Laserfiche WebLink
___ <br />_.I. I I 111 11 j L • n Il ijiml :' 1 1 1 III 14 1 <br />NOTES: <br />1, VERIFY NAMEPLATE RATINGS, L❑CATI❑NS, AND P❑INT OF <br />POWER C❑NNECTI❑NS PRI❑R TO R❑UGH-INS. <br />2, D❑ NOT LOCATE DISC❑NNECT SWITCHES OVER UNIT <br />ACCESS PANELS, <br />3. PR❑VIDE A 3/4' EMPTY C❑NDUIT THROUGH INACCESSIBLE <br />L❑CATI❑NS (i.e., WALLS, UNDER SLAB) FOR CONTROL WIRING. <br />C❑❑RDINATE WITH MECHANICAL PLANS, <br />4, EQUIPMENT REQUIREMANTS SHOWN ON PANEL SCHEDULE <br />ARE FOR TYPICAL EQUIPMENT SIZES. ELECTRICAL AND <br />MECHANICAL CONTRACTOR SHALL C❑❑RDINATE SIZE AND <br />RATING OF CIRCUITS FOR ACTUAL EQUIPMENT PR❑VIDED. <br />5, ALL MOTOR STARTERS AND/OR C❑MBINATI❑N STARTERS <br />SHALL BE PR❑VIDED BY MECHANICAL CONTRACTOR. <br />6, PR❑VIDE PADLOCKS WITH 2 KEYS FOR EACH OUTDOOR <br />NEMA 3R DISC❑NNECT SWITCH, TURN KEYS OVER TO OWNER, <br />7, SEE MECHANICAL PLANS FOR L❑CATI❑NS OF HEAT PUMPS <br />AND AIR HANDLING UNITS. <br />SYMBOL <br />DESCRIPTION <br />SWITCH <br />$3 <br />3 WAY SWITCH <br />$4 <br />4 WAY SWITCH <br />$R <br />RHEOSTAT SWITCH <br />8 <br />110 V RECEPTICLE(1/2 SWITCHED) <br />8 <br />110 V RECEPTICLE <br />8GFI <br />110 V RECEPTICLE - GROUND FAULT <br />8AFi <br />110 V RECEPTICLE - ARC FAULT <br />8VP <br />110 V RECEPTICLE - WATERPROOFOUTLET <br />�► <br />220 V RECEPTICLE <br />[ <br />DUPLEX OUTLET IN FLOOR <br />110 V QUAD <br />IBwP <br />110 V QUAD WATERPROOF OUTLET <br />® <br />RECESSED INCANDESCENT <br />' <br />LIGHT FIXTURE - WALL OR CEILING (TYP) <br />EXHAUST BATH FAN 110 V 50 CFM'S <br />EXHAUST FAN/LIGHT C❑MBINATION <br />® <br />FL❑URESCENT FIXTURE <br />ELECTRICAL METER <br />ELECTRICAL PANEL <br />NOTES: <br />UNLESS ❑THERWISE NOTED <br />1. ELECTRICAL OUTLETS HEIGHTS AS MEASURED FROM FINISHED FLOOR <br />CENTERED LINE OF THE BOX TO BE; 12' AFF (GENERAL) <br />EXTERI❑R WATERPROOF 12' AFF <br />2. ALL TRIM PLATES & DEVICES TO BE GANGED, WHERE POSSIBLE <br />3. ELECTRICAL SWITCHES TO BE 42' CENTERLINE AFF. <br />4, ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY, ALL WORK SHALL <br />BE DONE IN STRICT ACCORDANCE WITH THE NATIONAL ELECTRIC CODE, LATEST <br />EDITI❑N, BY LICENSED ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE <br />FOR THE INSTALLATI❑N & SIZING OF ALL ELECTRICAL, WIRING & ACCESS❑RIES, <br />5. ALL CIRCUITS ARE REQUIRED TO BE EITHER ARC FAULT OR GROUND FAULT <br />PROTECTED PER NEC 2011 210.12 (B) <br />6. ALL RECEPTACLES ARE TO BE CHILD PROTECTED PER NEC 2011 406.11 <br />ELECTRICAL SPECIFICATIONS <br />DIVISION 16000 - ELECTRICAL SYSTEMS <br />SECTION 16100 - GENERAL PROVISIONS <br />1. THE ELECTRICAL CONTRACTOR SHALL COMPLY WITH ALL FEDERAL, STATE <br />AND LOCAL LAWS, ORDINANCES, RULES AND REGULATIONS THAT ARE <br />APPLICABLE TO THIS PROJECT. THE CODES AND STANDARDS UTILIZED <br />SHALL INCLUDE: <br />NFPA - 70 (2001/2002 EDT) NATIONAL ELECTRICAL CODE. <br />NFPA - 90A (2001/2002 EDT) STANDARD FOR THE INSTALLATION OF <br />AIR CONDITIONING AND VENTILATING <br />SYSTEMS. <br />NFPA - 101 (2001/2002 EDT) LIFE SAFETY CODE <br />AMERICANS WITH DISABILITIES ACCESSIBILITY <br />IMPLEMENTATION ACT <br />STANDARD BUILDING CODE (2001/2002 EDT) <br />2. THE ELECTRICAL CONTRACTOR SHALL PROVIDE MATERIALS WHICH ARE <br />NEW AND OF HIGH-GRADE QUALITY AND CONSTRUCTION. ELECTRICAL <br />EQUIPMENT SHALL BEAR THE UNDERWRITER'S LABORATORY LABEL OF <br />APPROVAL WHERE SUCH A STANDARD HAS BEEN ESTABLISHED FOR THE <br />PARTICULAR MATERIAL IN QUESTION. <br />3. IN ADDITION TO THE GUARANTEE OF EQUIPMENT BY THE MANUFACTURER <br />OF EACH PIECE OF EQUIPMENT INSTALLED, THE CONTRACTOR SHALL <br />ALSO GUARANTEE SUCH EQUIPMENT AND SHALL BE HELD FOR A PERIOD <br />OF ONE YEAR FROM THE FINAL ACCEPTANCE TEST FOR NECESSARY <br />ADJUSTMENTS AND/OR REPLACEMENTS OF ALL DEFECTIVE EQUIPMENT, <br />MATERIALS AND WORKMANSHIP WITHOUT EXPENSE TO THE OWNER. <br />4. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL THE <br />FOLLOWING ITEMS: <br />A. ALL CONDUIT AND CONDUCTORS BETWEEN THE LOAD SIDE OF THE <br />TRANSFORMER AND THE MAIN ELECTRICAL EQUIPMENT. <br />B. ALL CONDUIT AND CONDUCTORS BETWEEN THE MAIN ELECTRICAL <br />EQUIPMENT AND THE DISTRIBUTION PANELBOARDS OR OTHER MAIN <br />LOADS. <br />C. ALL PANELBOARDS AND ALL SECONDARY CIRCUITS BETWEEN THE <br />PANELBOARDS AND THE FINAL TERMINALS. <br />D. ALL LIGHTING FIXTURES AND CONNECTIONS THERETO. <br />E. ALL DISCONNECT DEVICES, CONDUIT AND CONDUCTORS FOR <br />CONTROL AND POWER WIRING. <br />F. ALL ELECTRICAL CONNECTIONS BETWEEN THE MAIN AIR <br />CONDITIONING COMPRESSORS, AIR -HANDLING UNITS, PACKAGE <br />UNITS AND STRIP HEATERS. <br />G. ALL ELECTRICAL WIRING DEVICES INCLUDING BUT NOT LIMITED <br />TO SWITCHES, RECEPTACLES, TIME CLOCKS, RELAYS, ETC. <br />H. ALL CONDUIT, CONDUCTORS, DISCONNECT DEVICES, MOTOR <br />STARTERS NOT PROVIDED BY OTHERS, AND FLEXIBLE METALLIC <br />CONDUIT TO COMPLETELY WIRE MOTOR OPERATED EQUIPMENT. <br />I. NOT USED. <br />H VAC PLAN EXISTING 200A 40 PANEL BOX <br />1. EMPTY SLOTS AVAILABLE FOR NEW ROOM <br />SECTION 16200 - MATERIALS <br />1. RACEWAYS <br />A. UNDERGROUND - RIGID THICK WALL GALVANIZED STEEL CONDUIT <br />COATED WITH ASPHALTUM PAINT, OR SCHEDULE 40 PVC CONDUIT. <br />B. IN -FLOOR SLABS - RIGID THICK WALL GALVANIZED STEEL <br />CONDUIT. <br />C. EXPOSED IN AREAS WITHIN THE BUILDING - GALVANIZED <br />ELECTRICAL METALLIC TUBING. <br />D. EXPOSED IN AREAS OUTSIDE THE BUILDING - RIGID THICK WALL <br />GALVANIZED STEEL CONDUIT. <br />E. IN OR ABOVE CEILINGS OR WALLS - ELECTRICAL METALLIC <br />TUBING. <br />F. CONNECTIONS TO VIBRATING EQUIPMENT - FLEXIBLE METALLIC <br />CONDUIT FOR DRY LOCATIONS AND LIQUID -TIGHT PVC COVERED FLEXIBLE <br />METALLIC CONDUIT FOR WET LOCATIONS. <br />G. NOT USED. <br />H. ALL CONDUITS PENETRATING A FIREWALL OR BARRIER SHALL BE <br />SEALED WITH 3M BRAND FIRE BARRIER CAULK, PUTTY AND/OR <br />PENETRATION SEALING SYSTEMS. <br />2. WIRES <br />A. ALL CONDUCTORS SHALL BE COPPER OF 98% CONDUCTIVITY WITH <br />600-VOLT INSULATION TYPE THW OR THWN. <br />3. WIRING DEVICES <br />A. WIRING DEVICES SHALL BE SPECIFICATION GRADE EQUAL TO THE <br />FOLLOWING: <br />1. SINGLE POLE SWITCH HUBBELL 1221-1 <br />2. THREE WAY SWITCH HUBBELL 1223-1 <br />3. DUPLEX RECEPTACLE HUBBELL 5262-1 <br />B. SPECIAL PURPOSE RECEPTACLES SHALL BE OF SIMILAR GRADE <br />CONSTRUCTION AS DUPLEX RECEPTACLES. <br />4. DISTRIBUTION AND UTILIZATION EQUIPMENT <br />A. PANELBOARDS, DISCONNECT SWITCHES, STARTERS, ETC. SHALL BE <br />MANUFACTURED BY SQUARE "D" COMPANY, GENERAL ELECTRIC COMPANY, <br />WESTINGHOUSE ELECTRIC COMPANY, OR <br />SIEMENS-ALLIS I-T-E. <br />B. TIN-PLATED ALUMINUM BUSSING SHALL BE USED THROUGHOUT. <br />PANEL WITHSTAND RATINGS SHALL MEET MINIMUM REQUIREMENTS <br />INDICATED ON PLANS. <br />6. LIGHTING FIXTURES <br />A. FLUORESCENT FIXTURES SHALL INCORPORATE ENERGY SAVING T-8 <br />LAMPS AND /OR COMPACT FLUORESCENT AND SHALL INCLUDE ELECTRONIC <br />BALLAST'S PROVIDING A MAXIMUM 20% T.H.D. <br />B. INCANDESCENT LAMPS SHALL BE LONG LIFE HIGH OUTPUT HALOGEN <br />WITH RATED WATTAGE AS INDICATED ON DRAWINGS. <br />If x <br />`ICA L IOLA ELECrT -1-1 1- <br />U <br />I hereby certify that I have reviewed this plan and found it to be in <br />compliance with ASCE 7-10 and the Florida Building Code 5th Edition 2014 <br />David W, Smith, P,E, #53608 <br />