Laserfiche WebLink
ELECTRICAL SYMBOL LEGEND <br />GENERAL ELECTRICAL NOTES & SPECIFICATIONS <br />1. THE "GENERAL CONDITIONS OF THE CONTRACT", CURRENT EDITION, PUBLISHED IN STANDARD FORM BY <br />THE AMERICAN INSTITUTE OF ARCHITECTS SHALL BE PART OF THIS CONTRACT. <br />2. IT IS NOT THE INTENT OF THESE PLANS AND SPECIFICATIONS TO SHOW EVERY AND ALL DETAILS OF <br />CONSTRUCTION. THE CONTRACTOR SHALL FURNISH AND INSTALL ALL ITEMS REQUIRED FOR A COMPLETE <br />ELECTRICAL INSTALLATION IN PROPER WORKING ORDER. <br />3. ALL WORK AND MATERIALS SHALL BE IN FULL ACCORDANCE WITH THE LATEST ADOPTED EDITION OF THE <br />FLORIDA BUILDING CODE (2020) NEC 2017 AND THE LATEST STATE AND LOCAL CODES THAT APPLY. <br />4. THE CONTRACTOR SHALL TAKE OUT PERMITS, PROCURE CERTIFICATES AND PAY ALL FEES CONNECTED <br />WITH HIS WORK. <br />5. BIDDERS SHALL VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH ALL CONDITIONS SURROUNDING THE <br />WORK. IT SHALL BE THE RESPONSIBILITY OF THE BIDDERS TO VISIT THE SITE OF WORK AND ACQUAINT <br />THEMSELVES WITH ALL AVAILABLE INFORMATION REGARDING THE EXISTING FACILITIES. <br />FAILURE OF THE BIDDERS TO SO INFORM THEMSELVES OF EXISTING CONDITIONS AND TO INCLUDE IN <br />THEIR PROPOSALS A SUM SUFFICIENT TO COVER SAME WILL NOT ENTITLE THEM TO AN EXTRA. <br />6. THE CONTRACTOR IS REFERRED TO THE ARCHITECTURAL PLANS AND SPECIFICATIONS. SUCH PLANS AND <br />SPECIFICATIONS ARE CONTRACT DOCUMENTS. <br />7. DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW APPROXIMATE LOCATIONS OF ALL ELECTRICAL <br />ITEMS. EXACT CONDUIT ROUTING SHALL BE DETERMINED IN THE FIELD, UNLESS OTHERWISE NOTED (LION). <br />8. CONTRACTOR SHALL SUBMIT REQUESTS FOR SUBSTITUTION IN WRITING TO THE ENGINEER, 10 WORKING <br />DAYS PRIOR TO BIDDING DATE. <br />9. THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS FOR APPROVAL FOR ALL EQUIPMENT AND MATERIALS. <br />SUBMIT A MINIMUM OF FOUR SETS TO THE A/E. <br />10. THIS CONTRACTOR SHALL TOUCH UP OR REFINISH THE FACTORY FINISH OF EQUIPMENT MARRED DURING <br />DURING SHIPMENT OR INSTALLATION. THE CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR TO ORIGINAL <br />CONDITIONS ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT, AND FURNISHING CAUSED <br />DURING THE PERFORMANCE OF WORK. <br />11. THE ELECTRICAL INSTALLATION SHALL MEET THE APPROVAL OF THE ENGINEER BEFORE ACCEPTANCE BY <br />THE OWNER. <br />12. THE CONTRACTOR SHALL BE A STATE LICENSED CONTRACTOR. <br />13. THE ENTIRE INSTALLATION SHALL BE PERFORMED UNDER DIRECT SUPERVISION OF A LICENSED MASTER <br />ELECTRICIAN IN A FIRST CLASS WORKMANLIKE MANNER. IT SHALL BE THE RESPONSIBILITY OF THE <br />CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE <br />WORK AS SHOWN AND/OR NOTED ON THE DRAWINGS. <br />14. ELECTRICAL WORK SHALL NOT INTERFERE WITH CLEARANCES REQUIRED FOR GENERAL AND MECHANICAL <br />CONSTRUCTION. SHOULD ELECTRICAL WORK BE INSTALLED WHICH INTERFERES WITH THE WORK OF <br />OTHER TRADES, SUCH WORK SHALL BE CORRECTED AT NO COST TO THE OWNER. THE CONTRACTOR <br />SHALL SUBMIT (4 COPIES) EQUIPMENT LAYOUT OF ALL ELECTRICAL SPACES, ROOMS, ETC., TO <br />ARCHITECT FOR APPROVAL PRIOR TO ORDERING EQUIPMENT OR INSTALLING CONDUITS, ETC., <br />LAYOUTS SHALL CONSIST OF PLAN VIEWS (SCALED AT 1/2" = V-0") AND ELEVATIONS (DIMENSIONED) <br />FOR EACH SPACE, ROOM, ETC., .AND SHALL INCLUDED EQUIPMENT FURNISHED BY OTHER TRADES. <br />15. GROUNDING SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE (ARTICLE 250) AND REQUIREMENTS <br />OF THE INSPECTING AUTHORITY. ALL CONNECTIONS TO GROUND RODS SHALL BE MADE WITH UL <br />APPROVED ACCESSIBLE GROUND CLAMPS, UNLESS OTHERWISE NOTED. <br />16. UPON COMPLETION OF WORK, THIS CONTRACTOR SHALL REMOVE ALL RUBBISH CAUSED BY HIS WORK <br />AND SHALL THOROUGHLY CLEAN ALL ELECTRICAL EQUIPMENT. <br />17. ALL WORK SHALL BE GUARANTEED FREE FROM DEFECTS FOR A PERIOD OF ONE YEAR FROM DATE OF <br />FINAL ACCEPTANCE. <br />18. ALL ITEMS OF ELECTRICAL EQUIPMENT ASSOCIATED WITH THE CONTROL OF ELECTRICAL CIRCUITS AND <br />APPARATUS SHALL BE IDENTIFIED.. <br />19. ALL POWER AND LIGHTING CIRCUIT WIRING SHALL BE COLOR CODED AS FOLLOWS: <br />120 208V. 277 480V. <br />PHASE "A" - BLACK PHASE "A" - BROWN <br />PHASE "B" - RED PHASE "B" - ORANGE <br />PHASE "C" - BLUE PHASE "C" - YELLOW <br />NEUTRAL - WHITE NEUTRAL - GRAY <br />GROUND - GREEN GROUND - GREEN <br />20. ALL CONDUCTORS SHALL BE COPPER, 60OV. #12 AND SMALLER, SOLID TYPE THWN/THHN; <br />#10 AND LARGER, STRANDED TYPE THWN/THHN. <br />21. ALL CONDUCTORS FOR POWER LIMITED CABLES SHALL COMPLY WITH ARTICLES 725 & 760 OF N.E.C. <br />LATEST EDITION. <br />22. NOMINAL MOUNTING HEIGHT OF DEVICES IN EXPOSED CONCRETE BLOCK, TILE OR BRICK WALLS SHALL ALL <br />OCCUR WITHIN A STRUCTURAL COURSE. A MIN. AMOUNT OF BLOCK, TILE OR BRICK WALLS SHALL BE CU'i. <br />23. ALL ELECTRICAL EQUIPMENT AND DEVICES SHALL BE INDUSTRIAL GRADE, HEAVY-DUTY, AND U.L. LISTED <br />UNLESS SPECIFIED OTHERWISE. ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC., SHALL BE LISTED, <br />FOR THE INTENDED USE, WITH UNDERWRITER'S LABORATORIES INC. (UL), WHERE STANDARDS HAVE BEEN <br />ESTABLISHED BY UL. AS A MINIMUM, ALL EQUIPMENT SHALL MEET APPLICABLE STANDARDS, FOR THE <br />TYPE OF EQUIPMENT AND THE INTENDED USE, OF THE FOLLOWING. <br />A. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI) <br />B. ILLUMINATING ENGINEERS SOCIETY (IES) <br />C. AMERICAN SOCIETY FOR TESTING AND MATERIALS (ASTM) <br />D. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA) <br />NOTE: THESE STANDARDS ARE SUBORDINATE TO STANDARDS SET BY U.L. AND LOCAL CODES. <br />24. WIRING DEVICES SHALL BE SPECIFICATION GRADE. MINIMUM SIZE OF OUTLET BOXES SHALL BE 4" SQ. TRADE. <br />OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS IN WET <br />OR DAMP LOCATIONS AND SPECIAL ENCLOSURE FOR OTHER CLASSIFIED AREAS. <br />25. ALL ELECTRICAL CONDUCTORS MUST BE IN CONDUIT. ALL CONDUITS SHALL BE INTERMEDIATE (IMC) <br />OR RIGID GALVANIZED STEEL (RGS) EXCEPT THAT: (A) POLY VINYL CHLORIDE (PVC) CONDUITS MAY BE <br />USED IN CONCRETE SLABS AND UNDERGROUND PROVIDED THAT ELBOWS AND RISERS ARE RGS; (B) <br />ELECTRICAL METALLIC TUBING (EMT) MAY BE USED IN WALLS OR CEILINGS OF FINISHED AREAS WHERE <br />NOT SUBJECT TO MECHANICAL DAMAGE, OR CORROSIVE CONDITIONS; (C) LIQUID TIGHT FLEXIBLE CONDUIT <br />WHERE REQUIRED IN WET OR DAMP LOCATIONS; (D) FLEXIBLE METALLIC CONDUIT WHERE REQUIRED <br />IN DRY LOCATIONS. FLEXIBLE CONDUITS SHALL BE USED FOR ALL VIBRATING EQUIPMENT SUCH AS MOTORS, <br />ETC.ALL CONDUITS IN HAZARDOUS LOCATIONS SHALL MEET THE REQUIREMENTSOF NEC CHAPTER 5. <br />THE USE OF ENT CONDUIT IS PROHIBITED. <br />26. APPLY 2 COATS OF BITUMASTIC COATING TO ALL METALLIC CONDUITS INSTALLED UNDERGROUND. <br />27. NO CONDUITS TO BE RUN IN DUCT WORK. A POLYESTER PULL CORD SHALL BE INSTALLED IN ALL EMPTY <br />CONDUITS. <br />28. SIZE ALL WIREWAYS ACCORDING TO N.E.C. ARTICLE 376 AND 378 <br />29. ALL RATED WALL/FLOOR PENETRATIONS ARE TO BE SEALED WITH A FIRE RATED SEALER, PER ASTM E814. <br />30. WHERE CORE DRILLING OF FLOORS/WALLS IS REQUIRED, CONTRACTOR SHALL SEAL OPENINGS AFTER <br />UTILITIES HAVE BEEN INSTALLED. LOCATION OF CORED HOLES SHALL COORDINATE WITH LOCATION OF <br />EQUIPMENT IN A MANNER TO BE CLEAN AND FUNCTIONAL. THE CONTRACTOR SHALL INSTALL ONLY ONE <br />CONDUIT PER HOLE AND SEAL AROUND THE OPENING AS SPECIFIED ABOVE. <br />31, ANY VARIATION FROM THE PLANS ARE TO BE PREVIOUSLY APPROVED BY THE ENGINEER IN WRITING. <br />32. CONDUIT AND ELECTRICAL EQUIPMENT EXPOSED TO WEATHER MUST BE WEATHERPROOF (NEMA 3R). <br />33. FUSES SHALL BE BUSSMAN "FUSETRON" DUAL -ELEMENT FUSES FOR BRANCH CIRCUIT PROTECTION AND <br />ALSO FOR MOTOR RUNNING PROTECTION IF REQUIRED, OR FUSES AS CALLED FOR ON DRAWINGS. <br />34. TERMINATIONS ARE TO BE MADE AS PER U.L. ARTICLE 486B. <br />35. THE GENERAL CONTRACTOR SHALL COORDINATE ALL ELECTRICAL SITE WORK. <br />36. ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL MAGNETIC). MULTI -POLE CIRCUIT <br />BREAKERS SHALL BE COMMON TRIP. NO TIE HANDLES PERMITTED. <br />37. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR FOR THE ADVANCED ORDERING OF LONG LEAD <br />ITEMS, AS NOT TO INTERFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN <br />OR LAG TIME. <br />38. THE CONTRACTOR SHALL VERIFY CIRCUIT DEVICE PROTECTIVE RATING FOR EQUIPMENT PRIOR TO <br />CONSTRUCTION. <br />39. USE 3/4" EXTERIOR GRADE PLYWOOD BACKBOARDS FOR SURFACE MOUNTING GROUPED EQUIPMENT, <br />PAINTED ON BOTH SIDES AND EDGES WITH TWO COATS OF NAVAL GRAY PAINT (FIRE RESISTANT). <br />40. NO CUTTING OR DRILLING OF STRUCTURAL ITEMS SHALL BE DONE WITHOUT PRIOR WRITTEN APPROVAL <br />FROM A LICENSED STRUCURAL ENGINEER. <br />41 ALL DEDICATED OUTLETS SERVING EQUIPMENT SUCH AS REFRIGERATORS, WATER COOLERS, COPIERS, FAXES, <br />ETC. SHALL HAVE SEPARATE NEUTRAL CONDUCTORS TO EACH DEVICE OR APPLIANCE. <br />42 ELECTRICAL POWER AND CONTROL WIRING FOR H.V.A.C. AND MECHANICAL EQUIPMENT SHALL BE FURNISHED <br />AND INSTALLED BY THE ELECTRICAL CONTRACTOR. <br />43 ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES AND SUSPENSION SYSTEMS FOR SELECTION <br />OF THE PROPER TRIM AND SUPPORT ARRANGEMENTS OF THE FIXTURE. <br />44 ALL ELECTRICAL EQUIPMENT SHALL BE APPROVED AS SAFE FOR USE IN THE U.S. WORKPLACE, AS PER A <br />"NRTL" RECOGNIZED ORGANIZATION (U.L., C.S.A., ETC.). <br />45 PROVIDE EXPANSION JOINTS WHERE REQUIRED AS PER N.E.C. 300-7(b). <br />I To the best of the Architect's'<nowledge these plans comply with the minimum standards of the applicable codes and life safety standards as determined in accordance with Chapter 553 and 663 of the Florida statutes <br />For Construction <br />Review Set <br />Not for Construction <br />® <br />Permit Set <br />Bid Set <br />Record Set <br />LIGHTING FIXTURE <br />(SEE LIGHTING FIXTURE SCHEDULE ALSO) <br />® Oa <br />CEILING LIGHT FIXTURE -UPPER CASE LETTER DESIGNATES FIXTURE TYPE, LOWER CASE LETTER <br />DESIGNATES SWITCHING. <br />-, <br />EXIT SIGN (LIGHT FIXTURE) CEILING OR WALL MOUNTED DOUBLE SIDED SIGN- CONNECTED TO LIGHTING CIRCUIT. <br />ARROWS INDICATE DIRECTIONS. PROVIDE WITH BATTERY PACK. <br />TYPES <br />CEILING OR WALL MOUNTED EXIT SIGN FIXTURE. CONNECTED TO LIGHTING CIRCUIT. <br />AS SPECIFIED IN FIXTURE SCHEDULE. PROVIDE WITH BATTERY PACK. <br />pCEILING <br />TYPES <br />OR WALL MOUNTED EMERGENCY/EXIT SIGN COMBO FIXTURE. CONNECTED TO LIGHTING CIRCUIT. <br />AS SPECIFIED IN FIXTURE SCHEDULE. PROVIDE WITH BATTERY PACK. <br />DUAL HEAD EMERGENCY STAND-BY LIGHT, WITH BATTERY PACK, WALL MOUNTED. <br />MT. UP 7-6" A.F.F. TO � OF OUTLET BOX. <br />�--� <br />EXISTING HID EXTERIOR LIGHTING FIXTURE - POLE MOUNTED <br />RECESSED MOUNTED 2X4 LED FIXTURE. <br />E <br />RECESSED MOUNTED 2X2 LED FIXTURE. <br />&;J <br />RECESSED MOUNTED 2X4 LED FIXTURE. HATCH DENOTES BATTERY BACK UP <br />RECESSED MOUNTED 2X2 LED FIXTURE. HATCH DENOTES BATTERY BACK UP <br />CEILING MOUNTED OCCUPANCY SENSOR. MODEL VAC-DT SERIES OR EQUIVALENT. <br />WIRE AS PER MANUFACTURER SPECS <br />TOGGLE SWITCHES <br />(SPECIFICATION GRADE - IVORY COLOR) <br />$a <br />SINGLE POLE TOGGLE SWITCH, 20 AMP, 120/277V.,SPECIFICATION GRADE. LETTER DENOTES LIGHTS ON <br />SWITCH "A'. MOUNT AT 48' A.F.F. TO CL OF OUTLET BOX UNLESS NOTED. <br />2 <br />110 <br />TWO POLE TOGGLE SWITCH , 20 AMP, 120/277V., SPECIFICATION GRADE LETTER DENOTES <br />LIGHTS ON SWITCH "A'. MOUNT AT 48' A.F.F. TO CL OF OUTLET BOX UNLESS NOTED, <br />3 THREE <br />1'0 <br />WAY SWITCH , 20 AMP, 120/277V., SPECIFICATION GRADE LETTER DENOTES <br />LIGHTS SWITCHED. MOUNT AT 48" A.F.F. TO CL OUTLET BOX UNLESS NOTED. <br />4 <br />1'0 <br />FOUR WAY SWITCH , 20 AMP, 120/277V., SPECIFICATION GRADE LETTER DENOTES <br />LIGHTS SWITCHED. MOUNT AT 48" TO CL OF OUTLET BOX A.F.F. UNLESS NOTED. <br />6 = <br />OCCUPANCY/VACANCY SENSOR SWITCH VNW-D OR EQUIVALENT. <br />1,- <br />LED COMPATIBLE DIMMER SWITCH. MT. AS DIRECTED ON PLAN. <br />RECEPTACLES <br />(SPECIFICATION GRADE - IVORY COLOR) <br />po <br />DUPLEX RECEPTACLE; 20 A.,120 V.,GROUNDING TYPE. MOUNTED 18" A.F.F. TO CL OF OUTLET BOX. <br />(EXCEPT AS NOTED). HUBBELL 52621 U.O.N. <br />GO <br />DUPLEX RECEPTACLE; 20 A.,120 V.,GROUNDING TYPE. VERIFY MOUNTING HEIGHT. HUBBELL 52621 U.O.N. <br />k� <br />DUPLEX RECEPTACLE; 20 A.,120 V.,GROUNDING TYPE. SWITCHED AS PER PLAN. <br />C30 <br />QUADUPLEX RECEPTACLE 20 A., 120 V., GROUNDING TYPE. MOUNTED 18" A.F.F.. HUBBELL 4151 U.O.N. <br />D <br />DEDICATED HOSPITAL GRADE DUPLEX RECEPTACLE; 20 A.,120 V.,GROUNDING TYPE. MAY BE <br />INSTALLED IN COVER OF WIREMOLD. <br />DUPLEX RECEPTACLE MOUNTED HORIZONTALLY; 20 A.,120 V.,GROUNDING TYPE. MOUNTED AS NOTED ON PLANS <br />(EXCEPT AS NOTED). <br />DUPLEX GFI RECEPTACLE MOUNTED HORIZONTALLY; 20 A.,120 V.,GROUNDING TYP�. MOUNTED UP AS NOTED ON <br />PLANS. EXCEPT IN RESTROOMS NEXT TO SINKS WHERE IT SHALL BE MOUNTED AT 42' A.F.F. TO C OF OUTLET. <br />DUPLEX RECEPTACLE; 20 A.,120 V.,GROUNDING TYPE. MOUNTED 18" A.F.F. TO C OF OUTLET BOX. <br />(EXCEPT AS NOTED). CONNECTED THRU EMERGENCY PANEL. <br />14 <br />CEILING MOUNTED OUTLET BOX FLUSH WITH TILE. <br />F-0 <br />D <br />DRYER RECEPTACLE. MT. UP 42" TO � OF OUTLET BOX. <br />LJ <br />LJ <br />DENOTES FLOOR MOUNTED <br />TELEPHONE SYSTEM <br />DATA OUTLET 4-11/16" X 4-11/16" 2-1/8" WITH BUSHED HOLE COVER PLATE- MOUNTED <br />18" A.F.F. TO � OF OUTLET(EXCEPT AS NOTED) PROVIDED 3/4" E.C. FROM EACH OUTLET TO STUB UP 6" <br />ABOVE CL'G SPACE (EXCEPT AS NOTED.) <br />>1 <br />DEDICATE PHONE LINE MOUNTED 18" A.F.F.LTO C OF OUTLET(EXCEPT AS NOTED) PROVIDED 3/4" <br />E.C. FROM EACH OUTLET TO STUB UP 6" ABOVE CL'G SPACE (EXCEPT AS NOTED.) <br />CONDUITS <br />1� <br />ARROW DESIGNATES "HOMERUN" TO PANEL,HASH MARKS DESIGNATE NUMBER OF WIRES. <br />INDICATES GREEN BOND WIRE <br />------ <br />INDICATES CONDUIT RUN EXPOSED. <br />NSS <br />TRANSIENT VOLTAGE SURGE SUPPRESOR <br />POWER DISTRIBUTION <br />Vii <br />I� <br />VARIBLE FREQ. DRIVE WITH LINE SIDE BRAKER FURNISHED BY DIV. 15 MT'D AND CONNECTED BY DIV. 16 <br />EP <br />SAFETY SWITCH - HEAVY DUTY NEMA CLASS "A" IN NEMA 1 ENCLOSURE, OUTDOOR TYPE NEMA 3R. <br />20 <br />3 Q <br />DESIGNATES SWITCH RATING, "3" DESIGNATES POLES; "20" TIME DELAY FUSE; "30"SWITCH AMPS. <br />HVAC MOTORIZED DAMPER FURNISHED BY DIV. 15 <br />CONNECTED BY DIV. 16 CONTRACTOR. <br />4 <br />MOTOR. (FURNISHED BY ARCH. DIV. 13, OR 15 CONNECTED BY DIV 16. OR ELEV./ESC. INSTALLER) <br />® <br />120/208V., 30, 4W. PANEL BOARD. <br />REMOTE EMERGENCY OFF SHUNT TRIP SWITCH. <br />JUNCTION BOXES <br />EQUIPMENT JUNCTION BOX, FURNISHED WITH EQUIPMENT. <br />a/O <br />WALL CEILING MOUNTED JUNCTION BOX. <br />MINIMUM 4" X 4" X 1 1/2" WITH BLANK PLATE. MT. WALL BOX UP AS SHOWN ON PLAN. <br />dVos <br />WALL/CEILING MOUNTED J.BOX FOR SIGNAGE. MT. WALL BOX UP AS SHOWN ON RAN. <br />AUXILIARY SYSTEMS <br />INTERCOM CALL BUTTON AND VOLUME CONTROL SWITCH <br />C S <br />COMBINATION CLOCK SPEAKER <br />ED <br />SINGLE GANG JUNCTION BOX FOR P.A. HORN SPEAKER. CONTRACTOR TO FIELD COORDINATE MOUNTING HEIGHT. <br />ABBREVIATIONS <br />ABBREVIATION <br />DESCRIPTION <br />ABBREVIATION <br />DESCRIPTION <br />A.C.T. <br />ABOVE COUNTER TOP <br />K.V.A. <br />KILOVOLT AMPERES <br />A.F.F. <br />ABOVE FINISHED FLOOR <br />MAX. <br />MAXIMUM <br />(TYP.) <br />TYPICAL <br />MIN. <br />MINIMUM <br />PNL. <br />PANEL <br />(MFR) MANUF. <br />MANUFACTURER <br />L.T. <br />LIGHT <br />GFI. <br />GROUND FAULT INTERRUPTER <br />FIXT. <br />FIXTURE <br />GND. <br />GROUND <br />BRKR. <br />BREAKER <br />W.P. <br />WEATHER PROOF <br />0 <br />PHASE <br />M.C.B. <br />MAIN CIRCUIT BREAKER <br />PVC <br />POLYVINYL -CHLORIDE <br />F/N <br />FULL NEUTRAL <br />RGS <br />RIGID GALVANIZED STEEL <br />SURF. <br />SURFACE <br />PWR. <br />POWER <br />HTD. <br />MOUNTED <br />MTG. <br />MOUNTING <br />REC. <br />RECEPTACLE <br />oss if 1, 2 or 3 Hour Fire Rated <br />�a Through Penetration Firestop for <br />Single Metal Pipe through <br />Concrete floors or walls using <br />SYsIt TREMstop WBM. <br />CAJ1144 F-RATING = 1, 2 and 3 Hr. <br />T-RATING = 1, 2 AND 3 Hr. F=T <br />2 <br />3A 36 <br />1 <br />.d. <br />2 a. <br />a <br />3B <br />3A <br />DRAWING NOT TO SCALE <br />10 FLOOR OR WALL ASSEMBLY = 4" TO 6" THICK CONCRETE. <br />Q STEEL PIPE: 6" DIAMETER (OR SMALLER) SCHEDULE 40 (OR <br />HEAVIER) <br />STEEL. <br />Q Max. Pipe Min. Forming Min. Fill F <br />T <br />Diameter Mat[. Thkns Mat]. Thkns Rating <br />Rating <br />(inches) (inches) (inches) (Hour) <br />(Hour) <br />6 4 0.5 1 <br />0 <br />4 3.5 1 2 <br />0.5 <br />6 1.25 2.375 3 <br />0 <br />* ANNULAR SPACE IS 3/4" <br />A. 4.0 pcf MINIMUM DENSITY MINERAL WOOL INSULATION, FRICTION <br />FITTED. <br />B. MINIMUM FILL THICKNESS OF TREMstop WBM. <br />NOTE: <br />FOR WALLS APPLY TREMstop WBM TO BOTH SURFACES OF <br />WALL. <br />DETA L-A <br />CONCRETE WALL OR SLAB PENETRAT ON DUAL- <br />1 or 2 Hour Fire Rated Through <br />oss if/. Penetration Firestop for Single <br />G <br />`Do Metal Pipe through Gypsum <br />walls using TREMstop WBM. <br />SYS t � <br />VA/L1051 F-RATING = 1 and 2 Hr. <br />T-RATING = 1 and 2 Hr. <br />F=T <br />31. 3 - <br />Ito <br />2 =_ <br />2 <br />[DRAWING NOT TO SCALE <br />0 1 OR 2 HOUR FIRE RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY. <br />0 STEEL PIPE: 6" DIAMETER (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL. <br />CONDUIT:4" DIAMETER (OR SMALLER) EMT OR RIGID STEEL CONDUIT. <br />CIRCULAR DUCT: 4" DIAMETER (OR SMALLER) 26 GAUAGE (OR HEAVIER) <br />GALVANIZED STEEL VENT DUCT. <br />0 TREMstop WBM: FILL MAXIMUM 3/4" ANNULUS WITH A THICKNESS OF 1 <br />1/4" (2 HOUR F-RATING) OR 3/4" (1 HOUR F-RATING). <br />DETAIL-B. <br />GYPSUM WALL PENETRATION DETA L <br />All designs, details and drawings indicated and <br />represented are for use on and in conjunction with <br />the specified project, the designs and drawings <br />are the property of the Architect and shall not be <br />reproduced in whole or in part without the written <br />permission of M3o Architecture, Inc <br />