<br />Design No. U465
<br />BXUV.U465
<br />Fire Resistance Ratings - ANSI/UL 263
<br />Page Bottom
<br />Design/System/Construction/Assembly Usage Disclaimer
<br />. Authorities Having Jurisdiction should be consulted in all cases as to the particular requirements covering the installation and use of UL
<br />Certified products, equipment, system, devices, and materials.
<br />Authorities Having Jurisdiction should be consulted before construction.
<br />. Fire resistance assemblies and products are developed by the design submitter and have been investigated by UL for compliance with
<br />applicable requirements. The published information cannot always address every construction nuance encountered in the field.
<br />. When field issues arise, it is recommended the first contact for assistance be the technical service staff provided by the product
<br />manufacturer noted for the design. Users of fire resistance assemblies are advised to consult the general Guide Information for each
<br />product category and each group of assemblies. The Guide Information includes specifics concerning alternate materials and alternate
<br />methods of construction.
<br />. Only products which bear UUs Mark are considered Certified.
<br />BXUV - Fire Resistance Ratings - ANSI/UL 263
<br />BXUV7 - Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada
<br />See General Information for Fire -resistance Ratings - ANSI/UL 263
<br />See General Information for Fire Resistance Ratings - CAN/ULC-S101 Certified for Canada
<br />Design No. U465
<br />May 30, 2017
<br />Nonbearing Wall Rating — 1 HR.
<br />* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such
<br />assCCanada), respectively.
<br />, / � kS.:/
<br />I.i
<br />--.—t
<br />T 1 _. �:
<br />11 I i
<br />a A/
<br />I--_" _
<br />1 I~_ -' '� i .*.
<br />i
<br />1. Floor and Ceiling Runners — (Not Shown) — Channel shaped runners, 3-5/8 in. deep (min), 1-1/4 in. legs, formed
<br />from min No. 25 MSG gaiv steel, attached to floor and ceiling with fasteners spaced 24 in. OC max.
<br />IA. Framing Members* — Floor and Ceiling Runners — (Not Shown) — As an alternate to Item 1 — Channel
<br />shaped, min 3-5/8 in. deep, attached to floor and ceiling with fasteners 24 in. OC. max.
<br />ALLSTEEL & GYPSUM PRODUCTS INC — Type SUPREME Framing System
<br />CONSOLIDATED FABRICATORS CORP, BUILDING PRODUCTS DIV — Type SUPREME Framing System
<br />QUAIL RUN BUILDING MATERIALS INC — Type SUPREME Framing System
<br />SCAFCO STEEL STUD MANUFACTURING CO — Type SUPREME Framing System
<br />STEEL CONSTRUCTION SYSTEMS INC — Type SUPREME Framing System
<br />UNITED METAL PRODUCTS INC — Type SUPREME Framing System
<br />1B. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Item 1 — For use with Item 2B,
<br />proprietary channel shaped runners, 1-1/4 in. wide by min 3-5/8 in. deep fabricated from min 0.020 in. thick galv steel,
<br />attached to floor and ceiling with fasteners spaced 24 in. OC max.
<br />CALIFORNIA EXPANDED METAL PRODUCTS CO — Viper20-' Track
<br />CRACO MFG INC — SmartTrack20`"
<br />MARINO/WARE, DIV OF WARE INDUSTRIES INC — Viper20'" Track
<br />1C. Floor and Ceiling Runners — (Not Shown) — For use with Item 2C — Channel shaped, fabricated from min 20
<br />MSG corrosion -protected or gals steel, min depth to accommodate stud size, with min 1 in. long legs, attached to floor
<br />and ceiling with fasteners spaced max 24 in. OC.
<br />ID. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Items 1 through 1C — For use with
<br />Item 2D and 4G only, proprietary channel shaped runners, 1-1/4 in, deep by min 3-5/8 in. wide fabricated from min
<br />0.018 in. thick gaiv steel, attached to floor and ceiling with fasteners spaced 24 in. OC max.
<br />CLARKDIETRICH BUILDING SYSTEMS — CD ProTRAK
<br />DMFCWBS L L C — ProTRAK
<br />MBA METAL FRAMING — ProTRAK
<br />RAM SALES L L C — Ram ProTRAK
<br />STEEL STRUCTURAL PRODUCTS L L C — Tri-S ProTRAK
<br />I.E. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Items 1 through 1D — For use with
<br />Item 2E and 4I only, proprietary channel shaped runners, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min
<br />0.018 in. thick galv steel, attached to floor and ceiling with fasteners spaced 24 in. OC max.
<br />TELLING INDUSTRIES L L C — TRUE -TRACK'"'
<br />1F. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Items 1 through lE — For use with
<br />Item 2, channel shaped runners, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 25 MSG steel, attached to
<br />floor and ceiling with fasteners spaced 24 in. OC max.
<br />KIRII (HONG KONG) LTD — Type KIRII
<br />IG. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Items 1 through 1F — For use with
<br />Item 2, channel shaped runners, 1-1/4 in. deep by min 3-5/8 in. wide, attached to floor and ceiling with fasteners
<br />spaced 24 in. OC max.
<br />STUDCO BUILDING SYSTEMS — CROCSTUD Track
<br />1H. Floor and Ceiling Runners — (Not Shown) — Channel shaped, fabricated from min 0.02 in. galv steel, min width
<br />to accommodate stud size, with min I in. long legs, for use with studs specified below and fabricated from min 0.02 in
<br />galv steel or thicker, attached to floor and ceiling with fasteners spaced max 24 in. OC.
<br />MARINO/WARE, DIV OF WARE INDUSTRIES INC — Viper20' Track VT100
<br />1I. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Item 1 — For use with Item 2H,
<br />proprietary channel shaped runners, 1-1/4 in. wide by min 3-5/8 in. deep fabricated from min 0.020 in. thick galv steel,
<br />attached to floor and ceiling with fasteners spaced 24 in. OC max.
<br />TELLING INDUSTRIES L L C — Viper201' Track
<br />13. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Items 1 — For use with Item 2 L,
<br />proprietary channel shaped runners, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick gals steel,
<br />attached to floor and ceiling with fasteners spaced 24 in. OC max.
<br />STEEL INVESTMENT GROUP L L C — AlphaTRAK
<br />2, Steel Studs — Channel shaped, 3-5/8 in, deep (min), formed from min No. 25 MSG gaiv steel spaced 24 in. OC
<br />max. Studs to be cut 3/4 in. less than assembly height.
<br />2A. Framing Members* — Steel Studs — As an alternate to Item 2 — Channel shaped studs, min 3-5/8 in. deep,
<br />spaced a max of 24 in. OC. Studs to be cut 3/4 in. less than assembly height.
<br />ALLSTEEL & GYPSUM PRODUCTS INC — Type SUPREME Framing System
<br />CONSOLIDATED FABRICATORS CORP, BUILDING PRODUCTS DIV — Type SUPREME Framing System
<br />QUAIL RUN BUILDING MATERIALS INC — Type SUPREME Framing System
<br />SCAFCO STEEL STUD MANUFACTURING CO — Type SUPREME Framing System
<br />STEEL CONSTRUCTION SYSTEMS INC — Type SUPREME Framing System
<br />UNITED METAL PRODUCTS INC — Type SUPREME Framing System
<br />2B. Framing Members* — Steel Studs — Not Shown — In lieu of Item 2 — For use with Item 1B, proprietary
<br />channel shaped steel studs, 1-1/4 in. wide by min 3-5/8 in. deep fabricated from min 0.020 in. thick gals steel. Studs
<br />cut 3/4 in. less in length than assembly height.
<br />CALIFORNIA EXPANDED METAL PRODUCTS CO — Viper20'
<br />CRACO MFG INC — SmartStud20'
<br />MARINO/WARE, DIV OF WARE INDUSTRIES INC — Viper20'"
<br />Copyright © 2018. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the
<br />expressed written consent of this corporation is prohibited. All rights reserved.
<br />1I. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Item 1 — For use with Item 2H,
<br />proprietary channel shaped runners, 1-1/4 in. wide by min 3-5/8 in. deep fabricated from min 0.020 in. thick galv steel,
<br />attached to floor and ceiling with fasteners spaced 24 in. OC max.
<br />TELLING INDUSTRIES L L C — Viper20'" Track
<br />11. Framing Members* — Floor and Ceiling Runners — Not Shown — In lieu of Items 1 — For use with Item 2 L,
<br />proprietary channel shaped runners, 1-1/4 in. deep by min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel,
<br />attached to floor and ceiling with fasteners spaced 24 in. OC max.
<br />STEEL INVESTMENT GROUP L L C — AlphaTRAK
<br />2. Steel Studs — Channel shaped, 3-5/8 in. deep (min), formed from min No. 25 MSG galv steel spaced 24 in. OC
<br />max. Studs to be cut 3/4 in. less than assembly height.
<br />2A. Framing Members* — Steel Studs — As an alternate to Item 2 — Channel shaped studs, min 3-5/8 in. deep,
<br />spaced a max of 24 in. OC. Studs to be cut 3/4 in. less than assembly height.
<br />ALLSTEEL & GYPSUM PRODUCTS INC — Type SUPREME Framing System
<br />CONSOLIDATED FABRICATORS CORP, BUILDING PRODUCTS DIV — Type SUPREME Framing System
<br />QUAIL RUN BUILDING MATERIALS INC — Type SUPREME Framing System
<br />SCAFCO STEEL STUD MANUFACTURING CO — Type SUPREME Framing System
<br />STEEL CONSTRUCTION SYSTEMS INC — Type SUPREME Framing System
<br />UNITED METAL PRODUCTS INC — Type SUPREME Framing System
<br />2B. Framing Members* — Steel Studs — Not Shown — In lieu of Item 2 — For use with Item 1B, proprietary
<br />channel shaped steel studs, 1-1/4 in. wide by min 3-5/8 in. deep fabricated from min 0.020 in. thick galv steel. Studs
<br />cut 3/4 in. less in length than assembly height.
<br />CALIFORNIA EXPANDED METAL PRODUCTS CO — Viper2l) "
<br />CRACO MFG INC — SmartStud20'
<br />MARINO/ WARE, DIV OF WARE INDUSTRIES INC — Viper20'"
<br />2C. Steel Studs — (As an alternate to Item 2, For use with Item 4E) — Channel shaped, fabricated from min 20 MSG
<br />corrosion -protected or galv steel, 3-1/2 in. min depth, spaced a max of 16 in. OC. Studs friction -fit into floor and
<br />ceiling runners. Studs to be cut 5/8 to 3/4 in. less than assembly height.
<br />2D. Framing Members* — Steel Studs — As an alternate to Items 2 through 2C — For use with Item ID and 4G
<br />only, channel shaped studs, min 3-5/8 in, wide fabricated from min 0.018 in. thick galv steel, spaced a max of 24 in.
<br />OC. Studs to be cut 1/2 in. less than assembly height.
<br />CLARKDIETRICH BUILDING SYSTEMS — CD ProSTUD
<br />DMFCWBS L L C — ProSTUD
<br />MBA METAL FRAMING — ProSTUD
<br />RAM SALES L L C — Ram ProSTUD
<br />STEEL STRUCTURAL PRODUCTS L L C — Tri-S ProSTUD
<br />2E. Framing Members* — Steel Studs — As an alternate to Items 2 through 2D — For use with Item lE and 4I only,
<br />channel shaped studs, min 3-5/8 in. wide fabricated from min 0.018 in. thick gaiv steel, spaced a max of 24 in. OC.
<br />Studs to be cut 1/2 in. less than assembly height.
<br />TELLING INDUSTRIES L L C — TRUE -STUD'"
<br />2F. Framing Members* — Steel Studs — As an alternate to Items 2 through 2E — For use with Item 1F, channel
<br />shaped studs, min 3-5/8 in. wide fabricated from min 25 MSG steel, spaced a max of 24 In. OC. Studs to be cut 1/2 in
<br />less than assembly height.
<br />KIRII (HONG KONG) LTD — Type KIRII
<br />2G. Framing Members* — Steel Studs — Not Shown — In lieu of Item 2 through 2F — For use with Item IG.
<br />Proprietary channel shaped studs, minimum 3-5/8 in, wide, Studs to be cut 1/2 in, less than the assembly height.
<br />STUDCO BUILDING SYSTEMS — CROCSTUD
<br />2H. Framing Members* — Steel Studs — Not Shown — In lieu of Item 2 — For use with Item 11, proprietary channel
<br />shaped steel studs, 1-1/4 in. wide by min 3-5/8 in. deep fabricated from min 0.020 in. thick galv steel. Studs cut 3/4
<br />in. less in length than assembly height.
<br />TELLING INDUSTRIES L L C — ViP er20—
<br />2I. Framing Members* — Steel Studs — In lieu of Item 2 — For use with Item 1, channel shaped studs, fabricated
<br />from min 25 MSG corrosion -protected steel, 3-5/8 in. deep (min), spaced 24 in. OC max. Studs to be cut 3/4 in. less
<br />than assembly height.
<br />ES METAL INC — NITROSTUD
<br />2J. Framing Members* — Steel Studs — In lieu of Item 2 — For use with Item 1, channel shaped studs, fabricated
<br />from min 25 MSG corrosion -protected steel, 3-5/8 in. deep (min), spaced 24 in, OC max. Studs to be cut 3/4 in. less
<br />than assembly height.
<br />OL14AR SUPPLY INC — PRIMESTUD
<br />2K. Framing Members* — Steel Studs — As an alternate to Item 2 — For use with Item IB (3-5/8 in. wide track),
<br />channel shaped studs, fabricated from min 25 MSG corrosion -protected steel, 1-1/4 in. wide by 3-5/8 in. deep, spaced
<br />a max of 24 in. OC. Studs to be cut 3/8 to 3/4 in. less than assembly height.
<br />MARINO/WARE, DIV OF WARE INDUSTRIES INC — Studilite-
<br />2L. Framing Members* — Steel Studs — As an alternate to Items 2 — For use with Item 1J, channel shaped studs,
<br />min 3-5/8 in. wide fabricated from min 0.018 in. thick galv steel, spaced a max of 24 in. OC. Studs to be cut 3/4 in.
<br />less than assembly height.
<br />STEEL INVESTMENT GROUP L L C — AlphaSTUD
<br />3. Batts and Blankets* — (Optional) — Mineral wool or glass fiber batts partially or completely filling stud cavity.
<br />See Batts and Blankets (BZJZ) category for names of Classified companies.
<br />3A. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 3) — (100% Borate Formulation) — Spray applied
<br />cellulose material. The fiber is applied with water to completely fill the enclosed cavity in accordance with the
<br />application instructions supplied with the product with a nominal dry density of 2.7 Ib/ft3. Alternate Application Method:
<br />The fiber is applied without water or adhesive at a nominal dry density of 3.5 Ib/ft3, in accordance with the application
<br />instructions supplied with the product.
<br />U S GREENFIBER L L C — IN5735 & INS745 for use with wet or dry application. INS765LD and INS77OLD are to be
<br />used for dry application only
<br />3B. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 3) and Item 3A — Spray applied cellulose
<br />insulation material. The fiber is applied with water to interior surfaces in accordance with the application instructions
<br />supplied with the product. Applied to completely fill the enclosed cavity. Minimum dry density of 4.3 pounds per cubic
<br />ft.
<br />NU -WOOL CO INC — Cellulose Insulation
<br />3C. Fiber, Sprayed* — As an alternate to Batts and Blankets (Item 3) — Spray applied cellulose fiber The fiber is
<br />applied with water to completely fill the enclosed cavity in accordance with the application instructions supplied with the
<br />product. The minimum dry density shall be 4.30 Ibs/ft3.
<br />INTERNATIONAL CELLULOSE CORP — Celbar-RL
<br />3D. Batts and Blankets* — For use with Item S. Nom 3 in. thick, minimum 3.4 pcf mineral wool batts, friction fit
<br />between the studs and floor and ceiling runners.
<br />See Batts and Blankets (BZJZ) category for names of manufacturers.
<br />3E. Batts and Blankets* — For use with Item 4P. Placed in stud cavities, any min. 3-1/2 in. thick glass fiber
<br />insulation bearing the UL Classification Marking as to Surface Burning Characteristics and/or Fire Resistance,
<br />See Batts and Blankets (BKNV or BZJZ) Categories for names of Classified companies
<br />4. Gypsum Board* — 5/8 in. thick, 4 ft wide, attached to steel studs and floor and ceiling track with 1 in. long, Type
<br />S steel screws spaced 8 in. OC. along edges of board and 12 in. OC in the field of the board. Joints oriented vertically
<br />and staggered on opposite sides of the assembly. When attached to Items 6 (resilient channels) or 6A, 6B or 6C
<br />(fuming channels), gypsum board is screw attached to furring channels with 1 in. long, Type S steel screws spaced 12
<br />in. OC.
<br />ACADIA DRYWALL SUPPLIES LTD — Type X, 5/8 Type X, Type Biueglass Exterior Sheathing
<br />AMERICAN GYPSUM CO — Types AG-C, AGX-1, M-Glass
<br />BEIJING NEW BUILDING MATERIALS PUBLIC LTD CO — Type DBX-1
<br />CGC INC — Types AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, USGX, WRC or WRX (Joint tape and compound,
<br />Item 5, optional for use with Type USGX)
<br />CERTAINTEED GYPSUM INC — Types l EGRG G1asRoc Type
<br />Pe X Type X 1 Type C 5/8" Easi Lite TYPe X
<br />CONTINENTAL BUILDING PRODUCTS OPERATING CO, L L C — Types LGFC2A, LGFC6A, LGFC-C/A, LGFC-WD,
<br />LGLLX
<br />GEORGIA-PACIFIC GYPSUM L L C — Types 5, 6, 9, C, DAP, DD, DA, DAPC, DGG, DS, GPF56, LS, Type X, Veneer
<br />Piaster Base - Type X, Water Rated - Type X, Sheathing - Type X, Soffit - Type X, TG-C, GreenGlass Type X, Type X
<br />ComfortGuard Sound Deadening Gypsum Board, Type LWX, Veneer Plaster Base -Type LWX, Water Rated -Type LWX,
<br />Sheathing Type-LWX, Soffit -Type LWX, Type DGLW, Water Rated -Type DGLW, Sheathing Type- DGLW, Soffit -Type
<br />DGLW, Type LW2X, Veneer Plaster Base - Type LW2X, Water Rated - Type LW2X, Sheathing - Type LW2X, Soffit - Type
<br />LW2X, Type DGL2W, Water Rated - Type DGLZW, Sheathing - Type DGL2W
<br />K
<br />3
<br />NATIONAL GYPSUM CO — Types eXP-C, FSK, FSK-C, FSK-G, FSMR-C, FSW-C, FSW-G, FSW, FSW-3, FSW-5, FSW-6,
<br />FSW-8, FSL
<br />PA13CO BUILDING PRODUCTS L L C, DBA PASCO GYPSUM — Types PG-C, PG-9, PG-11, PGS-WRS
<br />PANEL REY S A — Types GREX, PRC, PRC2, PRX, RHX, MDX, ETX
<br />SAINT-GOBAIN GYPROC MIDDLE EAST FZE — Type Gyproc FireStop, Gyproc FireStop MR, Gyproc FireStop M2TECH,
<br />Gyproc FireStop ACTIV'Air, Gyproc FireStop MR ACTIV'Air, Gyproc FireStop M2TECH ACTIV'Air, Gyproc DuraLine, Gyproc
<br />DuraLine MR, Gyproc Dural-ine M2TECH, Gyproc Dural-ine ACTIV'Air, Gyproc DuraLine MR ACTIV'Air, Gyproc Dural-ine
<br />M2TECH ACTIV'Air
<br />SLAM GYPSUM INDUSTRY (SARABURI) CO LTD — Type EX-1
<br />THAI GYPSUM PRODUCTS PCL — Type X, Type C
<br />(Joint tape and compound, Item 5, optional for use with Type USGX)
<br />USG SORAL ZAWAWI DRYWALL L L C SFZ — Types C, SCX
<br />USG MEXICO S A DE C V — Type AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, USGX, WRC or WRX (Joint tape and
<br />compound, Item 5, optional for use with Type USGX)
<br />4A. Gypsum Board* — (As alternate to Item 4) — Nom 5/8 in. thick gypsum panels with beveled, square or tapered
<br />edges, applied vertically or horizontally. Vertical joints centered over studs and staggered one stud cavity on opposite
<br />sides of studs. Horizontal edge joints and horizontal butt joints on opposite sides of studs need not be staggered or
<br />backed by steel framing. Panels attached to steel studs and floor runner with 1 in. long Type 5 steel screws spaced 8 in
<br />OC when applied horizontally, or 8 in. OC along vertical and bottom edges and 12 in. OC in the field when panels are
<br />applied vertically. When used in widths other than 48 in., gypsum panels to be installed horizontally.
<br />CERTAINTEED GYPSUM INC — Type X, Type X-1, Type C, Type EGRG/ GlasRoc, Type SilentFX
<br />CGC INC — Types AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, USGX, WRC or WRX (Joint tape and compound,
<br />Item 5, optional for use with Type USGX)
<br />CONTINENTAL BUILDING PRODUCTS OPERATING CO, L L C — Types LGFC2A, LGFC6A, LGFC-C/A, LGFC-WD
<br />GEORGIA-PACIFIC GYPSUM L L C — Types DAP, DAPC, DGG, DS
<br />SAINT-GOBAIN GYPROC MIDDLE EAST FZE — Type Gyproc FireStop, Gyproc FireStop MR, Gyproc FireStop M2TECH,
<br />Gyproc FireStop ACTIV'Air, Gyproc FireStop MR ACTIV'Air, Gyproc FireStop M2TECH ACTIV'Air, Gyproc Dural-ine, Gyproc
<br />DuraLine MR, Gyproc DuraLine M2TECH, Gyproc DuraLine ACTIV'Air, Gyproc DuraLine MR ACTIV'Air, Gyproc DuraLine
<br />M2TECH ACTIV'Air
<br />THAI GYPSUM PRODUCTS PCL — Type X, Type C
<br />UNITED STATES GYPSUM CO — Types AR, C, FRX-G, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, WRC, WRX, USGX
<br />(Joint tape and compound, Item 5, optional for use with Type USGX)
<br />USG BORAL ZAWAWI DRYWALL L L C SFZ — Types C, SCX
<br />USG MEXICO S A DE C V — Type AR, C, IP-AR, IP-X1, IP-X2, IPC-AR, SCX, SHX, USGX, WRC or WRX (Joint tape and
<br />compound, Item 5, optional for use with Type USGX)
<br />48. Gypsum Board* — (As an alternate to Items 4 or 4A) — Nom 3/4 in. thick, 4 ft wide, installed as described in
<br />Item 4A with screw length increased to 1-1/4 in.
<br />CGC INC — Types AR, IP-AR
<br />UNITED STATES GYPSUM CO — Types AR, IP-AR
<br />USG MEXICO S A DE C V — Types AR, IP-AR
<br />4C. Gypsum Board* — As an alternate to Items 4, 4A, and 4B — Nom. 5/8 in. thick gypsum panels, with square
<br />edges, applied horizontally. Gypsum panels fastened to framing with 1 in. long bugle head steel screws spaced a max 8
<br />in. OC, with last 2 screws 3/4 in. and 4 in. from each edge of board. Horizontal joints need not be backed by steel
<br />framing. Horizontal edge joints and horizontal butt joints on opposite sides of studs on interior walls need not be
<br />staggered or backed by steel framing.
<br />GEORGIA-PACIFIC GYPSUM L L C — Type DGG, GreenGlass Type X
<br />4D. Gypsum Board* — As an alternate to Items 4, 4A, 4B, and 4C — Nom. 5/8 in. thick gypsum panels applied
<br />vertically or horizontally. Horizontal edge joints and horizontal butt joints on opposite sides of studs need not be
<br />staggered or backed by steel framing. Gypsum panels fastened to framing with 1 in. long Type S steel screws 8 in. OC
<br />along vertical edges and 12 in. OC in the field when panels are applied vertically. When gypsum panels applied
<br />horizontally, fasten to framing with 1 in. long Type S steel screws spaced 8 in. OC along vertical edges and in the field
<br />Screws spaced a max 12 in. along the top and bottom edges of the wall for both vertical and horizontal applications.
<br />NATIONAL GYPSUM CO — Types eXP-C, FSK, FSK-C, FSK-G, FSL, FSW-C, FSW-G, FSW, FSW-3, FSW-5, FSW-6,
<br />FSW-8, FSMR-C
<br />4E. Gypsum Board* — (As an alternate to Items 4 through 4D) — Installed as described in Item 4. 5/8 in. thick, 4 ft.
<br />wide, paper surfaced, applied vertically only and fastened to the studs and plates with 1 in. long, Type S steel screws
<br />spaced, 8 in. OC. Not to be used with item 6.
<br />NATIONAL GYPSUM CO — SoundBreak XP Type X Gypsum Board
<br />4F, Gypsum Board* — (Not Shown) — (As an alternate to Item 4 when used as the base layer on one or both sides of
<br />wall. For direct attachment only to steel studs Item 2C) - Nom 5/8 in. thick lead backed gypsum panels with beveled,
<br />square or tapered edges, applied vertically. Vertical joints centered over studs and staggered min 1 stud cavity on
<br />opposite sides of studs. Gypsum board secured to studs with 1-1/4 in. long Type S-12 steel screws spaced 8 in. OC at
<br />perimeter and 12 in. OC in the field.
<br />RAY -BAR ENGINEERING CORP — Type RB-LBG
<br />4G. Gypsum Board* — (As an alternate to Items 4 through 4F) — For use with Items 1D and 2D only, 5/8 in. thick, 4
<br />ft wide, attached to steel studs and floor and ceiling track with 1 in. long, Type S steel screws spaced 8 in. OC. along
<br />edges of board and 12 in. OC in the field of the board. Joints oriented vertically and staggered on opposite sides of the
<br />assembly.
<br />CONTINENTAL BUILDING PRODUCTS OPERATING CO, L L C — Type LGFC6A, LGFC-C/A
<br />NATIONAL GYPSUM CO — Types FSW
<br />UNITED STATES GYPSUM CO — Type SCX
<br />USG SORAL ZAWAWI DRYWALL L L C SFZ — Type SCX
<br />4H. Gypsum Board* — (As an alternate to Items 4 through 4G) — Nominal 5/8 in. thick, 4 ft wide panels, applied
<br />vertically and secured as described in Item 4.
<br />PASCO BUILDING PRODUCTS L L C, DBA PASCO GYPSUM — Type QufetRock ES
<br />4I. Gypsum Board* — (As an alternate to Items 4 through 4F) — For use with Items 1E and 2E only, 5/8 in. thick, 4
<br />ft wide, attached to steel studs and floor and ceiling track with 1 in. long, Type S steel screws spaced 8 in. OC. along
<br />edges of board and 12 in. OC in the field of the board. Joints oriented vertically and staggered on opposite sides of the
<br />assembly.
<br />UNITED STATES GYPSUM CO — Type SCX
<br />USG SORAL ZAWAWI DRYWALL L L C SFZ — Type SCX
<br />4). Gypsum Board* — (Not Shown) — (As an alternate to Item 4 when used as the base layer on one or both sides of
<br />wall. For direct attachment only to steel studs Item 2C) — Nom 5/8 in. thick lead backed gypsum panels with beveled,
<br />square or tapered edges, applied vertically, Vertical joints centered over studs and staggered min 1 stud cavity on
<br />opposite sides of studs. Gypsum board secured to studs with 1-1/4 in. long Type S-12 steel screws spaced 8 in. OC at
<br />perimeter and 12 in. OC in the field. To be used with Lead Batten Strips (see Item 9A) or Lead Discs (see Item 10A).
<br />MAYCO INDUSTRIES INC — Type X-Ray Shielded Gypsum
<br />4K. Gypsum Board* — (As an alternate to Item 4 and 4A, not for use with Items 1D, 1E, 2D and 2E) — Nom. 5/8 in
<br />thick gypsum panels with beveled, square or tapered edges installed as described in Item 4 and 4A.
<br />CGC INC — Type ULX
<br />UNITED STATES GYPSUM CO — Type ULX
<br />USG MEXICO S A DE C V — Type ULX
<br />4L. Gypsum Board* — (Not Shown) — (As an alternate to Item 4 when used as the base layer on one or both sides of
<br />wall. For direct attachment only to steel studs Item 2C). Nom 5/8 in. thick lead backed gypsum panels with beveled,
<br />square or tapered edges, applied vertically. Vertical joints centered over studs and staggered min 1 stud cavity on
<br />opposite sides of studs. Wallboard secured to studs with 1-1/4 in. long Type 5-12 steel screws gypsum panel steel
<br />screws spaced 8 in. OC at perimeter and 12 in. OC in the field. Lead batten strips required behind vertical joints of lead
<br />backed gypsum wallboard and optional at remaining stud locations. Lead batten strips, min 2 in. wide, max 8 ft long
<br />with a max thickness of 0.14 in. placed on the face of studs and attached to the stud with construction adhesive and
<br />two 1 in, long Type S-12 pan head steel screws, one at the top of the strip and one at the bottom of the strip. Lead
<br />discs,nominal 3 in. diam b max n. i /8 y a 0 O85 l thick. Compression fitted or adhered over the screw heads. Lead batten
<br />strips and discs to have a purity of 99.9% meeting the Federal specification QQ-L-201f, Grade "C".
<br />RADIATION PROTECTION PRODUCTS INC — Type RPP - Lead Lined Drywall
<br />4M. Gypsum Board* — (For use with Item 8) — 5/8 in. thick, 4 ft wide, applied vertically over Mineral and Fiber
<br />Board (Item 8) with vertical joints located anywhere over stud cavities. Secured to mineral and fiber boards with 1-1/2
<br />in. Type G Screws spaced 8 in. OC along edges of each vertical joint and 12 in. OC in intermediate field of the Mineral
<br />and Fiber Board (Item 8). Secured to outermost studs and floor and ceiling runners with 2 in. long Type S screws
<br />spaced 8 in. OC. Gypsum Board joints covered with paper tape and joint compound. Screw heads covered with joint
<br />compound.
<br />AMERICAN GYPSUM CO — Type AG-C
<br />CERTAINTEED GYPSUM INC — Type FRPC, Type C
<br />CGC INC — Types C, IP-X2, IPC-AR
<br />CONTINENTAL BUILDING PRODUCTS OPERATING CO, L L C — Type LGFC-C/A
<br />GEORGIA-PACIFIC GYPSUM L L C — Types 5, DAPC, TG-C
<br />NATIONAL GYPSUM CO —Types eXP-C, FSK-C, FSW-C
<br />PASCO BUILDING PRODUCTS L L C, DBA PASCO GYPSUM — Type PG-C
<br />PANEL REY S A — Types PRC, PRC2
<br />NOTE:
<br />REPRINTED FROM THE ONLINE
<br />CERTIFICATIONS DIRECTORY
<br />WITH PERMISSION FROM UL.
<br />2017 UL LLC
<br />SAINT-GOBAIN GYPROC MIDDLE EAST FZE — Type Gyproc FireStop, Gyproc FireStop MR, Gyproc FireStop M2TECH,
<br />Gyproc FireStop ACTIV'Air, Gyproc FireStop MR ACTIV'Air, Gyproc FireStop M2TECH ACTIV'Air, Gyproc Dural-ine, Gyproc
<br />Dural-ine MR, Gyproc Dural-ine M2TECH, Gyproc DuraLine ACTIV'Air, Gyproc DuraLine MR ACTIV'Air, Gyproc DuraLine
<br />M2TECH ACTIV'Air
<br />THAI GYPSUM PRODUCTS PCL — Type C
<br />UNITED STATES GYPSUM CO — Types C, IP-X2, IPC-AR
<br />USG BORAL ZAWAWI DRYWALL L L C SFZ — Type C
<br />USG MEXICO S A DE C V — Types C, IP-X2, IPC-AR
<br />4N. Wall and Partition Facings and Accessories* — (As an alternate to Item 4) — Nominal 5/8 in. thick, 4 ft wide
<br />panels, applied vertically and secured as described in Item 4.
<br />PASCO BUILDING PRODUCTS L L C, DBA PASCO GYPSUM — Type QufetRock 527
<br />40. Gypsum Board* — As an alternate to Items 4, 4A, 4B, and 4C — Two layers Nom. 5/16 in. thick gypsum panels
<br />applied vertically or horizontally. Horizontal edge joints and horizontal butt joints on opposite sides of studs need not be
<br />staggered or backed by steel framing. Horizontal joints on the same side need not be staggered. When applied
<br />horizontally, both layers of gypsum board fastened to each side of framing with 1 in. long Type S steel screws spaced 8
<br />in. OC and staggered 4 in. OC between layers. When applied vertically, both layers of gypsum board fastened to each
<br />side of framing with 1 in. long Type S steel screws spaced 8 in. OC along vertical edges and 12 in. OC in the field,
<br />staggered 4 in. OC between layers. Screws spaced a max 12 in. along the top and bottom edges of the wall.
<br />NATIONAL GYPSUM CO — Type FSW
<br />4P. Gypsum Board* — As an alternate to Item 4. For use with Item 3E, Batts and Blankets* — 5/8 in. thick, 4 ft
<br />wide, installed as described in Item 4.
<br />UNITED STATES GYPSUM CO — Types ULIX
<br />5. Joint Tape and Compound — Vinyl, dry or premixed joint compound, applied in two coats to joints and screw
<br />heads; paper tape, 2 in. wide, embedded in first layer of compound over all joints. As an alternate, nominal 3/32 in.
<br />thick gypsum veneer plaster may be applied to the entire surface of Classified veneer baseboard. Joints reinforced.
<br />Paper tape and joint compound may be omitted when gypsum boards are supplied with square edges.
<br />6. Resilient Channel — (Optional — Not Shown) — 25 MSG gaiv steel resilient channels spaced vertically max 24 in.
<br />OC, flange portion attached to each intersecting stud with 1/2 in. long type S- 12 pan head steel screws. May not be
<br />used with Item 4F or 43.
<br />6A. Steel Framing Members* — (Not Shown) — As an alternate to Item 6, furring channels and Steel Framing
<br />Members as described below:
<br />a. Furring Channels — Formed of No. 25 MSG gaiv steel. 2-9/16 in. or 2-23/32 in. wide by
<br />7/8 in. deep, spaced 24 in. OC perpendicular to studs. Channels secured to studs as described in
<br />Item b. Ends of adjoining channels are overlapped 6 in. and tied together with double strand of
<br />No. 18 SWG gaiv steel wire near each end of overlap. As an alternate, ends of adjoining
<br />channels may be overlapped 6 in. and secured together with two self -tapping No. 6 framing
<br />screws, min 7/16 in. long at the midpoint of the overlap, with one screw on each flange of the
<br />channel.
<br />b. Framing Members* — Used to attach furring channels (Item a) to studs (Item 2). Clips
<br />spaced 48 in. OC., and secured to studs with 1-5/8 in. wafer or hex head Type S steel screw
<br />through the center grommet. Furring channels are friction fitted into clips. RSIC-1 clip for use
<br />with 2-9/16 in. wide furring channels. RSIC-1 (2.75) clip for use with 2-23/32 in. wide furring
<br />channels.
<br />PAC INTERNATIONAL L L C — Types RSIC-1, RSIC-1 (2.75)
<br />68. Framing Members* — (Not Shown) — (Optional on one or both sides) — As an alternate to Item 6, furring
<br />channel and Steel Framing Members as described below:
<br />a. Furring Channels — Formed of No. 25 MSG galv steel. 2-3/8 in. wide by 7/8 in. deep,
<br />spaced max. 24 in. OC perpendicular to studs. Channels secured to studs as described in Item b.
<br />Gypsum board attached to furring channels as described in Item 4.
<br />b. Steel Framing Members* — Used to attach furring channels (Item 6Ba) to studs (Item 2).
<br />Clips spaced max. 48 in. OC. GENIECLIPS secured to studs with No. 8 x 1-1/2 in. minimum
<br />self -drilling, S- 12 steel screw through the center grommet. Furring channels are friction fitted
<br />into clips.
<br />PLITEQ INC — Type Genie Clip
<br />6C. Steel Framing Members* — (Optional, Not Shown) — Furring channels and Steel Framing Members as described
<br />below:
<br />a. Furring Channels — Formed of No. 25 MSG galv steel. Spaced 24 in. OC perpendicular to
<br />studs. Channels secured to studs as described in Item b, Ends of adjoining channels overlapped 6
<br />in. and secured together with four self -tapping No. 8x1/2 Self Drilling screws (2 per side 1 in.
<br />and 4 in. from overlap edge). Gypsum board attached to furring channels as described in Item
<br />4. Side joint furring channels shall be attached to studs with RESILMOUNT Sound Isolation Clips
<br />- Type A237R located approximately 2 in. from each end of length of channel. Both Gypsum
<br />Boards at side joints fastened into channel with screws spaced 8 in. OC, approximately 1/2 in.
<br />from joint edge.
<br />b. Steel Framing Members* — Used to attach furring channels (Item 6Ca) to studs. Clips
<br />spaced 24 in. OC., and secured to studs with No. 10 x 2-1/2 in. coarse drywall screw through
<br />the center hole. Furring channels are friction fitted into clips.
<br />STUDCO BUILDING SYSTEMS — RESILMOUNT Sound Isolation Clips - Type A237R
<br />7. Wall and Partition Facings and Accessories* — (Optional, Not Shown) — Nominal 1/2 in. thick, 4 ft wide panels,
<br />for optional use as an additional layer on one or both sides of the assembly. Panels attached in accordance with
<br />manufacturer's recommendations. When the QR-500 or QR-510 panel is installed between the steel framing and the UL
<br />Classified gypsum board, the required UL Classified gypsum board layer(s) is/are to be installed as indicated as to
<br />fastener type and spacing, except that the required fastener length shall be increased by a minimum of 1/2 in. Not
<br />evaluated or intended as a substitute for the required layer(s) of UL Classified Gypsum Board.
<br />PASCO BUILDING PRODUCTS L L C, DBA PASCO GYPSUM — Type QuietRock QR-500 and QR-510
<br />S. Mineral and Fiber Board* — (Optional, Not Shown) — For optional use as an additional layer on one side of wall.
<br />Nom 1/2 in. thick, 4 ft wide with long dimension parallel and centered over studs. Attached to studs and floor and
<br />ceiling runners with 1-5/8 in. long Type S steel screws, spaced 12 In. OC and 24 in. OC along all intermediate framing.
<br />The required UL Classified gypsum board layer (Item 4M) Is to be Installed over the Mineral and Fiber Boards. Batts and
<br />Blankets, Item 3D, and Adhesive, Item 11, are required.
<br />HOMASOTE CO — Homasote Type 440-32
<br />9. Lead Batten Strips — (Not Shown, For Use With Item 4E) — Lead batten strips, min 1-112 in. wide, max 10 ft long
<br />with a max thickness of 0.125 in. Strips placed on the interior face of studs and attached from the exterior face of the
<br />stud with two 1 in. long Type S-12 pan head steel screws, one at the top of the strip and one at the bottom of the strip.
<br />Lead batten strips to have a purity of 99.9% meeting the Federal specification QQ-L-201f, Grade "C". Lead batten
<br />strips required behind vertical joints of lead backed gypsum board (Item 4E) and optional at remaining stud locations.
<br />Required behind vertical joints.
<br />9A. Lead Batten Strips — (Not Shown, for use with Item 43) — Lead batten strips, 2 in. wide, max 10 ft long with a
<br />max thickness of 0.140 in. Strips placed on the face of studs and attached to the stud with two min. 1 in. long min.
<br />Type S-8 pan head steel screws, one at the top of the strip and one at the bottom of the strip or with one min. 1 in,
<br />long min. Type S-8 pan head steel screw at the top of the strip. Lead batten strips to have a purity of 99.5% meeting
<br />the Federal specification QQ-L-201f, Grades "B, C or W. Lead batten strips required behind vertical joints of lead
<br />backed gypsum wallboard (Item 41) and optional at remaining stud locations.
<br />10. Lead Discs or Tabs — (Not Shown, For Use With Item 4E) — Used in lieu of or in addition to the lead batten strips
<br />(Item 8) or optional at other locations - Max 3/4 in. diam by max 0.125 in. thick lead discs compression fitted or
<br />adhered over steel screw heads or max 1/2 in. by 1-1/4 in. by max 0.125 in. thick lead tabs placed on gypsum boards
<br />(Item 4E) underneath screw locations prior to the installation of the screws. Lead discs or tabs to have a purity of
<br />99.91/o meeting the Federal specification QQ-L-201f, Grade "C".
<br />10A. Lead Discs — (Not Shown, for use with Item 43) — Max 5/16 in. diam by max 0.140 in, thick lead discs
<br />compression fitted or adhered over steel screw heads. Lead discs to have a purity of 99.5% meeting the Federal
<br />Specification QQ-L-201f, Grades "B, C or D".
<br />11. Adhesive — Not Shown — (For use with Item 8) — Construction grade adhesive applied in vertical, serpentine,
<br />nominal 3/8 inr wide beads down the length of both vertical edges of Mineral and Fiber Board (Item 8).
<br />12. Wall and Partition Facings and Accessories* — (Optional, Not Shown) — For use with Items 1 to 1I, Items 2 to
<br />23, Item 3, Items 4 to 41, Item 5 and Item 6. For maximum fire rating of 1 hour. On one side of the wall, over the first
<br />layer of Gypsum Board (Item 4 to item 4I), install RefleXor membrane with the gold side facing outwards. Membrane
<br />installed with T50 staples spaced 12 inches on center in both directions as per manufacturer's instructions, seams in
<br />membrane to be overlapped by 2 inches. When RefleXor membrane is used an additional layer of Gypsum Board that is
<br />identical to the one used in the first layer and as specified in Item 4 to Item 4I shall be installed over the membrane.
<br />The additional layer of Gypsum Board to be Installed through the membrane to the stud as specified in Item 4 to Item
<br />41 except the fastener length shall be increased by a minimum of S/8 inch. Install Batts and Blankets in the stud cavity
<br />as per Item 3. On the other side of the wall, prior to the installation of the Gypsum Board, install Resilient Channels as
<br />per Item 6. Over the Resilient Channels install 3/4 inch thick SONOpan panel secured to the Resilient Channels with
<br />drywall screws and washers spaced at 16 in. OC an the perimeter of the panel and 8 in. OC in the field of the panel.
<br />Over the SONOpan panel install the same Gypsum Board as specified in Item 4 to Item 41 with the fastener length
<br />increased by minimum 3/4 inch. Not evaluated or intended as a substitute for the required layer(s) of UL Classified
<br />Gypsum Board.
<br />MSL — RefleXor membrane, SONOpan panel
<br />* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cull. Certification
<br />(such as Canada), respectively.
<br />Last Updated on 2017-05-30
<br />Ouestions? Print this page Terms of Use Page Top
<br />c 2017 UL LLC
<br />The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
<br />under UL's Follow -Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow -Up
<br />Service. Always look for the Mark on the product.
<br />UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
<br />Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non -
<br />misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
<br />with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
<br />the following format: "^c, 2017 UL LLC".
<br />4 1 5
<br />RS&H
<br />1715 N. Westshore Blvd., Suite 600
<br />Tampa„ Florida 33607-3999
<br />904-256-2500 Fax 904-256-2503
<br />www.rsandh.com
<br />FL Cert. Nos. AAC001886 * IB26000956
<br />5620 * LCC000210 * GB238
<br />1111111,00
<br />Advent Health
<br />PROJECT TITLE:
<br />KITCHEN RENOVATION
<br />ADVENTHEALTH ZEPHYRHILLS
<br />PROJECT ADDRESS:
<br />7050 Gall Blvd. Zephyrhills, FL 33541
<br />SEAL
<br />,(oo *,N K,�, -� I i—
<br />CO
<br />AR956j.&
<br />meI`1.
<br />Oos. %-
<br />FREDLij
<br />TAN
<br />SJ_ Digitally, by Yoo-Jin
<br />signed
<br />Kim
<br />Q
<br />O
<br />DN: C=US,
<br />Yoo-Jin KiM E=yoo-iln.ldm®rsandhxom.
<br />Kim
<br />0
<br />O=RSH, CN=Yw-Jin
<br />Date: 2020.04.08
<br />Z
<br />09:3e:45-04'00'
<br />uJ
<br />SIGNATURE
<br />J
<br />U
<br />a
<br />V
<br />2
<br />Q
<br />REVISIONS
<br />NO. DESCRIPTION DATE
<br />--I— J
<br />DATE ISSUED: 03/20/2020
<br />REVIEWED BY: Checker
<br />DRAWN BY: Author
<br />DESIGNED BY: Designer
<br />PROJECT NUMBER:
<br />504- 0226- 000
<br />© 2019 RS&H, INC.
<br />SHEET TITLE:
<br />UL DETAILS
<br />SHEET ID:
<br />PROJECT STATUS:
<br />CONSTRUCTION
<br />DOCUMENTS