<br />r
<br />HVAC EQUIPMENT SCHEDULE NOTE: ELECTRIC REQUIREMENT FOR EQUIPMENT TO BE
<br />FIELD VERIFIED BY ELECTRICAUMECHANICAL CONTRACTOR.
<br />MFG.
<br />MODEL NO.
<br />TOTAL-BTUH
<br />K�
<br />O/A
<br />DIA.
<br />RTU
<br />"OR EQUAL"
<br />"OR
<br />"OR EQUAL"
<br />TONNAGE
<br />COOLING/HEATING
<br />SENSIBLE
<br />LATENT
<br />EER
<br />TYPE
<br />RLA
<br />MCA
<br />MOCP
<br />CFM
<br />CFM
<br />O/A DUCT
<br />#1
<br />CARRIER
<br />50TC-D21C6"5
<br />17.5 TONS
<br />203,300
<br />85,304
<br />140,277
<br />63,023
<br />11.2
<br />E5 CV
<br />208-230/3/60
<br />27.6
<br />187
<br />253
<br />5250
<br />1470
<br />NA
<br />#2
<br />CARRIER
<br />50TC-D21C6"5
<br />17.5 TONS
<br />203,300
<br />85,304
<br />140,277
<br />63,023
<br />11.2
<br />25 KW
<br />208-230/3/60
<br />27.6
<br />187
<br />253
<br />5250
<br />1520
<br />NA
<br />ELEC.
<br />#3
<br />CARRIER
<br />50VL-C36--3
<br />3 TONS
<br />34,800 1HI:
<br />24,360
<br />10,440
<br />14.0
<br />10 KWF208-230/3/60
<br />8.3
<br />187
<br />253
<br />1150
<br />72
<br />NA
<br />ELEC.
<br />OUTSIDE AIR CALCULATION
<br />RTU
<br />CATEGORY
<br />SQ. FT. AREA
<br />CFM/PRSN + CFM/FT
<br />MIN.
<br />O.A. CFM
<br />1
<br />LOUNGE/BAR
<br />1915
<br />7.5 x 150 + 0.18 x 1915
<br />1470
<br />2
<br />LOUNGE/BAR
<br />1488
<br />7.5 x 150 + 0.18 x 1488
<br />1393
<br />2
<br />STAGE
<br />289
<br />10 x 11 + 0.06 x 289
<br />127
<br />3
<br />OFFICE/STORAGE
<br />1308
<br />5.0 x 2 + 0.05 x 1308
<br />72
<br />TOTAL OA
<br />3062
<br />FAN SCHEDULE
<br />MFG.
<br />TYPE
<br />CFM
<br />VOLTS
<br />DUCT DIA.
<br />"OR EQUAL"
<br />EF1(2)
<br />BROAN
<br />OR EQUAL
<br />CEILING EXHAUST FAN
<br />280
<br />120
<br />41NCHES
<br />EF2
<br />BROAN
<br />OR EQUAL
<br />CEILING EXHAUST FAN
<br />70
<br />120
<br />4 INCHES
<br />AIR BALANCE SCHEDULE
<br />RTU1
<br />OUTSIDE AIR INTAKE CFM +1470
<br />SUPPLY AIR CFM +5250
<br />RETURN AIR CFM -3780
<br />TOTAL BUILDING PRESSURE "0" CFM
<br />AIR BALANCE SCHEDULE
<br />RTU2
<br />OUTSIDE AIR INTAKE CFM +1520
<br />SUPPLY AIR CFM +5250
<br />RETURN AIR CFM -3730
<br />TOTAL BUILDING PRESSURE "0" CFM
<br />AIR BALANCE SCHEDULE
<br />RTU3
<br />OUTSIDE AIR INTAKE CFM +72
<br />SUPPLY AIR CFM +1150
<br />RETURN AIR CFM -1143
<br />TOTAL BUILDING PRESSURE 110" CFM
<br />GENERAL HVAC NOTES ARE IN COMPLIANCE WITH 2O17 F.B.C.M.
<br />1. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH PROPER CLEARANCE,
<br />A MIN. OF 4 INCHES ON EACH SIDE IS SUFFICIENT, 2017 F.B.C.M. SEC. 603.1.3
<br />2. ALL DUCT SYSTEMS INSTALLED IN "NON -CONDITIONED" AREAS SHALL BE CONSTRUCTED WITH APPROVED MATERIAL AND
<br />OF A VALUE OF NO LESS THEN R-6 RATING. ALL SEAMS SHALL BE SEALED WITH GLASS FAB & MASTIC "OR"
<br />APPROVED TAPES THAT EXTEND NOT LESS THAN 1 INCH AND LABELED IN ACCORDANCE WITH THE UL-181A, PART 1 FOR DUCT BOARD
<br />OR UL 181 B, PART 1 FOR FLEX. ALL CLOSURES 100% AND INSTALLATIONS SHALL BE INSTALLED AS PER 2017 F.M.C.M. CHAPTER 6, SEC. 603
<br />ALL THRU-WALL, FLOOR & CEILING PENETRATIONS INTO THE DUCT SECTION SHALL CONTAIN A BRANCH DUCT FABRICATED OF RIGID FIBROUS GLASS DUCT BOARD
<br />OR RIGID METAL AND IS SEALED TO BOTH DUCT SECTION AND GRILLE SIDE WALL SURFACE. THE BRANCH DUCT SHALL BE FARED. AND ATTACHED
<br />IN ACCORDANCE WITH M603.3 OR M603.4.2 RESPECTIVE TO THE DUCT TAPE USED,
<br />3. ALL DUCT TRUNK 90 DEGREE TURNS OR TEE'S, SHALL HAVE TURNING VANES. 3 PIECE OR 45 DEGREE TURNS CAN BE USED IN
<br />PLACE OF 90 DEGREE TURNS AND DO NOT NEED TURNING VANES.
<br />4. ALL REGISTERS, GRILLES & DIFFUSERS MUST BE TESTED IN ACCORDANCE WITH ASTM E 84, AND VOLUME DAMPERS OR
<br />OTHER MEANS OF SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED IN DUCTS OR AT EACH INDIVIDUAL REGISTER, GRILLE OR DIFFUSER.
<br />5. AIR DISTRIBUTION SYSTEMS EXCEEDING 5000 SQ.FT. SHALL BE TESTED, ADJUSTED, AND BALANCED BY A LICENSED ENGINEER OF THIS STATE A
<br />CURRENT CERTIFIED ORGANIZATION. (SEE EXCEPTIONS).
<br />EXCEPTION: 1) BUILDINGS WITH CAPACITIES OF 15 TONS OR LESS "PER SYSTEM" MAY BE TESTED AND BALANCED BY THE LICENSED MECH. CONTRACTOR.
<br />EXCEPTION: 2) BUILDINGS WITH CAPACITIES OF 65,000 BTU/H OR LESS "PER SYSTEM" ARE "EXEMPT". F.E.C.C. 2017, SEC. 503.2.9.1
<br />DOCUMENTS SHALL REQUIRE THAT ALL HVAC SYSTEMS BE BALANCED SERVING ZONES EXCEEDING.
<br />6. AIR HANDLERS (OVER 2000 CFM) SHALL HAVE A SMOKE DETECTOR INSTALLED IN THE SUPPLY. F.B.C.M. 2017 CHAPTER 6, SEC. 606.2.1.
<br />WHEN TWO AIR HANDLERS SHARE A COMMON SUPPLY OR RETURN "AIR DUCT" OR "PLEMUN" AND THE TOTAL CFM'S ARE GREATER THAN 2000,
<br />A SMOKE DETECTOR SHALL BE INSTALLED IN THE SUPPLY AND RETURN AS PER F.B.C.M. 2017 SEC. 606.2.3 AND BE IN ACCORDANCE WITH NFPA 72
<br />SMOKE DETECTOR TEST STATIONS SHALL HAVE A TROUBLE INDICATOR LIGHT, INUNDATING ANY AIR DUCT TROUBLE. NFPA 90A 2002, CHAPTER 6
<br />NOTE: A "PLEMUN" CAN NOT BE USED AS AN OCCUPANCY SPACE OR STORAGE AREAS. AS PER. NFPA-90A, SEC. 4.3.10.1.1
<br />7. FRESH AIR INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FT. FROM ANY CHIMNEY OR VENT OUTLET, OR SANITARY SEWER VENT OUTLET.
<br />ALL OUTDOOR INTAKES AND EXHAUSTS SHALL HAVE AUTOMATIC OR GRAVITY DAMPERS THAT CLOSE WHEN VENTILATION NOT OPERATING. F.E.C.C. 2017, SEC. 403.5
<br />8. ALL EXHAUST DUCTS, SHALL BE CONSTRUCTED OF METAL AND COMPLY WITH F.B.C.M. 2017 CHAPTER 5, SEC. 501.4
<br />9. BATHROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR BATHING FIXTURES SHALL BE MECHANICALLY VENTILATED.
<br />"EXCEPTION" RESIDENTIAL BATHROOMS HAVING NO LEES THAN 4 PERCENT OF FLOOR SPACE. F.B.C.M. 2017 CHAPTER 4, SEC. 402.3
<br />10. ALL EXHAUSTED BATHROOMS, CLOSETS & STORAGE ROOMS SHALL HAVE UNDER CUT DOORS OR A METHOD
<br />FOR MAKE UP AIR TO BE RETURNED EQUAL TO THE AMOUNT OF CFM'S EXHAUSTED. F.B.C.M. 2017 CHAPTER 6, SEC. 601.4
<br />11. CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE OF DISPOSAL.
<br />CONDENSATE SHALL NOT DISCHARGE INTO A STREET, ALLEY OR OTHER AREA AS TO CAUSE A NUISANCE. MUST TERMINATE A MIN. OF 18" FROM EXT. WALL.
<br />CONDENSATE DRAIN LINE SHALL NOT BE LESS THAN 3/4 INCH DIAMETER AND SHALL NOT DECREASE IN SIZE, 2017 F.B.C.M. CHAPTER 3, SEC. 307
<br />PER AUTHORITY OVER JURISDICTION CONDENSATE DRAIN MAY DRAIN TO A STORM SYSTEM, UTILITY SINK, OR SEWER BY APPROVED MEANS.
<br />ALL HORIZONTAL PRIMARY DRAIN LINE WITHIN UNCONDITIONAL AREA SHALL BE INSULATED. AS PER F.B.C.M. 2017 CHAPTER 3, SEC. 307
<br />AUXILIARY DRAIN PAN OR SECONDARY DRAIN LINE MAY BE REQUIRED WHERE DAMAGE TO ANY BUILDING MAY RESULT FROM OVERFLOW OR ANY STOPPAGE.
<br />AUXILIARY DRAIN PAN MUST HAVE A MIN. DEPTH OF 1.5 INCHES AND BE A MIN. 3 INCHES LARGER THAN UNIT OR COIL AND HAVE SEPARATE DRAIN LINE
<br />AN AUXILIARY PAN WITHOUT SEPARATE DRAIN LINE SHALL BE EQUIPPED WITH WATER LEVEL DETECTION DEVICE FOR SHUT OFF PRIOR TO OVERFLOW
<br />METALLIC PAN MUST HAVE A MIN. THICKNESS 0.0276-INCH, NONMETALLIC 0.0625-INCHES. AS PER F.B.C.M. 2017 CHAPTER 3, SEC. 307
<br />ALTERNATIVE TO SEPARATE DRAIN LINE: A WATER LEVEL DETECTION DEVICE THAT WILL SHUT EQUIPMENT PRIOR TO OVERFLOW OF PAN.
<br />WATER LEVEL DETECTION DEVICE SHALL CONNECT TO DRAIN PAN AT A HIGHER LEVEL THAN THE PRIMARY DRAIN CONNECTION.
<br />CONDENSATE DRAIN LINE CAN BE STRAPPED WITH 2" NYLON STRAP AND SUPPORTED EVERY 10' VERTICAL AND T HORIZONTAL
<br />12. REFRIGERANT PIPING FOR REFRIGERANT LINES SHALL BE INSULATED TO A THERMAL RESISTIVELY OF AT LEAST R=4HR.
<br />SUCTION LINE MUST BE INSULATED IN ACCORDANCE WITH ASTM E96. AS PER THE F.B.C.R. 2017 CHAPTER 3, SEC. 307
<br />13. ALL AIR DISTRIBUTION COMPONETS WILL BE INSTALLED IN ACCORDANCE TO 2017 F.B.C.M.
<br />14. IF HVAC EQUIPMENT OTHER THAN SPECIFIED BY DESIGNER IS SUBSTITUTED, IT'S CAPABILITIES OF BTU HEAT REMOVAL
<br />MUST BE EQUAL TO THE EQUIPMENT SPECIFIED BY THE HVAC DESIGNER.
<br />THE HVAC DESIGNER WILL NOT BE RESPONSIBLE FOR ANY SYSTEM NOT INSTALLED ACCORDING TO PLANS.
<br />SUPPORTS 5 ft. MAX. DISTANCE
<br />APPROVED HANGER WIRE
<br />MIN. R-6, 1 1/2" FIBERGLASS DUCT
<br />OR FLEX IN ATTIC OR UNCOND. SPACE
<br />OR NO INS, REQ. FOR SHEET METAL IN
<br />71 COND.SPACE
<br />' HANGER CHANNELL 1.5" WIDE (min.)
<br />TYPICAL DUCT TRUNK SUPPORT DETAIL
<br />�' f R V - Q , 10- III Cjv _�\ I
<br />cTRNq/ OpFc�Re -o ��OS,�P(
<br />ROOFTOP PACKAGED HEAT PUMP UNIT DETAIL
<br />NOT TO SCALE
<br />TYPICAL SPIN -IN FITTING / OR TAP COLLAR
<br />DRAW BAND FOR INTERIOR LINER
<br />APPROVED HANGER WIRE MIN. R-6, 1 1/2" INSULATED FLEX
<br />SUPPORTS 5 ft. MAX. DISTANCE IN ATTIC OR UNCOND. SPACE
<br />DUCT TRUNK TYPICAL DIFFUSER
<br />EXTERIOR LINER SEAL SHALL FASTEN TO DUCT TRUNK
<br />AS PER 2017 FLORIDA MECHANICAL CODE SECTION 603
<br />IN NO CASE MATERIAL SUPPORTING FLEX DUCT THAT IS IN
<br />SEE GENERAL HVAC NOTE #2
<br />HANGER (TYP.)
<br />1 1/2" MIN.
<br />SUPPORT STRAP
<br />18" MAX. FROM DEVICE,
<br />FASTENERS NOT PERMITTED
<br />DUCT TO PENETRATE EXHAUST OR
<br />DRYER VENT DUCTS.
<br />DUCT SUPPORT INTREVALS FOR 100% CLOSURES AND INSTALLATIONS
<br />HORIZONTAL DUCT - 5FT. NONMETALLIC DUCTS
<br />ALL DUCT SHALL BE TESTED IN ACCORDANCE WITH UL 181
<br />DUCTS MUCH BE IN COMPLIANCE WITH CHAPTER 6, 2017 F.B.C.M. SEC. 603 ALL DUCT SHALL BE LISTED AND LABELED AS CLASS 0 OR CLASS 1
<br />VERTICAL DUCT - 6FT. ALL DUCT SHALL BE A MIN OF R-6 INSULATION IN UNCONDITION AREAS
<br />DUCTWORK SUFFORT DETAILS
<br />NOT TO SCALE
<br />CEILING EXHAUST FAN DETAIL
<br />NTS
<br />ROOF CURB FLAT ROOF CAP
<br />ROOF CEILING/ROOF
<br />FLASHING MIN.
<br />EXH. DUCT
<br />FRAMING
<br />EXHAUST
<br />FAN
<br />EXHAUST DUCT Jy� CEILING
<br />CEILING GRILLE
<br />INLINE
<br />SUPPLY BRANCH
<br />2� SUPPLY BRANCHES
<br />/-AIR FLOW PERPENDICULAR
<br />SUPPLY TRUNK
<br />NOTE:
<br />ALL SUPPLY BRANCHES "MUST" HAVE A MIN. OF 2FT.
<br />DISTANCE BETWEEN EACH COLLIER WHEN APPLICABLE.
<br />EXCEPT BRANCHES STRAIT PERPENDICULAR ACROSS
<br />FROM EACH OTHER.
<br />O'��,\G E NSF
<br />•
<br />NOW
<br />HA1fJ6UF�F
<br />%Xel
<br />";6R1�
<br />�••.....
<br />�ONAL
<br />'•.� 0 'to
<br />Ld S 0.38654
<br />D,r L 33526
<br />0
<br />cal
<br />cz
<br />ifl
<br />U
<br />Z
<br />ON
<br />x `^ m
<br />M ul
<br />�r
<br />o
<br />wWsu�o
<br />u
<br />�=
<br />CD
<br />V
<br />Q 0
<br />�
<br />U
<br />Uz
<br />J
<br />oa
<br />J
<br />J
<br />F
<br />H
<br />d
<br />ZZ
<br />41*
<br />z�
<br />az
<br />f
<br />Co
<br />N
<br />Fl
<br />INN
<br />a
<br />U
<br />Z N
<br />qt
<br />LJ..
<br />Q M
<br />m Q cM
<br />J > _I
<br />Q J LL
<br />W w
<br />QJ
<br />L
<br />W
<br />W N
<br />A f�a
<br />M
<br />O
<br />ul
<br />d)
<br />O
<br />Z
<br />m
<br />0
<br />
|