"yEw . ll T' 117 - '11 <br />System No. C-AJ-1259 <br />F Rating - 3 Hr <br />T Rating - 0 Hr <br />Section A -A <br />1. Floor or Wall Assembly - Min 4-1/2 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Floor may also be <br />constructed of any min 6 in. thick UL Classified hollow -core Precast Concrete Units*. Wall may also be constructed of any UL <br />Classified Concrete Blocks*. Max diam of opening is 7 in. <br />See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of <br />manufacturers. <br />2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the <br />firestop system. The annular space between the pipe, conduit or tubing and the periphery of the opening shall be a min of 0 in. <br />(point contact) to a max of 3 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The <br />following types and sizes of metallic pipes, conduit or tubing may be used: <br />A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. <br />B. Iron Pipe - Nom 6 in. diam (or smaller) cast or ductile iron pipe. <br />C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit. <br />D. Copper Tube - Nom 4 in. diam (or smaller) Type L (or heavier) copper tube. <br />3. Forming Material - (Optional, Not Shown) - Mineral wool batt packing material or polyurethane backer rod friction fitted into <br />opening and recessed from floor or wall surfaces as required to accommodate required thickness of fill material. <br />4. Fill, Void or Cavity Material' - Sealant - Min 1/2 in. thickness of fill material applied within the annulus, flush with both <br />surfaces of floor or wall. At the point contact location between penetrating item and concrete, a min 1/4 in. thick bead of fill <br />material shall be applied at the concrete/penetrating item interface on both sides of floor or wall. <br />SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant <br />*Bearing the UL Classification Mark <br />Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 <br />Reproduced courtesy of Underwriters Laboratories, Inc. <br />STI Created or Revised: January 2, 2009 8 C-AJ-1259 <br />(800)992-1180 - (908)526-8000 - FAX (908)231-8415 - E-Mail:techserv@stifirestop.com - Websitemww.stifirestop.com PAGE 1 OF 1 <br />System No. W-L-1079 <br />F Ratings - 1 and 2 Hr (See Item 1B) <br />T Rating - 0 Hr <br />L Rating At Ambient - Less Than 1 CFM/sq ft <br />L Rating At 400 F - Less Than 1 CFM/sq ft <br />OeG110(1 H-/A <br />1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board/stud wall assembly shall be constructed of the materials and in the <br />manner described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall <br />include the following construction features: <br />A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. <br />lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-5/8 in. wide and <br />spaced max 24 in. OC. <br />B. Gypsum Board - 5!8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number of <br />layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire <br />Resistance Directory. Max diam of opening is in wood stud walls is 13 in. Max diam of opening in steel stud walls is 16 in. <br />The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. <br />2. Through Penetrant - One metallic pipe or conduit to be installed either concentrically or eccentrically within the firestop <br />system. The annular space between pipes or conduits and periphery of opening shall be min 0 in. (point contact) to max 3 in. <br />Pipe or conduit to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or <br />conduits may be used: <br />A. Steel Pipe - Nom 12 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. <br />B. Iron Pipe - Nom 12 in. diam (or smaller) cast or ductile iron pipe. <br />C. Conduit - Nom 4 in. diam (or smaller) electrical metallic tubing, nom 6 in. diam (or smaller) steel conduit or nom 1 in. diam <br />(or smaller) flexible steel tubing. <br />D. Copper Pipe - Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe. <br />E. Copper Tube - Nom 6 in. diam (or smaller) Type L (or heavier) copper tube. <br />79 Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876 <br />Reproduced courtesy of Underwriters Laboratories, Inc. <br />STI Created or Revised: January 2,2009 W L 1079 <br />(B00)992-1180 - (908)526-8000 - FAX (908)231-8415 - E-MaiLtechserv@stifirestop.com - Websitemww.stifirestop.com PAGE 1 OF 2 <br />LA <br />G6 <br />E <br />G1 <br />EX <br />r— N—------ <br />EW <br />I <br />r <br />NEW RISER WORK <br />——————— — — — —-� <br />I <br />LC EX L J <br />200 <br />EX NP rD200 <br />X ' <br />33d it AF <br />❑ <br />O CTM <br />NEW <br />I PNL I <br />100 <br />EX <br />i A I <br />100.S <br />200 M200 <br />CT <br />I I <br />CABINETI <br />20m I <br />EX <br />CT <br />i <br />L—— — — —--� <br />WW <br />ELECTRICAL RISER DIAGRAM <br />MISCELLANEOUS NOTES: <br />FXFMR <br />EXISTING UTILITY COMPANY PAD MOUNTED <br />TRANSFORMER. SECONDARY VOLTAGE TO BE <br />120/200Y 3 PHASE, 4 WIRE WYE_ <br />LA <br />EXISTING UL LISTED LIGHTNING ARRESTOR, <br />SQUARE D OR APPROVED EQUIVALENT, <br />ww <br />EXISTING 12"X12"X 12" NEMA 3R WIREWAY, <br />EXTEND FEEDER CONDUCTORS THE ENTIRE <br />LENGTH OF THE WIREWAY AND TERMINATE <br />WITH INSULATED KEY TAP STYLE <br />CONNECTORS. I LSCO OR APPROVED <br />EQUIVALENT. <br />EXISTING LIGHTING CONTACTORS) AND <br />LC TIMEGLOCK IN NEMA 3R ENCLOSURE_ REFER <br />TO DETAIL ON THIS SHEET FOR <br />REQUIREMENTS <br />D2 00 EXISTING A 200 AMP, 3 POLE, NEMA 3R, <br />SERVICE ENTRANCE RATED HEAVY DUTY <br />FUSED DISCONNECT SWITCH WITH SOLID <br />NEUTRAL KIT_ FUSE AT 200 AMPS WITH CLASS <br />RKl FUSES. <br />D8 00 EXISTING SOO AMP, 3 POLE, NEMA 3R, <br />SERVICE ENTRANCE RATED HEAVY DUTY <br />FUSED DISCONNECT SWITCH WITH SOLID <br />NEUTRAL KIT. FUSE AT 800 AMPS WITH CLASS <br />L FUSES. <br />FEEDER NOTES: F7 <br />1200.5 <br />(EXISTING SERVICE LATERAL - 1200 AMPS) <br />(3) SETS OF 4 0600 KCMIL IN 4" C <br />ROUTED UNDER GROUND EXTERIOR OF <br />THE BUILDING <br />800. <br />(EXISTING SERVICE ENTRANCE -000 AMPS) <br />(2) SETS OF 4 0600 KCMIL IN 4" C <br />ROUTED UNDER GROUND EXTERIOR OF <br />THE BUILDING <br />(EXISTING SERVICE ENTRANCE - 200 AMPS) <br />200. <br />4 03/0 AND 1 04 BONDING <br />CONDUCTOR IN 2" C <br />200 <br />(NEW FEEDER - 200 AMPS) <br />113/0 IN <br />EXTEND 4 AND 1"(o E G. 2" C <br />(EXISTING SERVICE ENTRANCE - 100 AMPS <br />100.S <br />4 *1 AND 104 BONDING <br />CONDUCTOR IN 1-1/2" C <br />I PA'\EL I 1 FLUSHED <br />O 208 OLT t SE <br />NIED <br />A PH.4 <br />4 fit' IRE WITH GROU.\D <br />EX <br />14�1�3 AFC <br />I LA I <br />1200.S <br />ErT <br />EX <br />EX <br />METER NOTES: <br />CT <br />EXISTING 3(o" X 36" X 12" NEMA 3R CT <br />CABINET WITH LOCKABLE HASP. VERIFY <br />EXACT REQUIREMENTS WITH UTILITY <br />COMPANY PRIOR TO ROUGH -IN. <br />FC T M <br />EXISTING 3 PHASE CT METER BASE PER <br />UTILITY COMPANY SPEC. <br />FM20 <br />EXISTING 200 AMP 3 PHASE SELF <br />CONTAINED METER BASE PER UTILITY <br />COMPANY SPEC. <br />GROUND INCx/BONDING NOTES: = <br />G1 IEXISTING <br />3/0 CU GROUND ELECTRODE <br />CONDUCTOR IN 3/4" CONDUIT_ <br />EXISTING 3/4" X 10' LONG COPPER CLAD <br />G2 <br />GROUND, <br />G3 <br />EXISTING GROUND ELECTRODE SYSTEM <br />CONNECTION TO A REBAR IN THE BUILDING <br />FOUNDATION AND BUILDING STEEL. <br />G4 <br />EXISTING METALLIC COLD WATER PIPE <br />CONNECTION TO GROUND ELECTRODE SYSTEM. <br />G6 <br />EXISTING METER AND CT CABINET <br />CONNECTION TO GROUND ELECTRODE <br />SYSTEM WITH A M4 CU GEC IN 3/4" CONDUIT_ <br />'ES <br />C1-T. <br />I <br />DESCRIPTION <br />BREAKER <br />A <br />B <br />NO. <br />TRIP <br />POLE <br />VOLT <br />I <br />I <br />OI-TICE,EXAM.TOILET RN,ISLTS E.�I <br />20 <br />1 <br />120 <br />812 '50 <br />1 <br />__1 <br />COi.RIDOR.'RECRPTIO'\5 LTS:'E\I <br />_0 <br />1 <br />124 <br />1 <br />5 <br />OFF ICE,EXA_II ST.R?.SSLTS'E\d <br />20 <br />1 <br />120 <br />1 <br />7 <br />ct ITINGAREALIGHT.EM <br />20 <br />1 <br />120 <br />1034 1200 <br />2 <br />9 <br />E.,AwI-119'121 REC. <br />20 <br />1 <br />120 <br />540 1000 <br />2 <br />11 <br />E\4\L 1_v'121 RFC. <br />_'0 <br />1 <br />120 <br />{ <br />13 <br />WAITING ROO\I EWC <br />20 <br />1 <br />120 <br />-;0 1000 <br />2 <br />15 <br />V, AITING ROO\I RECEPTACLES <br />20 <br />1 <br />120 <br />900 1200 <br />2 <br />17 <br />CHECK IN PALTER <br />20 <br />1 <br />110 <br />2 <br />19 <br />CHECK IN RE CEP <br />20 <br />1 <br />120 <br />720 1 900 <br />21 <br />SPARE <br />24 <br />1 <br />12.0 <br />540 <br />SPARE <br />20 <br />1 <br />120 <br />4 <br />25 <br />EWH <br />30 <br />2 <br />208 <br />2250 1 1000 <br />4 <br />?- <br />2250 ,a� <br />_ <br />29 <br />MEZ-1ANI\TRECIPTACLES <br />20 <br />1 <br />120 <br />3 <br />31 <br />CU-1 <br />30 <br />3 <br />208 <br />1'.•52 1-40 <br />3 <br />33 <br />---- <br />1752 1 1740 <br />4 <br />3? <br />AI;i;-1 <br />60 <br />2 <br />208 <br />4176 <br />4 <br />39 <br />-- - <br />41-6 1 4374 <br />41 <br />SPA C'E <br />t <br />CONNT-CTED VA <br />SYSTEM VOLTS <br />PHA SF. A\.PS <br />1808 # <br />21127 <br />12020SV.3PHASE <br />1511 <br />176 <br />C <br />BREAKER <br />DESCRIPTION( <br />VOLT <br />POLE <br />TRIP <br />120 <br />1 <br />.0 <br />1 TELEPHONE RECEPTACLE <br />120 <br />1 <br />20 <br />1 IT RECEPTA CLES <br />1210 750 <br />120 <br />1 <br />20 <br />TIME CiOCKr`REC'EPTACLES <br />120 <br />1 <br />20 <br />BREAKR-it REFRIGERATOR <br />120 <br />1 <br />20 <br />BREAKRIM COL TER RECEPT. <br />1080 1500 <br />120 <br />1 <br />20 <br />BREAKRM MICROWAVE <br />120 <br />1 <br />20 <br />BREAK Rive COUNTER RECEPT. <br />120 <br />1 <br />20 <br />BREAK RIM C;ARBAGE.DISPOSAL <br />1000 1200 <br />120' <br />1 <br />20 <br />SIGNS <br />120 <br />1 <br />20 <br />EXAM RBI : 109.+'107N RSE REC. <br />1.0 <br />1 <br />7 <br />.0 <br />[ i t <br />E�.�.4I RVI � 109 10. T,FL'RSE RE:C:. <br />720 <br />120 <br />1 <br />20 <br />E..XA�M R_M =101`N'U7RSEREC. <br />120 <br />1 <br />20 <br />NURSE RECEPTACLES <br />120 <br />1 <br />20 <br />OFFICES -EXAM R V1 # 115:'1IS REC., <br />360 1080 <br />120 <br />1 <br />20 <br />OFFIC S EXAM R'43 s1151118 RFC. <br />208 <br />3 <br />30 <br />CU-2 <br />1752- 1 1740 <br />120,1 1 1 20 1 SPARE <br />208 1 3 1 60 1 AHU'-2. <br />4374 ----- <br />16766 <br />NOTES <br />LOAD TYPE <br />IS LARGER <br />CO` CTED <br />\EC DENIAND <br />DENMAN"1D LOAD <br />I <br />LIGHTING <br />5081 <br />1.25 <br />635125 VA <br />8920 VA <br />0 VA <br />21600 VA <br />99G0 VA <br />0 VA <br />0 VA <br />46771 VA <br />2 <br />RECEPTACLES <br />8920 <br />1 <br />3 <br />AIR C'O\DITIONI\G <br />10476 <br />© <br />4 <br />HEATING <br />21600 <br />1 <br />5 <br />tvIISC. tdON-CONTIPIUOUG <br />9900 <br />1 <br />6 <br />CONTINUOUS <br />0 <br />1:25 <br />KITCHEN <br />0 <br />0.65 <br />TOTAL <br />120 20 I., 3 PIiA <br />SE <br />130 AtvtPS <br />DOTES ( } <br />G3 <br />MLO <br />Al <br />)AFC <br />8 2 <br />30 2 <br />32. 3 <br />34 3 <br />36 3 <br />38 <br />F44 <br />42 <br />ELECTRICAL SPECIFICATIONS: <br />THE WORK UNDER THE REQUIREMENTS OF THESE SPECIFICATIONS SHALL BE <br />OIN CONFORMANCE WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL <br />CODE, THE INSTALLATION SHALL ALSO COMPLY WITH ALL APPLICABLE <br />RULES AND REGULATIONS OF LOCAL AND STATE LAWS AND ORDINANCES. <br />OALL ELECTRICAL EQUIF ,LENT SHALL HAVE UL LABEL AND SHALL BE OF <br />SPECIFICATION GRADE <br />POWER DISTRIBUTION HOUSE PANELBOARD: PROVIDE DEAD -FRONT, <br />OSAFETY -TYPE POWER DApTRIBUTION PANELBOARDS AS INDICATEDt WITH <br />PANELBOARD SWITCH*AND PROTECTIVE DEVICES IN QUANTITIES, RATINGS, <br />TYPES, AND WITH ARRANGEMENT SHOWNt WITH ANTI -TURN, SOLDERLESS <br />PRESSURE TYPE MAIN LUG CONNECTORS APPROVED FOR USE WITH COPPER <br />CONDUCTORS. <br />®PANELBOARDS EQUAL TO SQUARE D TYPE "QO", VOLTAGE SHALL BE AS <br />INDICATED_ ACCEPTABLE MFG.t G.E., SIEMENS AND CUTLER -HAMMER <br />ALL PANEL50ARDS SHALL BE CONNECTED, DISTRIBUTED PHASE WITH <br />OCIRCUIT NUMBERING AS INDICATED ON THE DRAWINGS. PANELBOARDS SHALL <br />BE NUMBERED WITH ODD NUMBERS ON THE LEFT SIDE OF THE PANEL AND <br />EVEN NUMBERS ON THE RIGHT SIDE OF THE PANEL. <br />UNLESS OTHERWISE INDICATED, PROTECTIVE DEVICES SHALL BE MOUNTED <br />OWITH TOP OF CABINET OR ENCLOSURE 6'-6" ABOVE FINISHED FLOOR, SHALL <br />BE PROPERLY ALIGNED, AND SHALL BE ADEQUATELY SUPPORTED <br />INDEPENDENTLY OF THE CONNECTING RACEWAYS. ALL STEEL SHAPES, ETC., <br />NECESSARY FOR THE SUPPORT OF THE EQUIPMENT SHALL BE FURNISHED <br />AND INSTALLED BY THE CONTRACTOR WHERE THE BUILDING STRUCTURE IS <br />NOT SUITABLE FOR MOUNTING THE EQUIPMENT DIRECTLY THEREON, UNLESS <br />OTHERWISE INDICATED, ALL BRANCH CIRCUIT PROTECTIVE DEVICES <br />ENCLOSURES SHALL BE NEMA TYPE 1, GENERAL PURPOSE TYPE. CIRCUIT <br />PROTECTIVE DEVICES INSTALLED OUTDOORS OR EXPOSED TO THE <br />WEATHER SHALL HAVE WEATHERPROOF ENCLOSURES, NEMA TYPE "3R" OR <br />TYPE "4" <br />ALL SAFETY SWITCHES SHALL BE GENERAL DUTY TYPE_ SWITCH MECHANISM <br />OSHALL BE QUICK -MAKE, QUICK -BREAK_ COVER SHALL BE INTERLOCKED WITH <br />MECHANISM TO PREVENT OPENING UNLESS SWITCH IS IN THE "OFF" POSITION, <br />ALL ENCLOSURES SHALL BE PRIMED AND FINISHED TO RESIST RUSTING AND <br />CORROSION_ SWITCHES SHALL BE ITE, GENERAL ELECTRIC, SQUARE-D, OR <br />CUTLER -HAMMER <br />OCIRCUIT BREAKERS FOR MOUNTING IN HOUSE PANELBOARD SHALL BE <br />BOLT -ON OR PLUG IN TYPE, MOLDED PLASTIC CASE, AIR CIRCUIT BREAKER <br />TYPE. BREAKERS SHALL HAVE THERMAL MAGNETIC TRIP UNITS AND <br />MULTI -POLE BREAKERS SHALL HAVE A COMMON TRIP BAR SO THAT THE <br />TRIPPING OF ONE POLE WILL AUTOMATICALLY TRIP ALL POLES OF THE <br />BREAKER BREAKERS SHALL BE TRIP FREE AND TRIP INDICATING AND <br />SHALL HAVE QUICK -MAKE, QUICK -BREAK CONTACTS. <br />®UPON COMPLETION OF WORK CORRECT ALL PANELBOARD CIRCUIT <br />DIRECTORY CARDS TO REFLECT AS -BUILT CONDITIONS. PANELBOARD <br />DIRECTORIES SHALL BE UPDATED WITH TYPEWRITTEN ACCURATE AND <br />CURRENT INFORMATION BY THE CONTRACTOR AT THE END OF CONSTRUCTION_ <br />DIRECTORIES SHALL REFLECT RECORD CONDITIONS AND INCLUDE CIRCUIT <br />NUMBER, TYPE AND LOCATION OF LOAD. A SET OF AS -BUILT DRAWINGS <br />SHALL ALSO BE PREPARED AND TURNED OVER TO THE OWNER <br />ALL CONDUCTORS SHALL BE THHN/TI-IWN COPPER 012 MIN. AND INSTALLED IN <br />10 A COMPLETELY ENCLOSED RACEWAY SYSTEM. FEEDERS MAY BE ALUMINUM <br />WHEN LARGER THAN 06 AWG <br />UNLESS SPECIFICALLY NOTED ON DRAWINGS, RACEWAYS SHALL COMPLY <br />11 WITH THE FOLLOWING: <br />RACEWAYS EXPOSED TO THE WEATHER OR IN DAMP LOCATIONS <br />O12 SHALL BE SCHEDULE 40 PVC OR GALVANIZED RIGID STEEL WITH <br />THREADED CONNECTIONS WHEN EXPOSED TO DAMAGE_ <br />RACEWAYS SHALL BE SIZED FOR THE CONDUCTORS INSTALLED, <br />MINIMUM 1/2 FULL SIZE MC CABLE IS ACCEPTABLE IN DRY LOCATIONS. <br />13 HOME RUNS TO PANELS TO BE IN CONDUIT, <br />14 RACEWAYS RUN BELOW GRADE SHALL BE SCHEDULE 40 PVC <br />ALL METALLIC RACEWAYS SHALL BE MECHANICALLY AND ELECTRICALLY <br />15 SECURE AT ALL JOINTS AND AT ALL BOXES, CABINETS, FITTINGS, AND <br />EQUIPMENT_ <br />16 ALL RACEWAYS SHALL BE SECURELY SUPPORTED FROM THE BUILDING <br />STRUCTURE_ <br />O ALL RACEWAYS SHALL BE PROVIDED WITH EQUIPMENT GROUND CONDUCTOR - <br />ALL BOXES SHALL BE RIGIDLY MOUNTED AND SHALL BE EQUIPPED WITH <br />18 SUITABLE SCREW FASTENED COVERS, OPEN KNOCK -OUTS OR HOLES IN <br />BOXES SHALL BE PLUGGED WITH A SUITABLE BLANKING DEVICES. <br />OUTLET 5OXE5 FOR EXPOSED WALL MOUNTING AND OUTDOOR INSTALLATION <br />1g SHALL BE CAST METAL TYPE "FS" OR "FD" BOXES WITH SUITABLE <br />GALVANIZED SHEET STEEL COVERS, OR CAST METAL WEATHERPROOF OR <br />VAPOR TIGHT COVERS WHEN NOTED ON THE DRAWINGS. <br />UNLESS OTHERWISE INDICATED, ALL CONDUCTORS SHALL BE COPPER NO. 12 <br />20 AW'Cs_ MINIMUM. OR SIZE AS SHOWN ON DRAWINGS. CONDUCTORS SHALL HAVE <br />TYPE ' 'THHN/THWN' INSULATION. <br />SPLICES, TAPS AND ATTACHMENT FITTINGS AND LUGS SHALL BE <br />21 ELECTRICALLY AND MECHANICALLY SECURE AND SOLDERLESS FOR <br />CONDUCTORS SIZES NO. 8 AUG AND LARGER THERE SHALL BE PLENTY OF <br />SLACK CABLE IN BOXES, OUTLETS AND CABINETS TO INSURE THAT THERE 15 <br />NO BINDING AT THE BUSHINGS. ALL LUGS SHALL BE OF THE CORRECT SIZES <br />FOR THE CONDUCTORS JOINED AND IN NO CASE SHALL STRANDS BE CUT <br />FROM A CONDUCTOR IN ORDER TO FIT THE CONDUCTOR INTO A LUG. TAPING <br />OF JOINTS SHALL BE WITH VINYL PLASTIC ELECTRICAL TAPE TO SECURE <br />INSULATION STRENGTH EQUAL TO THAT OF THE CONDUCTORS JOINED_ <br />22 THE INTERIOR ELECTRICAL SYSTEMS SHALL BE COMPLETELY AND <br />EFFECTIVELY GROUNDED AS REQUIRED BY THE NEC AND AS SPECIFIED <br />HEREINAFTER. <br />23 CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS. <br />THE CONTRACTOR SHALL VERIFY ALL LOCATIONS WITH THE OWNER PRIOR TO <br />INSTALLATION. THEY SHALL NOT BE CHARGED FOR MINOR LOCATION <br />24 CHANGES PRIOR TO INSTALLATIONS. LOCATIONS ARE APPROXIMATE, (DO <br />NOT SCALE DRAWINGS). <br />THESE DRAWINGS ARE DIAGRAMMATIC AND SHOW GENERAL ELECTRICAL <br />25 LAYOUTS FOR BIDDING PURPOSES ONLY. IT IS THE RESPONSIBILITY OF THE <br />CONTRACTOR TO PREPARE DETAILED SHOP DRAWINGS AND CONFIRM <br />SPACE ALLOCATIONS. <br />THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL DISCIPLINES <br />' 26FOR ELECTRICAL CONDUIT ROUTING AND EQUIPMENT PLACEMENT. AVOID <br />O <br />INTERFERENCE WITH ARCHITECTURAL AND STRUCTURAL FEATURES SUCH AS: <br />BEAMS, FOOTINGS, WINDOWS, ETC. NOTIFY ARCHITECT IMMEDIATELY OF ANY <br />CONFLICTS_ <br />THE ELECTRICAL CONTRACTOR THE HVAC FOREMAN AND GENERAL <br />27 CONTRACTOR PROJECT MANAGER SHALL INSPECT a REVIEW THE <br />CONDITIONS, AND SHALL COORDINATE THEIR WORK SO AS TO PROVIDE <br />ADEQUATE SPACE ALLOWANCE ABOVE CEILING FOR ALL TRADES - <br />THE PLANS SHOW THE LOCATION OF ALL FIXTURES AND EQUIPMENT AND ARE <br />28 INTENDED TO DEPICT THE GENERAL INTENT OF THE WORK IN SCOPE, LAYOUT <br />AND QUALITY OF WORKMANSHIP. THEY ARE NOT INTENDED TO SHOW IN MINUTE <br />DETAIL EVERY AND ALL ACCESSORIES INTENDED FOR THE PURPOSE OF <br />EXECUTION OF THE WORK, BUT SHALL BE UNDERSTOOD THAT SUCH DETAILS <br />WILL BE PART OF THIS WORK. <br />THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL A COMPLETE <br />29 AND FUNCTIONAL SYSTEM: CONTROLS, AND CONNECTIONS TO NEW SERVICES, <br />SUPPORTS, AND HARDWARE REQUIRED FOR THE SATISFACTORY OPERATION <br />OF THE SYSTEM, WHETHER SPECIFICALLY SHOWN OR NOT ON THE DRAWINGS. <br />WHERE DRAWINGS AND SPECIFICATIONS CONFLICT, IT SHALL BE THE <br />30 RESPONSIBILITY OF THIS CONTRACTOR TO BRING SUCH CONFLICT TO THE <br />ATTENTION OF THE ENGINEER FOR CLARIFICATION. <br />E-LECTfRICAL S"T'1150L LEGEND <br />SYMBOL <br />DESCRIPTI❑N <br />M❑UNTING <br />- g <br />I X 4 FLUORESCENT FIXTURE <br />SEE FIXTURE <br />LETTER INDICATES TYPE <br />SCHEDULE <br />X 4 FLUORESCENT FIXTURE <br />SEE FIXTURE <br />F2 <br />LETTER INDICATES TYPE <br />SCHEDULE <br />SHADING DENOTES FIXTURE WITH EM BATTERY PACK. <br />SEE FIXTURE <br />'NL' DENOTES FIXTURE UNSWITCHED FOR NIGHT LIGHT <br />SCHEDULE <br />FLUORESCENT STRIP FIXTURE <br />SEE FIXTURE <br />LETTER INDICATES TYPE <br />SCHEDULE <br />FLUORESCENT WALL BRACKET FIXTURE <br />SEE FIXTURE <br />LETTER INDICATES TYPE <br />O <br />PL FLUORESCENT DOWNLIGHT <br />SEE FIXTURE <br />LETTER INDICATES TYPE <br />SCHEDULE <br />I-6 EX <br />EXIT -SHADING DENOTES FACEPLATE LOCATION_ LETTER <br />SEE FIXTURE <br />INDICATES TYPE. PROVIDE ARROWS AS REQUIRED. <br />SCHEDULE <br />SINGLE POLE SWITCH (20A-120/277) <br />48" AFF OR AS <br />S S3 So <br />'3' DENOTES 3;WAY 'O' DENOTES OCCUPANCY SENSOR <br />NOTED <br />DUPLEX RECEPTACLE, 125V, 20A <br />16" AFF OR AS <br />'IG' DENOTES ISOLATED GROUND <br />NOTED <br />DUPLEX RECEPTACLE, 125V, 20A <br />16" AFF OR AS <br />NOTED <br />& <br />DUPLEX RECEPTACLE, 125V, 20A <br />46" AFF OR AS <br />NOTED <br />0 <br />QUADRAPLEX RECEPTACLE, 125V, 20A <br />16" AFF OR AS <br />NOTED <br />0 <br />COMBINATION VOICE/DATA OUTLET <br />10" AFF OR AS <br />NOTED <br />TV <br />T.V_ OUTLET <br />18" AFF OR AS <br />NOTED <br />PANELBOARD 120/240V <br />SEE PANEL <br />SCHEDULE <br />�-� <br />RACEWAY CONCEALED IN WALL OR ABOVE CEILING <br />SEE SPECIFICATIONS <br />HOMERUN TO PANEL. LETTERS INDICATE PANEL, <br />SEE SPECIFICATIONS <br />NUMBERS INDICATE CIRCUIT. NOTE: HASH MARKS <br />INDICATES THE NUMBER OF WIRES EXCLUDING <br />THE REQUIRED EQUIPMENT GROUND. <br />/ �✓ <br />MOTOR, NUMERAL INDICATES HORSEPOWER <br />AS NOTED <br />MOTOR RATED SWITCH WITH OVERLOAD <br />MOUNTED ADJACENT <br />RELAYS IF REQUIRED. <br />TO EQUIPMENT <br />NON -FUSIBLE SAFETY SWITCH -SIZE AS NOTED <br />SEE SPECIFICATIONS <br />FUSIBLE SAFETY SWITCH-51ZE AS NOTED <br />SEE SPECIFICATIONS <br />2 R <br />�s <br />FIRE ALARM DUCT DETECTOR CRA'DENOTES <br />MOUNTED IN <br />RETURN AIR 'SA' DENOTES SUPPLY AIR) <br />HVAC DUCTWORK <br />® <br />FAN OR AIR HANDLER SHUTDOWN RELAY <br />MOUNTED ADJACENT <br />TO EQUIPMENT <br />0 <br />FIRE ALARM VISUAL SIGNAL <br />00" AFF OR <br />AS NOTED <br />FIRE ALARM MANUAL PULLSTATION <br />48" AFF ORAS <br />NOTED <br />FIRE ALARM AUDIBLE/VISUAL SIGNAL, ADA <br />80" AFF OR <br />Z< <br />COMPATIBLE , <br />AS NOTED <br />FIRE ALARM SMOKE DETECTOR <br />ON CEILING ORAS <br />NOTED <br />FACPP <br />FIRE ALARM PANEL CFACP' DENOTES FIRE ALARM <br />60" AFF OR <br />FAA <br />CONTROL PANEL, 'FAA' DENOTES ANNUNCIATOR) <br />AS NOTED <br />EX <br />DENOTES EXISTING DEVICE OR CIRCUIT TO REMAIN <br />R <br />DENOTE NEW LOCATION FOR RELOCATED DEVICE <br />O O <br />I REFER TO LIKE NUMBERED NOTES <br />NOTE: ALL MOUNTING HEIGHTS SHOWN ARE TO THE TOP OF THE <br />DEVICE UNLESS NOTED OTHERWISE. <br />NOT ALL SYMBOLS APPEAR ON PLANS, <br />ABBREVIATIONS: <br />AFF - <br />ABOVE FINISHED FLOOR <br />AHU - <br />AIR HANDLING UNIT <br />BFG - <br />BELOW FINISHED GRADE <br />C - <br />CONDUIT r <br />CW - <br />COOL WHITE <br />DACP - <br />DOOR ALARM CONTROL PANEL <br />DN - <br />DOWN <br />EF - <br />EXHAUST FAN <br />EG - <br />EQUIPMENT GROUND <br />ENCL - <br />ENCLOSURE <br />EWC - <br />ELECTRIC WATER COOLER <br />EWH - <br />ELECTRIC WATER HEATER <br />EX - <br />EXISTING <br />FCU - <br />FAN COIL UNIT <br />FHP - <br />FRACTIONAL HORSE POWER <br />FLA - <br />FULL LOAD AMPERES <br />G - <br />GROUND <br />GFI <br />GROUND FAULT INTERRUPTER <br />_ <br />HID <br />HIGH INTENSISTY DISCHARGE <br />HORIZ - <br />HORIZONTAL <br />IG - <br />ISOLATED GROUND <br />LW - <br />LIGHT WHITE . <br />HP - <br />HORSEPOWER, HEAT PUMP <br />HVAC - <br />HEATING, 5ENTIATING AI RCONDITIONING <br />JB - <br />JUNCTION BOX <br />LRA - <br />LOCKED ROTOR AMPERES <br />MCB - <br />MAIN CIRCUIT BREAKER <br />MLO - <br />MAIN LUGS ONLY <br />N - <br />NEW <br />NL - <br />NIGHT LIGHT <br />OB - <br />OUTLET BOX <br />PB - <br />PULL BOX, PUSH-BUTTON <br />R - <br />RELOCATED <br />RECEPT - <br />RECEPTACLE <br />SF - <br />SUPPLY FAN <br />SPEC - <br />SPECIFICATIONS <br />SWECS - <br />SMOKE WARNING EMERGENCY CALL SYSTEM <br />TL - <br />TWISTLOCK <br />TTB - <br />TELEPHONE TERMINAL BOARD <br />TVTB - <br />TELEVISION TERMINAL BOARD <br />UNO - <br />UNLESS NOTED OTHERWISE <br />VERT - <br />VERTICAL <br />WM - <br />WATT MISER <br />WP - <br />WEATHERPROOF <br />WW - <br />WARM WHITE . <br />XFMR - <br />TRANSFORMER <br />0 ELECTRICAL FIRE STING DETAILS 0 ELECTRICAL F ANEL SCHEDULE O ELECTRIC,�-�� LEGEND AND SPECIFICATIONSTING <br />NOT TO SCALE SCALE: NOT TO SCALE SCALE: NOT TO SCALE <br />REVISIONS <br />BY <br />f <br />r,. <br />00 <br />u cT cn <br />M CU <br />0 00 o <br />v <br />z N vi <br />` t <br />N �n'L2 <br />N <br />¢ E <br />O <br />3 <br />00 <br />3 � 3 <br />0 <br />�-- o z N . <br />M <br />3 <br />�4 <br />' �ggCBi aSE��J <br />� <br />{{tt <br />SE - OF <br />�J 3 NA, Y� n <br />I it <br />'''r +' <br />, <br />W U 0 <br />U <br />Z <br />0 J <br />L <br />J <br />-��- —J <br />C Q -0 <br />L)m N <br />LLJ L <br />v w a <br />� Q N <br />3 <br />N <br />z <br />O <br />LI_ <br />Date: 04. 15. 13 <br />Scale: AS NOTED <br />Project Mgr: AAY <br />Drawn: IIT <br />Job: 13-08b <br />Sheet <br />E( <br />