; No. 47646
<br />STATE OF r
<br />r0OR fJ
<br />'.
<br />(V
<br />S10NAI.E���``�
<br />01 /13/2023
<br />DAVID I FAERMAN, P.E.
<br />FL. LICENSE NO. 47646
<br />PERMIT SET