SECOND FLOOR ELECTRICAL PLAN (ALL ELEVATIONS' <br />1 /4" = 1'-0„ <br />ELECTRICAL NOTES: <br />1. GFCI'S ARE TO BE INSTALLED IN THE FOLLOWING <br />LOCATIONS AS SPECIFIED PER NFPA 70 (NEC) 2017 <br />A) BATHROOMS <br />B) GARAGES, AND ALSO ACCESSORY BUILDINGS THAT <br />HAVE A FLOOR LOCATED AT OR BELOW GRADE LEVEL <br />NOT INTENDED AS HABITABLE ROOMS AND LIMITED TO <br />STORAGE AREAS, WORK AREAS, AND AREAS OF <br />SIMILAR USE. <br />C) CRAWL SPACES AT OR BELOW GRADE. <br />D) KITCHENS - WHERE THE RECEPTACLES ARE <br />INSTALLED TO SERVE THE COUNTERTOP SURFACES. <br />E) LAUNDRY, UTILITY, AND WET BAR SINKS - WHERE <br />THE RECEPTACLES ARE INSTALLED WITHIN 6 FEET OF <br />THE OUTSIDE EDGE OF THE SINK. <br />2. ARCH FAULT OUTLETS ARE REQUIRED PER NFPA 70 <br />(NEC) 2017, INCLUDING ARTICLES 210 AND 400. <br />3. ANY CONFLICTS BET'JVEEN LOCATION OF <br />MECHANICAL FIXTURES ON PLANS AND THE ABILITY TO <br />LOCATE THEM IN THE FIELD MUST BE REPORTED TO THE <br />ARCHITECT PRIOR TO INSTALLATION. <br />4. RECEPTACLE OUTLETS IN GARAGE MUST BE <br />SERVED BY SEPARATE BRANCH CIRCUIT THAT DOES NOT <br />SUPPLY OTHER OUTLETS. <br />5. CM MUST BE AT LEAST S FROM BATH DOOR AND AT <br />LEAST 6' FROM KITCHEN RANGE/OVEN. <br />NOTES: <br />UNLESS OTHERWISE NOTED <br />1. ELECTRICAL OUTLET HEIGHTS AS MEASURED FROM FINISHED <br />FLOOR TO CENTERED LINE OF THE BOX TO BE: 12" AFF <br />(GENERAL) <br />KITCHEN <br />44" AFF <br />BATHROOM <br />39" AFF <br />LAUNDRY ROOM <br />36" AFF <br />EXTERIOR WATERPROOF <br />12" AFF <br />GARAGE GENERAL PURPOSE <br />42" AFF <br />RANGE <br />2" AFF <br />2. ALL TRIM PLATES & DEVICES TO BE GANGED, WHERE <br />POSSIBLE. <br />3. ELECTRICAL SWITCHES TO BE AT 42" CENTERLINE ABOVE <br />FINISHED FLOOR <br />4. ELECTRICAL PLAN IS INTENDED FOR BID PURPOSES ONLY. <br />ALL WORK SHALL. BE DONE IN STRICT ACCORDANCE WITH THE <br />NATIONAL ELECTRIC CODE, LATEST EDITION, BY A LICENSED <br />ELECTRICAL CONTRACTOR WHO SHALL BE RESPONSIBLE FOR <br />THE INSTALLATION & SIZING OF ALL ELECTRICAL, WIRING & <br />ACCESSORIES. <br />5. SMOKE DETECTORS SHALL BE INSTALLED AS DIRECTED BY <br />THE 2016 NFPA 72 NATIONAL FIRE ALARM CODE. <br />6. ALL ELECTRICAL IN THE LIVING ROOMS, DINING ROOMS, <br />SUNROOMS, FAMILY ROOMS, DENS, LIBRARIES, SLEEPING ROOMS, <br />PARLORS AND SIMILAR ROOMS OR AREAS SHALL BE ON AN A.F.C.I. <br />PROTECT CIRCUIT PER NFPA 70 (NEC) 2017, <br />7. IN ALL AREA SPECIFIED IN NFPA 70 (NEC) 2017 210.52, ALL 125 <br />VOLT, 15 AND 20 AMP RECEPTACLES SHALL BE LISTED <br />TAMPER -RESISTANT RECEPTACLES. <br />VIRTUAL REVIEW ASSIST <br />.Virtual Review Assist, Inc. <br />Plans Review completed and approved <br />for compliance with the 2020 FBC 7th <br />Edition by Debra P,nne Kkahr PX23CO <br />ELECTRICAL DETAIL: <br />INTERCOM <br />SPEAKER <br />ALIGNED W/ <br />EDGE OF <br />SWITCH ---- <br />SWITCH—° <br />4 1/2" <br />DOORJAMB DUPLEX <br />OUTLET c%> <br />TRIM o <br />0 <br />BASE <br />NOTE: <br />ALL DIMENSIONS ARE FROM ROUGH FRAMING <br />SMOKE DETECTOR LOCATION: <br />WALL <br />oZ_ <br />k �� <br />SMOKE DETECTOR <br />MIN. <br />ELECTRICAL LEGEND: <br />NOTE: ALL HEIGHTS ABOVE FINISH FLOOR <br />& 110V DUPLEX OUTLET AT 12" <br />110V DUPLEX OUTLET AT 39" <br />NOTE: ALL <br />RECEPTACLES <br />110V DUPLEX OUTLET AT 43" <br />ABOVE <br />COUNTERS <br />110V DUPLEX OUTLET AT 45" <br />SHALL BE <br />SPLIT 110V DUPLEX OUTLET <br />MOUNTED <br />AT 12" - TOP PLUG IS HOT <br />HORIZONTAL <br />110V QUAD OUTLET AT 12" <br />WEATHERPROOF GFCI OUTLET AT 12" <br />220V OUTLET AT 30" <br />110V DUPLEX FLOOR OUTLET <br />OUTLET -VERIFY W/MANUF. SPECS <br />FOR LOCATION & TYPE <br />TELEPHONE OUTLET AT 12" OR AS NOTED <br />TELEVISION OUTLET AT 12" - WIRE FOR <br />CABLE & SATELLITE <br />STRUCTURED WIRE OUTLET <br />-�— SWITCH AT 36" <br />6 3 WAY SWITCH AT 36" <br />4 WAY SWITCH AT 36" <br />—0 PUSH BUTTON FOR GARAGE DOOR OPENER <br />—o DIMMER SWITCH AT 36" <br />PUSH-BUTTON DOORBELL <br />-}- CLG MNT LT FIXTURE <br />-�- CLG MNT PREWIRE - FIXTURE BY OWNER <br />-�- SURFACE MNT FIXTURE <br />-} WALL MNT FIXTURE <br />NOTE: <br />C TUB/SHOWERND OPALEX - ALTERNATE <br />CANS MAY BE <br />0T 50W PAR30 NFL 6" WHITE BAFFLE USEDIF <br />APPROVED BY <br />C 50W MR16 4" LOW VOLTAGE OWNER <br />C 50W PAR20 NFL 4" MINI ROUND RECESS <br />�� 50W PAR20 NFL 6" RD REGRESSED BAFFLE EYEBALL <br />-} CLG FAN PREWIRE AND SWITCH <br />COMBINATION CARBON MONOIXED DETECTOR/ <br />cs SMOKE DETECTOR <br />C SMOKE DETECTOR <br />=U-18= UNDER CABINET 18" <br />=S-18= SINGLE 18" FLUOR STRIP <br />=U-24= UNDER CABINET 24" <br />=S-24= <br />SINGLE 24" FLUOR STRIP <br />=D-24= <br />DOUBLE 24" FLUOR STRIP <br />= U-36 = <br />UNDER CABINET 36" <br />= S-36 = <br />SINGLE 36" FLUOR STRIP <br />— D-36 = <br />DOUBLE 36" FLUOR STRIP <br />c S-48 — <br />SINGLE 48" FLUOR STRIP <br />r— D-48 <br />DOUBLE 48" FLUOR STRIP <br />24 <br />24"CLG MNT WRAPPED FLUOR LIGHT <br />48 <br />48"CLG MNT WRAPPED FLUOR LIGHT <br />9F24:R <br />24" VANITY LIGHTING <br />FF;;: 36 :FFR 36" VANITY LIGHTING <br />48 48" VANITY LIGHTING <br />® EXHAUST FAN/LIGHT <br />(� EXHAUST FAN <br />DOUBLE FLOOD LIGHT W/ COVERS AND <br />150W PAR 38 FL <br />® INTERCOM SPEAKER AT 5'-0" ABV FINISH FLOOR <br />CEILING MNT SPEAKER <br />M CHIMES (DELETE W/ INTERCOM) <br />MASTER STATION <br />ELEC PANEL <br />® VACUM OUTLET AT 12" <br />CEILING RETURN AIR <br />E3 A/C REGISTER <br />OTC THERMOSTAT <br />On SECURITY PAD <br />ELECTRICAL SPECIFICATION NOTES: <br />ELECTRICAL CONTRACTOR MUST VERIFY WITH THE <br />SPECIFICATIONS FOR THE TYPE OF FIXTURE TO BE USED. LIGHT <br />FIXTURES SHOWN ARE FOR LOCATION PURPOSES. <br />.. <br />N <br />" <br />AR001✓.s <br />00 <br />°< <br />F * 5 <br />w <br />;: <br />ems• <br />O <br />w <br />0 <br />z <br />ti <br />Q <br />to <br />/� ) <br />,I <br />(D LO 'L-,- E <br />> O I, o <br />W <br />CO v ai <br />0 <br />2 <br />-0w 41 M <br />6 :EW S � 1' <br />O <br />TZ1 •� O �- O Q <br />•N <br />V w Q� <br />7W) <br />V <br />00 F M <br />a` a <br />w <br />Ld w .J w M O- O <br />H a-, J =Z p� <br />a <br />LL1��QQ¢�( W0000 <br />Q I-- i- <br />J :0 � <br />�(JU)O'00w00oZ <br />Z� <br />— <br />J� <br />U- <br />Zw <br />-Z- <br />wCf)wZWZO0}a _jW�U)O <br />o <br />LL <br />Ow �F H �YZQQ <br />O� o oQZX <br />Q <br />wQ 0 �¢LL <br />O <br />N <br />Z <br />O IW— <br />(n O <br />cM O <br />Q U) M Lq <br />LL <br />QWQLn <br />a F' M <br />Q Q 00 <br />Z U F- <br />W <br />W <br />J O <br />O <br />tt <br />I <br />I <br />I <br />� <br />I <br />I <br />M <br />N <br />0 <br />N <br />N <br />N <br />N <br />N <br />O <br />N <br />c) <br />00 <br />o <br />O <br />O <br />r <br />o <br />N <br />o <br />I <br />; <br />' <br />Z <br />O <br />W <br />o <br />0 <br />0 <br />0 <br />o <br />I <br />; <br />i <br />V <br />> <br />c- <br />N <br />M <br />4 <br />L6 <br />w <br />w <br />¢Z <br />w <br />O <br />-1--+ <br />W <br />Z <br />z <br />O <br />z <br />U <br />n z j_ <br />O <br />o�� <br />Q <br />Z <br />a -a <br />WWQ <br />� <br />�Fw <br />1171.4 <br />W <br />O <br />ZO2 <br />W <br />n <br />2�2 <br />..MQ <br />Ozwo <br />VazLL <br />Z <br />z <br />LL <br />Z <br />U< <br />00 <br />W <br />Z <br />Z <br />z <br />LLI <br />_j <br />L <br />o <br />T_ <br />LAST PLOT DATE <br />N <br />• <br />March 29, 2022 <br />Z <br />O <br />2ND FLOOR <br />ELECTRICAL PLAN <br />