I <br />r <br />HVAC EQUIPMENT SCHEDULE NOTE: ELECTRIC REQUIREMENT FOR EQUIPMENT TO BE <br />FIELD VERIFIED BY ELECTRICAUMECHANICAL CONTRACTOR. <br />MFG. <br />MODEL NO. <br />TOTAL-BTUH <br />K� <br />O/A <br />DIA. <br />RTU <br />"OR EQUAL" <br />"OR <br />"OR EQUAL" <br />TONNAGE <br />COOLING/HEATING <br />SENSIBLE <br />LATENT <br />EER <br />TYPE <br />RLA <br />MCA <br />MOCP <br />CFM <br />CFM <br />O/A DUCT <br />#1 <br />CARRIER <br />50TC-D21C6"5 <br />17.5 TONS <br />203,300 <br />85,304 <br />140,277 <br />63,023 <br />11.2 <br />E5 CV <br />208-230/3/60 <br />27.6 <br />187 <br />253 <br />5250 <br />1470 <br />NA <br />#2 <br />CARRIER <br />50TC-D21C6"5 <br />17.5 TONS <br />203,300 <br />85,304 <br />140,277 <br />63,023 <br />11.2 <br />25 KW <br />208-230/3/60 <br />27.6 <br />187 <br />253 <br />5250 <br />1520 <br />NA <br />ELEC. <br />#3 <br />CARRIER <br />50VL-C36--3 <br />3 TONS <br />34,800 1HI: <br />24,360 <br />10,440 <br />14.0 <br />10 KWF208-230/3/60 <br />8.3 <br />187 <br />253 <br />1150 <br />72 <br />NA <br />ELEC. <br />OUTSIDE AIR CALCULATION <br />RTU <br />CATEGORY <br />SQ. FT. AREA <br />CFM/PRSN + CFM/FT <br />MIN. <br />O.A. CFM <br />1 <br />LOUNGE/BAR <br />1915 <br />7.5 x 150 + 0.18 x 1915 <br />1470 <br />2 <br />LOUNGE/BAR <br />1488 <br />7.5 x 150 + 0.18 x 1488 <br />1393 <br />2 <br />STAGE <br />289 <br />10 x 11 + 0.06 x 289 <br />127 <br />3 <br />OFFICE/STORAGE <br />1308 <br />5.0 x 2 + 0.05 x 1308 <br />72 <br />TOTAL OA <br />3062 <br />FAN SCHEDULE <br />MFG. <br />TYPE <br />CFM <br />VOLTS <br />DUCT DIA. <br />"OR EQUAL" <br />EF1(2) <br />BROAN <br />OR EQUAL <br />CEILING EXHAUST FAN <br />280 <br />120 <br />41NCHES <br />EF2 <br />BROAN <br />OR EQUAL <br />CEILING EXHAUST FAN <br />70 <br />120 <br />4 INCHES <br />AIR BALANCE SCHEDULE <br />RTU1 <br />OUTSIDE AIR INTAKE CFM +1470 <br />SUPPLY AIR CFM +5250 <br />RETURN AIR CFM -3780 <br />TOTAL BUILDING PRESSURE "0" CFM <br />AIR BALANCE SCHEDULE <br />RTU2 <br />OUTSIDE AIR INTAKE CFM +1520 <br />SUPPLY AIR CFM +5250 <br />RETURN AIR CFM -3730 <br />TOTAL BUILDING PRESSURE "0" CFM <br />AIR BALANCE SCHEDULE <br />RTU3 <br />OUTSIDE AIR INTAKE CFM +72 <br />SUPPLY AIR CFM +1150 <br />RETURN AIR CFM -1143 <br />TOTAL BUILDING PRESSURE 110" CFM <br />GENERAL HVAC NOTES ARE IN COMPLIANCE WITH 2O17 F.B.C.M. <br />1. ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH PROPER CLEARANCE, <br />A MIN. OF 4 INCHES ON EACH SIDE IS SUFFICIENT, 2017 F.B.C.M. SEC. 603.1.3 <br />2. ALL DUCT SYSTEMS INSTALLED IN "NON -CONDITIONED" AREAS SHALL BE CONSTRUCTED WITH APPROVED MATERIAL AND <br />OF A VALUE OF NO LESS THEN R-6 RATING. ALL SEAMS SHALL BE SEALED WITH GLASS FAB & MASTIC "OR" <br />APPROVED TAPES THAT EXTEND NOT LESS THAN 1 INCH AND LABELED IN ACCORDANCE WITH THE UL-181A, PART 1 FOR DUCT BOARD <br />OR UL 181 B, PART 1 FOR FLEX. ALL CLOSURES 100% AND INSTALLATIONS SHALL BE INSTALLED AS PER 2017 F.M.C.M. CHAPTER 6, SEC. 603 <br />ALL THRU-WALL, FLOOR & CEILING PENETRATIONS INTO THE DUCT SECTION SHALL CONTAIN A BRANCH DUCT FABRICATED OF RIGID FIBROUS GLASS DUCT BOARD <br />OR RIGID METAL AND IS SEALED TO BOTH DUCT SECTION AND GRILLE SIDE WALL SURFACE. THE BRANCH DUCT SHALL BE FARED. AND ATTACHED <br />IN ACCORDANCE WITH M603.3 OR M603.4.2 RESPECTIVE TO THE DUCT TAPE USED, <br />3. ALL DUCT TRUNK 90 DEGREE TURNS OR TEE'S, SHALL HAVE TURNING VANES. 3 PIECE OR 45 DEGREE TURNS CAN BE USED IN <br />PLACE OF 90 DEGREE TURNS AND DO NOT NEED TURNING VANES. <br />4. ALL REGISTERS, GRILLES & DIFFUSERS MUST BE TESTED IN ACCORDANCE WITH ASTM E 84, AND VOLUME DAMPERS OR <br />OTHER MEANS OF SUPPLY AIR ADJUSTMENT SHALL BE PROVIDED IN DUCTS OR AT EACH INDIVIDUAL REGISTER, GRILLE OR DIFFUSER. <br />5. AIR DISTRIBUTION SYSTEMS EXCEEDING 5000 SQ.FT. SHALL BE TESTED, ADJUSTED, AND BALANCED BY A LICENSED ENGINEER OF THIS STATE A <br />CURRENT CERTIFIED ORGANIZATION. (SEE EXCEPTIONS). <br />EXCEPTION: 1) BUILDINGS WITH CAPACITIES OF 15 TONS OR LESS "PER SYSTEM" MAY BE TESTED AND BALANCED BY THE LICENSED MECH. CONTRACTOR. <br />EXCEPTION: 2) BUILDINGS WITH CAPACITIES OF 65,000 BTU/H OR LESS "PER SYSTEM" ARE "EXEMPT". F.E.C.C. 2017, SEC. 503.2.9.1 <br />DOCUMENTS SHALL REQUIRE THAT ALL HVAC SYSTEMS BE BALANCED SERVING ZONES EXCEEDING. <br />6. AIR HANDLERS (OVER 2000 CFM) SHALL HAVE A SMOKE DETECTOR INSTALLED IN THE SUPPLY. F.B.C.M. 2017 CHAPTER 6, SEC. 606.2.1. <br />WHEN TWO AIR HANDLERS SHARE A COMMON SUPPLY OR RETURN "AIR DUCT" OR "PLEMUN" AND THE TOTAL CFM'S ARE GREATER THAN 2000, <br />A SMOKE DETECTOR SHALL BE INSTALLED IN THE SUPPLY AND RETURN AS PER F.B.C.M. 2017 SEC. 606.2.3 AND BE IN ACCORDANCE WITH NFPA 72 <br />SMOKE DETECTOR TEST STATIONS SHALL HAVE A TROUBLE INDICATOR LIGHT, INUNDATING ANY AIR DUCT TROUBLE. NFPA 90A 2002, CHAPTER 6 <br />NOTE: A "PLEMUN" CAN NOT BE USED AS AN OCCUPANCY SPACE OR STORAGE AREAS. AS PER. NFPA-90A, SEC. 4.3.10.1.1 <br />7. FRESH AIR INTAKES SHALL NOT BE LOCATED CLOSER THAN 10 FT. FROM ANY CHIMNEY OR VENT OUTLET, OR SANITARY SEWER VENT OUTLET. <br />ALL OUTDOOR INTAKES AND EXHAUSTS SHALL HAVE AUTOMATIC OR GRAVITY DAMPERS THAT CLOSE WHEN VENTILATION NOT OPERATING. F.E.C.C. 2017, SEC. 403.5 <br />8. ALL EXHAUST DUCTS, SHALL BE CONSTRUCTED OF METAL AND COMPLY WITH F.B.C.M. 2017 CHAPTER 5, SEC. 501.4 <br />9. BATHROOMS CONTAINING BATHTUBS, SHOWERS, SPAS AND SIMILAR BATHING FIXTURES SHALL BE MECHANICALLY VENTILATED. <br />"EXCEPTION" RESIDENTIAL BATHROOMS HAVING NO LEES THAN 4 PERCENT OF FLOOR SPACE. F.B.C.M. 2017 CHAPTER 4, SEC. 402.3 <br />10. ALL EXHAUSTED BATHROOMS, CLOSETS & STORAGE ROOMS SHALL HAVE UNDER CUT DOORS OR A METHOD <br />FOR MAKE UP AIR TO BE RETURNED EQUAL TO THE AMOUNT OF CFM'S EXHAUSTED. F.B.C.M. 2017 CHAPTER 6, SEC. 601.4 <br />11. CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED PLACE OF DISPOSAL. <br />CONDENSATE SHALL NOT DISCHARGE INTO A STREET, ALLEY OR OTHER AREA AS TO CAUSE A NUISANCE. MUST TERMINATE A MIN. OF 18" FROM EXT. WALL. <br />CONDENSATE DRAIN LINE SHALL NOT BE LESS THAN 3/4 INCH DIAMETER AND SHALL NOT DECREASE IN SIZE, 2017 F.B.C.M. CHAPTER 3, SEC. 307 <br />PER AUTHORITY OVER JURISDICTION CONDENSATE DRAIN MAY DRAIN TO A STORM SYSTEM, UTILITY SINK, OR SEWER BY APPROVED MEANS. <br />ALL HORIZONTAL PRIMARY DRAIN LINE WITHIN UNCONDITIONAL AREA SHALL BE INSULATED. AS PER F.B.C.M. 2017 CHAPTER 3, SEC. 307 <br />AUXILIARY DRAIN PAN OR SECONDARY DRAIN LINE MAY BE REQUIRED WHERE DAMAGE TO ANY BUILDING MAY RESULT FROM OVERFLOW OR ANY STOPPAGE. <br />AUXILIARY DRAIN PAN MUST HAVE A MIN. DEPTH OF 1.5 INCHES AND BE A MIN. 3 INCHES LARGER THAN UNIT OR COIL AND HAVE SEPARATE DRAIN LINE <br />AN AUXILIARY PAN WITHOUT SEPARATE DRAIN LINE SHALL BE EQUIPPED WITH WATER LEVEL DETECTION DEVICE FOR SHUT OFF PRIOR TO OVERFLOW <br />METALLIC PAN MUST HAVE A MIN. THICKNESS 0.0276-INCH, NONMETALLIC 0.0625-INCHES. AS PER F.B.C.M. 2017 CHAPTER 3, SEC. 307 <br />ALTERNATIVE TO SEPARATE DRAIN LINE: A WATER LEVEL DETECTION DEVICE THAT WILL SHUT EQUIPMENT PRIOR TO OVERFLOW OF PAN. <br />WATER LEVEL DETECTION DEVICE SHALL CONNECT TO DRAIN PAN AT A HIGHER LEVEL THAN THE PRIMARY DRAIN CONNECTION. <br />CONDENSATE DRAIN LINE CAN BE STRAPPED WITH 2" NYLON STRAP AND SUPPORTED EVERY 10' VERTICAL AND T HORIZONTAL <br />12. REFRIGERANT PIPING FOR REFRIGERANT LINES SHALL BE INSULATED TO A THERMAL RESISTIVELY OF AT LEAST R=4HR. <br />SUCTION LINE MUST BE INSULATED IN ACCORDANCE WITH ASTM E96. AS PER THE F.B.C.R. 2017 CHAPTER 3, SEC. 307 <br />13. ALL AIR DISTRIBUTION COMPONETS WILL BE INSTALLED IN ACCORDANCE TO 2017 F.B.C.M. <br />14. IF HVAC EQUIPMENT OTHER THAN SPECIFIED BY DESIGNER IS SUBSTITUTED, IT'S CAPABILITIES OF BTU HEAT REMOVAL <br />MUST BE EQUAL TO THE EQUIPMENT SPECIFIED BY THE HVAC DESIGNER. <br />THE HVAC DESIGNER WILL NOT BE RESPONSIBLE FOR ANY SYSTEM NOT INSTALLED ACCORDING TO PLANS. <br />SUPPORTS 5 ft. MAX. DISTANCE <br />APPROVED HANGER WIRE <br />MIN. R-6, 1 1/2" FIBERGLASS DUCT <br />OR FLEX IN ATTIC OR UNCOND. SPACE <br />OR NO INS, REQ. FOR SHEET METAL IN <br />71 COND.SPACE <br />' HANGER CHANNELL 1.5" WIDE (min.) <br />TYPICAL DUCT TRUNK SUPPORT DETAIL <br />�' f R V - Q , 10- III Cjv _�\ I <br />cTRNq/ OpFc�Re -o ��OS,�P( <br />ROOFTOP PACKAGED HEAT PUMP UNIT DETAIL <br />NOT TO SCALE <br />TYPICAL SPIN -IN FITTING / OR TAP COLLAR <br />DRAW BAND FOR INTERIOR LINER <br />APPROVED HANGER WIRE MIN. R-6, 1 1/2" INSULATED FLEX <br />SUPPORTS 5 ft. MAX. DISTANCE IN ATTIC OR UNCOND. SPACE <br />DUCT TRUNK TYPICAL DIFFUSER <br />EXTERIOR LINER SEAL SHALL FASTEN TO DUCT TRUNK <br />AS PER 2017 FLORIDA MECHANICAL CODE SECTION 603 <br />IN NO CASE MATERIAL SUPPORTING FLEX DUCT THAT IS IN <br />SEE GENERAL HVAC NOTE #2 <br />HANGER (TYP.) <br />1 1/2" MIN. <br />SUPPORT STRAP <br />18" MAX. FROM DEVICE, <br />FASTENERS NOT PERMITTED <br />DUCT TO PENETRATE EXHAUST OR <br />DRYER VENT DUCTS. <br />DUCT SUPPORT INTREVALS FOR 100% CLOSURES AND INSTALLATIONS <br />HORIZONTAL DUCT - 5FT. NONMETALLIC DUCTS <br />ALL DUCT SHALL BE TESTED IN ACCORDANCE WITH UL 181 <br />DUCTS MUCH BE IN COMPLIANCE WITH CHAPTER 6, 2017 F.B.C.M. SEC. 603 ALL DUCT SHALL BE LISTED AND LABELED AS CLASS 0 OR CLASS 1 <br />VERTICAL DUCT - 6FT. ALL DUCT SHALL BE A MIN OF R-6 INSULATION IN UNCONDITION AREAS <br />DUCTWORK SUFFORT DETAILS <br />NOT TO SCALE <br />CEILING EXHAUST FAN DETAIL <br />NTS <br />ROOF CURB FLAT ROOF CAP <br />ROOF CEILING/ROOF <br />FLASHING MIN. <br />EXH. DUCT <br />FRAMING <br />EXHAUST <br />FAN <br />EXHAUST DUCT Jy� CEILING <br />CEILING GRILLE <br />INLINE <br />SUPPLY BRANCH <br />2� SUPPLY BRANCHES <br />/-AIR FLOW PERPENDICULAR <br />SUPPLY TRUNK <br />NOTE: <br />ALL SUPPLY BRANCHES "MUST" HAVE A MIN. OF 2FT. <br />DISTANCE BETWEEN EACH COLLIER WHEN APPLICABLE. <br />EXCEPT BRANCHES STRAIT PERPENDICULAR ACROSS <br />FROM EACH OTHER. <br />O'��,\G E NSF <br />• <br />NOW <br />HA1fJ6UF�F <br />%Xel <br />";6R1� <br />�••..... <br />�ONAL <br />'•.� 0 'to <br />Ld S 0.38654 <br />D,r L 33526 <br />0 <br />cal <br />cz <br />ifl <br />U <br />Z <br />ON <br />x `^ m <br />M ul <br />�r <br />o <br />wWsu�o <br />u <br />�= <br />CD <br />V <br />Q 0 <br />� <br />U <br />Uz <br />J <br />oa <br />J <br />J <br />F <br />H <br />d <br />ZZ <br />41* <br />z� <br />az <br />f <br />Co <br />N <br />Fl <br />INN <br />a <br />U <br />Z N <br />qt <br />LJ.. <br />Q M <br />m Q cM <br />J > _I <br />Q J LL <br />W w <br />QJ <br />L <br />W <br />W N <br />A f�a <br />M <br />O <br />ul <br />d) <br />O <br />Z <br />m <br />0 <br />