_ L <br />I I 1111 If I I <br />GENERAL NOTES: <br />THIS BUILDING HAS BEEN DESIGNED TO CONFORM TO THE 2011 FLORIDA BUILDING CODE <br />6TH EDITION AND THE 2011 FLORIDA BUILDING CODE - RESIDENTIAL 6TH EDITION, <br />T.L. HANSON A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL ENGINEERING <br />COMPANY: HAS APPLIED "RATIONAL ANALYSIS" FOR THE STRUCTURAL DESIGN OF THIS STRUCTURE. <br />THE BUILDING (INCLUDING ALL COMPONENTS AND CLADDINGS) SHALL BE DESIGNED FOR THE <br />FOLLOWING SUPERIMPOSED LOADS: <br />FLOORS: <br />LIVE LOAD - 40 P.S.F. <br />DEAD LOAD - 10 P.S.F. <br />ROOF: <br />LIVE LOAD (TRUSS TOP CHORD) - 20 P.S.F. <br />DEAD LOAD (TRUSS TOP CHORD) - 10 P.S.F. (15 P.S.F. WHEN TILE ROOFING IS INSTALLED) <br />DEAD LOAD (TRUSS BOTTOM CHORD) - 10 P.S.F, <br />ASSUMED TRUSS SELF WEIGHT (DEAD LOAD) - l P.S.F. <br />WIND: <br />BUILDING 15 DESIGNED TO CONFORM TO ASCE 1-10, CHAPTERS 26 THRU 31; PER 2011 FLORIDA <br />BUILDING CODE, RESIDENTIAL 6TH EDITION - SECTION R301.2.1.1. AND 2011 FLORIDA BUILDING CODE <br />6TH EDITION SECTION 1609.1.1, <br />COMPONENT 4 CLADDING WIND LOADS <br />WIND DESIGN ASSUMPTIONS: <br />BUILDING EXPOSURE - B <br />BUILDING RISK CATEGORY - 11 <br />MEAN ROOF HEIGHT 30' OR LESS <br />HEIGHT 4 EXPOSURE ADJUSTMENT <br />COEFFICIENT • 1.0 <br />ENCLOSED BUILDING <br />INTERNAL PRESSURE COEFFICIENT • +/- 0.18 <br />WIND SPEED SHOWN AT THE BOTTOM RIGHT <br />CORNER OF THIS SHEET <br />ALL STRUCTURAL ELEMENTS, EXTERIOR <br />WALLS AND INTERIOR WALLS SHALL BE <br />TYPE V CONSTRUCTION PER FBC 602.5 <br />ALL OTHER <br />BUILDING <br />ROOF OVERHANG <br />COMPONENT <br />ZONE <br />LOADS <br />LOADS <br />I <br />N/A <br />+32.3/-35.3 <br />2 <br />-65.1 <br />+32.3/-56.2 <br />3 <br />-110.6 <br />+32.3/-89.0 <br />4 <br />N/A <br />+35.3/-38.2 <br />5 <br />N/A <br />+35.3/-41.2 <br />SOIL BEARING 4 COMPACTION: <br />THESE PLANS WERE DRAWN BASED UPON AN ALLOWABLE SOIL BEARING CAPACITY OF 2,000 P.S.F. <br />(MINIMUM). THE CONTRACTOR/PROPERTY OWNER ARE RESPONSIBLE FOR VERIFYING THAT THE SOIL <br />ON THE SITE IS PROPERLY PREPARED 4 COMPACTED SUCH THAT IT CAN SUPPORT A 2,000 P.S.F. <br />FOUNDATION LOADING. <br />T.L. HANSON; A REGISTERED, LICENSED, FLORIDA PROFESSIONAL STRUCTURAL <br />ENGINEERING COMPANY: DESIGNED THESE FOUNDATIONS WITHOUT VISITING THE CONSTRUCTION S1TE <br />NOR PERFORMING ANY SOIL TESTING. <br />T.L. WAN50N SHALL NOT BE RESPONISIBLE FOR THE SITE SOILS ABILITY TO SUPPORT <br />THE BUILDING LOADS. <br />FOUNDATIONS 4 SLAB -ON -GRADE: <br />BUILDING SITE SHALL BE SCRAPED TO REMOVE ALL ORGANIC MATERIALS WITHIN THE BUILDING AREA. <br />ANY ADDITIONAL FILL PLACED ON THE BUILDING PAD AREA, SHALL BE COMPACTED <br />SUCH THAT IT CAN ADEQUATELY SUPPORT A 2,000 P.S.F. FOUNDATION LOADING. <br />SLAB SHALL BE PLACED OVER A 6 MIL VAPOR BARRIER ON CLEAN, ADEQUATELY <br />COMPACTED AND TERMITE POISONED SOIL, <br />CONCRETE UTILIZED IN THE FOUNDATIONS AND SLABS SHALL HAVE A MINIMUM 28 DAY <br />COMPRESSIVE STRENGTH OF 2,500 P.S.I. <br />REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE <br />WITH ASTM A-615. LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 25" <br />FOR •5 REBAR, 30" FOR •6 REBAR 4 35" FOR 01 REBAR. <br />PLANS ARE ENGINEERED FOR A MAXIMUM STEMWALL HEIGHT OF 4 COURSES (AFTER <br />FINAL SITE GRADING). THE CONTRACTOR OR BUILDING OWNER SHALL DETERMINE THE <br />EXACT STEMWALL HEIGHT BASED UPON SITE CONDITIONS PRIOR TO POURING THE FOUNDATION <br />AND CONTACT ARKAY ENGINEERING WHEN MORE THAN 4 COURSES ARE REQUIRED. <br />A FOUNDATION SURVEY SHALL BE PERFORMED AND A COPY OF THE SURVEY SHALL BE ON THE <br />SITE FOR THE BUILDING INSPECTORS USE, OR ALL PROPERTY MARKERS SHALL BE EXPOSED AND <br />A STRING STRETCHED FROM MARKER TO MARKER TO VERIFY THE REQUIRED BUILDING SETBACKS. <br />MASONRY WALLS: <br />CONCRETE MASONRY UNITS SHALL BE HOLLOW UNIT MASONRY IN ACCORDANCE WITH ASTM C-90 <br />AND SHALL HAVE A MINIMUM F'M OF 1,500 P.5.1. <br />MORTAR SHALL CONFORM TO ASTM C-210 AND SHALL BE EITHER TYPE M OR S. <br />REINFORCING STEEL SHALL BE GRADE 40 MINIMUM AND IDENTIFIED IN ACCORDANCE <br />WITH ASTM A-615. LAP SPLICES, WHERE REQUIRED, SHALL BE A MINIMUM OF 25" <br />FOR 05 REBAR, 30" FOR 06 REBAR 4 35" FOR "1 REBAR. <br />GROUT FOR THE POURED CELLS AND LINTELS SHALL HAVE A MAXIMUM COURSE AGGREGATE SIZE <br />OF 3/8", PLACED AT AN 8 TO 11 INCH SLUMP AND HAVE A MINIMUM 28 DAY COMPRESSIVE STRENGTH <br />OF 2,500 P.S.I. (WHEN TESTED PER ASTM C-1019), <br />PROVIDE CLEAN -OUT OPENINGS (12 $0. IN.) IN CELLS CONTAINING SPLICED REINFORCEMENT, WHEN <br />THE GROUT POUR EXCEEDS 5 FEET IN HEIGHT. <br />TIMBER MATERIALS: <br />ALL TIMBER MATERIALS SHALL BE AS FOLLOWS: <br />ALL LUMBER IN CONTACT WITH MASONRY WILL BE PRESSURE TREATED <br />MATERIALS <br />INTERIOR STUD WALLS TO BE OF 2 X 4 02 SPRUCE OR BETTER WITH SINGLE 2 X 4 P.T. <br />PINE BOTTOM PLATE AND SINGLE 2 X 4 02 SPRUCE TOP PLATE WITH STUDS SPACED <br />MAXIMUM 24" OC. WALLS TO HAVE 1/2" GYPSUM BOARD EACH SIDE, WITH WALLS AT <br />GARAGE TO HAVE MINIMUM R-I1 INSULATION <br />ATTIC ACCESS: <br />ATTIC ACCESS SHALL BE PROVIDED TO ATTIC AREAS EXCEEDING 30 80. FT. AND HAVING MINIMUM <br />30 INCHES OF VERTICAL HEIGHT. ROUGH -FRAMED OPENING NOT TO BE LESS THAN 22 X 30 INCHES. <br />WHEN MECHANICAL EQUIPMENT IS LOCATED IN THE ATTIC, IT SHALL BE INSTALLED IN ACCORDANCE <br />WITH THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION M1305.1,3 <br />GARAGE: <br />NO OPENINGS SHALL BE PERMITTED FROM A GARAGE INTO A SLEEPING ROOM. OTHER OPENINGS <br />BETWEEN THE GARAGE AND RESIDENCE SHALL HAVE A DOOR (MIN. 1 3/8" THICK), OF SOLID WOOD, <br />SOLID OR HONEYCOMB CORE STEEL, OR 20-MINUTE FIRE -RATED WITH SELF CLOSING HINGES. <br />WALLS SEPARATING THE GARAGE AND RESIDENCE SHALL HAVE MIN, 1/2" GYPSUM BOARD <br />APPLIED TO THE GARAGE SIDE. THE CEILING SHALL HAVE MIN. 1/2" GYPSUM BOARD APPLIED <br />TO THE GARAGE SIDE. GARAGES BENEATH HABITABLE ROOMS SHALL BE SEPARATED BY ALL <br />HABITABLE ROOMS ABOVE WITH MIN, 5/8" 'TYPE-X' GYPSUM BOARD IN COMPLIANCE WITH THE <br />FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R30S <br />THE CLIENT UNDERSTANDS THAT THE DESIGNER CARRIES NO LIABILITY INSURANCE AND THEREFORE <br />AGREES TO HOLD HARMLESS, IDEMNIFY, AND DEFEND DESIGNER FROM ALL CLAIMS, LOSSES AND <br />EXPENSES (INCLUDING REASONABLE ATTORNEY FEES) ARISING OUT OF OR RESULTING FROM THE <br />PROJECT. THE DESIGNER WILL IN GOOD FAITH ATTEMPT TO PROVIDE ERROR FREE CONSTRUCTION <br />DRAWINGS, BUT IN THE EVENT ERRORS OCCUR THE DESIGNER WILL NOT BE LIABLE FOR COST OF <br />REPAIRS OR DELAY TO THE CONSTRUCTION <br />SOIL TERMITE TREATMENT: <br />TERMITE PROTECTION SHALL BE PROVIDED BY REGISTERED TERMITICIDES, INCLUDING PESTICIDES <br />APPLIED TO SOIL, OR WOOD, BAITING SYSTEMS, OR OTHER APPROVED PROTECTION LABELED FOR <br />USE AS A PREVENTATIVE TREATMENT TO NEW CONSTRUCTION. <br />A "CERTIFICATE OF COMPLIANCE" SHALL BE ISSUED TO THE BUILDING DEPARTMENT BY A LICENSED <br />PEST CONTROL COMPANY BEFORE A "CERTIFICATE OF OCCUPANCY" WILL BE ISSUED. THE CERTIFICATE <br />SHALL STATE <br />"THE BUILDING HAS RECEIVED A COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN <br />TERMITES. THE TREATMENT IS IN ACCORDANCE WITH THE RULES AND LAWS OF THE FLORIDA <br />DEPARTMENT OF AGRICULTURE AND CONSUMER SERVICES," <br />IF A REGISTERED TERMITICIDE BAIT SYSTEM IS TO BE USED FOR SUBTERRANEAN TERMITE PREVENTION, <br />DO NOT APPLY. A SIGNED FIVE YEAR CONTRACT FROM THE I5SUE <br />OF THE CERTIFICATE OF OCCUPANCY ASSURING INSTALLATION, MAINTENANCE AND MONITORING OF THE <br />BAITING SYSTEM SHALL BE PROVIDED TO THE BUILDING OFFICIAL PRIOR TO THE SLAB POUR. THE SYSTEM <br />MUST BE INSTALLED PRIOR TO FINAL BUILDING APPROVAL. <br />INITIAL SOIL POISONING TREATMENT SHALL BE DONE AFTER ALL EXCAVATION, <br />BACKFILLING 4 COMPACTION ARE COMPLETE <br />ANY SOIL DISTURBED AFTER THE INITIAL TREATMENT SHALL BE RE -TREATED <br />(INCLUDING ANY BOXED OR FORMED AREAS) - <br />BOXED AREAS IN THE CONCRETE SLAB FOR INSTALLATION OF TRAPS SHALL BE MADE <br />WITH PERMANENT METAL OR PLASTIC FORMS. PERMANENT FORMS MUST BE OF AN <br />ADEQUATE SIZE 4 DEPTH TO ELIMINATE ANY DISTURBANCE OF THE SOIL AFTER THE <br />INITIAL TREATMENT. <br />A MINIMUM 6 MIL VAPOR BARRIER MUST BE INSTALLED TO PROTECT AGAINST RAINFALL <br />DILUTION. IF RAINFALL OCCURS BEFORE VAPOR BARRIER PLACEMENT, RE -TREATMENT <br />SHALL BE REQUIRED <br />ANY CONCRETE OVERPOUR, MORTAR OR STUCCO MATERIALS ALONG THE FOUNDATION PERIMETER <br />MUST BE REMOVED PRIOR TO EXTERIOR SOIL TREATMENT <br />EXTERIOR SOIL TREATMENT MUST BE APPLIED UNDER ALL EXTERIOR CONCRETE OR GRADE <br />WITHIN 12 INCHES OF THE STRUCTURE SIDE WALLS <br />AN EXTERIOR VERTICAL CHEMICAL BARRIER SHALL BE INSTALLED AFTER CONSTRUCTION IS <br />COMPLETE (INCLUDING LANDSCAPING AND IRRIGATION). ANY SOILS DISTURBED AFTER THE <br />VERTICAL BARRIER 15 APPLIED, SHALL BE RE -TREATED, <br />CONDENSATE AND ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 12 INCHES AWAY FROM THE <br />BUILDING SIDEWALLS (PER FBC R3181 <br />AFTER ALL WORK IS COMPLETED, ANY LOOSE WOOD AND FILL MUST BE REMOVED FROM BELOW <br />AND WITHIN 12 INCHES OF THE BUILDING. THIS SHALL INCLUDE ALL GRADE STAKES, TUB TRAP BOXES <br />FORMS, SHORING AND ANY OTHER CELLULOSE CONTAINING MATERIALS. <br />THE DISTANCE FROM THE EXTERIOR WALL COVERING (EXCEPTIONS: PAINT AND DECORATIVE <br />CEMENTITIOUS FINISHES LESS THAN 5/8 INCH THICK ADHERED DIRECTLY ONTO THE FOUNDATION <br />WALL) AND FINAL EARTH GRADE SHALL NOT BE LESS THAN 6 INCHES TO ALLOW FOR INSPECTION <br />FOR FUTURE TERMITE INFESTATIONS <br />TRUSSES: <br />IF THE CONTRACTOR, TRUSS MANUFACTURER OR ANY OTHER DESIGN PROFESSIONALS REVISE THE <br />TRUSS SYSTEM LAYOUT FROM THOSE SHOWN ON THESE PLANS T. L. HANSON 4 ASSOCIATES IS <br />REQUIRED TO REVIEW ALL FINAL CONSTRUCTION DOCUMENTS FOR COMPLIANCE WITH THE DESIGN <br />INTENT PRIOR TO COMMENCEMENT OF THE PROJECT. <br />EXTERIOR WINDOWS 4 DOOR ASSEMBLIES: <br />ALL EXTERIOR WINDOW 4 GLASS DOORS SHALL BE TESTED IN ACCORDANCE WITH ANSI/AMMA/NWWDA <br />101/162 STANDARDS AND BEAR AN AMMA OR WDMA LABEL IDENTIFYING THE MANUFACTURER, <br />PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT TESTING ENTITY. <br />ALL MULLIONS AND ADJACENT DOOR/WINDOW ASSEMBLIES SHALL BE TESTED OR ENGINEERED TO <br />TRANSFER 1.5 TIMES THE DESIGN LOADS TO THE ROUGH OPENING SUBSTRATE. <br />INSTALL ALL WINDOW 4 DOOR ASSEMBLIES PER THE MANUFACTURERS ANCHORING RECOMMENDATIONS <br />TO ACHEIVE THE DESIGN PRESSURES SPECIFIED, <br />ELECTRICAL, PLUMBING 4 MECHANICAL: <br />IN ACCORDANCE WITH CHAPTER 411.003(2XU OF THE FLORIDA ADMINISTRATIVE CODE: ELECTRICAL, <br />PLUMBING AND MECHANICAL SYSTEMS SHALL BE DESIGNED BY THE RESPECTIVE CONTRACTORS TO <br />MEET ALL APPLICABLE CODES. THE ELECTRICAL, PLUMBING AND MECHANICAL SYSTEMS DRAWN HEREON <br />ARE BASED UPON A DESIGN PROVIDED BY THE OWNER TO ADDRESS HIS/HER REQUIREMENTS. <br />ALL ELECTRICAL OUTLETS IN BATHROOMS, KITCHEN (WITHIN 6 FEET OF SINKS), GARAGE AND AT <br />EXTERIOR LOCATIONS SHALL BE WIRED INTO A GROUND -FAULT INTERRUPTER "GFI" CIRCUIT. <br />ALL ELECTRICAL OUTLETS IN BEDROOMS SHALL BE WIRED INTO AN ARC -FAULT INTERRUPTER <br />"AFI" CIRCUIT. <br />SAFETY GLAZING: <br />THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS FOR THE PURPOSES OF <br />GLAZING PER THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R305: <br />(U GLAZING IN SWINGING DOORS, FIXED AND SLIDING PANELS OF SLIDING DOOR <br />ASSEMBLIES. <br />(2) GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS, WHIRLPOOLS, SAUNAS, STEAM <br />ROOMS, BATHTUBS, AND SHOWERS. GLAZING IN ANY PORTION OF A BUILDING WALL <br />ENCLOSING THESE COMPARTMENTS WHERE THE BOTTOM EDGE OF THE GLAZING IS LESS <br />THAN 60 INCHES ABOVE THE DRAIN INLET. <br />(3) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL ADJACENT A DOOR WHERE <br />THE NEAREST VERTICAL EDGE IS WITHIN A 24 INCH RADIUS OF THE DOOR IN A <br />CLOSED POSITION AND WHOSE BOTTOM EDGE IS LESS THAN 60 INCHES ABOVE THE <br />FINISHED FLOOR OR WALKING SURFACE. <br />(4) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL, OTHER THAN THOSE LOCATIONS <br />DESCRIBED IN ITEMS (2) AND (3) ABOVE. THAT MEETS ALL OF THE FOLLOWING <br />CONDITIONS: <br />A) EXPOSED AREA OF AN INDIVIDUAL PANE GREATER THAN 9 80, FT, <br />B) BOTTOM EDGE LESS THAN 18 INCHES ABOVE THE FLOOR. <br />C) TOP EDGE GREATER THAN 36 INCHES ABOVE THE FLOOR, <br />D) ONE OR MORE WALKING SURFACES WITHIN 36 INCHES HORIZONTALLY OF THE <br />PLANE OF THE GLAZING. <br />REFER TO THE FLORIDA BUILDING CODE, RESIDENTIAL - SECTION R308 FOR ADDITIONAL AREAS <br />THAT MAY BE CONSIDERED A HAZARDOUS LOCATION FOR THE PURPOSE OF GLAZING. <br />DRAFTSTOPPING: <br />IN SINGLE FAMILY DWELLINGS, DRAFTSTOPPING SHALL BE PROVIDED (PARALLEL TO THE MAIN <br />FRAMIMG MEMBERS) IN FLOOR/CEILING ASSEMBLIES SEPARATING USEABLE SPACES. DRAFTSTOPPING <br />SHALL BE CONSTUCTED SUCH THAT THE FLOOR/CEILING ASSEMBLY 15 BROKEN UP INTO TWO OR <br />MORE APPROXIMATE AREAS WITH NO AREA GREATER THAN 1000 SQ. FT. <br />1/2" CDX OR 1/16," O5B ROOF SHEATHING <br />NAILED PER ROOF SHEATHING DETAIL WITH <br />81) NAILS, USE STEEL PLYCLIPS AND GAF <br />UNDERLAYMENT AND GAF SHINGLES <br />RIDGE VENT AS REQUIRED <br />SEE ROOF TRUSS PLAN FOR TRUSS CONNECTIONS <br />2X8 PT TOP PLATE <br />2X4 02 SPRUCE SUB FASCIA WITH R-30 INSULATION <br />ALUMINUM FASCIA, DRIP AND SOFFIT <br />if <br />1/2" CEILING TYPE GYPSUM BOARD <br />I III <br />I I <br />L III ADD IX2 PT FURING STRIP AND <br />ADD I ROW 6" KNOCK OUT LINTEL I III AL FOIL INSULATION AT TOP OF <br />BLOCK TO TOP OF WALL WITH 1-05 I III WALL AND 1/2" GYPSUM BOARD <br />HORIZONTAL REBAR TIED OT ALL I III <br />VERTICAL THREAD RODS I lit <br />I III DRILL 6" INTO TOP OF EXISTING WALL AND <br />i III EPDXY A301 5/8" ALL THREAD ROD THAT <br />r _ _ 411 WILL EXTEND THROUGH TOP 2X8 PT PLATE <br />ill WITH 2" SQUARE WASHER AND NUT AT TOP. <br />1 III PLACE AT EACH SIDE OF OPENINGS, ALL <br />L _ _ III CORNERS AND SPACED 3"' OC <br />1 III <br />Q 1 III <br />� 1 III <br />� O I III <br />cn I III <br />r--JII <br />zI ul <br />N i III <br />I I it <br />1 III <br />1 III <br />I --111 <br />I III <br />1 III <br />r <br />I III <br />III <br />I III <br />r III <br />I III <br />I III <br />- - J IL - - - - - - - - - - - - - - - - <br />I <br />L- - - - - - - - - - - - - - - - - - - - <br />BLOCK WALL SECTION DETAIL 8-1 <br />NOT TO SCALE <br />DRILL 6" INTO TOP OF EXISTING WALL AND <br />EPDXY A301 5/8" ALL THREAD ROD THAT <br />WILL EXTEND THROUGH TOP 2X8 PT PLATE <br />WITH 2" SQUARE WASHER AND NUT AT TOP, <br />PLACE AT EACH SIDE OF OPENINGS, ALL <br />CORNERS AND SPACED 3"' OC <br />2X8 PT TOP PLATE <br />I I = <br />I I <br />I I 1 I I I <br />-- L — --I— <br />Z <br />D IROW 8" KNOCK OUT LINTELCK TO TOP OF WALL WITH 1-05 1 <br />HORIZONTAL REBAR TIED OT ALL I ADD I ROW 8" REGULAR BLOCK AND <br />VERTICAL THREAD RODS - I ROW 8" KNOCK OUT LINTEL BLOCK - <br />TO TOP OF WALL WITH 1-•5 HORIZONTAL <br />I I REBAR TIED OT ALL VERTICAL THREAD <br />- - - - - - - - - - T - - -- - - r - - -T - RODS <br />I I I I <br />I I I I I I <br />I I I I I <br />I I I I I I <br />- <br />-- - - - -I- - -'---,----- --T----- --I--- L---I---'---- <br />I I I I I <br />I I I I I <br />- - - I- - - - - - -i - - - '- - - T - - -' - - -- <br />I I I I I I <br />1 I I I I 1 <br />-------r--1'---i-- --- -- ---'---r--.i'---I---'---- <br />I I I <br />I I I I I <br />J - - - I- - - T - - -I - - - '- - - T - - -' - - -- <br />I I 1 I I I <br />I I I I I I <br />- - - - - - - - - - - - - - - - I- - - 1 - - -' - - - - - - 1 - - - - - -- <br />- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - <br />BLOCK WALL SECTION DETAIL 5-3 <br />NOT TO SCALE <br />1/2" CDX OR 1/16" OSB ROOF SHEATHING <br />NAILED PER ROOF SHEATHING DETAIL WITH <br />SD NAILS, USE STEEL PLYCLIPS AND GAF <br />UNDERLAYMENT AND GAF SHINGLES <br />RIDGE VENT AS REQUIRED <br />SEE ROOF TRUSS PLAN FOR TRUSS CONNECTIONS <br />2X8 PT TOP PLATE <br />2X4 02 SPRUCE SUB FASCIA WITH <br />ALUMINUM FASCIA, DRIP AND SOFFIT <br />�I <br />N <br />R-30 INSULATION <br />-1/2" CEILING TYPE GYPSUM BOARD <br />ADD IX2 PT FURING STRIP AND <br />AL FOIL INSULATION AT TOP OF <br />WALL AND 1/2" GYPSUM BOARD <br />DRILL roll INTO TOP OF EXISTING WALL AND <br />EPDXY A301 5/8" ALL THREAD ROD THAT <br />r - --III WILL EXTEND THROUGH TOP 2X8 PT PLATE <br />1 III WITH 2" SQUARE WASHER AND NUT AT TOP, <br />1 III PLACE AT EACH SIDE OF OPENINGS, ALL <br />CORNERS AND SPACED 3"' OC <br />1 III <br />1 III <br />1 III <br />1 III <br />1 III <br />r--JII <br />I III <br />I III <br />I III <br />I III <br />I III <br />I --ill <br />I III <br />I III <br />r _ —JII <br />I III <br />III <br />I III <br />r III <br />I III <br />I 111 <br />JI- - - - - - - - - - - - - - - - - <br />I <br />L- - - - - - - - - - - - - - - - - - - - <br />BLOCK WALL SECTION DETAIL 8-2 <br />1/2" CDX OR 1/16" OSB ROOF SHEATHING <br />NAILED PER ROOF SHEATHING DETAIL WITH <br />8D NAILS, USE STEEL PLYCLIPS AND GAF <br />UNDERLAYMENT AND GAF SHINGLES <br />RIDGE VENT AS REQUIRED <br />SEE ROOF TRUSS PL< <br />2X8 PT TOP PLATE <br />2X4 02 SPRUCE SUB <br />ALUMINUM FASCIA, D <br />I ROW 8" KNOCK <br />TO TOP OF WALL <br />REE3AR TIED OT <br />NOT TO SCALE <br />O INSULATION <br />TYPE GYPSUM BOARD <br />JRING STRIP 16" OC <br />INSULATION <br />3UM BOARD <br />,L RODS AS SHOWN ON FLOOR <br />>ATION PLAN FROM FOOTINGS <br />WALL WITH CELLS FILLED SOLID <br />=81 CONCRETE <br />110" 6" <br />BLOCK WALL SECTION DETAIL 8-4 <br />NOT TO SCALE <br />01 �AIL <br />f•'4rr•�i '�' <br />3L'41AhN8 LICENSE 1:39i54 <br />*ITY, fl- 33ft <br />.00 <br />VV �• • <br />I HERBY CER Nt•11 la • � SPECIFICATIONS <br />WERE PREPARkl:► � IRECt SUPERVISION <br />ARE IN COMPLIA�,t� SECTION 1609 OF THE <br />FLORIDA BUILDING full (t >� ITION AND ASCE 1-10 <br />FOR 13S MPH WIND ZONE RISK CATEGORY II AND THE ENTIRE <br />2011 BUILDING CODE RESIDENTIAL 6TH EDITION <br />cr) <br />C14 <br />Z�z <br />C7 M <br />z <br />cn a <br />W W O <br />�0 o <br />O <br />C� 0 N <br />Z LJL Co <br />Lo <br />Coul <br />J <br />>0 <br />z 5 c� <br />� <br />G7 co ccei <br />J W <br />a <br />Z <br />W� <br />A Ca M <br />0 m L <br />a <br />M <br />J W <br />a <br />F-- = <br />[z <br />W U- <br />_� 0 <br />W 04 <br />� M <br />e— <br />cq <br />uj cz 0 <br />0 0 M M <br />z `� Lu <br />W uoZ <br />UI i <br />to <br />N cp O z <br />Z <br />W zpo6_ <br />3: <br />W Q J <br />J Lu = <br />zz <br />1� <br />0 w <br />co <br />0 <br />n <br />L, <br />Ul <br />F- <br />4 <br />fA <br />Z <br />1 <br />� <br />O <br />a <br />r <br />M� <br />i1J <br />I <br />Z <br />Ia z <br />0 <br />Q <br />u- <br />O <br />!^ <br />z <br />O <br />(L <br />lu <br />Q <br />Q <br />ru <br />01 <br />U (Y- <br />O <br />l <br />O <br />O <br />ADDITION AREA <br />PORCH 221 80. FT, <br />GARAGE 85 SQ. FT. <br />PCB <br />4 OF <br />