<br />_.I. I I 111 11 j L • n Il ijiml :' 1 1 1 III 14 1
<br />NOTES:
<br />1, VERIFY NAMEPLATE RATINGS, L❑CATI❑NS, AND P❑INT OF
<br />POWER C❑NNECTI❑NS PRI❑R TO R❑UGH-INS.
<br />2, D❑ NOT LOCATE DISC❑NNECT SWITCHES OVER UNIT
<br />ACCESS PANELS,
<br />3. PR❑VIDE A 3/4' EMPTY C❑NDUIT THROUGH INACCESSIBLE
<br />L❑CATI❑NS (i.e., WALLS, UNDER SLAB) FOR CONTROL WIRING.
<br />C❑❑RDINATE WITH MECHANICAL PLANS,
<br />4, EQUIPMENT REQUIREMANTS SHOWN ON PANEL SCHEDULE
<br />ARE FOR TYPICAL EQUIPMENT SIZES. ELECTRICAL AND
<br />MECHANICAL CONTRACTOR SHALL C❑❑RDINATE SIZE AND
<br />RATING OF CIRCUITS FOR ACTUAL EQUIPMENT PR❑VIDED.
<br />5, ALL MOTOR STARTERS AND/OR C❑MBINATI❑N STARTERS
<br />SHALL BE PR❑VIDED BY MECHANICAL CONTRACTOR.
<br />6, PR❑VIDE PADLOCKS WITH 2 KEYS FOR EACH OUTDOOR
<br />NEMA 3R DISC❑NNECT SWITCH, TURN KEYS OVER TO OWNER,
<br />7, SEE MECHANICAL PLANS FOR L❑CATI❑NS OF HEAT PUMPS
<br />AND AIR HANDLING UNITS.
<br />SYMBOL
<br />DESCRIPTION
<br />SWITCH
<br />$3
<br />3 WAY SWITCH
<br />$4
<br />4 WAY SWITCH
<br />$R
<br />RHEOSTAT SWITCH
<br />8
<br />110 V RECEPTICLE(1/2 SWITCHED)
<br />8
<br />110 V RECEPTICLE
<br />8GFI
<br />110 V RECEPTICLE - GROUND FAULT
<br />8AFi
<br />110 V RECEPTICLE - ARC FAULT
<br />8VP
<br />110 V RECEPTICLE - WATERPROOFOUTLET
<br />�►
<br />220 V RECEPTICLE
<br />[
<br />DUPLEX OUTLET IN FLOOR
<br />110 V QUAD
<br />IBwP
<br />110 V QUAD WATERPROOF OUTLET
<br />®
<br />RECESSED INCANDESCENT
<br />'
<br />LIGHT FIXTURE - WALL OR CEILING (TYP)
<br />EXHAUST BATH FAN 110 V 50 CFM'S
<br />EXHAUST FAN/LIGHT C❑MBINATION
<br />®
<br />FL❑URESCENT FIXTURE
<br />ELECTRICAL METER
<br />ELECTRICAL PANEL
<br />NOTES:
<br />UNLESS ❑THERWISE NOTED
<br />1. ELECTRICAL OUTLETS HEIGHTS AS MEASURED FROM FINISHED FLOOR
<br />CENTERED LINE OF THE BOX TO BE; 12' AFF (GENERAL)
<br />EXTERI❑R WATERPROOF 12' AFF
<br />2. ALL TRIM PLATES & DEVICES TO BE GANGED, WHERE POSSIBLE
<br />3. ELECTRICAL SWITCHES TO BE 42' CENTERLINE AFF.
<br />4, ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY, ALL WORK SHALL
<br />BE DONE IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRIC CODE, LATEST
<br />EDITI❑N, BY LICENSED ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE
<br />FOR THE INSTALLATI❑N & SIZING OF ALL ELECTRICAL, WIRING & ACCESS❑RIES,
<br />5. ALL CIRCUITS ARE REQUIRED TO BE EITHER ARC FAULT OR GROUND FAULT
<br />PROTECTED PER NEC 2011 210.12 (B)
<br />6. ALL RECEPTACLES ARE TO BE CHILD PROTECTED PER NEC 2011 406.11
<br />ELECTRICAL SPECIFICATIONS
<br />DIVISION 16000 - ELECTRICAL SYSTEMS
<br />SECTION 16100 - GENERAL PROVISIONS
<br />1. THE ELECTRICAL CONTRACTOR SHALL COMPLY WITH ALL FEDERAL, STATE
<br />AND LOCAL LAWS, ORDINANCES, RULES AND REGULATIONS THAT ARE
<br />APPLICABLE TO THIS PROJECT. THE CODES AND STANDARDS UTILIZED
<br />SHALL INCLUDE:
<br />NFPA - 70 (2001/2002 EDT) NATIONAL ELECTRICAL CODE.
<br />NFPA - 90A (2001/2002 EDT) STANDARD FOR THE INSTALLATION OF
<br />AIR CONDITIONING AND VENTILATING
<br />SYSTEMS.
<br />NFPA - 101 (2001/2002 EDT) LIFE SAFETY CODE
<br />AMERICANS WITH DISABILITIES ACCESSIBILITY
<br />IMPLEMENTATION ACT
<br />STANDARD BUILDING CODE (2001/2002 EDT)
<br />2. THE ELECTRICAL CONTRACTOR SHALL PROVIDE MATERIALS WHICH ARE
<br />NEW AND OF HIGH-GRADE QUALITY AND CONSTRUCTION. ELECTRICAL
<br />EQUIPMENT SHALL BEAR THE UNDERWRITER'S LABORATORY LABEL OF
<br />APPROVAL WHERE SUCH A STANDARD HAS BEEN ESTABLISHED FOR THE
<br />PARTICULAR MATERIAL IN QUESTION.
<br />3. IN ADDITION TO THE GUARANTEE OF EQUIPMENT BY THE MANUFACTURER
<br />OF EACH PIECE OF EQUIPMENT INSTALLED, THE CONTRACTOR SHALL
<br />ALSO GUARANTEE SUCH EQUIPMENT AND SHALL BE HELD FOR A PERIOD
<br />OF ONE YEAR FROM THE FINAL ACCEPTANCE TEST FOR NECESSARY
<br />ADJUSTMENTS AND/OR REPLACEMENTS OF ALL DEFECTIVE EQUIPMENT,
<br />MATERIALS AND WORKMANSHIP WITHOUT EXPENSE TO THE OWNER.
<br />4. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL THE
<br />FOLLOWING ITEMS:
<br />A. ALL CONDUIT AND CONDUCTORS BETWEEN THE LOAD SIDE OF THE
<br />TRANSFORMER AND THE MAIN ELECTRICAL EQUIPMENT.
<br />B. ALL CONDUIT AND CONDUCTORS BETWEEN THE MAIN ELECTRICAL
<br />EQUIPMENT AND THE DISTRIBUTION PANELBOARDS OR OTHER MAIN
<br />LOADS.
<br />C. ALL PANELBOARDS AND ALL SECONDARY CIRCUITS BETWEEN THE
<br />PANELBOARDS AND THE FINAL TERMINALS.
<br />D. ALL LIGHTING FIXTURES AND CONNECTIONS THERETO.
<br />E. ALL DISCONNECT DEVICES, CONDUIT AND CONDUCTORS FOR
<br />CONTROL AND POWER WIRING.
<br />F. ALL ELECTRICAL CONNECTIONS BETWEEN THE MAIN AIR
<br />CONDITIONING COMPRESSORS, AIR -HANDLING UNITS, PACKAGE
<br />UNITS AND STRIP HEATERS.
<br />G. ALL ELECTRICAL WIRING DEVICES INCLUDING BUT NOT LIMITED
<br />TO SWITCHES, RECEPTACLES, TIME CLOCKS, RELAYS, ETC.
<br />H. ALL CONDUIT, CONDUCTORS, DISCONNECT DEVICES, MOTOR
<br />STARTERS NOT PROVIDED BY OTHERS, AND FLEXIBLE METALLIC
<br />CONDUIT TO COMPLETELY WIRE MOTOR OPERATED EQUIPMENT.
<br />I. NOT USED.
<br />H VAC PLAN EXISTING 200A 40 PANEL BOX
<br />1. EMPTY SLOTS AVAILABLE FOR NEW ROOM
<br />SECTION 16200 - MATERIALS
<br />1. RACEWAYS
<br />A. UNDERGROUND - RIGID THICK WALL GALVANIZED STEEL CONDUIT
<br />COATED WITH ASPHALTUM PAINT, OR SCHEDULE 40 PVC CONDUIT.
<br />B. IN -FLOOR SLABS - RIGID THICK WALL GALVANIZED STEEL
<br />CONDUIT.
<br />C. EXPOSED IN AREAS WITHIN THE BUILDING - GALVANIZED
<br />ELECTRICAL METALLIC TUBING.
<br />D. EXPOSED IN AREAS OUTSIDE THE BUILDING - RIGID THICK WALL
<br />GALVANIZED STEEL CONDUIT.
<br />E. IN OR ABOVE CEILINGS OR WALLS - ELECTRICAL METALLIC
<br />TUBING.
<br />F. CONNECTIONS TO VIBRATING EQUIPMENT - FLEXIBLE METALLIC
<br />CONDUIT FOR DRY LOCATIONS AND LIQUID -TIGHT PVC COVERED FLEXIBLE
<br />METALLIC CONDUIT FOR WET LOCATIONS.
<br />G. NOT USED.
<br />H. ALL CONDUITS PENETRATING A FIREWALL OR BARRIER SHALL BE
<br />SEALED WITH 3M BRAND FIRE BARRIER CAULK, PUTTY AND/OR
<br />PENETRATION SEALING SYSTEMS.
<br />2. WIRES
<br />A. ALL CONDUCTORS SHALL BE COPPER OF 98% CONDUCTIVITY WITH
<br />600-VOLT INSULATION TYPE THW OR THWN.
<br />3. WIRING DEVICES
<br />A. WIRING DEVICES SHALL BE SPECIFICATION GRADE EQUAL TO THE
<br />FOLLOWING:
<br />1. SINGLE POLE SWITCH HUBBELL 1221-1
<br />2. THREE WAY SWITCH HUBBELL 1223-1
<br />3. DUPLEX RECEPTACLE HUBBELL 5262-1
<br />B. SPECIAL PURPOSE RECEPTACLES SHALL BE OF SIMILAR GRADE
<br />CONSTRUCTION AS DUPLEX RECEPTACLES.
<br />4. DISTRIBUTION AND UTILIZATION EQUIPMENT
<br />A. PANELBOARDS, DISCONNECT SWITCHES, STARTERS, ETC. SHALL BE
<br />MANUFACTURED BY SQUARE "D" COMPANY, GENERAL ELECTRIC COMPANY,
<br />WESTINGHOUSE ELECTRIC COMPANY, OR
<br />SIEMENS-ALLIS I-T-E.
<br />B. TIN-PLATED ALUMINUM BUSSING SHALL BE USED THROUGHOUT.
<br />PANEL WITHSTAND RATINGS SHALL MEET MINIMUM REQUIREMENTS
<br />INDICATED ON PLANS.
<br />6. LIGHTING FIXTURES
<br />A. FLUORESCENT FIXTURES SHALL INCORPORATE ENERGY SAVING T-8
<br />LAMPS AND /OR COMPACT FLUORESCENT AND SHALL INCLUDE ELECTRONIC
<br />BALLAST'S PROVIDING A MAXIMUM 20% T.H.D.
<br />B. INCANDESCENT LAMPS SHALL BE LONG LIFE HIGH OUTPUT HALOGEN
<br />WITH RATED WATTAGE AS INDICATED ON DRAWINGS.
<br />If x
<br />`ICA L IOLA ELECrT -1-1 1-
<br />U
<br />I hereby certify that I have reviewed this plan and found it to be in
<br />compliance with ASCE 7-10 and the Florida Building Code 5th Edition 2014
<br />David W, Smith, P,E, #53608