PANEL 'SEC'
<br />PANEL SEC
<br />11/13/20 HERTZ
<br />60
<br />AUTO CALCULATIONS
<br />HI VOLTAGE
<br />208 SYM RMS AMPS
<br />22,000
<br />LOAD (VA)
<br />7,701
<br />LOW VOLTAGE
<br />120 BREAKER TYPE
<br />MCB
<br />DIVERSITY(VA)
<br />0
<br />PHASE
<br />3 MAIN LUG AMPS
<br />60A MCB
<br />25% C LOAD
<br />68
<br />#WIRES
<br />4 FED TOP/BOTTOM
<br />TOP
<br />TOTAL VA
<br />7,770
<br />NEUTRAL
<br />Y MOUNTING
<br />SURFACE
<br />TOTAL KVA
<br />8
<br />GROUND BUS Y/N
<br />Y NEMA TYPE
<br />NEMA 1
<br />CONN AMPS
<br />22
<br />GND WIRE Y/N
<br />Y MANUFACTURER
<br />SQUARE D
<br />FACTOR AMPS
<br />3
<br />WIRE THHN/THW
<br />THWN PANEL TYPE
<br />NQOD
<br />TOTAL AMPS
<br />25
<br />FROM
<br />M
<br />DESIGN AMPS
<br />60
<br />NO.OF POLES
<br />42
<br />MIN. AMPS
<br />60
<br />% FACTOR
<br />15
<br />BUSSING
<br />COPPER
<br />ISOLATED GND
<br />N
<br />X
<br />CIR # BREAKER
<br />CIRCUIT DESCRIPTION
<br />L1
<br />L2
<br />L3
<br />1 20A-1 P
<br />REC 102 A
<br />D
<br />360
<br />--
<br />-
<br />3 20A-1 P
<br />REC 102 B
<br />D
<br />-
<br />360
<br />-
<br />5 20A-1 P
<br />REC 102 C
<br />D
<br />-
<br />--
<br />360
<br />7 20A-1 P
<br />REC 102 D
<br />D
<br />360
<br />-
<br />-
<br />9 20A-1 P
<br />LTG 102 103 104 105 EF-1.4,1-5
<br />C
<br />-
<br />273
<br />-
<br />11 20A-1P
<br />REC COFFEE BREWER
<br />D
<br />-
<br />-
<br />1,200
<br />13 20A-1 P
<br />REC GENERAL ARMORY
<br />D
<br />180
<br />-
<br />--
<br />15 20A-1P
<br />REC GENERAL SECURITY
<br />D
<br />--
<br />180
<br />--
<br />17 15A-3P
<br />VAV-1.4
<br />V
<br />--
<br />--
<br />636
<br />19 --
<br />-
<br />V
<br />636
<br />-
<br />-
<br />21 -
<br />-
<br />V
<br />-
<br />636
<br />-
<br />23
<br />SPACE
<br />-
<br />-
<br />0
<br />25
<br />SPACE
<br />0
<br />-
<br />-
<br />27
<br />SPACE
<br />----
<br />0
<br />-
<br />29
<br />SPACE
<br />-
<br />-
<br />0
<br />31
<br />SPACE
<br />0
<br />--
<br />-
<br />33
<br />SPACE
<br />-
<br />0
<br />-
<br />35
<br />SPACE
<br />-
<br />-
<br />0
<br />37
<br />SPACE
<br />0
<br />-
<br />--
<br />39
<br />SPACE
<br />-
<br />0
<br />-
<br />41
<br />SPACE
<br />--
<br />-
<br />0
<br />CIR #
<br />BREAKER
<br />CIRCUIT DESCRIPTION
<br />L1
<br />L2
<br />L3
<br />2
<br />SPACE D
<br />360
<br />--
<br />-
<br />4
<br />SPACE D
<br />-
<br />360
<br />-
<br />6
<br />20A-1P
<br />SECURITY SYSTEM (BY OTHERS)
<br />-
<br />-
<br />1,200
<br />8
<br />20A-1P
<br />FACP
<br />600
<br />-
<br />-
<br />10
<br />SPACE
<br />-
<br />0
<br />-
<br />12
<br />SPACE
<br />-
<br />-
<br />0
<br />14
<br />SPACE
<br />0
<br />-
<br />-
<br />16
<br />SPACE
<br />-
<br />0
<br />-
<br />18
<br />SPACE
<br />-
<br />-
<br />0
<br />20
<br />SPACE
<br />0
<br />-
<br />-
<br />22
<br />SPACE
<br />-
<br />0
<br />-
<br />24
<br />SPACE
<br />-
<br />-
<br />0
<br />26
<br />SPACE
<br />0
<br />-
<br />-
<br />28
<br />SPACE
<br />-
<br />0
<br />-
<br />30
<br />SPACE
<br />-
<br />-
<br />0
<br />32
<br />SPACE
<br />0
<br />-
<br />-
<br />34
<br />SPACE
<br />-
<br />0
<br />-
<br />36
<br />SPACE
<br />-
<br />-
<br />0
<br />38
<br />30A-3P
<br />TVSS
<br />0
<br />-
<br />40
<br />-
<br />-
<br />--
<br />0
<br />-
<br />42
<br />-
<br />-
<br />-
<br />-
<br />0
<br />O RISER KEY NOTES
<br />1. UTILITY COMPANY TRANSFORMER. COORDINATE LOCATION WITH UTILITY COMPANY AND
<br />OWNER, AND STAKE OUT AGREED UPON LOCATION. PREPARE TRANSFORMER BASE
<br />PER UTILITY COMPANY REQUIREMENTS, STUB UP CONDUIT AND PROVIDE PRE -CAST
<br />OR CAST IN PLACE PAD PER UTILITY COMPANY REQUIREMENTS.
<br />2. PROVIDE SECONDARY OR FEEDER WIRING AS SHOWN. SEE FEEDER SCHEDULE.
<br />3. PROVIDE METER EQUIPMENT GROUP APPROVED CT METER OUTSIDE OF MEP ROOM.
<br />METER SHALL MEET ALL LOCAL REQUIREMENTS AND CERTIFICATIONS. BOND PER NEC
<br />REQUIREMENTS.
<br />4. PROVIDE 1200A RATED CT CABINET.
<br />5. PROVIDE 1200A NEMA 3R 208/120V 30. 4W FUSED DISCONNECT.
<br />6. PROVIDE NEC ARTICLE 250 COMPLIANT GROUNDING ELECTRODE SYSTEM. PROVIDE A
<br />#3/0 THWN COPPER MAIN SERVICE ELECTRODE GROUNDING CONDUCTOR IN CONDUIT
<br />FROM METER CENTER TO GROUND RODS WITH NAMEPLATE LABELED INSPECTION
<br />WELLS: PROVIDE THREE COPPER CLAD GROUND RODS, SPACED AND ARRANGED PER
<br />NEC ARTICLE 250.53, 5/8" DIA X 10'-0" LONG. DRIVE ADDITIONAL GROUND RODS
<br />TO ENSURE RESISTANCE IS 20 OHMS OR LESS. MEASURE RESISTANCE AND PROVIDE
<br />REPORT TO OWNER AND ENGINEER. CONNECT TO BUILDING STEEL, CONCRETE
<br />ENCASED ELECTRODE ('CEE') (IF NO VAPOR BARRIER PRESENT), AND METAL WATER
<br />LINES VIA #3/0 THWN CU WIRE. IF CEE IS PROVIDED, PROVIDE INSPECTION WELL
<br />OR METHOD TO INSPECT AND MONITOR CONNECTION.
<br />7. PROVIDE NEMA 3R GENERATOR DOCKING STATION FOR ATS TO PROVIDE A LOCATION
<br />FOR OWNER TO CONNECT A PORTABLE GENERATOR, TRYSTAR GENERATOR DOCKING
<br />STATION OR EQUAL. PROVIDE PAD FOR DOCKING STATION, SECURE TO STRUCTURE
<br />AND/OR PAD.
<br />8. PROVIDE 3-POLE 120/208V 1200A ATS, ASCO SERIES 300 OR APPROVED EQUAL.
<br />WHEN GENERATOR IS NOT PRESENT, ATS SHALL BE INHIBITED FROM TRANSFERRING
<br />LOAD.
<br />9. PROVIDE 120/208V 30, 4W NEMA 1 1200A MCB PANEL 'Mo. SEE PANEL SCHEDULE.
<br />SQUARE D I -LINE HCR-U OR APPROVED EQUAL.
<br />10. PROVIDE SERVICE ENTRANCE RATED, UL 3RD EDITION LISTED SURGE ARRESTOR
<br />(TVSS). INSTALL PER MANUFACTURER'S RECOMMENDATIONS.
<br />11. PROVIDE PANEL WITH INDICATED CHARACTERISTICS. SEE PANEL SCHEDULES AND
<br />FEEDER SCHEDULE.
<br />12. PROVIDE UL 3RD EDITION LISTED SURGE ARRESTOR (TVSS). INSTALL PER
<br />MANUFACTURER'S RECOMMENDATIONS.
<br />ass
<br />ELECTRICAL SCOPE
<br />1. PROVIDE ALL EQUIPMENT AND MATERIAL SHOWN ON DRAWINGS AND IN
<br />SPECIFICATIONS, WHETHER OR NOT NOTES INCLUDE THE WORDS 'PROVIDE' OR 'ALL'.
<br />2. PROVIDE ELECTRICAL FIXTURES, DEVICES AND EQUIPMENT SHOWN AND REQUIRED
<br />MATERIALS, LABOR AND EQUIPMENT FOR A COMPLETE AND OPERATIONAL FACILITY.
<br />3. POWER: COORDINATE WITH UTILITY COMPANY TO PROVIDE ELECTRICAL SERVICE.
<br />PROVIDE SECONDARY WIRING, MAIN ELECTRICAL PANEL, FEEDERS, BRANCH PANELS,
<br />BRANCH CIRCUITS, AUTOMATIC TRANSFER SWITCH, OVER CURRENT PROTECTION
<br />DEVICES, BREAKERS, EQUIPMENT CONNECTIONS, SURGE SUPPRESSION AND OTHER
<br />DEVICES AS SHOWN. PROVIDE PERMANENT LABELS ON ALL DEVICE COVERS WITH
<br />CIRCUIT NUMBER. DEVICE COLOR AND COVER PLATES SHALL BE SELECTED BY
<br />ARCHITECT. PROVIDE ENGRAVED NAMEPLATES ON ALL EQUIPMENT WITH ITEM NAME
<br />AND CIRCUIT NUMBER.
<br />4. LIGHTING: PROVIDE A COMPLETE LIGHTING SYSTEM INCLUDING LIGHT FIXTURES,
<br />BRANCH CIRCUITS, BREAKERS, SWITCHES, AND CONTROLS. OCCUPANCY AND VACANCY
<br />SENSORS SHALL BE PROVIDED TO COMPLY WITH ENERGY CODE REQUIREMENTS.
<br />EMERGENCY LIGHTING IS PROVIDED BY EMERGENCY BATTERIES INTEGRAL WITHIN
<br />DESIGNATED FIXTURES. AUTOMATIC DAYLIGHT CONTROLS ARE PROVIDED BY DAYLIGHT
<br />SENSORS WITHIN EACH DAYLIGHT ZONE. PROVIDE ROOM CONTROLLERS, POWER
<br />SUPPLIES AND ALL OTHER REQUIRED EQUIPMENT, MATERIALS AND PROGRAMMING
<br />REQUIRED FOR A COMPLETE AND FUNCTIONAL LIGHTING AND LIGHTING CONTROL
<br />SYSTEM.
<br />5. DATA: PROVIDE DATA SYSTEM AS SHOWN ON PLANS.
<br />6. FIRE ALARM SYSTEM: PROVIDE A COMPLETE SYSTEMS AS SHOWN.
<br />7. SECURITY: SECURITY CAMERAS, ACCESS CONTROL AND SECURITY INTRUSION
<br />DETECTION: COMPLETE SYSTEMS (SECURITY CAMERA, ACCESS CONTROL AND
<br />SECURITY INTRUSION DETECTION) SHALL BE PROVIDED. THE INFORMATION ON THE
<br />PLANS IS DIAGRAMMATIC AND PROVIDED FOR LAYOUT COORDINATION PURPOSES.
<br />SHOP DRAWINGS SHALL BE PROVIDED FOR LOW VOLTAGE PERMITTING AND
<br />INSTALLATION WILL BE PROVIDED BY THE DEVELOPER'S SUB -CONTRACTORS. THE
<br />SHOP DRAWINGS SHALL SHOW ALL DEVICE LOCATIONS, WIRING, POWER SOURCES,
<br />EQUIPMENT LOCATIONS AND INSTALLATION REQUIREMENTS. CUT SHEET FOR
<br />EQUIPMENT WILL BE PROVIDED, AS WELL AS CALCULATIONS FOR ANY BATTERY
<br />BACKUP REQUIREMENTS. SYSTEMS SHALL BE INSTALLED, TESTED AND CONNECTED TO
<br />OWNER DESIGNATED MONITORING SERVICES (IF MONITORING IS APPLICABLE OR
<br />REQUIRED). SYSTEMS NOT SHOWN IN PLANS, VERIFY REQUIREMENTS: NURSE CALL
<br />OR EXAM ROOM 'IN USE' LIGHTS.
<br />8. WORKMANSHIP FOR ALL ELECTRICAL SYSTEMS SHALL BE NEAT AND PROFESSIONAL
<br />AND SHALL COMPLY WITH CURRENT NECA/NEIS STANDARDS.
<br />F3
<br />CT NORMAL
<br />O O CABINET POWER --------- --
<br />MAIN QUICK CONNECT/
<br />UTILITY PROVIDED M NEMA 3R DISCONNECT GENERATOR
<br />NEMA 3R DOCKING STATION
<br />120/208 VOLT - - O5
<br />TRANSFORMER; 0 1200A
<br />AVAILABLE FAULT CURRENT FUSES
<br />(AFC) CALCULATED USING: 1200A S2 120/208V G3
<br />120/208V 30,4W
<br />Z=1.6%, POWER FACTOR = .9, 30,4W OWNER PROVIDED
<br />AND 300kVA: PORTABLE
<br />AFC = 57,828 AMPS. GENERATOR
<br />SCCR=65KA CABLES
<br />INSTALLED HERE,
<br />BY OTHERS
<br />b O2 TYPICAL
<br />L-------------------------J
<br />MEP ROOM SECURITY SW AREA NW AREA SE AREA SHARED NW AREA
<br />r------------------------------- --------------------------------------- --------�
<br />- _---_--------------------------- ----- ------
<br />F4 I r---------------- � 2 TYPICAL I
<br />----------- ----- -----
<br />1l l f =__ __ ______ - -- 1 I I I
<br />__l I I I F9 I
<br />ram-- ---� IIIIII I I F6 I F7 I F8 I I
<br />I I IIIIII F5 I 10 I I I I I
<br />ATS MAIN PANEL PANEL PANEL PANEL PANEL PANEL
<br />PANEL 'M' 'NE' 'SEC' 'SW' 'NW' 'SE' 'NW2'
<br />NEMA 1
<br />NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1 NEMA 1
<br />(D SPACE
<br />POLE 42 POLE 72 POLE 72 POLE 72 POLE 42 POLE
<br />(DSPACE SPACE SPACE SPACE SPACE SPACE
<br />1200A
<br />120/208V 1200A MCB 11 11 11 11 11 11
<br />30,4W 120/208V 200A MCB 60A MCB 200A MCB 200A MCB 200A MCB 60A MCB
<br />30,4W 120/208V 120/208V 120/208V 120/208V 120/208V 120/208V
<br />30,4W 34,4W 30,4W 30.4W 30,4W 30,4W
<br />a a a 12 a 12 a 12 a
<br />in V Ln LLn
<br />10 12 12 12
<br />GENERAL
<br />NOTES
<br />1.
<br />WORK SHALL MEET OR EXCEED REGULATORY
<br />11. CONTRACTOR SHALL OBTAIN AND PAY FOR PERMITS AND
<br />NAMEPLATES ATTACHED TO EQUIPMENT BY STAINLESS
<br />RECEPTACLES FOR SECURITY PANELS, HVAC EMS PANELS,
<br />REQUIREMENTS, INCLUDING LATEST EDITION OF THE NFPA
<br />INSPECTIONS.
<br />STEEL SCREWS.
<br />COMPUTER OUTLETS, SOUND / INTERCOM SYSTEM AND
<br />101 (LIFE SAFETY CODE), THE KENTUCKY BUILDING CODE
<br />CABLE TV HEAD END EQUIPMENT AND TV RECEPTACLES
<br />FIRST EDITION (2018), THE NATIONAL ELECTRICAL CODE
<br />12. EXPOSED EXTERIOR CONDUIT SHALL BE RIGID GALVANIZED
<br />18. WIREWAYS, PULLBOXES, OUTLETS AND JUNCTION BOXES
<br />WITH CORD & PLUG.
<br />2014, AND LOCAL REQUIREMENTS & BUILDING CODES.
<br />STEEL. ALL EXPOSED INTERIOR CONDUIT SHALL BE RIGID
<br />SHALL BE PROPERLY SIZED PER THE NATIONAL
<br />GALVANIZED STEEL OR EMT. MC CABLE IS ALLOWABLE
<br />ELECTRICAL CODE. ALL PULLBOXES AND OUTLET BOXES
<br />28. BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR NO
<br />2.
<br />EQUIPMENT, FIXTURES, SWITCHES, STARTERS, CONTACTORS,
<br />WHERE CONCEALED AND ALLOWED BY CODE. CONDUIT
<br />SHALL BE PLAINLY COLOR CODED AND HAVE WIRING
<br />MORE THAN 3% VOLTAGE DROP AT THE FARTHEST POINT.
<br />CONTROLS, DEVICES, CONNECTIONS, BOXES, MOUNTING
<br />INSTALLED BELOW SLAB OR UNDERGROUND MAY BE
<br />TAGGED TO INDICATE PANEL AND CIRCUIT NUMBERS.
<br />20 AMPERE BRANCH CIRCUITS SHALL HAVE MINIMUM SIZE
<br />SUPPORTS, HARDWARE, WIRE, CONDUIT & ACCESSORIES
<br />SCHEDULE 40 PVC OR RIGID GALVANIZED STEEL PAINTED
<br />#10 COPPER HOMERUN WIRING FOR CIRCUITS OVER 57'
<br />SHALL BE PER PLANS AND SPECIFICATIONS FOR
<br />WITH HEAVY COAT OF BITUMASTIC PAINT (3/4" MINIMUM).
<br />19. DISCONNECT SWITCHES SHALL BE SQUARE D, SIEMENS,
<br />LONG & #8 COPPER HOMERUN WIRING FOR CIRCUITS
<br />COMPLETE AND OPERATING ELECTRICAL SYSTEMS.
<br />CONDUIT SHALL BE CONCEALED WHERE POSSIBLE.
<br />GENERAL ELECTRIC OR CUTLER HAMMER SAFETY
<br />OVER 150' LONG. WHERE BRANCH CIRCUITS AND FEEDER
<br />CONCEALED CONDUIT IN WALLS AND CEILINGS SHALL BE
<br />SWITCHES. SWITCHES SHALL BE HEAVY DUTY AND RATED
<br />CIRCUITS ARE OVERSIZED FOR VOLTAGE DROP, ENSURE
<br />3.
<br />CIRCUIT NUMBERS INDICATED ON THE DRAWINGS ARE FOR
<br />EMT. EMT FITTINGS SHALL BE DIE CAST SET SCREW
<br />FOR THE PROPER VOLTAGE. SWITCHES SHALL BE RATED
<br />LUGS AND OTHER TERMINALS FOR MAIN CIRCUIT
<br />REFERENCE USE, CONTRACTOR TO BALANCE THE LOADS
<br />TYPE AT DRY INTERIOR LOCATIONS. EMT FITTINGS AT
<br />AS INDICATED ON THE DRAWINGS FOR SIZE, NUMBER OF
<br />BREAKERS, BRANCH CIRCUIT BREAKERS, DISCONNECT
<br />IN ALL PANELS IN WHICH WORK IS PERFORMED.
<br />DAMP, OR WET LOCATIONS SHALL BE DIE CAST
<br />POLES AND TYPE ENCLOSURE.
<br />SWITCHES, OR ANY OTHER EQUIPMENT WITH LUGS FOR
<br />MAINTAIN COMPLETE AS -BUILT DRAWINGS. PROVIDE
<br />COMPRESSION RAIN -TIGHT TYPE. WIRING (POWER,
<br />WIRING TERMINATION ARE LARGE ENOUGH TO TERMINATE
<br />ELECTRONIC AS -BUILT DRAWINGS AT COMPLETION OF
<br />LIGHTING, FIRE ALARM) SHALL BE IN CONDUIT.
<br />20. FUSES SHALL BE BUSSMAN CURRENT LIMITING TYPE.
<br />THE OVERSIZED WIRING.
<br />PROJECT. ELECTRONIC SET OF DRAWINGS WILL BE
<br />PROVIDED FOR USE TO UPDATE THROUGHOUT PROJECT.
<br />13. RECESSED LIGHTING FIXTURES SHALL HAVE THERMAL
<br />21. LETTER INSIDE OR ADJACENT TO FIXTURE SYMBOL
<br />29• DISPOSE OF LAMPS, BALLASTS, & OTHER HAZARDOUS
<br />PROTECTION. PROVIDE A FIXTURE SUPPORT AT EACH
<br />INDICATED TYPE - SEE FIXTURE SCHEDULE.
<br />MATERIALS IN ACCORDANCE WITH FEDERAL, STATE, LOCAL,
<br />4.
<br />PROVIDE ENGRAVED NAMEPLATES FOR ALL ELECTRICAL
<br />CORNER FOR ALL LAY -IN LIGHT FIXTURES, OR PROVIDE
<br />& EPA REGULATIONS.
<br />EQUIPMENT.
<br />UL LISTED FIXTURE CLIPS AND REQUIRED MOUNTING
<br />22. FOR EXACT LOCATIONS OF INTERIOR LIGHTING FIXTURES,
<br />HARDWARE & ACCESSORIES. DRIVERS AND BALLASTS
<br />SEE ARCH. REFLECTED CEILING PLANS.
<br />30. MOTOR STARTERS, SAFETY SWITCHES, VARIABLE SPEED
<br />5.
<br />PROVIDE REQUIRED CONDUIT & CABLE PENETRATIONS
<br />SHALL BE FUSED.
<br />DRIVES, RELAYS, MOTOR CONTROL CENTER, MDP'S,
<br />THROUGH PARTITIONS, WALLS, FLOORS, SLABS & ROOFS,
<br />23. PROVIDE TELEPHONE/DATA OUTLETS WITH WIRING BACK
<br />SWITCHBOARDS, PANELBOARDS, CONTACTORS, & ALL
<br />WITH APPROVED FIRE SEALANT COMPOUND.
<br />14. PROVIDE GREEN GROUND WIRE IN EACH RACEWAY, SIZE
<br />TO TELEPHONE BOARD AND NETWORK SERVER.
<br />OTHER ELECTRICAL EQUIPMENT, SHALL BE OF THE SAME
<br />WIRE IN ACCORDANCE WITH TABLE 250.122 OF THE NEC.
<br />MANUFACTURER UNLESS PROVIDED AS ELECTRICAL
<br />6.
<br />CONDUCTORS SHALL BE COPPER, 600 VOLT WITH
<br />24. WHERE RECEPTACLES ARE INSTALLED CLOSER THAN 72"
<br />EQUIPMENT ON APPROVED FACTORY FABRICATED
<br />MINIMUM SIZE OF #12 AWG THWN / THHN, UNLESS
<br />15. PANELBOARDS SHALL BE CIRCUIT BREAKER TYPE AS
<br />FROM EDGE OF SINK OR LAV, RECEPTACLE SHALL BE OF
<br />EQUIPMENT, SUCH AS CHILLER STARTERS, ROOF TOP
<br />OTHERWISE SPECIFIED. WIRE SIZES OF #10 AND LARGER
<br />MANUFACTURED BY SQUARE D, SIEMENS, GENERAL
<br />THE GROUND FAULT CIRCUIT INT. TYPE, OR SERVED BY A
<br />UNITS, CONDENSING UNITS, ETC.
<br />SHALL BE STRANDED.
<br />ELECTRIC, OR CUTLER HAMMER, OR AS NOTED.
<br />GFCI BREAKER.
<br />PANELBOARDS SHALL HAVE A HINGED LOCKING DOOR.
<br />31. PROVIDE FLEXIBLE CONDUIT & WIRING CONNECTION TO
<br />7.
<br />EQUIPMENT SHALL BE RATED FOR MAXIMUM AVAILABLE
<br />PANELS RATED 600 AMPS AND LARGER SHALL HAVE
<br />25. EXTERIOR RECEPTACLES SHALL BE WP GFCI TYPE WITH
<br />MOTORS &VIBRATING EQUIPMENT.
<br />VOLTAGE AND GROUND FAULT CURRENT. ALL EQUIPMENT
<br />HINGES ON THE COVER SO THAT THE COVER IS
<br />WP WHILE IN USE COVER. PROVIDE RECEPTACLE AT
<br />SHALL BE TESTED BY A NATIONAL TESTING LAB.
<br />SUPPORTED AND MAY SWING TO THE SIDE WHEN THE
<br />HVAC EQUIPMENT.
<br />32. OUTDOOR EQUIPMENT, CONDUIT & CONNECTIONS SHALL
<br />COVER BOLTS ARE REMOVED.
<br />BE WEATHERPROOF.
<br />8.
<br />CONTRACTOR SHALL COORDINATE ELECTRICAL
<br />26. IN ADDITION TO THE LEGEND THE CONTRACTOR SHALL
<br />REQUIREMENTS AND MAKE FINAL CONNECTIONS OF
<br />16. PROVIDE A TYPEWRITTEN CIRCUIT DIRECTORY WITH
<br />COORDINATE EXACT LOCATION OF OUTLETS AND DEVICES
<br />33. PROVIDE A DEDICATED NEUTRAL FOR ALL CIRCUITS.
<br />EQUIPMENT FURNISHED BY OTHER TRADES.
<br />PROTECTIVE COVERING. WIRES IN PANEL SHALL BE
<br />WITH ARCHITECTURAL INTERIOR ELEVATIONS & CABINET
<br />TAGGED WITH CIRCUIT NUMBER. CIRCUIT BREAKERS FOR
<br />WORK.
<br />34. WHERE GFCI RECEPTACLES ARE SHOWN, A SEPARATE GFCI
<br />9.
<br />CONTRACTOR SHALL MAINTAIN A COMPLETE TEMPORARY
<br />MECHANICAL EQUIPMENT SHALL BE HACR TYPE.
<br />DEVICE SHALL BE PROVIDED, THEY SHALL NOT BE
<br />POWER SYSTEM DURING CONSTRUCTION. COORDINATE ALL
<br />27. PROVIDE SERVICE RATED LIGHTNING SURGE ARRESTOR &
<br />SLAVED.
<br />POWER OUTAGES & CHANGEOVERS WITH THE OWNER.
<br />17. SWITCHBOARDS, MCC'S, PANELBOARDS, CIRCUIT BREAKERS,
<br />SERVICE RATED TVSS SURGE PROTECTION AT THE MAIN
<br />TRANSFORMERS, DISCONNECT SWITCHES, MOTOR STARTERS
<br />SERVICE ENTRANCE. PROVIDE SUBPANEL RATED TVSS
<br />35. PRIOR TO COMPLETION OF THE PROJECT, PROVIDE
<br />10.
<br />CONTRACTOR SHALL GUARANTEE MATERIALS AND
<br />AND OTHER ELECTRICAL APPARATUS INSTALLED FOR THE
<br />SURGE PROTECTION AT PANELS PROVIDING POWER TO
<br />WRITTEN CERTIFICATION FOR EACH LIFE SAFETY AND LOW
<br />WORKMANSHIP FOR ONE YEAR.
<br />OPERATION OF ANY EQUIPMENT SHALL BE PROPERLY
<br />HVAC EQUIPMENT, MOTORS, COMPUTERS AND ELECTRONIC
<br />VOLTAGE ELECTRICAL SYSTEM.
<br />IDENTIFIED WITH ENGRAVED LAMINATED PLASTIC
<br />EQUIPMENT. PROVIDE SURGE PROTECTION TYPE
<br />f�SniF^�1
<br />U i( Ss yA
<br />u�r. _cut! Ib. ron t t ",a9i
<br />The- plans ere coppphted end» subject 10
<br />copyrvl pmwbw n - YrchRa t work' under
<br />sac 102 of as copyright as 17 u a.o.a
<br />emend.d Doo-ber 1990 and known-.."eclur.l
<br />woke capydghl probacbm nt of 1990. The
<br />protschon inoluOn bulls not bmtso d to the nnab
<br />forma well ee arrangement and compoaPoon d
<br />spoon and elements of the deignunder such
<br />p"'c""' uns.ftmad u-of dross plena, work or
<br />home repr-ent d, an lagelly muh in Me cn-ban
<br />of conal-bon or bulldmps being seed endo
<br />monat" compen-bon to 1.1119MloRDERRemps m ,
<br />Flonde regabsbon AA21=460
<br />ISSUE DATE
<br />09/21 /2020
<br />REVISIONS
<br />as
<br />m
<br />-
<br />-
<br />m
<br />O
<br />rc
<br />-soLL
<br />L
<br />c
<br />V,
<br />CL,-
<br />W
<br />-_
<br />N
<br />Q`
<br />N
<br />�
<br />�
<br />con
<br />/
<br />a)
<br />CO
<br />N
<br />FEEDER SCHEDULE
<br />Q
<br />V
<br />-'
<br />w
<br />(n
<br />V IT
<br />W
<br />J
<br />W
<br />AVAILABLE
<br />AVAILABLE
<br />AMPERE INTERUPT
<br />DISTANCE
<br />VOLTAGE
<br />SINGLE OR
<br />CONDUIT
<br />RISER
<br />ID
<br />FROM
<br />TO
<br />AMPERAGE
<br />(AMPS)
<br />LOAD
<br />(AMPS)
<br />FAULT CURRENT
<br />(AFC) L-L (AMPS)
<br />FAULT CURRENT
<br />(AFC) L-N (AMPS)
<br />CAPACITY RATING
<br />(AIC RATING)
<br />(HORIZ+VERY)
<br />(FEET)
<br />DROP
<br />N
<br />THREE PHASE
<br />10 / 30
<br /># OF
<br />SETS
<br />CONDUCTOR
<br />MATERIAL
<br />PHASE CONDUCTORS
<br />QTY SIZE
<br />NEUTRAL CONDUCTOR
<br />QTY SIZE
<br />GROUND EGC/GEC
<br />QTY GEC/EGC SIZE
<br />SIZE
<br />(PER SE
<br />CONDUIT
<br />MATERIAL
<br />S1
<br />UTIL
<br />CT CABINET
<br />1,200
<br />955
<br />48,262
<br />41,404
<br />65,000
<br />40
<br />0.37%
<br />3
<br />4
<br />CU
<br />3
<br />#400 KCM
<br />1
<br />#400 KCM
<br />1
<br />GEC
<br />#3/0
<br />3"
<br />PVC
<br />S2
<br />CT CABINET
<br />MAIN D/C
<br />1,200
<br />955
<br />47,112
<br />39,737
<br />65,000
<br />5
<br />0.43%
<br />3
<br />4
<br />CU
<br />3
<br />#400 KCM
<br />1
<br />#400 KCM
<br />1
<br />EGC
<br />#4/0
<br />3"
<br />EMT
<br />F3
<br />MAIN D/C
<br />MTS N
<br />1,200
<br />955
<br />46,014
<br />38,199
<br />65,000
<br />5
<br />0.48%
<br />3
<br />4
<br />CU
<br />3
<br />#400 KCM
<br />1
<br />#400 KCM
<br />1
<br />EGC
<br />#4/0
<br />3"
<br />EMT
<br />G3
<br />GDS
<br />MTS SB
<br />1,200
<br />955
<br />34,667
<br />28,865
<br />65,000
<br />5
<br />0.62%
<br />3
<br />4
<br />CU
<br />3
<br />#400 KCM
<br />1
<br />#400 KCM
<br />1
<br />EGC
<br />#4/0
<br />3"
<br />1 EMT
<br />F4
<br />MTS N
<br />M
<br />1,200
<br />955
<br />42,887
<br />34,071
<br />65,000
<br />15
<br />0.65%
<br />3
<br />4
<br />CU
<br />3
<br />#350 KCM
<br />1
<br />#350 KCM
<br />1
<br />EGC
<br />#3/0
<br />3"
<br />EMT
<br />F5
<br />M
<br />NE
<br />200
<br />120
<br />37,652
<br />27,903
<br />42,000
<br />5
<br />0.70%
<br />3
<br />1
<br />CU
<br />3
<br />#3/0
<br />1
<br />#3/0
<br />1
<br />EGC
<br />#6
<br />2"
<br />EMT
<br />F6
<br />M
<br />SW
<br />200
<br />123
<br />9,582
<br />5,220
<br />22,000
<br />125
<br />1.85%
<br />3
<br />1
<br />CU
<br />3
<br />#3/0
<br />1
<br />#3/0
<br />1
<br />EGC
<br />#6
<br />2"
<br />EMT
<br />F7
<br />M
<br />NW
<br />200
<br />187
<br />11,237
<br />6,219
<br />22,000
<br />130
<br />2.09%
<br />3
<br />1
<br />CU
<br />3
<br />#250 KCM
<br />1
<br />#250 KCM
<br />1
<br />EGC
<br />#4
<br />2 1/2"
<br />EMT
<br />F8
<br />M
<br />SE
<br />200
<br />111
<br />13,300
<br />7,510
<br />22,000
<br />80
<br />1.34%
<br />3
<br />1
<br />CU
<br />3
<br />#3/0
<br />1
<br />#3/0
<br />1
<br />EGC
<br />#6
<br />2"
<br />EMT
<br />F9
<br />M
<br />NW2
<br />60
<br />12
<br />1,858
<br />943
<br />22,000
<br />150
<br />1.34%
<br />3
<br />1
<br />CU
<br />3
<br />#6
<br />1
<br />#6
<br />1
<br />EGC
<br />#10
<br />1"
<br />EMT
<br />F10
<br />M
<br />SEC
<br />60
<br />25
<br />4,361
<br />1 2,264
<br />22,000
<br />60
<br />1.23%
<br />3
<br />1
<br />CU
<br />3
<br />#6
<br />1 1
<br />1 #6
<br />1
<br />EGC
<br />#10
<br />1"
<br />EMT
<br />NOTES:
<br />1. LENGTHS ARE FOR FAULT CURRENT AND VOLTAGE DROP CALCULATIONS ONLY. CONTRACTOR SHALL FIELD VERIFY ALL CONDUIT
<br />2. SELECTED FEEDERS PHASE AND EGC CONDUCTORS ARE OVERSIZED FOR VOLTAGE DROP.
<br />ROUTES AND LENGTHS.
<br />LUMINAIRE SCHEDULE
<br />MARK
<br />VOLTAGE
<br />LAMP TYPE
<br />WATTS
<br />MOUNTING
<br />DIMMING
<br />DESCRIPTION
<br />L1(EM)
<br />METALUX CRUZE 24CZ2 40 UNV (EL7W) L835 CD1
<br />UNV
<br />LED
<br />40
<br />GRID LAY -IN
<br />0-1 OV
<br />2'X4' LED GRID LAY -IN FLAT PANEL, 0-1 OV DIMMING; (WITH EMERGENCY BATTERY)
<br />L2
<br />METALUX 4VVNLED LD4 32SL F UNV CD1
<br />UNV
<br />LED
<br />29
<br />CEILING SURFACE
<br />0-10V
<br />SURFACE MOUNTED STRIP LIGHT FOR UTILITY ROOMS
<br />L3(EM)
<br />HALO COMMERCIAL HC6 20 D010 (REM7) HM6 12 835 61 MD X 61 PS WD W
<br />UNV
<br />LED
<br />21
<br />RECESSED CEILING
<br />0-10V
<br />RECESSED 6 INCH LED (WITH EMERGENCY BATTERY)
<br />L4 (EM)
<br />HALO COMMERCIAL HC6 20 DO 10 HM6 12 835 61 MD X 61 PS WD W
<br />UNV
<br />LED
<br />21
<br />RECESSED CEILING
<br />0-10V
<br />RECESSED 6 INCH LED, WET LOCATION LISTED (WITH EMERGENCY BATTERY)
<br />L5(EM)
<br />CORONET LS4 LED UPDN 4 35 IN-LTG1 D-LTG1 UNV DB WAC IN -SD D-SD (EM 120V)
<br />UNV
<br />LED
<br />36
<br />PENDANT
<br />0-10V
<br />PENDANT LIGHT, 4' DECORATIVE STRIP (WTH EM BATTERY)
<br />L6
<br />METALUX 2 BCLED LD4 20SL F UNV 835 CD1
<br />UNV
<br />LED
<br />23
<br />WALL
<br />0-1 OV
<br />WALL MOUNTED VANITY LIGHT
<br />L8 (EM)
<br />COOPER INVUE ENC-E02-LED-El-BL3-XX-8030-BBB120-DIM
<br />UNV
<br />LED
<br />52
<br />EXTERIOR WALL
<br />0-1 OV
<br />WALL MOUNTED EXTERIOR LIGHT, COLOR TEMPERATURE AND FINISH BY ARCHITECT.
<br />X
<br />SURELITE LPX7 SD
<br />UNV
<br />LED
<br />10
<br />WALL/CEILING
<br />NO
<br />LED EXIT LIGHT WITH BATTERY, OPTIONS SELECTED BYARCHITECT
<br />NOTES:
<br />1. VERIFYCOLOR TEMPERATURE OF ALL LAMPS PRIOR TO ORDERING. ALL LUMINAIRES SHALL BE SAME COLOR TEMP UNLESS DIRECTED OTHERVVISE.
<br />2. PROVIDE PROPER SUPPORT FOR ALL LUMINAIRES.
<br />3. PROVIDE FUSES FOR ALL LUMINAIRES.
<br />4. PROVIDE LAMPS FOR ALL FIXTURES.
<br />DATE: 11 /13/2020
<br />DRWN: J.D.E.
<br />CHKD: J.J.H.
<br />SCALE: 1 /8" = V-0"
<br />SHEET NUMBER
<br />E�6
<br />2:4
<br />1-0