Laserfiche WebLink
ELECTRICAL SPECIFICATION <br />NOTES: <br />ELECTRICAL CONTRACTOR <br />MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR <br />LOCATION PURPOSES. <br />GENERAL ELECTRICAL NOTES: <br />Notes: unless otherwise noted, <br />1. Electrical outlet heights as measured from finished floor to center line of the box to be: 16" AFF (general). <br />In a Flood Zone, all electrical equipment to be at or above DFE. <br />Kitchen 44" AFF <br />Bathroom 39" AFF <br />Laundry Room 36" AFF <br />Exterior Waterproof 12" AFF <br />Garage - general purpose 44" AFF <br />Range 2" AFF <br />2. All trim plates and devices to be ganged, where possible. <br />3. Electrical switches to be at 42" centerline above finished floor. <br />4. Electrical plan is intended for bid purposes only. All work shall be done in strict accordance with the National <br />Electric Codes (NEC 2017), by a licensed electrical contractor who shall be responsible for the installation & <br />sizing of all electrical, wiring & accessories. <br />5. Smoke detectors shall be in accordance with R314.1 and listed in accordance with UL 217. <br />6. Provide AFCI's (Arc -Fault Circuit Interrupters) combination type installed to provide protection of the branch <br />circuits in all dwelling units per NFPA 70-17, National Electrical Codes (NEC 2017) and as defined in UL 1699. <br />7. Provide Tamper Resistant Receptacles as required by the NFPA 70-17, National Electrical Codes (NEC <br />2017). <br />8. Carbon Monoxide Protection: carbon monoxide alarms or detectors shall be installed in all dwelling units in <br />accordance with FBC R315 and NFPA 70-17, National Electrical Codes (NEC 2017). Such devices shall be <br />listed by the appropriate standard, either ANSI/UL 2034, standard for single and multiple station CO alarms or <br />UL 2075, gas and vapor detector sensor, according to the installation. <br />9. R315.1.2 Combination Alarms: combination smoke/carbon monoxide alarms shall be listed and labeled by a <br />Nationally Recognized Testing Laboratory. <br />10. Keep all smoke detectors minimum of 36" from bathroom doors. <br />11. In new construction, smoke detectors shall be hardwired into an A/C electrical power source and shall be <br />equipped with a monitored battery backup. <br />12. Bathroom exhaust fans must vent to the exterior of the building, ventilation to attic space and soffit is not <br />acceptable. <br />13. Chapter 45 Private Swimming Pools - Outdoor swimming pools shall be provided with a barrier Complying <br />with R4501.17.1.1 through R4501.17.1.14. <br />14. Add GFCI protection to receptacles in laundry rooms and utility rooms of dwellings where installed within 6' of <br />the outside edge of a sink. This would include the receptacle installed for a washing machine. Receptacle <br />outlets shall not be required on a wall directly behind a range or sink to fulfill the requirement of an outlet <br />every 24". The width of the sink or range is not to be included in the spacing of the outlets unless the distance <br />from the sink or range is greater than 12" for straight counter tops and 18" for sinks and ranges installed in <br />corner counters. <br />ELECTRICAL KEY <br />'� <br />DUPLEX CONVENIENCE OUTLET <br />DUPLEX OUTLET ABOVE COUNTER <br />W.P. <br />WEATHERPROOF DUPLEX OUTLET <br />G.F.I. <br />GROUND FAULT INTERRUPTER DUPLEX OUTLET <br />HALF -SWITCHED DUPLEX OUTLET <br />SPECIAL PURPOSE OUTLET <br />DUPLEX OUTLET IN FLOOR <br />220 VOLT OUTLET <br />$ <br />WALL SWITCH <br />$3 <br />THREE-WAY SWITCH <br />?4 <br />FOUR-WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />CEILING MOUNTED LIGHT FIXTURE <br />® <br />HI -HAT - TO BE SURFACE MOUNTED ON J-BOX <br />WALL MOUNTED LIGHT FIXTURE <br />ORECESSED <br />LIGHT FIXTURE <br />P.C. <br />LIGHT FIXTURE WITH PULL CHAIN IN ATTIC ACCESS <br />TRACK LIGHT <br />�--{- <br />FLUORESCENT LIGHT FIXTURE <br />O <br />EXHAUST FAN <br />;Q <br />EXHAUST FAN/LIGHT COMBINATION <br />ELECTRIC DOOR OPERATOR (OPTIONAL) <br />CH <br />CHIMES (OPTIONAL) <br />kEg <br />PUSH BUTTON SWITCH (OPTIONAL) <br />H0 <br />PUSH BUTTON SWITCH - DOOR BELL <br />SD <br />SMOKE DETECTOR <br />CM <br />SMOKE/CARBON MONOXIDE DETECTOR (COMBO UNIT) <br />TELEPHONE (OPTIONAL) <br />USB <br />TELEPHONE/USB (OPTIONAL) <br />© <br />TELEVISION (OPTIONAL) <br />TV 2 <br />(2) TELEVISION (OPTIONAL) (1)@ STD. HT. & (1)@ 60" A.F.F. <br />O <br />THERMOSTAT <br />ELECTRIC METER <br />ELECTRIC PANEL <br />—z� <br />DISCONNECT SWITCH <br />G J <br />ROUGH -IN FOR OPT. CEILING FAN <br />CEILING MOUNTED LIGHT FIXTURE W/ ROUGH -IN FOR <br />G T J <br />OPT, CEILING FAN <br />GD <br />(1) PHONE LINE, (1) DATA PORT <br />3" VTR <br />AIL <br />l <br />I <br />I <br />I <br />II HANSON <br />BOX <br />I I <br />3" VTR <br />AIL <br />I <br />I <br />I <br />I <br />I <br />I OPT. <br />,J LAV <br />LI JAV <br />I <br />I <br />---- — I I _U W/C <br />LAV 1\ <br />.J I 3" SHOWER <br />L TUB/ <br />W/C SHOWER <br />3 ` \na F FAR <br />STUDOR <br />VENT DBL SINK <br />W/ DISP. <br />2" <br />LAV WIC z" <br />PLUMBING RISER <br />SCALE: NTS NOTE: PLUMBING RISER IS SCHEMATIC <br />TO BE VERIFIED WITH PLUMBER <br />LOAD CALCULATIONS <br />UNIT-C 1624 (1624) <br />SQ. FT. AT 3 WATTS / SQ. F.T. <br />1625 S.F. <br />4875 <br />SMALL APPLIANCE CIRCUITS AT 1500 WATTS <br />3 <br />4500 <br />LAUNDRY CIRCUITS AT 1500 WATTS <br />1 <br />1500 <br />SUBTOTAL: 10875 <br />DISHWASHER AT 1200 WATTS <br />1 <br />1200 <br />DISPOSAL AT 960 WATTS <br />1 <br />960 <br />WATER HEATER AT 5500 WATTS <br />1 <br />5500 <br />DRYER OUTLET AT 5000 WATTS <br />1 <br />5000 <br />AIR HANDLER UNIT AT 1200 WATTS <br />1 <br />1200 <br />RANGE AT 8000 WATTS <br />1 <br />8000 <br />MICROWAVE AT 1200 WATTS <br />1 <br />1200 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />0 <br />OTHER LOAD WATTS <br />SUBTOTAL: 23060 <br />TOTAL: 33935 <br />1st 10 KW at 100% <br />10000 <br />BALANCE OF WATTS AT 40% <br />9574 <br />AIR CONDITIONER WATTS AT 100% <br />1 <br />7104 <br />HEAT PUMP WATTS AT 100% <br />0 <br />HEAT PUMP & SUP. HEAT WATTS AT 65% <br />1 <br />5200 <br />TOTAL: 31878 <br />LOAD WATTS --- 240 VOLTS <br />AMPS: 133 <br />PROVIDE 150 AMP SERVICE <br />C.O. <br />------------------------- <br />OUTDOOR LIVING <br />INSTALL LIGHT <br />ROUGH -IN <br />FOR OPT. / t�/r�� <br />FAN/LIGHT i WP <br />GFI <br />an <br />----- 7--- <br />DINING <br />KITCHEN <br />GFI ( <br />SWITCH FOR <br />DISPOSAL IN CAB <br />UNDER SINK <br />GREAT ROOM <br />/,-"ROUGH-IN\ <br />FOR OPT. <br /><,�fi-,FAN/LIGHT <br />�' <br />r� <br />/ I <br />I <br />1 <br />I <br />I <br />1 <br />I <br />I <br />I <br />�CaFl_� <br />C.M <br />1 UPSTAIRS F <br />r- V V rN . <br />FOYER <br />\ <br />I 3MV <br />GFI LLk <br />@ 44" W.H. <br />�- <br />A.F.F. ' ` 0 <br />/ I <br />DB <br />/ I <br />NTRY <br />GARAG E <br />IGHT AS 0 G F <br />I <br />ER SPECS <br />DB & GFI TO <br />1 <br />BE ALIGNED >0 I7 <br />GARAGE <br />VERTICALLY <br />LIGHT AS <br />PER SPECS <br />' <br />GARAGE <br />DOOR <br />GFI <br />— — — — — — — — — — — — — — — <br />I I <br />/ <br />W <br />/ <br />IZ I <br />O <br />Optional Overhead Service 200A <br />iQ <br />Same As Underground Indoor Panel <br />IV Q I <br />150 Or 200 Amp Service Center <br />i0 <br />LU <br />NEMA 1 <br />200AMP <br />2 OO <br />LLJILL <br />I <br />Lou <br />_j <br />IN <br />P;WIREAS <br />PSerial Cabl01. <br />mNEMA <br />LIGHTS <br />Power Co. Feed —� �T__ #4 Solid COPPER Ground <br />PER SPECS <br />Intersystem Bonding <br />Termination Per <br />NEC 17, 250.94 5/8" Galvanized Driven Ground <br />Rods at least 6' apart <br />Typical 150-200 Amp Electrical Riser Diagram <br />NOTE: ELECTRICAL MATERIAL AND INSTALLATIONS SHALL COMPLY WITH APPLICABLE PROVISIONS OF <br />THE NFPA 70 - 17, LOCAL CODES AND THE LOCAL POWER CO. <br />DISCONNECT <br />1ST ELECTRICAL —UNIT—C 1624 <br />SCALE: Y"=1'-0" <br />DEDICATED <br />RECEPTACLE FOR <br />MICROWAVE <br />RANGE HOOD PER <br />SPECS <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY <br />WITH THE SPECIFICATIONS FOR THE TYPE <br />OF FIXTURE TO BE USED. LIGHT FIXTURES <br />SHOWN ARE FOR LOCATION PURPOSES. <br />2ND ELECTRICAL — UNIT—C 1624 <br />SCALE: ),4"=1'-0" <br />_ <br />7 LU <br />_ -0 CM <br />y C LA_ Ca <br />w a <br />Q Qf N f0 <br />dY <br />�asd <br />� <br />3 <br />W 3 <br />vi r- -� <br />_ E <br />� ca <br />ck W <br />M <br />0 <br />fV <br />OO <br />N <br />;, rn <br />0 <br />'tP <br />4. <br />To the best of the Engineers knowledge, information and belief, <br />the structural plans and specifications contained within these <br />drawings comply with the 2020 Florida <br />Building Code - <br />Residential 7th Edition. Engineer's <br />signature and seal is only <br />for <br />the structural engineering portions of the drawing pages bearing <br />Engineers signature and seal. <br />E <br />Q <br />US" <br />o <br />O M N v <br />O <br />N <br />N O c: # ik <br />i ei <br />.7 C? LL LL <br />(n h r` -0 IJi uj <br />N <br />a <br />�Mv w a a <br />it r2 <br />tV <br />(a LL LL <L y <br />Z <br />_a o 0 <br />i Z <br />L N C pMCc,o � <br />' <br />r$ W W <br />N NCO m Q <br />0) O) Q k Z <br />aO O r O W <br />O U ❑❑❑ <br />M � <br />o05 g <br />z � N <br />z o � <br />I ^ <br />�/ , <br />N <br />M <br />z �O <br />4 <br />U <br />0 <br />�v,U) <br />-. <br />U <br />W J <br />w aj <br />U 'o °N <br />c m Y <br />¢ 0 <br />_® <br />N <br />I� <br />o <br />M <br />M <br />N <br />J <br />Z <br />Q <br />LL <br />Q O <br />zo <br />o � <br />¢o <br />r N <br />Z 0 <br />� <br />� <br />x UU <br />UO <br />O <br />AW <br />CQ9 M <br />a' <br />Q Z <br />O <br />. <br />W Z <br />t <br />co <br />c <br />m J <br /><o <br />m <br />mo <br />ZZr <br />a w <br />a� <br />3z <br />`: <br />C) <br />02 <br />1 � <br />4O <br />z O <br />Z <br />F- <br />F <br />�rt <br />o <br />Qz <br />J z <br />= <br />>° <br />MillM <br />Ir <br />0 <br />d H <br />o 3 <br />c <br />•2 T— <br />> o6 <br />rn <br />N <br />� <br />� <br />c� <br />C� <br />r <br />W^, <br />0 <br />L <br />CO 00 <br />T O <br />O <br />T <br />T <br />LO <br />OTO00 <br />VJ m <br />F- <br />p <br />L0 <br />:+= <br />M <br />LO <br />O <br />M <br />N <br />Ln <br />Cfl <br />t <br />N <br />T <br />m <br />T <br />LO <br />iii <br />o <br />Z <br />z <br />E O <br />2 <br />cc <br />@E <br />a <br />L; <br />U _j <br />_0 4? <br />Q <br />c <br />0 <br />JOB <br />NO: 23-12154-12159 <br />SCALE : <br />AS NOTED <br />SHEET NO. <br />11.2 <br />